SmartLine
Technical Information
STT650 SmartLine DIN Rail Temperature
Transmitter Specification 34-TT-03-15
Introduction
Part of the SmartLine family of products, the
STT650 is a DIN Rail mounted high performance
Temperature transmitter offering high measurement
accuracy, stability and reliability over a wide range of
process and ambient temperatures. SmartLine easily
meets the most demanding needs for temperature
measurement applications.
Description
The SmartLine Temperature transmitter is designed
and manufactured to deliver very high performance.
The total accuracy level of the transmitter including
the ambient temperature effect in, harsh industrial
environments, allows the STT650 to replace virtually
any competitive transmitter available today.
Best in Class Features:
Figure 1 SmartLine STT650 DIN Rail
Temperature Transmitter
Leading performance
o
High accuracy 0.1 Deg C for RTD
Faster response, up to 135 msec update
Stable measurement, 0.12% of span for two years
Communications/Output Options:
o 4-20mA dc
Reliable measurement
o
Built in 1500VAC Galvanic Isolation
Superior noise performance
Sensor error detection in accordance with Namur 89
Lower Cost of Ownership
o
Universal input
Dual channel option saves panel space
Easy to configure, install and commission
Can double up as position and level transmitters for
valves and ohmic level sensors.
o HART
(version 7.0)
o FOUNDATION Fieldbus* compliant to ITK 4.6.
o PROFIBUS PA* ver. 3.0
* Device registration in progress for FF, Profibus, HART 7
STT650 SmartLine DIN Rail
Common for all the Models
EMC Specifications:
All the STT650 DIN Rail models with universal input are tested for the following parameters:
Conducted Noise - 10Vrms in the range of 15Hz to 100MHz
Radiated Noise - 10V/m in the range of 80 to 1000MHz
Surge test - 1KV Differential mode ; 2 KV Common mode
Burst Noise - 2.5KV
STT650 RTD Input type
Features
Analog 4-20 mA output
RTD or Ohm input
Single or dual channel option
NAMUR NE43 sensor error response
Programmable using the STT17C PC Configuration tool
Performance specifications
Sensor
Type
Basic Accuracy*
Rated Range
RTD
(2,3 wire)
Fixed
% of span
Pt100
0.3C (32.54F)
+/- 0.1
-200 to 850
-328 to1562
Ni 100
0.3C (32.54F)
+/- 0.1
-60 to 250
-76 to 482
Ohms
0.2
+/- 0.1
0 to 10000
Minimum
Span**
Temperature Effects per 1.0 C
(1.8 F)***
Change in Ambient
Temperature
Fixed
% of span
25C (45F)
0.01C (0.018F)
+/- 0.01
25C (45F)
0.01C (0.018F)
+/- 0.01
30
20 m
+/- 0.01
* Basic accuracy or +/- 0.1% of Span whichever is greater
** or 50% of upper range value, whichever is greater
*** reference temperature 20 Deg C, Ambient temp effect is greater of the fixed value or the applicable % of Span
STT650 SmartLine DIN Rail
Operating Conditions
Ambient temperature, rated
-40 to + 85C (-40 185F)
Humidity
0 to 95% RH (non cond.)
Electrical Input specification
Supply voltage
8 to 30 VDC for Intrinsically Safe version.
