Magnum DS
ANSI/UL Low Voltage Power Circuit Breakers
Product Focus
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Contents
July 2003
Introduction
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
One Family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Smaller Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Higher Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Drawout Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Enclosure Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Functions and Characteristics
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Characteristics Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Design and Testing Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Nameplate Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation and Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Circuit Breaker Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Trip Units and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Fixed Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Drawout Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Phasing on Double-wide Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . 40
Accessory Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Breaker Lock OFF Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Application and Installation Information
Ambient Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Bus Bar Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Altitude Rating Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Watts Loss Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Electrical Clearances. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Maintenance Guidelines
Breaker Specifications
Ordering Information
Factory Configured Breakers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Factory Configured Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Field Option Kits for Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Field Option Kits for Circuit Breakers . . . . . . . . . . . . . . . . . . . . . . . 67
Miscellaneous Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Engineering Data Reference Chart . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Trip Unit Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Overview
July 2003
Magnum DS
The New Standard in Low Voltage Power Circuit Breakers
Cutler-Hammer Type DS Low
Voltage Power Circuit Breakers
have set the industry standard for
over three decades. When reliability and customer service are
paramount, Cutler-Hammer is the
market leader for ANSI/UL applications
A compact and modular family
of breaker frame sizes makes the
design of compact, economical
and versatile enclosures a reality.
Field installable accessories
minimize inventory and permit ULapproved field installation of current sensors, rating plugs, trip units
and accessories.
There is a new generation of CutlerHammer Power Circuit Breakers
that are smaller with higher performance and more versatility.
Magnum DS
Magnum DS Low Voltage Power
Circuit Breakers are designed for
ultimate application flexibility,
with the needs of both the power
distribution equipment user and
the low voltage electrical equipment manufacturer in mind.
For maximum safety, a modern,
through-the-door design permits
access to the breaker levering system, trip unit, controls, and indicators with the door closed.
High withstand and interrupting
ratings provide for maximum selectivity and system coordination to
meet the needs of the high available fault currents on todays electrical power distribution systems.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
One Family
July 2003
Three Frame Sizes in One Family
Magnum DS circuit breakers are
available in a family of three
physical frame sizes.
The MDN narrow frame is the
highest performing power circuit
breaker of its size and rating class.
Continuous current ratings are
available from 800 to 1600
amperes (drawout) and 800 to 2000
amperes (fixed mounted).
Withstand and interrupting ratings
are available from 42 to 65 kA at
600Vac. The MDN compact size
allows for application in compact
enclosures of many types.
The MDS standard frame is ideally suited for the construction of vertically stacked modular ANSI/UL
Switchgear and Switchboards.
Continuous current ratings are
available from 800 to 3200 amperes
in the same frame with uniform 5
inch pole center spacing.
Withstand ratings are available to
85 kA and interrupting ratings to
100 kA at 600 Vac for improved system coordination and service continuity.
The MDS double-wide frame is
ideal for application as main and
tie breakers in high capacity power
distribution systems. Continuous
current ratings are available in 4000
and 5000 amperes. A 6000 rating is
available when the breaker is
applied in a suitably designed and
tested fan cooled enclosure.
Withstand and interrupting ratings
are available to 100 kA at 600Vac
for maximum system coordination
with down stream devices.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Smaller Size
July 2003
More Circuit Breakers
per
Square Foot of Space
The Magnum DS circuit breaker is
significantly smaller than previous generation open type metal
frame power circuit breakers. High
strength, thermoset composite
resin materials used in the breaker
frame provide increased strength
for higher capacity ratings. This
leads to the design of smaller and
more economic enclosures
using far less critical floor
space.
The modern, through-the-door
design construction results in
enclosures of shallower depth,
while providing three position drawout levering and storage with the
enclosure door closed.
The modular design of the
Magnum DS standard and doublewide frames is the key to design
simplification and more compact
Switchgear. Two columns of single-wide circuit breakers can be
stacked over or under double-wide
breakers with a common riser bus.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Higher Performance
July 2003
Higher Levels of Performance
Magnum DS circuit breakers have
higher levels of performance
than conventional metal frame
power circuit breakers.
Higher interrupting capacity
allows Magnum DS to be applied
on power distribution systems with
higher available fault currents.
Higher short time (withstand)
current ratings along with selective
(LS) Digitrip RMS trip units results
in improved selectivity between
main, feeder, and branch circuit
breakers.
MDN
Narrow
MDS
Standard
MDS
Double-wide
Interrupting
up to
65 kA
Interrupting
up to
100 kA
Interrupting
up to
100 kA
Short Time
up to
65 kA
Short Time
up to
85 kA
Short Time
up to
100 kA
Continuous Current (A)
Performance Family
I.C. at 635 (v) 800 1200 1600 2000 2500 3000 3200 4000 5000 6000
Magnum MDN
Narrow Frame
800 - 2000 A.
42 kA
50 kA
65 kA
Magnum MDS
Standard Frame
800 - 3200 A.
42 kA
50 kA
65 kA
85 kA
100 kA
Magnum MDS
Double-wide Frame
4000 - 6000 A.
PG01301001E
85 kA
100 kA
For more information visit: www.cutler-hammer.eaton.com
Drawout Cassettes
July 2003
Three Drawout Cassette Options
MDN Narrow Frame Cassette
The MDN narrow frame circuit
breaker is available in a compact
cassette with horizontal primary
stabs and terminals, making it ideal
for single high compact enclosures.
Optional vertical adapter kits are
available for applications where
bus bar termination in the vertical
plane or multiple stacking of breakers is preferred.
Front View (with circuit breaker)
MDS standard and double-wide
frame circuit breakers are available in two types of cassettes; the
universal and basic cassette. Both
have vertical primary terminal
stabs for interface with the breaker.
A uniform 5 inch pole center spacing makes these cassettes ideal for
applications that require stacking of
multiple circuit breakers in a single
enclosure structure.
The Universal Cassette is available in 3-pole and 4-pole configurations and is supplied with large flat
primary pre-drilled terminal pads.
This offers maximum flexibility for
the enclosure manufacturer by
allowing for bus bar termination in
the horizontal or vertical planes or
from the top or bottom direction.
Rear View
MDS Universal Cassette
Front View
(with Optional Shutters)
Rear View
MDS Basic Cassette (with Optional Line and Load Stabs)
The Basic Cassette is designed to
accommodate 3-pole applications
where the enclosure manufacturer
prefers primary terminations with
bus bars in the vertical plane.
Optional vertical bus bar stab kits
are available for purchase or the
enclosure manufacturer can choose
to self-fabricate these stabs as part
of their manufacturing system.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Enclosure Solutions
July 2003
Enclosure Solutions
Cutler-Hammer offers a hierarchy
of enclosure solutions from
breaker and cassette components
to complete UL Listed Switchgear
Assemblies and Switchboards.
Power distribution equipment manufacturers can apply these solutions to add value based on their
individual capabilities to customize
product for their customers.
Magnum DS Switchgear Assembly (UL1558 Listed)
Pow-R-Line C UL891 Low
Voltage Switchboards use
Magnum DS breakers for commercial and light industrial applications.
Magnum DS UL1558 Listed
Low Voltage Switchgear sets
the industry standard for complete
and customized switchgear applications.
Magnum DS Bare Bones
Switchgear provides an assembly
solution that is as complete as
specified by the OEM, but still has
provisions for added value. Bare
Bones Switchgear is generally
provided without enclosure wiring
and includes sufficient blank panel
space and room for OEM added
components. The OEM typically
adds the relaying, metering and
other customized components and
completes the wiring and tests the
complete assembly to customize it
to their customer requirements.
Magnum DS Power Module (UL Recognized)
Magnum DS Power Modules
provide a shell frame assembly,
which allows for substantial modification and value added by the
enclosure manufacturer. Power
modules consist of base metal
structures, compartment cells and
vertical bus. Typically the OEM will
self-fabricate the horizontal bus, the
exterior panels, and the compartment doors. The OEM then assembles the individual structures, adds
the relaying, metering, and other
customized components. Finally
the assembly is wired and tested to
customer requirements.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Overview
July 2003
Introduction
The Magnum DS Low Voltage Power
Circuit Breaker affords customers
the opportunity to meet the increasingly complex requirements of
modern distribution systems. It is
designed and tested for use in low
voltage power distribution assemblies applied at nominal voltages of
240, 480, and 600 volts ac.
Magnum DS is available in drawout
and fixed circuit breaker mounting
configurations. High interrupting
ratings up to 100kA without fuses
and continuous current ratings
from 800 through 6000 amperes
are covered by three different
frame sizes.
Magnum DS circuit breakers are UL
listed, and are built and tested in an
ISO 9000 certified facility. The circuit
breakers meet or exceed all applicable ANSI, NEMA, UL and CSA standards including:
ANSI C37.13, C37.16, C37.17 and
C37.50
NEMA SG3 and UL 1066
Suitable in UL 1558 LV
Switchgear
Suitable in UL 891 Switchboards
Suitable in UL CSA 22.2.31 LV
Assemblies
Controls and indicators are functionally grouped on the circuit
breakers front cover. The throughthe-door drawout design permits
easy and safe access to the front
cover controls, as well as the trip
unit and racking device.
Magnum DS circuit breakers utilize
one of a family of microprocessorbased Digitrip RMS electronic, rms
sensing and programmable trip
units to provide system selectivity,
advanced coordination and communications.
Functional and Flexible
Rigid frame of high strength
engineered thermoset composite
resins
Compact and lightweight
Rugged, maintainable
construction
Three frame sizes
Four position drawout or fixed
mounting configurations
Through-the-door drawout
construction
Common height, depth and door
cutout
Spring stored energy mechanism
Electrical or manual operation
(field convertible)
Field installable UL Approved
accessories
Performance Plus
Designed and tested to ANSI,
NEMA, UL and CSA Standards
Nine continuous current frame
sizes (800 through 5000A without
fans)
6000 amp rating in fan cooled
enclosure
High interrupting ratings
High withstand ratings
Rated for 100% continuous
operation in enclosure
3 cycle closing
For more information visit: www.cutler-hammer.eaton.com
Intelligence Systems
Digitrip microprocessor-based
true rms sensing trip units
Protection and coordination
Energy monitoring and power
quality
Communications
Protective relay features
Integral testing
Hand held test kit
Special Application Circuit
Breakers
Non-automatic circuit breakers a non-automatic circuit breaker
does not include a trip unit, sensors or overcurrent release.
Contact Cutler-Hammer for other
special applications.
Functional Techniques
Patented Heal -Toe contacstructure
Improved contact material
C Loop current path
Braided current path connections
Sealed, removable arc chambers
Reliability, Maintenance and Safety
Front accessible and dedicated
secondary wiring
Finger proof secondary contacts
Drawout rail construction
Front mounted, plug-in accessories
Accessory viewing windows
Proven operating mechanism
Fewer individual parts
Mechanical main contact wear
indicator
One piece removable arc chutes
and covers
Insulating and isolating arc
chambers
Replaceable current path structures, current sensors and trip
units
PG01301001E
Characteristics Table
July 2003
MDN
Narrow
Frame
MDS
Standard
Frame
Magnum DS Characteristics, Dimensions and Weights
Magnum DS Frame
Circuit Breaker Characteristics
Continuous Current Rating (Amps at 40C)
Short Circuit Current (kA rms sym)
Short Time Withstand Current (kA rms sym)
Maximum Break Time (msec)
Maximum Closing Time (msec)
Circuit Breaker Dimensions (in)
Height
Depth
Fixed
Width (3-pole)
Width (4-pole)
Height
Depth
Drawout
Width (3-pole)
Width (4-pole)
Narrow Frame (MDN)
800
800
800
1200
1200
1200
1600
1600
1600
2000
42
42
50
50
30
50
65
65
(continued on next page)
Standard Frame
800
800
1600
1600
2000
2500
3000
3200
800
50
50
42
42
16.8
14.6
12.5
16.2
21
18.7
13.3
17
(MDS)
800
1600
2000
2500
3000
3200
85
85
65
65
30
50
800
1600
2000
2500
3000
3200
100
85
16.8
14.6
16.2
21.2
21.0
18.7 (Universal Type)
17.74
23.0
Circuit Breaker Weight (lb)
Fixed
Drawout
Cassette
95
120
107
136
61
70
3-pole
4-pole
3-pole
4-pole
3-pole
4-pole
128
160
155
194
117
123
to
to
to
to
to
to
150
190
189
246
123
150
Non-Auto Switch Characteristics
Short Circuit Current (kA rms sym)
42
Short Time Withstand Current (kA rms sym)
Continuous Current Range (Amps)
Close and Latch Current (kA rms peak)
Continuous Current Range (Amps)
Close and Latch Current (kA rms peak)
50
65
50
65
42
to 1600 to 2000 to 2000
55
69
43
50
42
42
to 800
27
65
65
50
to 1600 to 2000
55
55
3200
110
85
69
to 2000
110
3200
Circuit breakers equipped with integral trip units have a making current release set to trip instantaneously when the peak instantaneous current exceeds 25 x In (In is established by the breakers current sensors and rating plug).
The short circuit current rating is applicable at 635Vac, 508Vac and 254Vac.
The approximate weights and depth dimension shown do not include optional adapters on the primary terminals.
Standard frame circuit breakers rated 100kA are equipped with a high instantaneous trip set to the withstand level.
Close and latch ratings are applicable only to non-automatic switches. Non-automatic switches should be applied with a suitable external
overcurrent device with instantaneous trip to protect above the published close and latch rating.
The maximum available instantaneous interrupting rating for the standard frame non-automatic switch is 85kA.
The 2000A Narrow frame is available as fixed mount only.
Magnum DS 6000A circuit breaker applied in a suitably designed and tested fan cooled enclosure.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Characteristics Table
July 2003
MDS
Double-wide
Frame
(continued from previous page)
Magnum DS Frame
Circuit Breaker Characteristics
Double-wide Frame MDS
4000
5000
4000
5000
6000
85
85
100
100
Continuous Current Rating Amps at 40C
Short Circuit Current (kA rms sym)
Short Time Withstand Current (kA rms sym)
Maximum Break Time (msec)
Maximum Closing Time (msec)
Circuit Breaker Dimensions (in)
Height
Depth
Fixed
Width (3-pole)
Width (4-pole)
Height
Depth
Drawout
Width (3-pole)
Width (4-pole)
40
70
16.8
14.6
34.9
44.1
21.0
18.7
36.0
45.8
(Universal Type)
Circuit Breaker Weight (lb)
Fixed
Drawout
Cassette
237
319
303
366
199
250
3-pole
4-pole
3-pole
4-pole
3-pole
4-pole
to
to
to
to
to
to
276
360
343
441
212
266
Non-Auto Switch Characteristics
Short Circuit Current (kA rms sym)
Short Time Withstand Current (kA rms sym)
Continuous Current Range (Amps)
Close and Latch Current (kA rms peak)
Continuous Current Range (Amps)
Close and Latch Current (kA rms peak)
PG01301001E
100
100
100
to 4000
138
to 4000
207
100
5000 & 6000 5000 & 6000
138
207
For more information visit: www.cutler-hammer.eaton.com
10
Design and Testing Standards
July 2003
Introduction
The Magnum DS power circuit
breaker was designed and tested to
meet the requirements of the ANSI
market. It is a 100% rated device,
designed to carry 100% of its
nameplate current rating in an
enclosure without derating.
Magnum DS circuit breakers are UL
Listed, and tested to all applicable
NEMA, ANSI, IEEE and UL standards.
Specifically, the circuit breakers
comply with the following:
ANSI C37.13 (Low Voltage AC
Power Circuit Breakers Used In
Enclosures)
ANSI C37.16 (Preferred Ratings,
Related Requirements And
Application Recommendations
For Low Voltage Power Circuit
Breakers And AC Power Circuit
Protectors)
ANSI C37.17 (Trip Devices For AC
And General Purpose DC Low
Voltage Power Circuit Breakers)
ANSI C37.50 (Test Procedures
For Low Voltage AC Power
Circuit Breakers Used In
Enclosures)
PG01301001E
UL 1066 (Standard For Low
Voltage AC And DC Power Circuit
Breakers Used In Enclosures)
NEMA SG3 (This Standard
Adopts ANSI C37.16 In Its
Entirety)
In addition, Magnum DS is suitable
for use in:
UL 1558 LV Switchgear
UL 891 LV Switchboards
UL CSA 22.2.31 LV Assemblies
Magnum DS circuit breakers can be
used in forward or reverse feed
applications.
