APPENDIX

A
Flame Arrester Specification Sheet
for Manufacturer Quotation
To enable flame arrester manufacturers to select and provide the correct
flame arrester for a specific application, they must be given all relevant
data pertaining to the proposed installation. These data are usually trans-
mitted to manufacturers by means of a flame arrester specification (data)
sheet. When in-line detonation flame arresters are to be installed in a
vented manifold (vapor collection) system, it is imperative that a system
sketch (or piping isometric drawing) be included with the specification
sheet to show all horizontal and vertical piping runs (with dimensions) and
all fittings (elbows, tees, valves, etc.). These are needed to estimate the
potential for DDT and to determine where all detonation arresters must be
located in the piping. Also, if the gashapor stream is a multicomponent
mixture, a complete definition of the stream composition, including minor
corrosive or fouling components, should be appended to the data sheet.
The MESG, NEC group, and AIT for each component should be listed as
well.
Printed on the next page is a flame arrester specification (data) sheet
that is a composite of data sheets from several flame arrester manufactur-
ers and CPI companies. Most flame arrester manufacturers have their own
data sheets, which can be used with additional data added as the user
deems necessary.
185
Deflagration and Detonation Flame Arresters
by Stanley S. Grossel
Copyright 2002 American Institute of Chemical Engineers
FLAME ARRESTER SPECIFICATION (DATA) SHEET
Customer
Date
Project No.
Flowsheet No. ~
Flame Arrester No. Plant Site
Process (Application) Data
Gas/Vapor Composition
Normal Flow Rate
Normal Operating Press.
Normal Operating Temp.
NEC Group IEC Group MESG mm
Max. Allowable Pressure Drop
Is Continuous Burning Possible on FA Element 0 Yes 0 No
Distance To Be Installed from Potential Ignition Source
Applicable Test Protocol: 0 UL 525 0 USCG 0 FM 0 CEN 0 Other
Listing/Approval: 0 UL Listed or Classified
Additional Information
Max. Flow Rate
Max. Operating Press.
Max. Operating Temp.
Molecular Weight AIT
0 FM Approved
Design Data
Type: 0 Detonation FA
0 In-Line Deflagration FA
0 Hydraulic (Liquid Seal)
0 Removable Element
0 Unidirectional Bidirectional
0 End-of-Line Deflagration FA
0 Nonremovable Element
Installation: 0 Horizontal 0 Vertical IJ Other
Pipe Size/Schedule Flange Press. Rating/Face
Materials of Construction:
Options:
Housing Element Flange
Pressure Tap
Temperature Probe Fitting
Drain Plug
Coating6pecial Paint
No./SizeRype
No./Sizflype
NoJSizeRype
Other Options
Manufacturer Deliverables
0 Certified Drawings 0 Certified Flow Curves 0 Weight
0 Calculations 0 Installation and Maintenance Instructions