8 to 35 VDC for non-Intrinsically Safe version
Power supply voltage effect
0.005% of span per VDC
Warm-up time
5 min
Damping (programmable)
0.33 to 60 sec
Current Output Specifications
Signal output range
4 to 20 mA
Update time
135 msec
Load resistance
(V supply -8) / 0.023 A
0 to 870
Alarm Levels
Programmable
3.5 to 4 mA downscale
20 to 23 mA upscale
NAMUR NE43 Upscale
23 mA
NAMUR NE43 Downscale
3.5 mA
STT650 SmartLine DIN Rail
STT650 Universal Input type Analogue Output only
Features
Analog 4-20 mA output
RTD, T/C, Ohm or mV input
NAMUR NE43 sensor error response
Programmable using STT17C PC configuration tool
Galvanic isolation
Performance specifications
Sensor
Type
RTD
(2,3,4 wire)
Basic Accuracy*
Rated Range
Fixed
% of span
Pt100
0.2C (0.36F)
0,05%
-200 to 850
-328 to1562
Ni 100
0.2C (0.36F)
0,05%
-60 to 250
-76 to 482
2C (3.6F)
0,05%
1C (1.8F)
Minimum
Span**
Temperature Effects per 1.0 C
(1.8 F)***
Change in Ambient
Temperature
Fixed
% of span
25C (45F)
0.01C (0.018F)
+/- 0.01
25C (45F)
0.01C (0.018F)
+/- 0.01
400 to 1820 +752 to 3308 100C (180F)
0.2C (0.36F)
+/- 0.01
0,05%
-100 to 1000 -148 to 1832
50C (90F)
0.05C (0.09F)
+/- 0.01
1C (0.1.8F)
0,05%
-100 to 1200 -148 to 2192
50C (90F)
0.05C (0.09F)
+/- 0.01
1C (0.1.8F)
0,05%
-180 to 1372 -292 to 2501
50C (90F)
0.05C (0.09F)
+/- 0.01
1C (0.1.8F)
0,05%
-100 to 900
-148 to 1652
50C (90F)
0.05C (0.09F)
+/- 0.01
1C (0.1.8F)
0,05%
-180 to 1300 -292 to 2372
50C (90F)
0.05C (0.09F)
+/- 0.01
2C (3.6F)
0,05%
-50 to 1760
-58 to 320
100C (180F)
0.2C (0.36F)
+/- 0.01
2C (3.6F)
0,05%
-50 to 1760
-58 to 3200 100C (180F)
0.2C (0.36F)
+/- 0.01
1C (1.8F)
0,05%
-200 to 400
-328 to 752
50C (90F)
0.05C (0.09F)
+/- 0.01
1C (1.8F)
0,05%
-200 to 600
-328 to 1112
50C (90F)
0.05C (0.09F)
+/- 0.01
STT650 SmartLine DIN Rail
W3
2C (3.6F)
0,05%
0 to 2300
+32 to 4172 100C (180F)
0.2C (0.36F)
+/- 0.01
W5
2C (3.6F)
0,05%
0 to 2300
+32 to 4172 100C (180F)
0.2C (0.36F)
+/- 0.01
+Lr
2C (3.6F)
0,05%
-200 to 800
-328 to 1472
50C (90F)
0.2C (0.36F)
+/- 0.01
Ohms
0.1
0,05%
0 to 5000
30
10 m
+/- 0.01
mV
10
0,05%
-12 to 800 mV
5 mV
+/- 0.01
* Basic accuracy or +/- 0.1% of Span whichever is greater
** or 50% of upper range value, whichever is greater
*** reference temperature 20 Deg C, Ambient temp effect is greater of the fixed value or the applicable % of Span
Operating Conditions
Ambient temperature, rated
-40 to + 85C (-40 185F)
Humidity
0 to 95% RH (non cond)
Cold junction Accuracy
+/- 1C
Electrical Input specification
Supply voltage
8 to 30 VDC for Intrinsically Safe version.
8 to 35 VDC for non-Intrinsically Safe version
Power supply voltage effect
0.005% of span per VDC
Warm-up time
5 min
Response time
(programmable)
1 to 60 sec
Galvanic isolation
1500 VAC
Current Output Specifications
Signal output range
4 to 20 mA
Update time
440 msec
Load resistance
(V supply -7.2) / 0.023 A
0 to 904
Alarm Levels
Programmable
3.5 to 4 mA downscale
20 to 23 mA upscale
NAMUR NE43 Upscale
23 mA
NAMUR NE43 Downscale
3.5 mA
STT650 SmartLine DIN Rail
STT650 Universal Input type - HART protocol
Features
HART/4-20 mA output
RTD, T/C, Ohm or mV input
Single or dual channel option
Supports Differential or Averaging measurement
NAMUR NE43 sensor error response
Programmable using MCT404 or STT17C PC configuration tool
Galvanic isolation
HART is a registered trademark of the HART Communication Foundation.