The standards outlined establish
the minimum requirements. There
is nothing prohibiting a circuit
breaker design from exceeding
standards by offering additional
features and/or higher levels of performance. Magnum DS does this
in a number of areas.
ANSI 37.50 Testing
Low voltage power circuit breakers
can be applied at or below their
nameplate rating. That nameplate
rating is a result of having successfully completed a series of rigrous
tests. This is the 100% rating.
For more information visit: www.cutler-hammer.eaton.com
ANSI C37.50 testing is demanding
and consists of four test sequences.
All tests are performed using a
drawout circuit breaker in its minimum size enclosure for each frame
size. The first three tests are similar
in a number of ways to tests performed on other types of low voltage circuit breakers, such as molded
case circuit breakers. It is the
fourth test sequence that differentiates the power circuit breaker from
other circuit breakers.
Test Sequence 1
This test sequence consists of a
temperature rise test, an overload
calibration, and then a short circuit
test.
Test Sequence 2
This test sequence consists of a
series of short circuit tests.
Test Sequence 3
This test sequence is a test of
endurance.
Test Sequence 4
This test sequence is a momentary
rating test. Other types of low voltage circuit breakers are not subjected to this type of test and, therefore,
have no full 30 cycle short time rating.
11
12
Nameplate Identification
July 2003
Nameplate Identification
Typical Magnum DS Nameplate
Magnum DS low voltage power circuit breakers must be applied within their nameplate ratings.
Nameplates are prominently displayed on the front of the circuit
breaker, and provide important
information relative to that specific
circuit breaker.
A
B
A Magnum DS circuit breaker is
easily identified by its specific designation.
Magnum DS Designation Example
MD S
Circuit Breaker
Type
MDS - Standard and
Double Wide Frames
MDN - Narrow Frame
Interrupting
Capacity
4 - 42,000
5 - 50,000
6 - 65,000
8 - 85,000
C - 100,000
L - 200,000
X - 200,000
C32
Frame
Size
08 - 800 Amps
12 - 1200 Amps
16 - 1600 Amps
20 - 2000 Amps
25 - 2500 Amps
30 - 3000 Amps
32 - 3200 Amps
40 - 4000 Amps
50 - 5000 Amps
60 - 6000 Amps
A Low voltage power circuit breaker family name
B Breaker family designation number
C Breaker frame size in amperes
D Interrupting capacity rating
E Factory Equipped Accessories
Reserved for future breaker with integral current limiters
Reserved for future breaker with fuse-less 200 kA performance
4N for 4000A AABBCC phasing
5N for 5000A AABBCC phasing
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Installation and Use
July 2003
Sized to Simplify
Magnum DS low voltage power circuit breakers are designed for simplified installation and use.
Three physical frame sizes
through 6000 amperes
- More circuit breakers per
square foot
- Increased ratings in less space
Four position drawout and fixed
mountings
- Customer flexibility
Fixed mounting with horizontal
or vertical bus bar connections
- Accommodate different bus
configurations
Through-the-door drawout
- Clear access to trip unit, controls and indicators
- Closed door circuit breaker levering
- DISCONNECT, TEST and CONNECT with door closed
Common height, depth and door
cutout
- Installation ease and economy
Zero clearance mounting with
drawout cassette
- Vertical stacking economy
- Installation economy of
time,material and space
Common Height, Depth and Cutout (3-Pole Illustration)
14.7
(391mm)
Dotted Line
Represents
CommonCutout
16.4
(417mm)
12.5
(318mm)
Narrow
800-1600A
16.3
(414mm)
Standard
800-3200A
34.2
(894mm)
Double
4000-5000A
Through-The-Door Drawout (Connect Position Shown)
Secondary
Connection Made
Rear of
Compartment
Compartment
Front Door
Circuit
Breaker
Side View
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Primary
Connections
Made
13
14
Circuit Breaker Features
July 2003
Summary
Rigid Frame Housing
Magnum DS circuit breakers use a
rigid frame housing construction of
engineered thermoset composite
resins. This material is strong and
lightweight having a strength to
weight ratio twice that of steel. In
addition to high strength structural
properties, this material has excellent dielectric characteristics and
resists arc tracking.
The 3-piece construction provides
support while isolating and insulating power conductors:
A 2-piece case encloses current
paths and arc chambers. The
chambers act to channel arc gases
up and out during interruption.
The operating mechanism and
accessories sit on the front of the
case and are covered by an insulating front cover. Only the cover
needs to be removed to access the
mechanism or add accessories.
lable accessory items can be identified by name and rating through
viewing windows. An optional
padlockable cover limits access to
the ON and OFF pushbuttons.
Complete access to the ON pushbutton can be prevented with an
optional prevent close cover.
The overall strength and rigidity of
the design also contributes to higher performance capabilities:
Higher Withstand
Higher Interrupting
Magnum DS Rigid Frame Construction
The Magnum DS rigid frame housing design allows for precise construction, eliminating the need for
adjustments. The significantly
reduced frame deflection during
operation along with stiff component mounting results in a longer
life operating mechanism.
Front Cover
Case
Operating Panel
The Magnum DS front cover (next
page) contains a convenient operating panel with clear words and
symbols indicating functions and
guiding operations. Field instal
Magnum DS Front Accessible Operating Mechanism and Accessories
1
1
Secondary Wiring Points
Field Installable Accessories
(3 maximum)
Trip Unit
Electric Charging Motor
Manual Charge Handle
Operations Counter (optional)
Padlockable Levering Device
Access Door
Breaker Position Indicator
5
3
8
7
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Circuit Breaker Features
July 2003
Magnum DS Drawout Circuit Breaker Front Cover
2
5
9
9
CLOSED
(Red)
(Green)
OPEN
CHARGED
(Yellow)
(White)
DISCHARGED
4
4
8
PUSH ON
(Green)
14
PUSH OFF
(Red)
10
15
13
11
CONNECT
12
TEST
DISCONNECT
Red = Connect
Yellow = Test
Green = Disconnect
Optional Trip Flag (Pop Out Indicator)
Manual OFF Button (Push)
Three Accessory Windows
Manual ON Button (Push)
Trip Unit
Manual Charge Handle
Rating Plug
10 Optional Operation Counter
Contact Status (Open-Close)
11 Padlockable Levering Device Access
Spring Status (Charged-Discharged)
PG01301001E
Door for Drawout Breaker
For more information visit: www.cutler-hammer.eaton.com
12 Color Coded-Breaker
Position Indicator
13 Nameplate
14 Trip Unit Test Port
15 Trip Unit Cover with Two
Mounting Screws (Mounting
Screws will Accept Customer
Supplied Lead Security Meter
Seals
15
16
Circuit Breaker Features
July 2003
2-Step Stored Energy
Mechanism
Magnum DS circuit breakers are
equipped with a 2-step stored energy mechanism. The mechanism
closing springs can be charged
manually or electrically, providing
the stored energy to CLOSE the
breaker. After the breaker is closed,
the mechanism closing springs can
again be charged and the stored
energy mechanism allows the
breaker to OPEN CLOSE OPEN
without performing another charging operation.
on different parts of the same finger.
A complete movable contact
assembly is merely a combination
of a number of single contact fingers. The exact number of contact
fingers required depends upon the
frame size and interrupting rating
of the circuit breaker.
The braided connectors (flexible
shunts) used to attach each contact
finger serve several important purposes:
Main Contact System
Single Contact Finger
The performance characteristics of
the Magnum DS air circuit breaker
are primarily attributed to the contact design and its movement. A
single contact finger is the focal
point of the moving contact. This
single contact performs both the
main and arcing contact functions
Eliminate bolted joints reducing
hot spots
Reduce required mounting space
for primary contacts
Allow contact finger motion for
Heel - Toe rocking
main contact system. The main
contact portion can be viewed as
the Heel and the arcing portion
the Toe. Its movement is similar
to the rocking of a foot forward and
backward from heel to toe and toe
to heel. When the circuit breaker is
closed, the Heel (main contact
portion) is in contact with the stationary contact and carrying current. At the same time, the Toe
(arcing contact portion) is separated
from the stationary arcing contact.
A compact C Loop current path
permits electromagnetic forces, primarily produced as a result of a
fault current, to supplement the
closing contact forces provided by
the operating mechanism. This
helps to accomplish two important
things:
Heel-Toe Action
The Heel-Toe movement of the
contact fingers is a critical factor in
the efficiency of the Magnum DS
Graphic of Single Magnum DS Contact Finger
Operating mechanism does not
have to be as large or heavy
Higher short time ratings (withstand) are achievable
Magnum DS Standard Frame (12 Finger) Contact Assembly
Contact
Finger
Pivot
Point
Dual
Flexible
Connections
Moving
MainContact
Conductive Pad
(Heel)
Moving
Arcing
Contact
Area
(Toe)
Toe
(Arcing Contact)
Heel
(Main Contact)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Circuit Breaker Features
July 2003
Integral Arc Runner
The integral arc runner serves a
dual purpose:
Contact Wear Indicator
A contact wear indicator provided
for each primary contact structure
permits their condition to be determined. This is accomplished by
viewing the contacts while in the
closed position only.
Functions as circuit breaker fixed
arcing contact
Functions as a critical part of the
arc chute
,,,
yyy
,
y
yy
,,
y
,
,,,
yyy
,
y
,,
yy
,,,
yyy
yy
,,
,
y
,,
yy
,,
yy
,,
yy
,
yy
,
,,,,
yyyy
,,,,
yyyy
,,,,,
yyyy
y
The contact wear indicator is the
relative position of the individual
Magnum DS Arc Running System (Crosssectional View)
Top Arc
Plate
contact fingers to a narrow, sideto-side ledge inside the arc chamber. When the contacts are in good
condition, the narrow ledge is covered by the back end of the contacts and not visible. When the
narrow ledge becomes visible with
the primary contacts closed, contact replacement is indicated.
Integral Arc Runner Viewed from Top of Circuit Breaker
Integral
Arc Runner
Integral
Arc Runner
Current
Flow
xxxxxxxx
x
x
x
x
xxxxxxxx
Current
Flow
Contact Wear Indication
Side-to-Side
Ledge
Side-to-Side
Ledge
Contact Wear
Inspection Area
(Ledge Not Visible
Under Contacts)
Contact Wear Indicator - Contacts
Closed and in Good Condition
PG01301001E
Contact Wear
Inspection Area
(Ledge Now Becoming
Visible Under
Contacts)
Contact Wear Indicator - Contacts
Closed and Wear is Indicated
For more information visit: www.cutler-hammer.eaton.com
17
18
Circuit Breaker Features
July 2003
Arc Chambers
Arc chambers, one per pole, are
used to insulate and isolate each
pole from one another, from the
rest of the circuit breaker, and from
operating personnel.
Arc Chute
Enclosed within each arc chamber
is an arc chute which mounts over
each set of primary contacts.
Alternating V-shaped arc chute
plates effectively attract the arc and
interrupt it. Each arc chute has a
baffled cover to assist with the
speed and efficiency of the interruption.
Partial Top Rear View Breaker (One Arc Chute Removed)
Arc Chute (Bottom View)
Baffled Cover
Arc Chamber
Alternating
V Shaped
Plates
Top Arc Plate
for
Arcing Contact
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Circuit Breaker Features
July 2003
Manual Operation
On manually operated circuit
breakers, the closing spring is
charged manually. This is accomplished through the use of the front
mounted spring-charge handle. It
takes from 5 to 7 downward strokes
on the handle to complete the
charging process.
Magnum DS Circuit Breaker Being Manually Charged
Standard manually operated circuit
breakers are closed and opened by
hand using the front mounted
Manual ON and Manual OFF
buttons respectively. Access to
these buttons can be limited by the
use of an optional, padlockable
cover. Complete access to the
ON button can be prevented with
an optional prevent close cover.
Spring and primary contact status
indicator windows are located just
above the pushbuttons.
Optional electrically operated
devices are available to automatically close or trip open manually
operated circuit breakers, and are
field installable.
Motor Operator Installed
An optional motor operator is used
to charge the closing spring automatically. It can be field installed in
a manually operated circuit breaker.
Manual circuit breakers are prewired for this addition.
Electrical Operation
The closing spring is charged automatically by the optional motor operator. It can also be manually charged.
Manual ON and Manual OFF buttons are also provided as described
under manual operation.
Through the use of a mechanical antipump feature, an open circuit breaker
only accepts one attempt to reclose
even if the close command continues,
preventing motor operator burnout.
Motor Operator
A standard circuit breaker with electrical operation also has optional electrically operated devices available to
automatically close or trip open the
circuit breaker.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
19
20
Circuit Breaker Features
July 2003
Breaker Secondary Connectors
(Black)
Magnum secondary connectors
provide reliable low impedance
connections for up to 60 terminal
points of breaker control wiring.
The secondary connectors are black
in color and consist of 2 blocks,
each with 30 terminal points. The
terminals receive plug-in type pin
and socket wire terminals. Terminal
points have dedicated locations to
receive the breaker accessory
devices and to facilitate standardized automated testing of the control wiring and accessories during
breaker manufacturing. Labels are
provided on the blocks to assist the
customer in terminal point identification and use.
The dedicated secondary connectors make it easy to add accessories
(like shunt trips, spring release
devices, etc.) to the breaker at the
point of use with field option kits.
Wiring removal from breaker secondary connector is easily accomplished using an extraction tool
(AMP part number 305183).
Secondary Terminal Blocks
(White)
White secondary terminal blocks
can be provided mounted at the top
front of the breaker for customer
use. The 6-point terminal blocks
have hinged IP20 finger-proof covers and are designed to terminate
various customer wire terminals
including ring type terminals. Up
to 72 terminal block points can be
accommodated for Standard and
Double frame breakers. Up to 48
terminal block points can be accommodated for Narrow Frame breakers.
Secondary Wiring Removal Tool
Mounted Secondary Terminal Blocks
Closed Hinged
Covers with
Testing Holes
Open
hinged
Covers
Wire kits and terminal block kits are
available for use by the panel
assembler to custom configure the
black breaker secondary connectors
to the white terminal blocks. As an
option, factory pre-wired cassettes
are available for drawout circuit
breakers.
Secondary Terminals and Terminal Wires
Top View Secondary ConnectorsCharged
Secondary Connector Labels
Labels Legend
OTS
UVR
ATR
Overcurrent Trip Switch
Undervoltage Release
Automatic Trip Relay
(520M and 1150 Trip
Units Only)
INCOM PowerNet
Communications Network
A BUS (Future Use)
A/S Auxiliary Contacts
NEUTRAL Neutral Sensor Input
GF SGND Source Ground Input
ZONE Zone Interlocking
ST Shunt Trip
SR Spring Release
MOTOR Charging Motor
LCS Latch Check Switch
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Digitrip RMS
Trip Unit Summary
Magnum circuit breakers can use
any one of a family of microprocessor-based, true rms sensing Digitrip
RMS electronic trip units:
Digitrip
Digitrip
Digitrip
Digitrip
Digitrip
RMS
RMS
RMS
RMS
RMS
220
520
520M
520MC
1150
The trip units themselves are self
powered; no external power is
required to operate the protective
systems. Current signal levels and
the control power are derived from
integrally mounted torroidal wound
current sensors. The use of torroidal wound sensors reduces magnetizing currents, resulting in
improved metered value accuracy
over a broad range of sensor ratings.
All trip unit models, except for
model 220, have red LEDs on the
face of the trip unit to indicate the
cause for an automatic trip operation, for example earth fault, overload or short circuit. They flash red
to make the indication. A battery in
the trip unit maintains the trip indication until the Reset/Battery Test
button is pushed. The battery is
satisfactory if its LED lights green
when the Battery Check button is
pushed.
A clear, tamper-proof, plexiglass
cover sits on the front of the circuit
breaker over the trip unit. This
cover allows the settings to be
viewed but not changed, except by
authorized personnel. The cover is
held in place by two cover screws.
Security is insured by the insertion
of a standard meter seal through
the holes in both of the cover
retention screws.
Magnum Hand Held Tester
Common Features
All trip units have a green light
emitting diode (LED), labeled
Status, which blinks approximately
once each second to indicate that
the trip unit is operating normally.
