Important note !
65
List of builders work:
30
1 2 3 4 5 6 7
60
SL=
FFL
1. The local building authorities approve the construction of the enclosure work.
2. The lift shaft must be built according EN81-3 items 5.2.1 and 5.6.4. It is also
recommended to provide a slight slope in front of every landing sill to avoid the
infiltration of water.
3. Ventilation of the shaft resp. the machine room according to the local authority
requirements.
4. Determine exact final position of F.F.L.
5. Preferably the shaft enclosure has to be built after the lift installation. However,
when the shaft is built before the lift installation, it is imperative that shaft
enclosure is rectangular and plumb. Maximum admissible variation on size is +20
mm -0 mm. Door side (s) wall must be formed after lift installation.
6. On existing lift shafts the shaft door side(s) has (have) to be opened in full floor
height and shaft width. If necessary door openings according drawing no.
5-60002-0165 and 5-60002-0106.
7. An ambient temperature of at least +5C to max. +40C has to be ensured in the
machine room and the shaft.
8. The electrical supply for the machine room has to correspond to the National
demands. The following requirements have to be met:
8.1. Power line 5 x 1,5 mm, fuse protection: max. 3 x 10 A slow fuse
8.2. Light line 3 x 1,5 mm, fuse protection: max. 1 x 16 A slow fuse
8.3. Light line 3 x 1,5 mm, fuse protection: max. 1 x 16 A slow fuse socket outlet
in the pit by others
Attention: For bigger line lengths a corresponding cross section has to be chosen.
9. A safe machine room access has to be ensured. Ladders are only admissible
when the sill of the inspection door is not more than 2,7 m above floor level. The
corresponding regulations have to be considered. Within a distance of 1,5 m
around the ladder a fall from a height bigger than the ladder height must be
excluded (see EN81-3 appendix J).
10. Lighting of landing entrances according EN81-3 Item 7.6.1.
11. For installation or replacement of heavy parts suitable hoisting mechanism has to
be provided.
(x)
DH=CH=
Headroom min.=
SL + (1,5 x DH) + 250
B
min. 750
B-B
Trailing cable
SD=
60
30
DW=CW=
120
SL=
Notes:
30
1. Mark the position of the doors in the landing chart(s).
2. All height dimensions refer to the finished floor level (FFL), dimensions are in mm.
3. Suitable means at the car entrance must avoid the contact of the goods and the
wall.
4. During maintenance works in the pit the governor acc. EN81-3 Item 5.6.4.2 must be
provided in at least 1,8 m height from the shaft bottom.
5. During maintenance works on the car roof a device acc. EN81-3 Item 9.7.4 to stop
the car mechanically must be provided.
6. In front of the sill of the inspection door there must be a clear area of at least 700
x 600 mm acc. EN81-3 Item 6.3.2.
7. Exclusive use of the lift shaft and the machine room.
8. Further requirements of the building inspection remain untouched.
9. Loads:
9.1. Bearing pressure of each corner strut= 2950 N for 2 landings, each add.
landing plus 500 N for standard floor distances up to 3,0 m.
9.2. Bending load of each guide rail= 681 N
10. Subject to modification.
SW=
1 2 3 4 5 6 7
left
A-A
Machine room access C
(x)
65
140
Job-No.:
Orderer:
Specification agreed
Modifications
Accessible rooms below the shaft are forbidden.
Date
the
Lift owner:
c
d
Manufacturer:
Service lift
175
FFL
30
DH=CH=
min. 50
Travel height=
See "works by others"
item 6
FFL
SL min.900
Floor designations
E-installation
Governor acc.
EN81-3 item 5.6.4.2
7
6
5
4
3
2
1
Push-button designation
Floor switch
600
CD=
Final limit switch
Minimum floor distance
2 x DH + 330
Real existing headroom
min. 200
The position of the winding unit at bottom in the shaft which is
significant for this BKG-type is not intended in the EN81-3. Before
providing an offer the responsible inspection office has to be
contacted as they may have objections.
It is rather important that the controller is placed outside in a
lockable cubicle, however, in the area and view of the machine room
otherwise an additional, perhaps lockable main switch is required.
Please indicate the position of the controller cubicle.
Type BKG 100.45/41
Controller cubicle
Please indicate position
Capacity: 100 kg
Speed: v = 0,45 m/s
Date
Without
scale
Name
Drawing No.:
Drawn
Order No.:
Appr.
Issue: 02 / 2001
BKG-No.:
Art.-No.:
5-64100-0020-GB
CAD: C:00007828.SZN