Performance specifications
Sensor
Type
RTD
(2,3,4 wire)
Basic Accuracy*
Rated Range
Fixed
% of span
Pt50
0.1C (1.8F)
0,05%
-200 to 850
-328 to1562
Pt100
0.1C (1.8F)
0,05%
-200 to 850
Pt200
0.1C (1.8F)
0,05%
Pt500
0.1C (1.8F)
Pt1000
Ni 100
B
Minimum
Span**
Temperature Effects per 1.0 C
(1.8 F)***
Change in Ambient
Temperature
Fixed
% of span
25C (45F)
0.005C (0.009F)
+/- 0.005
-328 to1562
25C (45F)
0.005C (0.009F)
+/- 0.005
-200 to 850
-328 to1562
25C (45F)
0.005C (0.009F)
+/- 0.005
0,05%
-200 to 850
-328 to1562
25C (45F)
0.005C (0.009F)
+/- 0.005
0.1C (1.8F)
0,05%
-200 to 850
-328 to1562
25C (45F)
0.005C (0.009F)
+/- 0.005
0.2C (0.36F)
0,05%
-60 to 250
-76 to 482
25C (45F)
0.1C (0.18F)
+/- 0.005
1C (1.8F)
0,05%
0 to 1820
0.1C (0.18F)
+/- 0.005
0.5C (0.9F)
0,05%
-100 to 1000 -148 to 1832
50C (90F)
0.025C (0.045F)
+/- 0.005
0.5C (0.9F)
0,05%
-100 to 1200 -148 to 2192
50C (90F)
0.025C (0.045F)
+/- 0.005
0.5C (0.9F)
0,05%
-180 to 1372 -292 to 2501
50C (90F)
0.025C (0.045F)
+/- 0.005
0.5C (0.9F)
0,05%
-100 to 900
-148 to 1652
50C (90F)
0.025C (0.045F)
+/- 0.005
0.5C (0.9F)
0,05%
-180 to 1300 -292 to 2372
50C (90F)
0.025C (0.045F)
+/- 0.005
1C (1.8F)
0,05%
-50 to 1760
-58 to 3200 100C (180F)
0.1C (0.18F)
+/- 0.005
1C (1.8F)
0,05%
-50 to 1760
-58 to 3200 100C (180F)
0.1C (0.18F)
+/- 0.005
0.5C (0.9F)
0,05%
-200 to 400
-328 to 752
0.025C (0.045F)
+/- 0.005
1,2,3
+32 to 3308 100C (180F)
25C (45F)
STT650 SmartLine DIN Rail
0.5C (0.9F)
0,05%
-200 to 600
W3
1C (1.8F)
0,05%
0 to 2300
W5
1C (1.8F)
0,05%
0 to 2300
+Lr
1C (1.8F)
0,05%
-200 to 800
Ohms
0.1
0,05%
mV
10
0,05%
-328 to 1112
0.025C (0.045F)
+/- 0.005
+32 to 4172 130C (234F)
0.1C (0.18F)
+/- 0.005
+32 to 4172 130C (234F)
0.1C (0.18F)
+/- 0.005
-328 to 1472
50C (90F)
0.1C (0.18F)
+/- 0.005
0 to 7000
25
5 m
+/- 0.005
-800 to 800 mV
2.5 mV
0.5
+/- 0.005
50C (90F)
* Basic accuracy or +/- 0.1% of Span whichever is greater
** or 50% of upper range value, whichever is greater
*** reference temperature 20 Deg C, Ambient temp effect is greater of the fixed value or the applicable % of Span
1,2,3
TC B accuracy specification range ................ > 400C
2
TC B accuracy specification range ................ > 160C < 400C
3
TC B accuracy specification range ................ > 85C < 160C
Operating Conditions
Ambient temperature, rated
-40 to + 85C (-40 185F)
Humidity
0 to 95% RH (non cond)
Cold junction Accuracy
+/- 1C
Electrical Input specification
Supply voltage
8 to 30 VDC for Intrinsically Safe version.