This same Status LED will blink at a
faster rate if the trip unit is in a
pick-up or overload condition.
Rating Plugs
All Magnum DS circuit breaker trip
units use a fixed type rating plug.
Rating plugs are available in
ampere ratings of 200 through 6000
amperes. The current rating of the
rating plug must match the current
rating of the integrally mounted
current sensors. Therefore, the
continuous current rating of the circuit breaker cannot be changed by
only changing the rating plug.
The rating plug performs a number
of functions:
Trip units are interchangeable in
the field, except for Model 520MC
and Model 1150. Contact CutlerHammer for interchangeability
details.
A functional local test of a major
portion of every trip units electronic circuitry and the circuit breakers
mechanical tripping action can be
verified through the trip units test
receptacle. Every test receptacle is
supplied with a test receptacle
cover. This is accomplished using
a Digitrip Test Kit which provides a
secondary injection test. A small
hand held functional Test Kit can
also be used to check circuitry and
mechanical tripping functions. In
addition, the model 1150 trip unit
has an integral testing system.
PG01301001E
Rating Plug Installed in Digitrip 1150
It tells the trip unit what the rating is of the current sensors. A
label on the rating plug clearly
states that the rating plug and
current sensors must have the
same rating.
It determines the maximum
instantaneous setting which is a
function of the current sensor
rating.
Lifting the rating plug lid will
expose a small battery which supplies power for the trip units cause
of trip LEDs.
If the rating plug is removed from
the trip unit, the circuit breaker will
open (trip) if it is carrying current.
The rating plug should always be
secured in position when the circuit
breaker is in use.
For more information visit: www.cutler-hammer.eaton.com
21
22
Trip Units and Communications
July 2003
Digitrip 220
The Digitrip 220 Trip Unit is
designed to provide basic overcurrent protection with maximum
economy. The Model 220 is available on Narrow and Standard
Frame Magnum Circuit Breakers up
to 3200 amperes. Product features
include:
LI Protection Option
Unit Status LED (Green)
Indicator
Microprocessor-Based True
RMS Sensing
Long Delay Pick-up Setting
fixed at In
Long Delay Time Setting fixed
at 10 seconds at 6xIn
Long Time (Thermal) Memory
Trip
Overtemperature Trip when
temperature exceeds 85C
Instantaneous Pick-up
adjustable from 2x to 10x In and
M1
Neutral Protection
Test Port with cover to receive
Hand Held Tester
Note:
The Digitrip 220+ is coming
soon.
The Digitrip 220+ will replace the
Digitrip 220 Trip Unit some time in
late 2003. The Digitrip 220+ Trip
Unit will have the following features when it is phased into production:
The Long Delay Pick-up
Setting will be changed to
adjustable from 0.4 to 1.0 Ir
The Long Delay Time Setting
will be changed to adjustable from 2 to 24 seconds at 6 x
Ir
LED (Red) Trip Indicators will
be added for Long Delay and
Instantaneous Trip Functions
Battery Included to Power
Cause of Trip LEDs
Reset/Battery Test
Pushbutton
Contact Cutler-Hammer for the
future availability of the Digitrip
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Digitrip 520
The Digitrip 520 Trip Unit is a
versatile trip unit with added features designed to provide
increased flexibility in overcurrent
protection and coordination. The
Model 520 is available on all
Magnum DS Circuit Breakers.
Product features include:
LSI and LSIG Protection
Options with adjustable
Instantaneous Off Setting
Unit Status LED (Green)
Microprocessor-Based True
RMS Sensing
Long Delay Pick-up Setting
adjustable from 0.4 to 1.0 Ir
Long Delay Time Setting
adjustable from 2 to 24 seconds
at 6 x Ir
Long Time (Thermal) Memory
Trip
Overtemperature Trip when
temperature exceeds 85C
Short Delay Pick-up setting
adjustable from 2 to 10 Ir and M1
Short Delay Time Setting
adjustable flat response from 0.1
to 0.5 seconds and I2t Response
at 0.1, 0.3 and 0.5 seconds
Adjustable Instantaneous
Pick-up Settings, Off, 2x to 10x
In and M1
Ground Pick-up Setting
adjustable from .25 to 1.0 x In
Neutral Protection (Model LSI
Trip Unit)
Ground Time Setting
adjustable flat response from 0.1
to 0.5 seconds and I2t Response
at 0.1, 0.3 and 0.5 seconds
Zone Interlocking of Short
Time and Ground Fault Time
Delay Functions
Test Port with Cover to
receive Hand Held Tester
LED (Red) Trip Indicators for
Long Delay, Short Delay,
Instantaneous and Ground Fault
Trip Functions
Battery Included to Power
LEDs
Reset/Battery Test
Pushbutton
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
23
24
Trip Units and Communications
July 2003
Digitrip 520M
The Digitrip 520M Trip Unit
includes all the features of the 520
Trip Unit with the following additions:
LSI,LSIG and LSIA Protection
Options with adjustable
Instantaneous Off Setting
4 Digit LCD Display
Step Pushbutton to Scroll
through the LCD Display
Data:
PH1 Phase 1 (A) Current
PH2 Phase 2 (B) Current
PH3 Phase 3 (C) Current
PH4 Neutral Current
PH5 Ground Current
HI
Highest Phase Current
OL
Overload Condition
HELP Trip Unit Error
Magnitude of Trip Current
Optional Earth Alarm/Power
Supply Module:
Powers the trip units 4
Digit LCD Display through
the breaker secondary contacts with a customer supplied
voltage source:
24-48 Vdc
110 Vac
220 Vac
Provides a ground fault
alarm contact (when used
with LSIA)
Provides a ground fault
trip contact (when used with
LSIG)
Provides a High Load
Alarm contact (when used
with LSI)
Alarm Contact rating (with
resistive load):
0.5 Amp at 220 Vac
1.0 Amp at 110 Vac
1.0 Amp at 24-48 Vdc
High Load Indicator LED
(RED) (LSI Trip Units)
Note: If an Ground Alarm/Power
Supply Module is not provided, the
4 Digit LCD Display will power up
when the 3 phase currents reach
approximately 20% of the sensor
rating or 30% of a single phase
current.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Digitrip 520MC
The Digitrip 520MC Trip Unit
includes all the features of the
520M Trip Unit, but also includes
ampere-based communications
capability. The 520MC Trip Unit has
the following additions:
Communications Functions
and Data:
Transmit LED (Red) indicates
when trip unit is transmitting
INCOM signal
Device Settable INCOM
Address from 001 to 999 hexadecimal
Bkr Status (Open, Closed,
Tripped)
PH1
Phase 1 (A) Current
PH2
Phase 2 (B) Current
PH3
Phase 3 (C) Current
PH4
Neutral Current
PH5
Ground Current
LDPU
Long Delay Pick-up
SDT
Short Delay Trip
INST
Instantaneous Trip
GNDT
Ground Fault Trip
PLUG
Plug Trip
MCR
Making Current
Release
OTEMP Over Temperature
HL High Load (LSI only)
Earth Alarm/Power Supply
Module is Supplied as
Standard to power trip unit
communications functions
The 520MC is designed for applications where communication capability is specified with maximum
economy. The 520MC Trip Unit
communicates current-based information, but does not have the voltage, power, harmonic or remote
control capability of the Digitrip
1150 Trip Unit. The 520MC
is ideally suited for application on
feeder breakers and can be used in
tandem with mains and tie breakers
that are equipped with the full
capability of the 1150 Trip Unit.
Note: Digitrip 520MC requires
PowerNet Version 3.2 or higher if
PowerNet Software is used.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
25
26
Trip Units and Communications
July 2003
Wiring Diagram for 520M Family Models with
Ground Alarm/Power Supply Module
Ground
Fault Trip
Ground
Fault Alarm
A-10
A-11
A14
A-15
G-ALM 1
J4-4
G-ALM 2
J4-3
ATR Volt.
J4-2
ATR COM
J4-1
J3-2
Output J3-3
Output +
J3-1
Remote
Control Voltage
G-Alarm
K2-6
K2-3
Ground Alarm / Power Supply Module
K2-1
Ground Alarm/Power Supply Module for
520M or 520MC Trip Units
Digitrip 520M/MC
Available
Input Voltages
120 VAC
230 VAC
24-48 VDC
Style 2
Number
7802C83G01
7802C83G02
7802C82G01
Contact Rating (resistive load)
AC 0.5A @ 230VAC
AC 1A @ 120VAC
DC 1A @ 48VDC
Verify input voltage rating before energizing circuit.
When used in conjunction with a T. U. Cat. 5MWLSIG,
5MLSIG, 5CWLSIG or 5CLSIG, will indicate GF trip.
When used in conjunction with T.U. Cat. 5MLSIA or
5CLSIA, will indicate GF alarm.
having
UnitCat
When used in conjunction with a Trip
Trip Unit
5MLSI
indicate High Load alarm.
will alarm.
protection,
LSI
will indicate
high load
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Digitrip 1150+
The Digitrip 1150 + is an
enhanced version of the 1150
trip unit that provides comprehensive protection, metering, communications, relay and remote control
capabilities. For a complete listing
of the Digitrip 1150+ Trip Unit capabilities, refer to its Instruction
Leaflet. The following is a brief
first level summary of the 1150+
product features:
LSI,LSIG and LSIA Protection
24 Character Digital LED
Display
Unit Status LED (Green)
Indicator
Programmable Protective
Settings:
I2T and I4T Curves
Moderately Inverse, Very
Inverse and Extremely
Inverse IEEE Curves
IEC Curves
Neutral Protection
(Model LSI Trip Unit)
Instantaneous Off Setting
Ground Fault Trip or Alarm
Undervoltage and
Overvoltage Protection (Trip
or Alarm)
Underfrequency and
Overfrequency Protection
(Trip or Alarm)
Reverse Power (Trip)
Voltage Unbalance
Protection (Trip or Alarm)
Phase Rotation (Alarm)
Long Time (Thermal) Memory
Trip
Overtemperature Trip when
the temperature exceeds 85C
View Selection Touch Pads
for Local Metering Display:
Current (1% Accuracy, Three
Phase, Neutral and Ground
Voltage L-L (1% Accuracy)
Frequency ( 0.05 Hz)
Power & Energy (2%
Accuracy)
Kilowatts (kW)
Kilowatt Hours (kWH)
Kilovoltamperes (kVAR)
PG01301001E
kVA Hours
Fixed 15 Minute Demand
for kW, kVAR & kVA
Sliding 15 Minute
Demand for kW or kVA
Power Factor Including
Min and Max
Power Quality Monitoring,
Trip and Alarm:
Waveform Capture
For more information visit: www.cutler-hammer.eaton.com
% Total Harmonic
Distortion
Kilovoltamperes (kVAR)
Programmable Alarm
Contacts
Breaker Control (Remote
Open & Close via
Communications)
Operations Counter
(Note: continued next page)
27
28
Trip Units and Communications
July 2003
Test Port with cover to receive
Digitrip Hand Held Tester
Power Receptacle for
Auxiliary Power Module to
power up trip unit when breaker
is in the Disconnect or Remove
Position
Internal Self-Test
Accessory Bus for additional
programmable contacts
Battery Included to Power
LEDs
Reset/Battery Test
Pushbutton
Communications Functions
and Data:
Communications information
and functions are comprehensive. Refer to the 1150 Trip Unit
Instruction Leaflet I.L.
70C1036H03 for complete details
and capabilities.
Power Relay Module
The Power Relay Module is provided with the 1150 Trip Unit to perform the following features:
Power Supply to power the trip
units 24 Character LED display and
communications functions. The
power relay module requires an
external customer supplied voltage
source that is wired through the
breaker secondary contacts. The
source voltage is selected at order
entry and includes the following
voltage options with 10% tolerance and 10VA burden.
Power Relay Module for 1150 Trip Unit
Alarm Contact Ratings
(resistive load):
0.5 Amp at 230 Vac
1.0 Amp at 120 Vac
1.0 Amp at 24-48 Vdc
Potential Transformer (PT)
Module
The PT module provides system
line voltage information to the
Digitrip 1150 Trip Unit. It consists of
a 3-phase, 3-wire input and 3-wire
output step down transformer with
a wye to wye hookup. A white disconnecting plug is provided to disconnect the PT Module circuit from
the line voltage during dielectric
testing.
The PT Module primary input voltage connection is selected when
the breaker is ordered to accommodate normal or reverse feed application. PT Module line-side pr
load-side
voltage connections are made via
hard wire termination to the breaker upper or lower conductors.
The normal convention is that the
breaker line side is the upper conductors, with power flowing
through the breaker from top to
bottom. In reverse feed applications, the bottom conductors are
the line side with power flowing
through the breaker from bottom to
top. In this case the trip unit will
indicate REVERSE POWER, but the
reading can be made an absolute
value by installing a jumper from
B3 to B7 on the breaker secondary
contacts.
PT Module with Dielectric Disconnect Plug
24-48 Vdc
120 Vac
240 Vac
Programmable Relay Contacts
via the Digitrip 1150 Trip Unit trip
and alarm programming menus:
Contact A: Alarming and
Tripping Relay for use with the
trip unit protective functions.
Contact B: Block close relay
prohibits the remote closing of
the circuit breaker
Contact C: This latch relay
will hold status upon loss of auxiliary power
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Power Relay Module Connection to 1150 Trip Unit
SR
110
220
230 VAC
110 VAC
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
29
30
Trip Units and Communications
July 2003
Accessory Bus
The accessory bus feature on the
Digitrip 1150 Trip Unit permits the
application of additional discrete
programmable relay contacts by
the use of one or more Digital
Relay Modules. The accessory bus
is brought out from the trip unit to
secondary terminals A17 and A18
for external connections to the
Digital Relay Modules via twisted
pair communications cable.
Programming
The Digitrip 1150 Trip Unit can be
programmed to drive the Digital
Relay Module relay contacts for
any combination of the following:
Digital Relay Module
The Digital Relay Module is mounted by DIN Rail, separate from the
circuit breaker. Up to 4 Digital
Relay Modules (addresses 001 to
004) can be applied per circuit
breaker. Each Digital Relay Module
has has relays with form C contacts
rated at 10 amps maximum at 250
Vdc. A control voltage source of
120 Vac 20% or 38-125 Vdc is
required to power each unit.
Auxiliary Switch
Bell Alarm
Long Delay Trip
Short Delay Trip
Instantaneous Trip
Ground Fault Trip
Ground Fault Alarm
High Load Alarm
Deadman
Watchdog
INCOM Network with Remote Master Computer BIM II
Typical IBM
Compatible
Computer
Breaker
Interface
Monitor
(BIM )
See View A
Twisted Pair.
No. 18 AWG.
Typical Magnum
Circuit Breaker
with Digitrip Trip Unit
Cut-off Shield or connect to
unused customer
terminal -- Do not Ground.
1
1
Baud Rate
1200 or 9600
(Y)
001
(BL)
002
3 Digit
INCOM
Address
View A
NOTICE
100 OHM 1/2W terminating
resistor required on network
even if network is unused
Refer to Master Circuit Breaker Connection Diagrams in Appendix C.
Modular telephone connector, Type RJ11, supplied by user.
Ground shielding at computer BIM as shown. Where devices
are daisy-chained, interconnect shielding, but do not ground the connection.
100 ohm watt carbon resistor required at last breaker.
See T.D. 17-513.
See Appendix D-11 for programming INCOM function.
AEM is
compatible with Digitrip 1150 with AEM firmware version 7.1and the
Digitrip 1150 set in the DT 910 COMM mode. (See page D-11)
Breaker Interface Module (BIM )Version 3.12 is compatible with Digitrip 1150
3.13 or greater is compatible with Digitrip 1150
BIM version
Cat # 1****.
