Certificate of Compliance
Certificate:
2557737 (LR104031)
Master Contract:
182407
Project:
2645104
Date Issued:
August 12, 2013
Issued to:
Hummel AG
Lise-Meitner-Strasse 2
Denzlingen, 79211
Germany
Attention: Klaus Gehri
The products listed below are eligible to bear the CSA
Mark shown with adjacent indicators 'C' and 'US' for
Canada and US or with adjacent indicator 'US' for
US only or without either indicator for Canada only.
Marin Banu
Issued by: Marin Banu, P. Eng.
PRODUCTS
CLASS 4418 05
CLASS 4418 85
- CABLE - Hardware - For Hazardous Locations
- CABLE-Hardware - For Hazardous Locations-Certified to U.S. Standards
CLASS 4418 05 - CABLE - Hardware - For Hazardous Locations
Ex de IIC Gb
Ex ta IIIC Da IP66/68
Class I, Div 2, Groups A, B, C, D; Class II, Div 1 or 2, Groups E, F and G; Encl Type 4, 4X and 6
Cable gland connectors, for use with armored cables, series type EXIOS 20-1, type EXIOS 20-2, type EXIOS
20-3, type EXIOS 25, type EXIOS 32, type EXIOS 40, type EXIOS 50, type EXIOS 63 and type EXIOS 75,
and series type EXIOS-MZ 20-1, type EXIOS-MZ 20-2, type EXIOS-MZ 20-3, type EXIOS-MZ 25, type
EXIOS-MZ 32, type EXIOS 40-MZ, type EXIOS 50-MZ, type EXIOS 63-MZ and type EXIOS 75-MZ. IP
66 and IP68.
Notes:
1.
Permitted temperature range of the cable glands is -60C to +105C.
DQD 507 Rev. 2012-05-22
Page: 1
Certificate:
2557737 (LR104031)
Master Contract:
182407
Project:
2645104
Date Issued:
August 12, 2013
2.
The ambient temperature of electrical equipment is usually limited to -20C to +40C. The maximum
ambient temperature permitted for these cable glands may be exceeded or fall below as long as the permitted
temperature range of the cable glands meets the range -60C to +105C
3.
Cable glands can be used on enclosures of up to 20 bar reference pressure.
4.
Cable Glands material may be of brass, nickel-plated brass or stainless steel.
5.
Cable Glands will be restricted to Hazardous Location Areas stated under the NEC/CEC Part I, Installation
Code under WIRING METHOD.
Cable gland connectors, series type EXIOS BARRIER for use with armored cable and series type EXIOS
BARRIER and EXIOS A2F for use with non-armored cables. IP 66 and IP68.
Notes:
1.
Permitted temperature range of the cable glands is -60C to +85 C for series type EXIOS BARRIER and
-60C to +105 C for series type EXIOS A2F.
2.
The ambient temperature of electrical equipment is usually limited to -20C to +40C. The maximum
ambient temperature permitted for these cable glands may be exceeded or fall below as long as the permitted
temperature range of the cable glands meets the range -60C to +85 C for series type EXIOS BARRIER and
-60C to +105 C for series type EXIOS A2F.
3.
Cable glands can be used on enclosures of up to 20 bar reference pressure.
4.
Cable Glands material may be of brass, nickel-plated brass or stainless steel.
5.
Cable Glands will be restricted to Hazardous Location Areas stated under the NEC/CEC Part I, Installation
Code under WIRING METHOD.
CLASS 4418 85 - CABLE - Hardware - For Hazardous Locations US Requirements
Class I, Zone 1, AEx de IIC Gb
Zone 20, AEx ta IIIC, T125C; Da
Class I, Div 2, Groups A, B, C, D; Class II, Div 1 or 2, Groups E, F and G; Encl Type 4, 4X and 6
Cable gland connectors, for use with armored cables, series type EXIOS 20-1, type EXIOS 20-2, type EXIOS
20-3, type EXIOS 25, type EXIOS 32, type EXIOS 40, type EXIOS 50, type EXIOS 63 and type EXIOS 75,
and series type EXIOS-MZ 20-1, type EXIOS-MZ 20-2, type EXIOS-MZ 20-3, type EXIOS-MZ 25, type
DQD 507 Rev. 2012-05-22
Page: 2
Certificate:
2557737 (LR104031)
Master Contract:
182407
Project:
2645104
Date Issued:
August 12, 2013
EXIOS-MZ 32, type EXIOS 40-MZ, type EXIOS 50-MZ, type EXIOS 63-MZ and type EXIOS 75-MZ. IP
66 and IP68.
Notes:
1.
Permitted temperature range of the cable glands is -60C to +105C.
2.