8 to 35 VDC for non-Intrinsically Safe version
Power supply voltage effect
0.005% of span per VDC
Warm-up time
30 sec
Response time (programmable)
1 to 60 sec
Galvanic isolation
1500 VAC
Current Output Specifications
Signal output range
4 to 20 mA
Update time
440 msec
Load resistance
(V supply -8) / 0.023 A
0 to 870
Alarm Levels
Programmable
(Sensor error detection)
3.5 to 23 mA downscale
3.5 to 23 mA upscale
NAMUR NE43 Upscale
23 mA
NAMUR NE43 Downscale
3.5 mA
STT650 SmartLine DIN Rail
STT650 Universal Input type FF/PA Protocol
Fieldbus and Profibus are separate models
Features
FOUNDATION Fieldbus protocol*
PROFIBUS PA protocol*
RTD, T/C, Ohm or mV input +mA +/- 100mA
Single or dual (difference, average or redundant) sensor input
Function blocks: 2 analogue, 1 PID
FISCO certified
Basic or LAS capability
Galvanic isolation
FOUNDATION is a registered trademark of the Fieldbus Foundation.
* Device registration in progress
Performance specifications
Sensor
Type
Basic Accuracy*
Temperature Effects per 1.0 C (1.8
F)***
Change in Ambient Temperature
Rated Range
RTD
(2,3,4 wire)
Fixed
% of reading
Fixed
% of reading
Pt100
0.1C (1.8F)
0,05%
-200 to 850
-328 to1562
0.002C (0.0036F)
+/- 0.002
Pt1000
0.1C (1.8F)
0,05%
-200 to 850
-328 to1562
0.002C (0.0036F)
+/- 0.002
Ni 100
0.15C (0.27F)
0,05%
-60 to 250
-76 to 482
0.002C (0.0036F)
+/- 0.002
Cu10
01.3C (0.2.3F)
0,05%
-200 to 260
-328 to 500
0.02C (0.0036F)
+/- 0.002
1C (1.8F)
0,05%
0 to 1820
+32 to 3308
0.025C (0.045F)
+/- 0.002
0.5C (0.9F)
0,05%
-100 to 1000
-148 to 1832
0.01C (0.018F)
+/- 0.002
0.5C (0.9F)
0,05%
-100 to 1200
-148 to 2192
0.01C (0.018F)
+/- 0.002
0.5C (0.9F)
0,05%
-180 to 1372
-292 to 2501
0.01C (0.018F)
+/- 0.002
0.5C (0.9F)
0,05%
-200 to 900
-328 to 1652
0.01C (0.018F)
+/- 0.002
0.5C (0.9F)
0,05%
-180 to 1300
-292 to 2372
0.01C (0.018F)
+/- 0.002
1C (1.8F)
0,05%
-50 to 1760
-58 to 3200
0.025C (0.045F)
+/- 0.002
STT650 SmartLine DIN Rail
1C (1.8F)
0,05%
-50 to 1760
-58 to 3200
0.025C (0.045F)
+/- 0.002
0.5C (0.9F)
0,05%
-200 to 400
-328 to 752
0.01C (0.018F)
+/- 0.002
0.5C (0.9F)
0,05%
-200 to 600
-328 to 1112
0.01C (0.018F)
+/- 0.002
W3
1C (1.8F)
0,05%
0 to 2300
+32 to 4172
0.025C (0.045F)
+/- 0.002
W5
1C (1.8F)
0,05%
0 to 2300
+32 to 4172
0.025C (0.045F)
+/- 0.002
mA
+/-1A
0,05%
-100 to 100
0.06A
+/- 0.003
Ohms
0.05
0,05%
0 to 7000
2 m
+/- 0.002
mV
10
0,05%
-800 to 800 mV
0.2
+/- 0.002
* Basic accuracy or +/- 0.1% of Span whichever is greater
*** reference temperature 20 Deg C, Ambient temp effect is greater of the fixed value or the applicable % of Span
Operating Conditions
Ambient temperature, rated
-40 to + 85C (-40 185F)
Humidity
0 to 95% RH (non cond)
Cold junction Accuracy
+/- 0.5C
Electrical Input Specification
Supply voltage
in FISCO installations
9 to 30 VDC
9 to 17.5 VDC
Consumption
11 mA / ch. max.