1
Cat # 1****
1P and Cat # 11****.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Digital Relay Accessory Module
110
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
31
32
Trip Units and Communications
July 2003
MODBUS TRANSLATOR Wiring
110
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Trip Units and Communications
July 2003
Trip Unit Summary Table
DIGITRIP 220
DIGITRIP 520
DIGITRIP 520M
DIGITRIP 520MC
200A-3200A
200A-6000A
200A-6000A
200A-6000A
200A-6000A
42 through 100kA
42 through 100kA
42 through 100kA
42 through 100kA
42 through 100kA
Yes
Yes
Yes
Yes
Yes
Ordering Options
LI
LSI, LSIG
LSI, LSIG, LSIA
LSI, LSIG, LSIA
LSI, LSIG, LSIA
Fixed Rate Plug (In)
Yes
Yes
Yes
Yes
Yes
Overtemperature Trip
Yes
Yes
Yes
Yes
Yes
1.0 x (In) Fixed
0.4-1.0 x (In)
0.4-1.0 x (In)
0.4-1.0 x (In)
0.4-1.0 x (In)
10 seconds
TRIP UNIT TYPE
Ampere Range (16)
Interrupting Rating at 480V
rms Sensing
DIGITRIP 1150
PROTECTION AND COORDINATION
Protection
Long
Delay
Long Delay Pickup
Long Delay Time I2t at 6 x Ir
2-24 Seconds
2-24 Seconds
2-24 Seconds
2-24 Seconds
Protection
Long Delay Time I4t
No
No
No
No
1-5 Seconds
(L)
Long Delay Thermal Memory
Yes
Yes
Yes
Yes
Yes
High Load Alarm
No
No
No
No
0.5 - 1.0 x (Ir)
Short
Delay
Short Delay Pickup
Short Delay Time I2t at 8 x Ir
No
No
200-1000% x (Ir) and M1
100-500 ms
200-1000% x (Ir) and M1
100-500 ms
200-1000% x (Ir) and M1
100-500 ms
200-1000% x (Ir) and M1
100-500 ms
Protection
Short Delay Time Flat
No
100-500 ms
100-500 ms
100-500 ms
(S)
Short Delay Time ZSI
No
Yes
Yes
Yes
Yes
Instantaneous
Protection
Instantaneous Pickup
Making Current Release
200-1000% x (In)
Yes
200-1000% x (In) and M1
Yes
200-1000% x (In) and M1
Yes
200-1000% x (In) and M1
Yes
200-1000% x (In) and M1
Yes
100-500 ms
(I)
Off Position
No
Yes
Yes
Yes
Yes
Ground
Ground Fault Alarm
No
No
Yes
Yes
Yes
Fault
Ground Fault Pickup
No
25-100% x (In)
25-100% x (In)
24-100% x (In)
Protection
Ground Fault Delay I2t at .625 x ln
No
100-500 ms
100-500 ms
100-500 ms
100-500 ms
(G)
Ground Fault Delay Flat
No
100-500 ms
100-500 ms
100-500 ms
100-500 ms
25-100% x (In)
Ground Fault ZSI
No
Yes
Yes
Yes
Yes
Ground Fault Thermal Memory
No
Yes
Yes
Yes
Yes
Neutral Protection (N)
SYSTEM DIAGNOSTICS
Yes
Model LSI Only
Model LSI Only
Model LSI Only
Model LSI Only
Cause of Trip LEDs
No
Yes
Yes
Yes
Yes
Magnitude of Trip Information
No
No
No
Yes
Yes
Remote Signal Contacts
No
No
Yes
Yes
Yes
Programmable Contacts
No
No
No
No
Yes
Digital Display
No
No
4 Char. LCD
4 Char. LCD
24 Char. LED
Current (%) Full Scale Sensor
No
No
Yes
Yes
Yes +/- 1%
Voltage (%) L to L
No
No
No
No
Yes
Power and Energy (%)
Apparent Power kVA and Demand
No
No
No
No
No
No
No
No
Yes
Yes
Reactive Power kVAR
No
No
No
No
Yes
Power Factor
No
No
No
No
Yes
Crest Factor
No
No
No
No
Yes
Power Quality - Harmonics
No
No
No
No
Yes
% THD
No
No
No
No
Yes
INCOM/PowerNet
SYSTEM MONITORING
SYSTEM COMMUNICATIONS
Type
No
No
No
Power Supply
N/A
N/A
Optional PRM in Breaker
ADDITIONAL FEATURES
Trip Log (3 Events)
No
No
No
No
Electronic Operations Counter
No
No
No
No
Yes
Testing Method
Test Set
Test Set
Test Set
Test Set
Integral and Test Set
Waveform Capture
No
No
No
No
Yes
PRM in Breaker
INCOM/PowerNet/TripLink
PRM in Breaker
Yes
In = Rating Plug and Sensor Rating
Ir = Long Delay Pickup Setting
Not to exceed 1200 amperes
Test set for secondary injection
Model 220+ will be available in the second half of 2003. Long Delay Pickup will be adjustable 0.4-1.0 x (In), Long Delay time will be adjustable 2-24 seconds. Cause of Trip Indicators with Battery Back-up
will be added. Contact Cutler-Hammer for availability.
Model 1150+ will be available in the second half of 2003. Over and Undervoltage Alarm or Trip, Over and Underfrequency Alarm or Trip, Voltage Unbalance Alarm or Trip, Reverse Power Trip, and Phase
Rotation Alarm will be added. Contact Cutler-Hammer for availability.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
33
34
Trip Units and Communications
July 2003
Rating Plugs and Matching Sensors
Current Sensor
Toroidally wound current sensors
are installed at the rear of the circuit breaker on the lower horizontal
terminals. They are available in
ampere ratings of 200 through 6000
amperes, and must match the current rating of the installed rating
plug.
Ratings (Amperes)
200
250
300
400
600
630
2500
3000
3200
4000
5000
6000
800
1000
1200
1250
1600
2000
Note: Refer to Tables 3.4, 3.5 and 3.6 in the
section entitled Circuit Breaker Catalog
Number for the availability of sensor and rating plug ratings for specific circuit breaker
frame sizes.
The sensors produce an output current proportional to the load current. Under preselected conditions
of current magnitude and time, the
sensors furnish the trip unit with a
signal and the energy required to
open (trip) the circuit breaker.
The current rating of the installed
sensors can be easily viewed from
the rear of the circuit breaker
through small viewing windows.
The viewing windows are part of
the sensor cover plate which is
removed to change the sensors.
Mechanical Trip Flag Pop-Out
Indicator
The mechanical trip flag pop-out
indicator is an overcurrent indication feature that can be supplied as
an option on Magnum DS Circuit
Breakers with integral trip units.
This device is located just above
the trip unit on the breakers front
faceplate. In the event the trip unit
trips the breaker on an overcurrent
condition, the red trip flag releases
and pops out to give local visual
indication. This trip indication is in
addition to any LED trip indication
provided by the trip unit.
The red flag can be reset by manually pushing it back in. The circuit
breaker can be re-closed, even if
the flag is not reset. An optional
Overcurrent Trip Switch (OTS) is
available in the event that an electrical lock-out is required on an
overcurrent trip condition.
Neutral Sensor (unmounted)
Neutral current sensors are available
for customer installation. The additional sensor is not supplied with the
circuit breaker and must be ordered
separately. They are wired to the trip
unit through the secondary contacts
on the circuit breaker.
Making Current Release
The Making Current Release (MCR)
is a standard safety feature provided on all Magnum DS Circuit
Breakers that are equipped with
integral trip units. The MCR provides an instantaneous trip when
closing on a fault current which
exceeds a specified magnitude.
The MCR is non-adjustable, preset
Current Sensor Cover in Place Over Sensors
Current Sensor Cover and One Sensor Removed
Current
Sensor
Cover
Sensor
Rating
Sensor Rating
Viewing
Window
Wiring
Plug
For more information visit: www.cutler-hammer.eaton.com
Toroidal
Current
Sensor
PG01301001E
Trip Units and Communications
July 2003
to trip the breaker when the peak
instantaneous current exceeds 25 x
In (In is established by the breakers
current sensors and rating plug).
Digitrip RMS 1150 Programmable Trip Unit Installed
Trip Flag
Pop-Out
Indicator
The MCR is enabled for only the
first two cycles following the circuit
breaker closing operation. When
the MCR trips the breaker, the red
trip flag of the mechanical indicator
will pop out and the red
Instantaneous LED of the trip unit
will flash if the breaker is so
equipped.
Bell Alarm/Overcurrent Trip
Switch (OTS)
The Bell Alarm/Overcurrent Trip
Switch (OTS) is an overcurrent indication feature that can be supplied
as an option on Magnum DS Circuit
Breakers with integral trip units.
The OTS is physically mounted on
the Mechanical Trip Flag Pop-out
Indicator. The OTS Switch includes
2 Form C contacts that are wired to
the breaker secondary terminals as
shown in the Magnum DS breaker
connection diagram. These contacts are available for external
wiring to provide remote trip indication or for electrical lock-out of a
circuit breaker as required.
In the event the trip unit trips the
breaker on an overcurrent condition, the red flag of the Mechanical
Trip Flag Pop-ot Indicator releases
and pops out and the OTS contacts
change state. The OTS Switch can
be reset by manually pushing in
the red trip flag. When the trip flag
is reset, the OTS Switch contacts
return to their normal state.
High Instantaneous Trip
Magnum DS Circuit Breakers that
are rated 100kA and manufactured
in the Standard Frame with 800 to
3200 ampere continuous current
ratings (MDSC08 to MDSC32) are
equipped with a high instantaneous
trip. This instantaneous trip system consists of small air core sensors (one per phase) which produce a signal and transmit it back
to the trip unit. When the fault current approaches the 85kA withstand rating of the circuit breaker,
Auxiliary
Power
Module
Port
Rating
Plug
In = 800A
Test
Receptacle
(with
Cover)
the trip unit trips the breaker
instantaneously. This allows the
breaker to be applied on a power
distribution system with a 100kA
available fault current while maintaining selectivity up to 85kA.
Long Time Memory (LTM)
Long Time Memory (Thermal
Memory) is a standard feature on
Magnum DS Circuit Breakers supplied with integral trip units. The
thermal memory function provides
overtemperature protection on load
circuits against the effects of
repeated overload conditions. If a
breaker is closed soon after an
overload trip and the current again
exceeds the Long Delay Setting,
the LTM reduces the time to trip to
allow for the fact that the load circuit temperature is higher than normal due to the previous overload
condition. If the breaker continues
to be closed into repeated overload
conditions, the breaker will trip in
successively shorter times to allow
for the cooling of the load circuit.
When the overload condition
returns to normal, the LTM function
begins to slowly reset and will fully
reset back to the normal Long
Delay Time setting after about 10
minutes, provided that another
overload is not experienced.
In some applications, for example
fire pumps, electric welders or during primary injection current testing, it may be desirable to defeat
the LTM. This can be accomplished
at the trip unitby moving a jumper
located inside the cavity behind the
test port cover located at the front
of the trip unit to the Inactive position. The LTM can be reactivated
by returning the jumper to the
Active position.
For more information visit: www.cutler-hammer.eaton.com
35
Trip Units and Communications
July 2003
Over-Temperature Trip
Magnum DS Circuit Breakers
equipped with integral trip units
have an over-temperature trip function provided as a standard feature.
The over-temperature trip is
designed to trip the breaker when
the internal temperature of the trip
unit exceeds 85C. This is the
approximate manufacturers published maximum temperature rating for the trip unit electronic components. An 85C temperature
inside the trip unit indicates that
there are much higher temperatures and potentially significant
heating problems elsewhere in the
circuit breaker enclosure.
When the over-temperature function trips the breaker, the red trip
flag of the mechanical indicator will
pop-out and the red Long Time
Delay LED of the trip unit will flash
is the breaker is so equipped.
Ground Fault Provisions and
Protective Schemes
As a standard feature, Magnum
DS Circuit Breakers are internally
wired with provisions for ground
fault protection. However, ground
fault protection is provided only if
the breaker is equipped with a trip
unit with optional LSIG protection.
Ground fault protection can be easily added to breakers not originally
equipped with a ground fault trip
unit. For example, an LSI trip unit
can simply be changed out with a
like model trip unit that has LSIG
protection. Modifications to the circuit breaker internal wiring are generally not required as long as the
trip unit changeout is with a like
model trip unit.
To provide for maximum application flexibility, breaker ground fault
provisions are wired out to the
breaker secondary terminals for
external use. The secondary terminals can be easily configured to
accommodate the most common
ground fault schemes, including:
NOTE: For detailed wiring diagrams that describe all ground
fault sensing options and
wiring connections, refer to
the Trip Unit Instruction
Leaflet.
Residual Sensing
Residual sensing is the standard or
PG01301001E
default wiring configurations provided. It is also the most common
mode of ground fault sensing used
in 3-pole and 4-pole breaker applications. One current sensor per
pole on each phase conductor is
provided internal to the circuit
breaker. When 3-pole breakers are
applied on 3 phase, 4 wire systems,
an external sensor matched to the
breaker sensor ratio is mounted on
the Switchgear neutral bus and
wired to the breaker secondary
contacts to connect all sensors in
the residual circuit.
Multiple Source/Multiple
Ground
Multiple Source/Multiple Ground
sensing schemes are also possible
on systems with multiple sensors.
Source Ground Sensing
Source ground sensing is commonly found on 3 pole breakers applied
as a main breaker on single-ended
radial or on double-ended systems
where a mid-point grounding electrode is employed.
The zone interlock function provides for hard-wired selective circuit breaker coordination in the
power distribution system. When
employed, breaker secondary terminals B8 and B9 are connected to
establish zones of downstream and
upstream breakers using 3 wires:
Zin, Zout, and a common wire to
establish the zone.
To configure a breaker for source
ground sensing, a shorting jumper
is applied to breaker secondary
contacts B6 and B7 to defeat the
residual sensing mode. An external current sensor is mounted
directly on the bonding conductor
to ground to measure the ground
current flowing in the grounding
electrode conductor and all other
grounding conductors. The sensor
is then wired to the breaker secondary contacts B4 and B5.
NOTE: The secondary current
rating of the sensors must be
1 ampere.
Zero Sequence Sensing
Zero sequence sensing is applied
on main and feeder breakers, and
other breakers employed in zone
interlocking ground protection
schemes.
To configure a breaker for zero
sequence sensing, a shorting
jumper is applied to breaker secondary contacts B6 and B7 to
defeat the residual sensing mode.
Zero sequence sensors with 1000:1
and 100:1 ratios are available for
mounting in the switchgear cable
compartment. The sensor internal
window dimensions are 4.5 x 13.5
inches (114 x 342 mm) for accommodating power cables. The zero
sequence sensors are wired to
breaker secondary contacts B4 and
B5.
For more information visit: www.cutler-hammer.eaton.com
Zone Interlocking
Zone Selective Interlocking is a
standard feature provided on
Magnum DS Circuit Breakers that
are supplied with Digitrip 520 or
higher trip units. The trip unit
Short Time and Ground Fault Time
Delay Zone Interlock function is
wired out to breaker secondary terminals B8 and B9 for customer use.
NOTE: For detailed wiring diagrams that describe zone selective interlocking schemes and
wiring connections, refer to
the trip unit instruction leaflet.
In the event that a fault current on
the system exceeds the trip unit
Short Time or Ground Fault pick-up
settings or the Short Delay Setting
2xIr is exceeded, the breaker nearest to the fault trips instantaneously. At the same time the trip unit
sends a logic signal to the connected upstream trip unit to restrain it
from tripping immediately and follow its protective delay settings.
Coordination is maintained, the
breaker closest to the fault trips
first and power is only selectively
disrupted.
NOTE: If zone interlocking is
not employed, it may be
defeated by installing a shorting jumper across breaker secondary terminals B8 and B9.
Installing a jumper in this manner
defeats the zone interlock function
and tells the trip unit to follow its
set Short Time and Ground Fault
Time protective delays. If breaker
secondary terminals B8 and B9 are
left as open circuit, the trip unit
Short Time and Ground Fault Time
Delay functions will trip instantaneously if the system fault current
exceeds the pick up setting.
36
37
Fixed Circuit Breakers
July 2003
Fixed Mounted Circuit Breakers
Magnum DS fixed mounted circuit
breakers are commonly applied in
Cutler-Hammer Pow-R-Line C
UL891 certified switchboards and
other specialty power distribution
enclosures and switchboards manufactured by OEMs.
Catalog Number MWK40 wire bundle kits with 30 wires 40 inches
long can be purchased for this purpose. The wire bundles can also
be self-fabricated by the enclosure
manufacturer, provided the proper
AMP terminal and crimping tool
are used.
The fixed circuit breaker construction is simple and economic
because there are no drawout system components. The breaker
bolts directly to the enclosure main
bus, which allows for efficient current transfer under loaded conditions. This improves thermal management and provides for the
design of compact enclosures with
shallow depth.