The ambient temperature of electrical equipment is usually limited to -20C to +40C. The maximum
ambient temperature permitted for these cable glands may be exceeded or fall below as long as the permitted
temperature range of the cable glands meets the range -60C to +105C
3.
Cable glands can be used on enclosures of up to 20 bar reference pressure.
4.
Cable Glands material may be of brass, nickel-plated brass or stainless steel.
5.
Cable Glands will be restricted to Hazardous Location Areas stated under the NEC/CEC Part I, Installation
Code under WIRING METHOD.
Cable gland connectors, series type EXIOS BARRIER for use with armored cable and series type EXIOS
BARRIER and EXIOS A2F for use with non-armored cables. IP 66 and IP68.
Notes:
1.
Permitted temperature range of the cable glands is -60C to +85 C for series type EXIOS BARRIER and
-60C to +105 C for series type EXIOS A2F.
2.
The ambient temperature of electrical equipment is usually limited to -20C to +40C. The maximum
ambient temperature permitted for these cable glands may be exceeded or fall below as long as the permitted
temperature range of the cable glands meets the range -60C to +85 C for series type EXIOS BARRIER and
-60C to +105 C for series type EXIOS A2F.
3.
Cable glands can be used on enclosures of up to 20 bar reference pressure.
4.
Cable Glands material may be of brass, nickel-plated brass or stainless steel.
5.
Cable Glands will be restricted to Hazardous Location Areas stated under the NEC/CEC Part I, Installation
Code under WIRING METHOD.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No 0-10
- General Requirements
CAN/CSA-C22.2 No 18.3-04
- Outlet Boxes, Conduit Boxes, and Fittings
CAN/CSA-C22.2 No.174-M1984 (R 2003) - Cables and Cable Glands for Use in Hazardous Locations
CAN/CSA-C22.2 No.94-M91
DQD 507 Rev. 2012-05-22
- Special Purpose Enclosures
Page: 3
Certificate:
2557737 (LR104031)
Master Contract:
182407
Project:
2645104
Date Issued:
August 12, 2013
CSA - C22.2 No. 213-M1987 (R 2004)
- Non-incendive Electrical Equipment for Use in Class I,
Division 2 Hazardous Locations
CSA - C22.2 No. 25-1966 (R 2004)
- Enclosures for Use in Class II, Groups E, F and G Hazardous
Locations
CAN/CSA-C22.2 No. 60079-0:11
- Electrical apparatus for explosive gas atmospheres - Part 0:
General requirements
CAN/CSA-C22.2 No. 60079-1:11
- Explosive atmospheres Part 1: Equipment protection by
Flameproof enclosures d
CAN/CSA-C22.2 No. 60079-7:12
- Explosive atmospheres - Part 7: Equipment
protection by increased safety "e"
CAN/CSA-C22.2 No. 60079-31:12
- Explosive atmospheres - Part 31: Equipment dust
ignition protection by enclosure "t"
ANSI/UL 514B, Edition 5
- Conduit, Tubing and Cable Fittings
UL 886, 10th Ed.,
- Outlet Boxes and Fitings For Use In Hazardous (Classified)
Locations
UL 2225, 2nd Ed.,
- Cables and Cable-Fittings For Use In Hazardous (Classified)
Locations
ISA 12.12.01: 2007
- Nonincendive Electrical Equipment for Use in Class I and II,
Division 2 and Class III, Divisions 1 and 2
Std. UL 1203 4th ed
- Explosion-Proof and Dust-Ignition-Proof Electrical Equipment
for Use in Hazardous (Classified) Locations
ANSI/UL 50 Edition 11
- Enclosures for Electrical Equipment
ANSI/UL 60079-0 (5th Ed. 2009)
- Explosive Atmospheres Part 0: Equipment - General
Requirements
ANSI/UL 60079-1 (6th Ed. 2009)
DQD 507 Rev. 2012-05-22
- Explosive Atmospheres Part 1: Equipment Protection by
Page: 4
Certificate:
2557737 (LR104031)
Master Contract:
182407
Project:
2645104
Date Issued:
August 12, 2013
Flameproof Enclosures d
ANSI/UL 60079-7:2008
- Electrical Apparatus for Explosive Gas Atmospheres - Part 7:
Increased safety "e"
ANSI/UL 60079-31:2009
- Explosive atmospheres - Part 31: Equipment dust ignition
protection by enclosure "t"
MARKINGS
- Manufacturer name or trade mark
- Catalogue number designation (provided on packaging or on the product)
- Hazardous Location designation (may be optionally marked with the addition of Class I, Zone 1, Groups IIC,
IIB, IIA)
- Type
- Trade size
- CSA Monogram (provided on packaging or on the product)
- CSA12.2557737X (provided on packaging or on the product)
DQD 507 Rev. 2012-05-22
Page: 5