Warm-up time
30 sec
Response time (programmable)
1 to 60 sec
Galvanic isolation
1500 VAC
Update time
< 400 msec
Execution time, PID controller
< 200 msec
Execution time, analogue input
< 50 msec
Output Specifications
Foundation
Fieldbus connection
Foundation Fieldbus version
ITK 4.6
Foundation F.capability
Basic or LAS
Foundation F.function blocks
2 analogue and PID
PROFIBUS PA connection
PROFIBUS PA protocol
Profile A&B, ver. 3.0
PROFIBUS PA protocol standard
EN 50170 vol. 2
PROFIBUS PA address (at delivery)
126
PROFIBUS PA function blocks
2 analogue
10
Wiring Connections
STT650 RTD Input type
STT650 SmartLine DIN Rail
STT650 SmartLine DIN Rail
11
Wiring Connections
STT650 Universal Input type (Analogue Output model)
* Terminal Block with built in CJC is supplied as a standard accessory for all the universal input STT650 Models
12
STT650 SmartLine DIN Rail
Wiring Connections
STT650 Universal Input type - HART Protocol
* Terminal Block with built in CJC is supplied as a standard accessory for all the universal input STT650 Models
STT650 SmartLine DIN Rail
13
Wiring Connections
STT650 Universal Input type FF/PA Protocol
* Terminal Block with built in CJC is supplied as a standard accessory for all the universal input STT650 Models
14
STT650 SmartLine DIN Rail
Configuration Tools
The STT17C configures the STT650 programmable and HART units. The intuitive graphical user interface of the
STT17C* virtually eliminates the need for operator training after installation on a PC. The STT17C includes all
software and transmitter interface hardware necessary to configure the STT650 programmable and HART
models in non-hazardous work environments.
* Check with factory for the availability
WARNING: The STT17C is not approved for use in Hazardous work environments.
System Requirements:
Windows XP, Vista and Windows 7/8/8.1 with the following recommendations:
Memory:
16 MB
Display resolution:
800 x 600
Hard disk space:
12 MB
Approval Certifications
SIL Certification
Hardware assessed by EXIDA for use in SIL applications.
STT650 Smart Temperature
15
Mounting & Dimensional Drawings
Figure 2 STT650 DIN Rail Dimensions
16
STT650 Smart Temperature
Model Selection Guides are subject to change and are inserted into the specifications as guidance only.
Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published
at: www.honeywellprocess.com/en-US/pages/default.aspx
Model Selection Guide
Model STT650
SmartLine Temperature DIN Rail
Model Selection Guide:
34-44-16-16 Issue 1
Instructions: Make selections from all Tables Key through XIII using column below the proper arrow. Asterisk indicates
availability. Letter (a) refer to restrictions highlighted in the restrictions table. Tables delimited with dashes.