If the benefit of front accessible
dedicated terminal blocks at the top
front of the breaker is desired, the
terminal block mounting bracket
included in the secondary connec-
Full visual and physical access to
the circuit breaker trip unit, controls, and indicators is available
through the compartment front
panel. A door frame and
escutcheon kit is available as an
option to provide a finished trim to
the front panel cutout. Extensive
accessorization capability of the
breaker is retained, including trip
units, internal accessories, lock-off
devices, and mechanical interlocks.
Primary Terminations
Horizontal pre-drilled terminal pads
are provided as a standard feature
for use in terminating the breaker
to the enclosure bus. Optional vertical adapters can be factory
installed or are available as field
option kits to provide the capability
to terminate the enclosure bus in
the vertical plane. Field option kits
are also available for front connected applications.
tion terminal kit can be used.
Catalog Number MSECBK white
terminal block kits can be purchased and assembled to the
mounting bracket. Catalog
Number MSECWR wire kits can be
purchased to connect the white terminal block to the black AMP connector block points.
Mounting Feet
Metal mounting feet are provided
as a standard feature for use in
securely bolting the breaker to the
enclosure.
Closeup of Fixed Circuit Breakers Connection Possibilities
Standard
Horizontal
Connection
Optional
Vertical
Adapter
Fixed Circuit Breaker (front view)
Secondary Connections
Two black 30-pin AMP connector
blocks are located at the top front
of the breaker to receive up to 60
points of external secondary
wiring. A secondary connection
terminal kit is included with each
fixed breaker to provide for several
wiring options.
The most economic solution is to
terminate external wiring directly to
the black AMP connector blocks.
Mounting
Foot
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Drawout Circuit Breakers
July 2003
Drawout Circuit Breakers
Magnum DS drawout circuit breakers are commonly applied in CutlerHammer Magnum DS UL1558 certified switchgear and other specialty
power distribution enclosures,
switchgear and switchboards manufactured by OEMs.
The primary disconnecting contacts are mounted on the rear of
the breaker so that they can be easily inspected or replaced. Standard
and Double frame breakers have
vertical primary disconnects, while
Narrow frame breakers have horizontal primary disconnects.
Circuit Breaker Being Levered
The Magnum DS drawout circuit
breaker construction is a throughthe-door design. Full visual and
physical access to the trip unit and
all breaker controls and indicators
is available through the compartment front panel. For maximum
safety, circuit breaker levering can
be performed with the compartment door closed. When the circuit
breaker is in the OPEN position, a
padlockable access door can be
raised to receive the levering
device. No special device is
required. Levering can be accomplished with a common 3/8 inch
size square drive and rachet. When
inserted, the levering device holds
the levering access door open. As
long as the access door is raised
open, the breaker is held in the
trip-free condition. The breaker
can be levered to three positions in
the cell compartment. Color coded
position indicators are provided on
the breaker front panel to provide
positive indication of each position:
CONNECT
TEST
DISCONNECT
Green = DISCONNECT
Yellow = TEST
Red = CONNECT.
Secondary Disconnect
Contacts
The breaker secondary disconnecting contacts engage or disconnect
with the cassette secondary contacts as the breaker is levered into
or out of the TEST position.
Rear View Standard Frame Breaker
Rear View Narrow Frame Breaker
Primary Disconnecting
Contacts
The primary disconnecting contacts
(finger clusters) engage or disconnect with the cell compartment bus
stabs as the breaker is levered into
or out of the CONNECT position.
Vertical
Primary
Disconnect
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Horizontal
Primary
Disconnect
38
39
Drawout Circuit Breakers
July 2003
Drawout Cassette
A drawout circuit breaker is used in
combination with a fixed drawout
cassette. The cassette provides for
all the required fixed drawout features as well as fixed primary and
secondary connections. Mounting
locations for cell (TOC) switches,
primary safety shutters and various
key interlocks are part of the cassette design.
Cutler-Hammer offers several drawout cassette options. The narrow frame circuit breaker
mates only with the Narrow
cassette which has built in horizontal stabs and primary terminals.
Optional bolt-on 90 degree
adapters are available to rotate the
primary terminals on the rear of the
cassette to a vertical orientation;
these can be used on either the
line, load or both primary connections.
Standard frame circuit breakers also offer two optional drawout cassettes. Both use vertical
stabs internal to the cassette. The
Universal cassette offers a flat
terminal pad on the rear of the cassette which will accept customer
bus bar connections in various bent
configurations; optional T-bar
adapters are available which can be
rotated to give either vertical or
horizontal terminals. The Basic
cassette has a molded back plane
with vertical aperturers that can be
used when the bus bar connections
will remain vertical. The OEM can
simply continue bus bar through
the openings in the back plane to
form stabs for the circuit breaker.
Note that these stabs must be silver-plated. Optionally, CutlerHammer will supply short straight
pieces which are pre-plated, and
will bolt into the back plane to
accept bolted bus bar connections.
Narrow Frame Breaker and Cassette
supports must be provided. The
design of these supports depends
upon the bus bar configuration and
short circuit rating and is the
responsibility of the assembly
builder.
The cassette's drawout extension
rails can be padlocked to prevent a
circuit breaker from being inserted
during maintenance periods. In
addition, the cassette includes all
required safety interlocks which
function with the circuit breaker's
interlock system to insure safe
operation.
An arc hood is positioned above
where the circuit breaker's arc
chutes will be allowing for zero
clearance mounting when vertically
stacked in an assembly. Mounting
holes are provided at the rear and
in the floor of the cassette for
secure mounting in an assembly.
Universal Cassette With Flat Pads
Basic Cassette Without Optional Stabs
It should be noted that short circuit
currents create very large EM
forces on the bus bars which must
be adequately supported by the
assembly builder. Outline drawings for each cassette give minimum distances from the rear of the
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Phasing on Double-Wide Breakers
July 2003
Phasing on Double-Wide Frame
Breakers
Magnum DS circuit breakers manufactured in the double-wide frame
have two available phasing configurations which must be confirmed
when the breaker is ordered.
Magnum DS Double-Wide Frame Breaker with AABBCC Phasing (front and rear views)
The phasing convention is determined facing the front of the breaker from left to right. For 4-pole
applications, the neutral is located
on the left and is rated 100% of the
breaker continuous current rating.
The following phasing configurations are available:
3-Pole AABBCC
4-Pole NNAABBCC
3-Pole ABCABC
4-Pole NNABCABC
The type of phasing selected
depends on how the circuit breaker
will be applied in the enclosure and
the type of Cutler-Hammer power
distribution enclosure that it will be
applied in.
AABBCC or NNAABBCC
Phasing
AABBCC phasing is the convention
commonly used in Cutler-Hammer
Pow-R-Line C Switchboards using
Magnum DS Circuit Breakers.
The AABBCC convention is recommended for most OEMs manufacturing their own power distribution
enclosures. It is ideal for applications where the breaker is mounted
single high (one breaker in a structure).
ABCABC or NNABCABC
Phasing
ABCABC phasing is the convention
commonly used in Cutler-Hammer
Magnum DS UL1558 Switchgear.
Double-wide breakers with this
type of phasing are designed to
accommodate 2 sets of vertical risers in the same structure. This provides for significant space savings
because two or more standard
frame feeder breakers can be
mounted above or below the dou
PG01301001E
ble-wide breaker in the same structure.
Cutler-Hammer offers Magnum DS
Switchgear power modules with
ABCABC phasing for use by OEMs.
Power Modules provide the OEM
with a shell frame assembly,
which allows for substantial modification. Power Modules consist of
base metal structures, compartment cells and vertical bus.
Typically the OEM will provide the
For more information visit: www.cutler-hammer.eaton.com
value add to customize the power
modules into their own switchgear
design.
The ABCABC convention is more
difficult for OEMs who manufacture
their own power distribution enclosures to apply. Switchgear bus
design and testing as well as placement and balance of the feeder
breaker loads are very important to
assure that phase currents divide
evenly through the double-wide
breaker.
40
Accessory Devices
July 2003
Accessory Devices
A variety of accessory devices are
available for use with Magnum DS
circuit breakers. Unless otherwise
stated, they are all considered
optional devices in the sense that
they are not provided as standard
on a manually operated circuit
breaker. Available accessories are
identified here and discussed in
general terms. For more detailed
information and/or installation
instructions, refer to individual
instruction leaflets dedicated to the
accessories.
Magnum DS circuit breaker accessories are designed to fit all frame
sizes. The accessories fall into one
of three categories:
Plug-in electrical
Internal electrical
Mechanical
Plug-In Electrical Accessories
There are four Magnum DS Plug-In
electrical accessories. Three can be
viewed for identification by name
and rating through viewing windows located in the right front of
the circuit breaker(Figure 1). All
four are plug-in type and can be
factory installed or field installed
using a UL listed kit.
Accessory Viewing Windows
Figure 1 Through-the-Window Electrical Accessories
A second shunt trip (with the same
or different control voltage) can be
mounted in the same space as the
Undervoltage Release (UVR).
When a second shunt trip is used,
one of the auxiliary switch stages
must be used to provide the trip
coil cut off contact.
The four Plug-In accessories are:
Shunt Trip (ST)
Spring Release (SR)
Undervoltage Release (UVR)
Auxiliary Switch
Shunt Trip (ST) - The ST (Shunt
Trip Device, Figures 2 and 3) is an
optional accessory device that is
mounted internal to the circuit
breaker. The ST acts to electrically
open the circuit breaker when its
trip coil is energized by a rated trip
voltage signal (Table 1) that is
applied through the breaker secondary contacts, typically by a control switch or other similar device.
The ST has a dedicated auxiliary
switch with contacts that change
state as the breaker opens, cutting
off trip voltage signal to the trip
coil.
PG01301001E
Figure 2 Shunt Trip with Cutoff
Switch
Figure 3 Shunt Trip Switch Installed
Table 1 Shunt Trip Ratings
Control
Voltages
Operational
Voltage Range
70-110%
24 Vdc
17-26 Vdc
250 W
35
48 Vdc
34-53 Vdc
250 W
35
110-125 Vdc
77-138 Vdc
450 W
35
220-250 Vdc
154-275 Vdc
450 W
35
110-127 Vac
77-140 Vac
450 VA
35
208-240 Vac
146-264 Vac
450 VA
35
Required for less than 35 ms
For more information visit: www.cutler-hammer.eaton.com
Inrush Power
Consumption
Opening
Time
(ms)
41
42
Accessory Devices
July 2003
Spring Release (SR) - The SR
(Spring Release Device, Figure 4) is
an optional accessory device that is
mounted internal to the circuit
breaker. The SR acts to electrically
close the circuit breaker when its
close coil is energized by a rated
close voltage signal (Table 2)
applied through the breaker secondary contacts, typically by a control switch or other similar device.
The breaker must be ready to close
for the SR to close the circuit breaker. The breaker stored energy
springs must be fully charged and
the trip latch must be in the reset
(not the trip) position. If the close
voltage signal is applied before
these two conditions are met, the
SR will not close the circuit breaker.
The close voltage signal must be
removed and then reapplied at a
time when the breaker is ready to
close.
Figure 4 Spring Release with
Optional Latch Switch
Latch Check Switch (LCS) - The
LCS (Latch Check Switch) is an
optional accessory switch mounted
internal to the circuit breaker that
changes state when the breaker is
ready to close (the closing springs
are fully charged and trip latch is in
the reset position). The LCS is very
useful in fast transfer and automatic transfer applications when it is
important that the breaker
responds to close on a single close
voltage signal of rated magnitude.
The LCS is available in two versions:
Latch Check Switch Wired To
Spring Release - The LCS can
be wired directly to the Spring
Release Device to provide a contact closure when the breaker is
ready to close. This delays the
voltage signal to the Spring
Release until the breaker is ready
to close.
Figure 5 Undervoltage Release
Latch Check Switch Wired
For External Use - The LCS can
also be wired to the breaker secondary contacts. One Form C
contact is provided for remote
indication that the breaker is
ready to close for use in breaker
external customer control wiring.
Undervoltage Release - The
undervoltage release is an optional
device on both manually and electrically operated circuit breakers
(Figure 5). It opens the circuit
breaker when its supply voltage
falls to between 35-60% of rated
voltage. If the release is not energized to 85% of its supply voltage,
the circuit breaker cannot
be closed electrically or manually
(Table 3).
Figure 6 Shunt Trip, Spring Release
and Undervoltage Release Installed
Table 2 Spring Release Ratings
Control
Voltages
Operational
Voltage Range
70-110%
24 Vdc
17-26 Vdc
250 W
40
Inrush Power
Consumption
Closing
Time
(ms)
48 Vdc
34-53 Vdc
250 W
40
110-125 Vdc
77-138 Vdc
450 W
40
220-250 Vdc
154-275 Vdc
450 W
40
110-127 Vac
77-140 Vac
450 VA
40
208-240 Vac
146-264 Vac
450 VA
40
Required for less than 200 ms
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Accessory Devices
July 2003
Table 3 Undervoltage Release
Opening
Inrush/Continuous Time
Power Consumption (ms)
Operational
Voltage Range
85-110%
Dropout
Volts
30-60%
20-26 Vdc
7-14 Vdc
250 W/18 W
70
27-35 Vdc
10-19 Vdc
275 W/15 W
70
41-53 Vdc
14-29 Vdc
275 W/18 W
70
110-125 Vdc
94-138 Vdc
33-75 Vdc
450 W/10 W
70
220-250 Vdc
187-275 Vdc
66-150 Vdc
450 W/10 W
70
110-127 Vac
94-140 Vac
33-76 Vac
450 VA/10 VA
70
208-240 Vac
177-264 Vac
62-144 Vac
400 VA/10 VA
70
380-415 Vac
323-457 Vac
114-249 Vac
480 VA/10 VA
70
480 Vac
408-528 Vac
144-288 Vac
400 VA/10 VA
70
600 Vac
510-660 Vac
180-360 Vac
400 VA/10 VA
70
Control
Voltages
24 Vdc
32 Vdc
48 Vdc
Required for 200 ms
Required for 400 ms
Auxiliary Switch - An auxiliary
switch is an optional accessory
device that is mounted internal to
the circuit breaker. Each auxiliary
switch stage (Figure 7) has 2a (normally open) and 2b (normally
closed) contacts wired to the breaker secondary contacts for customer
use in remote indication or external
electrical schemes. (See Table 4
for auxiliary switch contact ratings.)
The contacts change state as the
breaker opens and closes.
A maximum of 3 switch stages of
2a/2b contacts can be mounted in
Magnum Standard and Double
Frame Circuit Breakers for a total of
6a and 6b available contacts. If
more than two switch stages are
required on the Narrow Frame
Breaker, refer the application to
Cutler-Hammer. Due to the 48
point secondary terminal block limitation on the Narrow Frame
Breaker, only 2 stages of 2a/2b contacts can be mounted if the full
compliment of breaker internal
accessories are employed.
However, if the breaker is not fully
accessorized, the Narrow Frame
Breaker can accommodate 3 auxiliary switch stages of 2a/2b contacts.
PG01301001E
Internal Electrical Accessories
Other electrical accessories are
mounted inside the circuit breaker.
They can be factory or site
installed. There are two different
internally mounted accessories:
Overcurrent Trip Switch (Bell
Alarm)
Motor Operator
Overcurrent Trip Switch (Bell
Alarm) - An overcurrent trip switch
(bell alarm) is an optional device
(Figure 8). It provides an electrical
indication when a circuit
breaker trips as a result of the trip
unit reacting to an overcurrent condition. Opening as a result of a circuit breakers manual open button,
shunt trip or undervoltage release
does not cause the overcurrent trip
switch to operate. The overcurrent
trip switch has (2a 2b) Form C contacts (Table 4).
The status of the contacts change
when the trip indicator pops out.
This permits the switch to be used
as an alarm or in conjunction with a
spring release to block a subsequent remote electrical closing signal.
Figure 7 Auxiliary Switch (2A/2B)
Table 4 Auxiliary Switch,
Overcurrent Trip Switch and
Cell Switch Contact Ratings
Control Contact Rating
Voltages Inductive Load
(amperes)
250 Vac
10
125 Vdc
0.5
250 Vdc
0.25
Mechanical
Trip
Indicator
Figure 8 Mechanical Trip Indicator
with Associated Overcurrent Trip
Switch
For more information visit: www.cutler-hammer.eaton.com
43
44
Accessory Devices
July 2003
Motor Operator - A Motor operator is an electric motor assembly
internally mounted in the circuit
breaker (Figures 9 and 10). It
charges the closing springs electrically for remote or local operation.
The motor operator can be factory
or site installed (Table 5).
To convert a manually operated circuit breaker to an electrically operated circuit breaker, a UL listed
motor operator kit is available.
Figure 10 Motor Operator Installed
in Narrow Frame Circuit Breaker
Figure 9 Motor Operator Kit
Table 5 Motor Operator
Control
Voltages
Operational
Running
Voltage Range Current
85-110 %
(A. avg.)
Typical
Inrush
Current
Power
Maximum
Consumption Charging Time
(watts or VA)
(seconds)
24 Vdc
20-26
12.0
300% of Running
300
48 Vdc
41-53
5.0
500% of Running
250
110-125 Vdc
94-138
2.0
600% of Running
250
220-250 Vdc
187-225
1.0
600% of Running
250
250
250
110-127 Vac
94-140
2.0
600% of Running
208-240 Vac
177-264
1.0
600% of Running
AC voltages are 50/60Hz
Spring Charged Indication Spring charged indication is available on Magnum DS circuit breakers that are equipped with motor
operators. The motor operator circuit includes a motor cut-off switch
that changes state at the end of the
closing spring charging cycle. The
cut-off contact is wired to breaker
secondary contact terminal points
B14 and B15 for remote indication
and customer use in external
breaker control schemes.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Accessory Devices
July 2003
Mechanical Accessories
There are six optional mechanical
type accessories:
Operations Counter
Cassette Safety Shutters
Cassette Cell Switch
Door Escutcheon
IP54 Cover
Mechanical Interlock
Operations Counter - The operations counter is a mechanical
device used to provide a record of
the number of circuit operations. It
is mounted in the lower right portion of the circuit breaker and can
be viewed through the front cover
(Figure 11).
Operations
Counter
Cassette Cell Switch - The cassette cell switch (Figures 14 and
15) is also known as the cell position switch or the TOC (Truck
Operated Cell) switch. The cell
switch is an optional accessory that
is provided in kit form for installation by the panel assembler. Up to
3 cell switch stages, each with 4
Form C contacts can be mounted
on the right hand side of the cassette. (See Table 4 for cell switch
contact ratings.) One stage can be
mounted on each of the DISCONNECT, TEST, or CONNECT mounting locations on the cassette. The
switch contacts change state when
the breaker is levered into the DISCONNECT, TEST, or CONNECT
positions. Wires are provided for
each set of Form C contacts for termination to the breaker secondary
terminal blocks (white) or other
customer supplied terminal blocks
in the breaker cell compartment.
The contacts are generally used for
remote indication or for customer
use in external breaker control
schemes.
Figure 12 Safety Shutters in Closed
Position
PG01301001E
Door Escutcheon - The door
escutcheon is a molded frame used
to seal the space between the circuit breaker and the compartment
door cutout. It is supplied with a
mounting gasket (Figure16).
Figure 16 Door Escutcheon and
Gasket
Figure 11 Operations Counter
Cassette Safety Shutters Automatically operated insulating
type safety shutters are available
for use with the drawout cassette.
When the drawout circuit breaker is
levered from the CONNECT position, the shutters automatically
close to cover the fixed primary
contacts (Figure 12). When the cir-
Figure 15 Cell Switch (Drawout
Position Indicator) Unmounted
IP54 Cover - A hinged dome
shaped waterproof cover attaches
to the metal compartment door to
provide waterproof protection for
the circuit breaker (Figure 17).
Figure 14 Cell Switches Mounted
on Cassette
Figure 13 Safety Shutters in Open
Position
For more information visit: www.cutler-hammer.eaton.com
Figure 17 IP54 Cover
45
46
Accessory Devices
July 2003
Mechanical Interlock - A family
of mechanical interlocks are available to interlock the closing of two
or three Magnum circuit breakers.
The mechanical interlock holds one
or more circuit breakers tripped
(prevents closure) when others are
closed. A lever assembly is mounted on each breaker which interfaces with the pole shaft and the
tripper bar. The lever assemblies
are interconnected with either
cables or rods, depending upon the
relative orientation of the breakers.
Rods can be used only when the
circuit breakers to be interlocked
are vertically stacked. Cables can
be used for any orientation of the
breakers. Mechanical interlocks are
available for both fixed and drawout circuit breakers and in both 2way and 3-way versions. An illustration of a 2-way cable interlock
mounted on two drawout circuit
breakers is shown in Figure 18. In
addition, refer to Table 6 for the
possible mechanical interlock configurations.
Figure 18 Cassette-Mounted 2-Way
Cable Interlock
Table 6 Mechanical Interlock Configurations
Type of Number of Breakers
Interlock
Interlocked
Description of Interlocks
Type 2
Across 2 Breakers
One Normal Power Supply (A)
One Emergency Power Supply (B)
Type 31
Across 3 Breakers
Two Normal Power Supplies (A & C)
One Emergency Power Supply (B)
Circuit Breakers A and C can be closed if B is
open. B can only be closed if A and C are open.
Type 32
Across 3 Breakers
Two Power Supplies (A & C)
One Bus Tie Breaker (B)
One or two breakers out of 3 can be closed at the
same time.
Type 33
Across 3 Breakers
Three Power Supplies (A, B & C)
Normal or Emergency, only one of which can be
closed at a time.
Possible
Interlock Logic
AB
00
10
01
ABC
000
100
010
001
101
ABC
000
100
010
001
110
011
101
ABC
000
100
010
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Breaker Lock OFF Devices
July 2003
Breaker Lock OFF Devices
Magnum DS Circuit Breakers
are equipped with a variety of
lock off devices for both the
Circuit Breaker and the Drawout
Cassette to maximize safety during
equipment operation and maintenance.
Padlockable Levering Device
Access Door - The levering
Device access door includes padlock provisions as a standard feature on all drawout circuit breakers.
It is designed to receive a padlock
up to 0.312 inches (8 mm) in diameter. When the access door is padlocked shut, the breaker levering
tool cannot be inserted, preventing
the breaker from being levered to
another position (Figure 1).
padlockable pushbutton cover will
receive a padlock with up to a 0.312
inches (8 mm) diameter.
OFF
Key Lock
Figure 3 Cover Mounted Key Lock
Figure 2 ON-OFF Pushbutton
Lockable Cover Plate
Breaker OFF Key Lock
Provisions - The breaker OFF key
lock is an optional accessory that
allows the breaker to be locked in
the OFF position with the key
removed, preventing the breaker
from being closed. It is primarily
intended for use on fixed mounted
circuit breakers, but can also be
applied on drawout breakers
(Figure 3).
Figure 1 Closeup of Padlockable
Levering Device Access Door
Access Door - The padlockable
pushbutton cover is an optional
factory configured or field option
kit accessory that mounts on the
breaker faceplate. It is available
with either molded plastic or metal
frames with clear plastic hinged
blocking plates (Figure 2). When
they are closed and padlocked, the
blocking plates prevent access to
the breaker PUSH OFF and PUSH
ON mechanical pushbuttons. This
device can also be configured with
an additional plate to block only the
PUSH ON pushbutton. A small
hole is pre-drilled in the blocking
plates to provide emergency access
with a special tool as required per
the National Electric Code. The
PG01301001E
When selected as a factory configured option, the breaker includes a
pre-drilled hole covered with a
plastic cap on the breaker front
cover. A lock provisions hardware
kit is shipped with the breaker to
facilitate installation of a single
Kirk, Castell or Ronis cylinder lock.
The cylinder lock is generally provided and assembled to the breaker
at the point of use by the enclosure
manufacturer or customer. For
existing breakers, a breaker key
lock provisions field option kit is
also available. To facilitate installation, a drill point mark is located on
the inside of the breaker front
cover to identify the drilling location for the key lock installation.
Cassette Lock Provisions - The
cassette lock provisions field option
kit is an accessory that mounts on
the side of a circuit breaker cassette (Figure 4). The customer
For more information visit: www.cutler-hammer.eaton.com
must specify if the lock is to be
located on the left or right-hand
side of the cassette. When
installed, the device holds the
breaker trip-free when the breaker
is levered to the CONNECTED position. This prevents the breaker
from being closed and circuit energized.
Single or multiple cylinder Kirk,
Castell or Ronis locks can be
accommodated. The device can be
used with commonly applied breaker interlocking schemes such as
Main-Tie-Main configurations, etc.
Figure 4 Cassette Mounted Key
Lock
Cassette Shutter Lock
Provisions - As a standard feature, the narrow frame cassette
shutter system includes provisions
to padlock the shutter in the
CLOSED position when the breaker is
withdrawn. The shutter lock provisions will receive a padlock with up
to a 0.312 inches (8 mm) diameter.
47
48
Application and Installation Information
July 2003
Ambient Temperature
Circuit Breaker Continuous Current at Different Ambients
This table gives derating factors for
circuit breakers operating in switchboards at various internal ambient
temperatures. The switchboards
internal ambient should be estimated using an industry accepted calculation method.
Continuous Current
Current By Breaker
Type (Amperes)
Ambient Temperature (C)
40
50
45
55
60
800
800
800
800
1200
1200
????
????
1600
1600
1600
1600
????
1600
????
1600
2000
2000
2000
2000
2000
2500
2500
2500
2500
2500
3000
3000
3000
3000
3000
3000
MDS-632, 832, C32
3200
3200
3200
3200
3200
3200
MDS-84N, C4N, 840, C40
MDS-85N, C5N, 850, C50
4000
5000
4000
5000
4000
5000
4000
5000
4000
5000
4000
5000
MDS-C6N, C60
????
????
????
????
????
????
MDN-408, 508, 608
MDS-408, 508, 608, 808, C08
800
800
MDN-412, 512, 612
1200
1200
MDN-416, 516, 616
MDS-516, 616, 816, C16
1600
1600
1600
1600
MDS-620, 820, C20
2000
MDS-625, 825, C25
2500
MDS-630, 830, C30
Bus Bar Recommendations
Bus Bar Sizes and Quantities
The bus bar sizes shown in the
table are those specified by ANSI
and/or used by Cutler-Hammer in
their circuit breaker type testing.
They are for 3 meter long bus bar
with the faces vertical and painted
flat black. For other bus bar configurations, larger bus bar sizes may
be required or the circuit breaker
may have to be derated. Refer to
the table in this section entitled
Circuit Breaker Continuous Current
Ratings at Different Ambients for
derating information at higher
ambient temperatures. Refer to the
two graphic examples below.
Maximum Service Circuit Breaker
Current, Amperes Frame (MDN- &
(40C Ambient)
MDS-)
800
1000
1200
1600
2000
2500
3200
4000
5000
6000
08
10
12
16
20
25
32
40
50
63
70
Recommended
Bus Bar Quantities
and Sizes
(in)
(mm)
(1) .25 x 3.0
(2) .25 x 2.0
(2) .25 x 3.0
(2) .25 x 3.0
(3) .25 x 3.0
(4) .25 x 3.0
(3) .25 x 6
(4) .25 x 6
(5) .25 x 6
(6) .25 x 6
(2) 5 x 50
(2) 5 x 60
(2) 5 x 80
(2) 5 x 100
(3) 5 x 100
(4) 5 x 100
(3) 10 x 100
(4) 10 x 100
(5) 10 x 100
(6) 10 x 100
(T)
(3in)
(W
5in
(.2
Example 1
Example 2
T = Thickness of Bus Bar
W = Width of Bus Bar
Illustration of 2 .25 inch by 3 inch Bus
Bars stacked to carry 1600 amperes
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Application and Installation Information
July 2003
Altitude Rating Factors
Watts Loss Data
Magnum DS circuit breakers can be
applied at their full voltage and current ratings up to a maximum altitude of 2000 meters above sea
level. When installed at higher altitudes, the ratings are subject to correction factors. Short circuit current is not affected as long as the
voltage is rated in accordance with
the table.
Refer to the table for Magnum DS
resistance and watts loss data to be
used in temperature rise calculations.
Altitude Rating Factors
Magnum DS Resistance and Watts Loss Data
Altitude
(Meters)
Voltage
Correction
Current
Correction
2000
2150
2300
2450
2600
2750
2900
3050
3200
3350
3500
3650
3800
3950
5000
1.000
0.989
0.976
0.963
0.950
0.933
0.917
0.900
0.883
0.867
0.850
0.833
0.817
0.800
0.700
1.000
0.998
0.995
0.993
0.990
0.987
0.983
0.980
0.977
0.973
0.970
0.967
0.963
0.960
0.940
Circuit
Breaker
Frame
MDN-408
MDN-412
MDN-416
24
24
24
60
60
60
60
95
150
150
240
370
MDN-508
MDN-512
MDN-516
24
24
24
42
42
42
60
150
240
110
260
420
MDN-608
MDN-612
MDN-616
18
18
18
36
36
36
45
110
180
90
220
360
MDS-408
MDS-508
MDS-608
MDS-808
MDS-C08
24
???
15
12
12
60
???
33
24
24
60
???
40
35
30
150
???
85
70
60
MDS-516
MDS-616
MDS-816
MDS-C16
??
15
12
12
??
33
24
24
??
150
120
120
??
330
240
240
MDS-620
MDS-820
MDS-C20
12
12
12
24
24
24
190
190
190
330
380
380
MDS-625
MDS-825
MDS-C25
8
8
8
20
20
20
200
200
200
500
500
500
MDS-630
MDS-830
MDS-C30
?
?
?
??
??
??
???
???
???
???
???
???
MDS-632
MDS-832
MDS-C32
8
8
8
20
20
20
320
320
320
800
800
800
MDS-84N
MDS-840
MDS-C4N
MDS-C40
?
6
?
6
??
12
??
12
???
380
??
380
???
750
??
750
MDS-85N
MDS-850
MDS-C5N
MDS-C50
?
4
?
4
?
?
??
10
??
10
???
400
??
400
???
1000
??
1000
?
?
?
?
?
?
MDS-C6N
MDS-C60
PG01301001E
DC Resistance DC Resistance AC Watts Loss AC Watts Loss
(Total 3 Poles)
(Total 3 Poles)
(/pole)
(/pole)
Fixed
Drawout
Fixed
Drawout
Estimate based on RAC/RDC = 1.30, total loss at fully rated current.
For more information visit: www.cutler-hammer.eaton.com
49
50
Application and Installation Information
July 2003
Recommended Electrical
Clearances
Electrical Clearance Dimensions (in)
The following electrical clearance
information is provided as guidance when installing drawout or
fixed circuit breakers in an enclosure. Refer to the graphic representations and the associated
dimensional table.
Breaker
Mounting
Enclosure
Dimension
To Insulated
Surface
To Grounded
Metal Surface
With Cell Switch
or Key Lock
Drawout
A
B
0
1.0
0
1.0
0
1.0/2.9
Fixed
A
B
5.9
1.2
9.8
2.8
Recommended Enclosure Electrical Clearances
4.0
Cell
Switch
(optional)
Key Lock
(optional)
Do Not Block Vent
Openings in
Drawout Cassette
Minimum Enclosure Size and Ventilation
Recommended Enclosure Size
and Ventilation
A graphic of a typical enclosure
and an associated table of dimensions are provided as guidance for
circuit breaker enclosure design
with respect to the enclosure size
and the required amount of ventilation space.
Top or Rear
Vent Open Area
V
Recommended Enclosure/Ventilation Dimensions
W
Width
Cassette Width + 3.0 in
Height
21.7 in
Depth
17.7 in (Front Compartment)
in2
Ventilation 25
(800-3200A)
50 in2 (4000-6000A)
For more information visit: www.cutler-hammer.eaton.com
V
Rear or Bottom
Vent Open Area
PG01301001E
Maintenance Guidelines
July 2003
Suggested Tools
Maintenance Overview
General Cleaning
When to Inspect
What to Inspect
Suggested Tools
A large number of different tools
are not required to maintain
Magnum DS circuit breakers. The
following tools are suggested:
Flat blade screw driver
Phillips head screw driver
3/8 socket (rachet) wrench
6 socket extension with 3/8
square drive
10mm socket
17mm socket
Secondary wiring removal tool
Maintenance Overview
Design tests and actual installation
experience shows the Magnum DS
low voltage circuit breaker to have
durability well beyond minimum
standards requirements. However,
because of the variability of application conditions, inspection and
maintenance activities should take
place on a regularly scheduled
basis.