Key
STT650
II
- _ _ - _
KEY NUMBER
III
-
IV
VI
- ___ - ___ -
VII
-
VIII
_ _, _ _, _ _
0000
Input Type
DIN Rail Mount Temperature Transmitter
Table I
No of Channels
Input
ChanneI Details
Single
Single
Dual
Dual
RTD
Universal
RTD
Universal
Table II
TABLE III
Agency Approvals (see data sheet for Approval Code Details)
Approvals
No Approvals
TABLE IV
TRANSMITTER ELECTRONICS SELECTIONS
Housing and Material
Input Type
Galvanic Isolation
Plastic
Plastic
RTD
Universal
No
Yes
b. Output/ Protocol
c. No selection
TABLE V
a. Application
Software
b. Output Limit,
Failsafe & Write
Protect Settings
c. General
Configuration
3
S1
S2
T1
T2
*
*
*
*
A_ _
C__
h
i
_ A_
_H_
_F_
_P_
*
a
a
a
__0
1__
_3_
_6_
__S
No Selection
No Selection
a. Electronic
Housing Material &
Input Type
Availability
Selection
STT650
Analog Output
Digital Protocol
4-20mA dc
4-20mA dc
none
none
PC Programable
HART7 Protocol
Foundation Fieldbus
Profibus PA
No Selection
CONFIGURATION SELECTIONS
Diagnostics
Standard Diagnostics
Write Protect
No
No
Factory Standard
High & Low Output Lim its 3
Fail Mode
High> 21.0mAdc Honeywell Std (3.8 - 20.8 mAdc)
N/A
N/A
Fieldbus or Profibus
NAMUR Output Limits 3.8 - 20.5mAdc can be configured by the customer or select custom configuration Table Vc
f
*
STT650 Smart Temperature
TABLE VI
17
CALIBRATION & ACCURACY SELECTIONS
a. Accuracy and
Calibration
Accuracy
Standard
TABLE VII
Calibrated Range
Calibration Qty
Factory Std
Single Calibration
None - No additional options
00
Certificate of Conform ance
F3
F5
01
02
03
04
05
*
*
*
*
*
*
*
0000
Other Certifications and Options
Certificate of Origin
c. Certifications
and Warranty
Extended Warranty Additional 1 year
Extended Warranty Additional 2 years
Extended Warranty Additional 3 years
Extended Warranty Additional 4 years
Extended Warranty Additional 5 years
TABLE VIII
Factory
Manufacturing Specials
Factory Identification
MODEL RESTRICTIONS
Restriction Letter
Available Only with
Table
a
f
g
h
i
j
b
IVb
Not Available with
Table
Selection(s)
I
S1,T1
IVb
_ F,P_
IVb
_ H,A_
IVb
_ H,F,P_
I
S2,T2
I
S1,T1
_ H_
Vb
_6_
Select only one option from this group
Selection(s)
Sales and Service
For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices
below.
ASIA PACIFIC
EMEA
AMERICAS
Honeywell Process Solutions,
Honeywell Process Solutions,
Honeywell Process Solutions,
(TAC) hfs-tac-support@honeywell.com
Phone: + 80012026455 or
+44 (0)1202645583
Phone: (TAC) 1-800-423-9883 or
215/641-3610
(Sales) 1-800-343-0228
Australia
Honeywell Limited
Email: (Sales)
Phone: +(61) 7-3846 1255
FP-Sales-Apps@Honeywell.com
Email: (Sales)
FAX: +(61) 7-3840 6481
or
FP-Sales-Apps@Honeywell.com
Toll Free 1300-36-39-36
(TAC)
or
Toll Free Fax:
hfs-tac-support@honeywell.com
(TAC)
hfs-tac-support@honeywell.com
1300-36-04-70
China PRC - Shanghai
Honeywell China Inc.
Phone: (86-21) 5257-4568
Fax: (86-21) 6237-2826
Singapore
Honeywell Pte Ltd.
Phone: +(65) 6580 3278
Fax: +(65) 6445-3033
South Korea
Honeywell Korea Co Ltd
Phone: +(822) 799 6114
Fax: +(822) 792 9015
Specifications are subject to change without notice.
For more information
To learn more about SmartLine Temperature, visit
www.honeywellprocess.com
Or contact your Honeywell Account Manager
Process Solutions
Honeywell
1250 W Sam Houston Pkwy S
Houston, TX 77042
Honeywell Control Systems Ltd
Honeywell House, Skimped Hill Lane
Bracknell, England, RG12 1EB
Shanghai City Centre, 100 Jungi Road
Shanghai, China 20061
www.honeywellprocess.com
34-TT-03-15
October 2014
2014 Honeywell International Inc.