These circuit breakers are designed
to be relatively maintenance free.
The maintenance consists mainly
of keeping them clean. Cleaning
and preventive measures are part
of any good maintenance program.
Plant operating and local conditions can vary to such an extent
that the actual schedule should be
tailored to the conditions.
Maintenance record sheets should
be completed each time maintenance is performed. Careful and
accurate documentation of maintenance activities provides a valuable
historical reference on equipment
condition over time.
General Cleaning
Circuit breaker cleaning should be
part of an overall maintenance program that includes the assembly in
which the circuit breaker is
PG01301001E
installed. Loose dust and dirt
should be removed from external
surfaces using an industrial quality
vacuum cleaner and/or lint free
cloth. Unless otherwise indicated,
never use high pressure blowing
air, since dirt or foreign objects can
be driven into areas, such as the
operating mechanism. Never use a
wire brush to clean any part of the
circuit breaker.
When to inspect
Do not wait for specific scheduled
periods to visually inspect the
equipment, if there are earlier
opportunities. For this type of
equipment, it is recommended that
a general inspection and lubrication take place after the number of
operations listed in the Inspection
Frequency table. This type of
general inspection should also take
place at the end of the first six
months of service, even if the number of operations indicated in the
table has not been reached.
After the first inspection, inspect at
least once a year. If these recommended inspections show no maintenance requirements, the period
can be extended to a more economical point. Conversely, if the
recommended inspection shows,
for instance, a heavy accumulation
of dirt or other foreign matter that
might cause mechanical, electrical
or insulation damage, the inspection and maintenance interval
should be decreased.
What To Inspect
What to inspect and to what extent
is dictated by the nature of the
maintenance function. Routine
inspections require one type of
observation. Inspections following
a known high level fault require
more detailed inspections. When
inspections are complete, be certain that any parts removed during
the inspection process are properly
put back in place.
General Circuit Breaker
A drawout type circuit breaker
should first be withdrawn from its
For more information visit: www.cutler-hammer.eaton.com
compartment onto the compartments extension rails. When the
inspection is complete, the circuit
breaker can be levered to the TEST
position to check any electrical
operations of the circuit breaker.
During movement of the circuit
breaker out of and back into its
compartment, be alert for any signs
indicating improper operation.
During the inspection of fixed type
circuit breakers, bus systems supplying the circuit breakers should
be de-energized for convenience
and safety.
Once the circuit breaker has been
cleaned, visually inspect it for any
signs of damage, missing or loose
parts and unusual wear. On drawout circuit breakers, inspect the
primary disconnect finger clusters
for signs of wear and erosion.
Make appropriate corrections for
anything found out of order.
The trip unit can also be functionally
tested during this general inspection.
Arc Chute
When the circuit breaker experiences a high level fault or during
regularly scheduled maintenance
periods, arc chambers and their
enclosed arc chutes should be
inspected for any kind of damage
or dirt. Be especially alert for signs
of erosion of the V-shaped plates
inside the arc chutes.
Primary Contacts
Since the arc chutes are removed,
this is an ideal time to inspect primary contacts for wear using the
circuit breakers contact wear indicators. Visually inspect each primary
contact structure for signs of wear
and/or damage. This inspection is
conducted with the circuit breaker
closed. Look straight down into the
arc chamber when observing the
closed contacts. If the contacts
show unacceptable wear as indicated by the contact wear indicator discussed earlier in this document, the
contacts should be replaced.
51
52
Breaker Specifications
July 2003
Power Circuit Breakers
All protective devices shall be low
voltage [drawout ] [fixed] type
power circuit breakers. The breaker
shall be available in two physical
frame sizes covering current ratings
from 800-5000 amperes. They shall
have a common height and depth
across the range. All breakers shall
be suitable for application in their
intended enclosures for 100% of
their continuous ampere rating
assuming an enclosure.
All breakers shall be equipped with
a true, two step stored energy
mechanism providing a maximum
5 cycle closing. All the energy for
closing the breaker shall be stored
and held in readiness pending a
release to close action. Manually
operated breakers shall be convertible to electrical operation by field
fitting of an internally mounted
motor operator. Both manual and
electrically operated breakers shall
have multiple charge/close provisions providing the following possible sequence: charge-closerecharge-open-close-open. As a
safety feature, provisions shall be
available to manually discharge the
stored energy without closing the
breaker. Anti-pump provisions shall
be provided as standard.
The breaker shall be manually
operated unless electrical operation
is indicated on the drawings. The
circuit breaker control face plate
shall include color coded visual
indicators to indicate contact OPEN
(green) and CLOSED (red) positions
as well as mechanism CHARGED
(yellow) and DISCHARGED (white)
positions. Manual control pushbuttons on the breaker face shall be
provided for opening and closing
the circuit breaker.
The Power Circuit Breaker shall
have a positive on feature. The
contact position flag will read
CLOSED if the contacts have
been welded.
Electrically operated circuit breakers shall be complete with
[110/120Vac] [208/240Vac]
[24V/dc] [48Vdc] [110/125Vdc]
[220/250Vdc] motor operators,
[OPEN/CLOSE pushbuttons] [control switch] plus a red and green
indicating flag to indicate breaker
contact position. [DC source shall
be supplied from a remote battery
system] [AC source shall be taken
from a (remote source) (control
power transformer internal to the
trol switch] plus a red and green
indicating flag to indicate breaker
contact position. [DC source shall
be supplied from a remote battery
system] [AC source shall be taken
from a (remote source) (control
power transformer internal to the
switchgear assembly)]. The charging time of the motor shall not
exceed 10 seconds.
The symmetrical interrupting
capacity and short time current
ratings respectively at 240, 480
and 600VAC shall be: [42/42kA]
[65/65kA] [85/85kA]
[100/85kA][100/100kA].
To facilitate lifting, the Power Circuit
Breaker shall have integral handles
on the side of the unit, and shall
have optional lifting brackets available for hoisting.
The Primary contacts of the unit
shall have an easily accessible
Contact Wear Indicator to indicate
main contact erosion.
The Power Circuit Breaker shall
have a trip flag pop-out indicator to
confirm an overcurrent trip signal.
The trip flag shall not be interlocked
to the breaker reset to facilitate
remote reset of the breaker.
The Power Circuit Breaker shall have
three windows in the front cover to
offer clear indication of closing or
opening electrical accessories that
are mounted in the breaker. Each
accessory will have a label to indicate its function and voltage. The
accessories shall be plug and lock
type to allow easy field installation.
They shall be modular in design and
shall be common to all frame sizes
and ratings.
offer 60 front mounted dedicated
secondary wiring points, each wiring
point having finger safe contacts to
IP20 and shall allow no more than
two wires per terminal.
The Torroidal Current Sensors, for
use with the trip units, shall be
mounted at the rear of the circuit
breaker and shall have a back cover
window that will permit viewing the
current sensor rating on the back of
the breaker. A front of breaker
mounted trip unit will have a Rating
Plug which will offer indication of
the actual sensor rating on the front
of the Trip Unit.
On Drawout type Circuit Breakers,
the Racking-in device shall be
mounted integral to the breaker.
This mechanism will be located on
the front of the breaker. A breaker
position indicator shall be located
on the faceplate of the breaker. This
indicator shall offer clear color indication of the breaker position in the
cassette. These positions shall be
Connected (Red), Test (Yellow)
and Disconnected (Green). The
racking-in door shall be interlocked
so that when the breaker is in the
closed position, the breaker rackingin door shall not open. As a safety
feature the breaker spring mechanism shall discharge as the breaker
is withrawn from the Connected to
the Disconnected position.
On Drawout type Circuit Breakers,
the finger clusters shall withdraw
with the breaker for safe and easy
installation.
All Power Circuit Breakers shall be
designed, manufactured and tested in accordance with ANSI
C37.13, C37.16, C37.17, C37.50, UL
1066 and NEMA SG-3 Standards.
To verify this, the circuit breaker
shall carry a UL label.
Circuit breakers shall be CutlerHammer Magnum type or
approved equal.
Each Power Circuit Breaker shall
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Breaker Specifications
July 2003
Trip Units (Digitrip)
Note to Specification Writer
Digitrip RMS Trip Units are available as follows:
Digitrip 220 - Basic Protection (select Paragraph 1 through 5)
vidually adjustable time/current
curve shaping solid-state elements:
a. All breakers shall have adjustments for long delay pick-up and
time.
representation of the Time/Current
curve of the trip unit that will indicate the protection function settings. The unit shall be continuously self-checking and provide a visual indication that the internal circuitry is being monitored and is
fully operational.
b. [Main] [Tie] [and Feeders] shall
have a fixed instantaneous pick-up.
Digitrip 1150 - Advanced
Protection - with metering, LED display and remote communication
facility (select Paragraph I through
to BB)
(4) The trip unit shall be provided
with a making-current release circuit. The circuit shall be armed for
approximately one cycle after
breaker closing and shall operate
for all fault levels above 15 times
the ampere RMS value of the current sensor.
(D) Complete system selective coordination shall be provided by the
addition of the following individually adjustable Time/Current curve
shaping solid state elements :
(5) Trip unit shall have selectable
thermal memory for enhanced circuit protection.
b. [Main Incoming] [Bus Coupler]
[Feeders] shall have individual
adjustments for short delay pick-up
2
and time, and include I t settings.
Digitrip 520 - Basic Protection
with an optional local current indication only, optional LCD display
(select Paragragh A through H)
Basic Trip Unit
(1) Each power circuit breaker shall
be equipped with a solid-state tripping system consisting of three (3)
current sensors, microprocessorbased trip device low energy trip
actuator. Current sensors shall provide operation and signal function.
The trip unit shall use microprocessor-based technology to provide
the basic adjustable time-current
protection functions. True RMS
sensing circuit protection shall be
achieved by analysing the secondary current signals received
from the circuit breaker current
sensors and initiating a trip signal
to the circuit breaker trip actuator
when predetermined trip levels and
time delay settings are reached.
Interchangeable Current sensors
(with associated rating plugs) shall
establish the continuous trip rating
of each circuit breaker. The trip unit
shall be Cutler-Hammer type DIGITRIP.
(2) The trip unit shall be provided
with a display panel, including a
representation of the Time/Current
curve of the trip unit, that will indicate the protection function settings. The unit shall be continuously self-checking and provide a visual indication that the internal circuitry is being monitored and is
fully operational.
(3) Complete system selective
coordination shall be provided by
the addition of the following indi-
PG01301001E
(A) Each power circuit breaker shall
be equipped with a solid-state tripping system consisting of three (3)
current sensors, microprocessorbased trip device and low energy
trip actuator. Current sensors shall
provide operation and signal function. The trip unit shall use microprocessor-based technology to provide the basic adjustable time-current protection functions. True RMS
sensing circuit protection shall be
achieved by analysing the secondary
current signals received from the circuit breaker current sensors and initiating a trip signal to the circuit
breaker trip actuator when predetermined trip levels and time delay settings are reached. Interchangeable
Current Sensors with its associated
Rating Plug shall establish the continuous trip rating of each circuit
breaker. The trip unit shall be CutlerHammer type DIGITRIP.
(B) The trip unit shall have an information system that provides LEDs
to indicate mode of trip following
an automatic trip operation. The
indication of the mode of trip shall
be retained after an automatic trip.
A reset button shall be provided to
turn off the flashing LED indication
after an automatic trip.
(C) The Trip Unit shall be provided
with a display panel, including a
For more information visit: www.cutler-hammer.eaton.com
a. All breakers shall have adjustments for long delay pick-up and
time.
c. [Main Incoming] [Bus Coupler]
[Feeders] shall have an adjustable
instantaneous pick-up.
d. When indicated on the drawing
circuit breakers shall have individually adjustable earth fault current
pick-up and time and include I2t
settings or ground fault alarm only.
(E) The Trip Unit shall be provided
with a making-current release circuit.
The circuit shall be armed for
approximately eight cycles after
breaker closing and shall operate
for all fault levels above 15 timesthe ampere value of the current
sensor.
(F) Trip Units shall have selectable
thermal memory for enhanced circuit protection.
(G) There shall be an optional display. This display will show phase,
neutral and ground sensors and
high phase current. The accuracy of
these readings shall be 2% of full
scale.
(H) The Trip Unit shall provide
zone interlocking for the short time
delay and ground fault delay trip
functions for improved system coordination. The zone interlocking
53
54
Breaker Specifications
Breaker Specifications
July 2003
system shall restrain the tripping of
the upstream breaker and allow the
breaker closest to the fault to trip
with no intentional time delay. In
the event that the downstream
breaker does not trip, the upstream
breaker shall trip after the preset
time delay.
Advanced Trip Unit
(I) Each power circuit breaker shall
be equipped with a solid-state tripping system consisting of three (3)
current sensors, microprocessorbased trip device and Low energy
trip actuator. Current sensors shall
provide operation and signal function. The trip unit shall use microprocessor-based technology to provide the basic adjustable time-current protection functions. True RMS
sensing circuit protection shall be
achieved by analysing the secondary current signal received from
the circuit breaker current sensors
and initiating trip signal to the circuit breaker trip actuator when predetermined trip levels and time
delay settings are reached.
Interchangeable Current Sensors
with its associated Rating Plug
shall establish the continuous trip
rating of each circuit breaker. The
trip unit shall be Cutler-Hammer
type DIGITRIP.
(J) The trip unit shall have an information system that provides LEDs
to indicate mode of trip following
an automatic trip operation. The
indication of the mode of trip shall
be retained after an automatic trip.
A reset button shall be provided to
turn off the LED indication after an
automatic trip.
(K) The Trip Unit shall be provided
with a display panel, including a
representation of the Time/Current
curve of the trip unit that will indicate the protection function settings. The unit shall be continuously self-checking and provide a visual indication that the internal circuitry is being monitored and is
operational.
(L) Complete system selective coordination shall be provided by the
addition of the following individually adjustable Time/Current curve
shaping solid state elements :
a. All breakers shall have adjustments for long delay pick-up and
time.
b. [Main Incoming] [Bus Coupler]
[Feeders] shall have individual
adjustments for short delay pick-up
and time, and include I2t settings.
c. [Main Incoming] [Bus
Coupler] [Feeders] shall have an
adjustable instantaneous pick-up.
d. When indicated on the drawing circuit breakers shall have individually adjustable ground fault
current pick-up and time and
include I2t settings and ground
fault alarm only.
(M) The Trip Unit shall be provided
with a making-current release circuit. The circuit shall be armed for
approximately eight cycles after
breaker closing and shall operate
for all fault levels above 15 timesthe ampere value of the current
sensor.
(N) Trip Units shall have selectable
thermal memory for enhanced circuit protection to provide protection against cumulative overheating should a number of overload
conditions occur in quick succession.
(O) An adjustable high load function shall be provided to avoid nuisance alarms.
(P) The Trip Unit shall contain an
integral test pushbutton. A keypad
shall be provided to enable the
user to select the values of test currents within a range of available
settings. The protection functions
shall not be affected during test
operations. The circuit breaker may
be tested in the Trip or No Trip test
mode.
(Q) The Trip Unit shall include a
power/relay module which shall
supply control power to the readout display. Following an automatic
trip operation of the circuit breaker,
For more information visit: www.cutler-hammer.eaton.com
the trip unit shall maintain the
cause of trip history and the mode
of trip LED indication as long as its
internal power supply is available.
Internal relays are programmable
to provide contacts for remote indication.
(R) Metering display accuracy of
the complete system including current sensors, auxiliary CTs and the
trip unit shall be 1% of full scale
for current values.
(S) The Trip Unit shall include a
potential transformer module, suitable for operation up to 600V, 50/60
Hz. The primary of the potential
transformer module shall be connected internally to the line side of
the circuit breaker through a dielectric disconnect plug.
(T) The Trip Unit shall provide zone
interlocking for the short time delay
and ground fault delay trip functions for improved system protection. The zone interlocking system
shall restrain the tripping of the
upstream breaker and allow the
breaker closest to the fault to trip
with no intentional time delay. In
the event that the downstream
breaker does not trip, the upstream
breaker shall trip after the preset
time delay.
(U) The Trip Unit shall have an
information system that utilises
battery backup LEDs to indicate
mode of trip following an automatic trip operation. The indication of
the mode of trip shall be retained
after an automatic trip. A test pushbutton shall energise an LED to
indicate the battery status.
(V) The Trip Unit shall be capable
of monitoring the following data :
Instantaneous value of phase,
neutral and ground current
Instantaneous value of line to line
voltage
Maximum and minimum current
values
Watts, Vars, VA, Watt-hours, and VAhours
PG01301001E
51
Breaker Specifications
July 2003
The energy monitoring parameter
values (peak demand, present
demand and forward and reverse
energy consumption) shall be indicated in the trip units alphanumeric display panel.
The trip unit shall display the following power quality values:
Crest Factor, Power Factor, percent
total harmonic distortion and harmonic values of all phases through
to the 31st harmonic.
(W) Metering display accuracy of
the complete system shall be 2%
of full scale for Power and Energy
values.
(AA) The trip Unit shall offer a 3
event trip log that will store the trip
data and shall time and date stamp
the event.
Programmable curve shapes of
moderately, very or extremely
inverse
(BB) The Trip Unit shall be
equipped to permit communication
via a network twisted pair for
remote monitoring and control.
Programmable long time setting.
Programmable long time delay
with selectable I2t or It curve shaping.
Programmable short time setting.
Programmable short time delay
with selectable flat or I2t curve
shaping and zone selective interlocking.
Programmable instantaneous
setting.
Programmable ground fault setting trip or earth fault setting alarm.
(X) The display for the Advanced
Trip Units shall be LED display
(Y) Programming may be done via
a keypad at the faceplate of the
unit, download via a cable link,
Triplink or via the communication
network.
Programmable
ground fault delay
with selectable flat or I2t curve shaping and zone selective interlocking.
(Z) System coordination shall be
provided by the following microprocessor-based programmable
Time/Current curve shaping adjustments. The short time pick-up
adjustments shall be dependent on
the long delay setting.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
Note to Specification Writer - For
centralized monitoring of the
Digitrip 1150 trip units, select the
BIM (Breaker Interface Module).
55
56
Factory Configured Circuit Breakers
July 2003
Factory Configured Circuit
Breakers
Magnum DS Power Circuit
Breakers are ordered using a 25digit catalog numbering system
that allows for maximum options
and flexibility. Circuit breaker configuration is achieved by using a
simple 2-step process.
Note: If the breaker is drawout
construction and a cassette is
required, the cassette must be configured separately.
Step 1: Select a 10-Digit
Breaker Catalog Number Prefix.
Choose the breaker prefix from
Tables 3.1 or 3.2 based on the following:
Drawout of Fixed Construction
Number of Poles
Continuous Current Rating
Magnum Frame Type
Interrupting Rating
Short Time Withstand
Phasing (Double-wides only)
Step 2: Select Breaker Catalog
Positions 11 through 25 to designate factory installed options
as follows:
Catalog Positions 11 and 12
establish the sensor and rating
plug ratings per Tables 3.3, 3.4
and 3.5.
Catalog Position 20 establishes if an optional OTS/Bell Alarm
Switch and/or a Mechanical Trip
Indicator is installed per Table
3.12.
Catalog Positions 13 and 14
establish the trip unit type per
Table 3.6.
Catalog Position 21 establishes if an optional Padlockable
Pushbutton Cover is installed per
Table 3.13.
Catalog Position 15 establishes if an optional Shunt Trip is
installed per Table 3.7.
Catalog Position 16 establishes if an optional Motor Operator is
installed per Table 3.8.
Catalog Position 17 establishes if an optional Spring Release
Device is installed per Table 3.9.
Catalog Position 18 establishes if an optional Undervoltage
Release or Second Shunt Trip is
installed per Table 3.10.
Catalog Position 19 establishes if optional Auxiliary Switches
are installed per Table 3.11.
For more information visit: www.cutler-hammer.eaton.com
Catalog Position 22 establishes if an optional Key Interlock
Provision is installed per Table
3.14.
Catalog Position 23 establishes if an optional Latch Check
Switch is installed per Table 3.15
and/or designates the voltage connection ifan 1150 Trip Unit is supplied.
Catalog Position 24 establishes if the breaker is shipped alone or
in a cassette with options per
Table 3.16.
Catalog Position 25 is
reserved for Cutler-Hammer use
per Table 3.17.
PG01301001E
Factory Configured Circuit Breakers
July 2003
Catalog Number Character Positions
1
MD
Character
Position
10
11 12 13 14 15 16 17 18 19 20 21
22 23 24 25
A
Description
X
Character
Position
Description
Circuit Breaker Frame
16
Motor Operator for Charging Closing Spring
Interrupting/Withstand Rating
17
Spring Release Device (SRD)
5&6
Continuous Amperes and Phasing (Facing
Front of Breaker)
18
Undervoltage Release (UVR) or 2nd. Shunt
Trip (ST)
Poles and Neutral (Facing Front of Breaker)
19
Auxiliary Switch
Mounting Configuration and Load Terminals
20
OTS/Bell Alarm Switch and/or Mechanical
Indicator
Nameplate Language
21
Padlock Provisions for Close & Open Buttons
10
Future Use
22
Operations Counter and/or Keylock Provisions
23
Latch Check Switch/Trip Unit Line Voltage
Connection for 1150 Trip Unit
24
Shipping Instructions
25
Future Use
11 & 12 Sensor and Rating Plug Rating
13 & 14 Trip Unit and Protection (and External Control
Voltage When Required)
15
Shunt Trip (ST)
Figure 3-1 Circuit Breaker 25-character Catalog Number Selections
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
57
58
Factory Configured Circuit Breakers
July 2003
Table 3.1 Magnum DS Drawout Mounted Circuit Breakers UL LIsted UL1066
(First 10 Character Positions of Catalog Number)
This selection is for a drawout circuit breaker with primary disconnecting contacts (finger clusters).
3-Pole
Phasing
(Left to Right)
4-Pole Catalog
Number
Positions 1-10
4-Pole
Phasing
(Left to Right)
MDN4083LEA
MDN4123LEA
MDN4163LEA
ABC
ABC
ABC
MDN4084LEA
MDN4124LEA
MDN4164LEA
NABC
NABC
NABC
50
50
50
MDN5083LEA
MDN5123LEA
MDN5163LEA
ABC
ABC
ABC
MDN5084LEA
MDN5124LEA
MDN5164LEA
NABC
NABC
NABC
65
65
65
MDN6083LEA
MDN6123LEA
MDN6163LEA
ABC
ABC
ABC
MDN6084LEA
MDN6124LEA
MDN6164LEA
NABC
NABC
NABC
MDS4083WEA
ABC
MDS4084WEA
NABC
50
50
MDS5083WEA
MDS5163WEA
ABC
ABC
MDS5084WEA
MDS5164WEA
NABC
NABC
65
65
65
65
65
65
65
65
65
65
65
65
MDS6083WEA
MDS6163WEA
MDS6203WEA
MDS6253WEA
MDS6303WEA
MDS6323WEA
ABC
ABC
ABC
ABC
ABC
ABC
MDS6084WEA
MDS6164WEA
MDS6204WEA
MDS6254WEA
MDS6304WEA
MDS6324WEA
NABC
NABC
NABC
NABC
NABC
NABC
Standard
Standard
Standard
Standard
Standard
Standard
85
85
85
85
85
85
85
85
85
85
85
85
MDS8083WEA
MDS8163WEA
MDS8203WEA
MDS8253WEA
MDS8303WEA
MDS8323WEA
ABC
ABC
ABC
ABC
ABC
ABC
MDS8084WEA
MDS8164WEA
MDS8204WEA
MDS8254WEA
MDS8304WEA
MDS8324WEA
NABC
NABC
NABC
NABC
NABC
NABC
800
1600
2000
2500
3000
3200
Standard
Standard
Standard
Standard
Standard
Standard
100
100
100
100
100
100
85
85
85
85
85
85
MDSC083WEA
MDSC163WEA
MDSC203WEA
MDSC253WEA
MDSC303WEA
MDSC323WEA
ABC
ABC
ABC
ABC
ABC
ABC
MDSC084WEA
MDSC164WEA
MDSC204WEA
MDSC254WEA
MDSC304WEA
MDSC324WEA
NABC
NABC
NABC
NABC
NABC
NABC
4000
5000
Double
Double
85
85
85
85
MDS84N3WEA
MDS85N3WEA
AABBCC
AABBCC
MDS84N4WEA
MDS85N4WEA
NNAABBCC
NNAABBCC
4000
5000
6000
Double
Double
Double
100
100
100
100
100
100
MDSC4N3WEA
MDSC5N3WEA
Contact C-H
AABBCC
AABBCC
AABBCC
MDSC4N4WEA
MDSC5N4WEA
Contact C-H
NNAABBCC
NNAABBCC
NNAABBCC
4000
5000
Double
Double
85
85
85
85
MDS8403WEA
MDS8503WEA
ABCABC
ABCABC
MDS8404WEA
MDS8504WEA
NNABCABC
NNABCABC
4000
5000
6000
Double
Double
Double
100
100
100
100
100
100
MDSC403WEA
MDSC503WEA
Contact C-H
ABCABC
ABCABC
ABCABC
MDSC404WEA
MDSC504WEA
NNABCABC
NNABCABC
Continuous
Current Rating
Amps at 40C
Magnum ACB
Frame Type
Interrupting
Rating (kA) at
600V Inst. Trip
800
1200
1600
Narrow
Narrow
Narrow
42
42
42
42
42
42
800
1200
1600
Narrow
Narrow
Narrow
50
50
50
800
1200
1600
Narrow
Narrow
Narrow
65
65
65
800
Standard
42
42
800
1600
Standard
Standard
50
50
800
1600
2000
2500
3000
3200
Standard
Standard
Standard
Standard
Standard
Standard
800
1600
2000
2500
3000
3200
Short-Time
Withstand
Rating (kA) at
600V
3-Pole Catalog
Number
Positions 1-10
Narrow Frame Drawout Circuit Breaker
Standard Frame Drawout Circuit Breaker
Double Frame Drawout Circuit Breaker
Magnum air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure).
Phasing Left to Right when facing front of circuit breaker - Neutral rated 100% of continuous current.
6000 Amp circuit breaker for use in a forced air cooled enclosure manufactured and tested by the OEM.
6000 Amp circuit breaker for use in a forced air cooled switchgear or power module manufactured by Cutler-Hammer.
AABBCC or NNAABBCC phasing is the type used in Cutler-Hammer Pow-R-Line C Switchboards and is the recommended phasing for use by OEMs.
ABCABC or NNABCABC phasing is for use in Cutler-Hammer Magnum DS Low Voltage Switchgear and Power Modules.
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Factory Configured Circuit Breakers
July 2003
Table 3.2 Magnum DS Fixed Mounted Circuit Breakers UL LIsted UL1066
(First 10 Character Positions of Catalog Number)
This selection is for a fixed circuit breaker with fixed mounting feet and horizontal terminal pads for bus connections.
3-Pole
Phasing
(Left to Right)
4-Pole Catalog
Number
Positions 1-10
4-Pole
Phasing
(Left to Right)
MDN4083HEA
MDN4123HEA
MDN4163HEA
ABC
ABC
ABC
MDN4084HEA
MDN4124HEA
MDN4164HEA
NABC
NABC
NABC
50
50
50
MDN5083HEA
MDN5123HEA
MDN5163HEA
ABC
ABC
ABC
MDN5084HEA
MDN5124HEA
MDN5164HEA
NABC
NABC
NABC
65
65
65
65
MDN6083HEA
MDN6123HEA
MDN6163HEA
MDN6203HEA
ABC
ABC
ABC
ABC
MDN6084HEA
MDN6124HEA
MDN6164HEA
MDN6205HEA
NABC
NABC
NABC
NABC
MDS4083HEA
ABC
MDS4084HEA
NABC
50
50
MDS5083HEA
MDS5163HEA
ABC
ABC
MDS5084HEA
MDS5164HEA
NABC
NABC
65
65
65
65
65
65
65
65
65
65
65
65
MDS6083HEA
MDS6163HEA
MDS6203HEA
MDS6253HEA
MDS6303HEA
MDS6323HEA
ABC
ABC
ABC
ABC
ABC
ABC
MDS6084HEA
MDS6164HEA
MDS6204HEA
MDS6254HEA
MDS6304HEA
MDS6324HEA
NABC
NABC
NABC
NABC
NABC
NABC
Standard
Standard
Standard
Standard
Standard
Standard
85
85
85
85
85
85
85
85
85
85
85
85
MDS8083HEA
MDS8163HEA
MDS8203HEA
MDS8253HEA
MDS8303HEA
MDS8323HEA
ABC
ABC
ABC
ABC
ABC
ABC
MDS8084HEA
MDS8164HEA
MDS8204HEA
MDS8254HEA
MDS8304HEA
MDS8324HEA
NABC
NABC
NABC
NABC
NABC
NABC
800
1600
2000
2500
3000
3200
Standard
Standard
Standard
Standard
Standard
Standard
100
100
100
100
100
100
85
85
85
85
85
85
MDSC083HEA
MDSC163HEA
MDSC203HEA
MDSC253HEA
MDSC303HEA
MDSC323HEA
ABC
ABC
ABC
ABC
ABC
ABC
MDSC084HEA
MDSC164HEA
MDSC204HEA
MDSC254HEA
MDSC304HEA
MDSC324HEA
NABC
NABC
NABC
NABC
NABC
NABC
4000
5000
Double
Double
85
85
85
85
MDS84N3HEA
MDS85N3HEA
AABBCC
AABBCC
MDS84N4HEA
MDS85N4HEA
NNAABBCC
NNAABBCC
4000
5000
6000
Double
Double
Double
100
100
100
100
100
100
MDSC4N3HEA
MDSC5N3HEA
Contact C-H
AABBCC
AABBCC
AABBCC
MDSC4N4HEA
MDSC5N4HEA
Contact C-H
NNAABBCC
NNAABBCC
NNAABBCC
4000
5000
Double
Double
85
85
85
85
MDS8403HEA
MDS8503HEA
ABCABC
ABCABC
MDS8404HEA
MDS8504HEA
NNABCABC
NNABCABC
4000
5000
6000
Double
Double
Double
100
100
100
100
100
100
MDSC403HEA
MDSC503HEA
Contact C-H
ABCABC
ABCABC
ABCABC
MDSC404HEA
MDSC504HEA
NNABCABC
NNABCABC
Short-Time
Withstand
Rating (kA) at
600V
Continuous
Current Rating
Amps at 40C
Magnum ACB
Frame Type
Interrupting
Rating (kA) at
600V Inst. Trip
800
1200
1600
Narrow
Narrow
Narrow
42
42
42
42
42
42
800
1200
1600
Narrow
Narrow
Narrow
50
50
50
800
1200
1600
2000
Narrow
Narrow
Narrow
Narrow
65
65
65
65
800
Standard
42
42
800
1600
Standard
Standard
50
50
800
1600
2000
2500
3000
3200
Standard
Standard
Standard
Standard
Standard
Standard
800
1600
2000
2500
3000
3200
3-Pole Catalog
Number
Positions 1-10
Narrow Frame Fixed Circuit Breaker
Standard Frame Fixed Circuit Breaker
Double Frame Fixed Circuit Breaker
Magnum air circuit breakers are 100% thermal rated (no de-rating necessary when properly applied in a specified enclosure).
Phasing Left to Right when facing front of circuit breaker - Neutral rated 100% of continuous current.
6000 Amp circuit breaker for use in forced air switchgear or switchboard enclosure manufactured and tested by the OEM.
AABBCC or NNAABBCC phasing is the type used in Cutler-Hammer Pow-R-Line C Switchboards and is the recommended phasing for use by OEMs.
ABCABC or NNABCABC phasing is for use in Cutler-Hammer Magnum DS Low Voltage Switchgear and Power Modules.
Use a V in lieu of a H as the 8th. (eighth) character in the Catalog Number when factory installed vertical adapters are required instead of standard horizontal terminals.
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
59
60
Factory Configured Circuit Breakers
July 2003
Tables 3.3, 3.4 and 3.5 Magnum DS Factory Installed Current Sensors and Rating Plugs Option for Fixed
or Drawout Circuit Breakers (Character Positions 11 and 12 of Catalog Number)
Depending on the circuit breaker frame type, select current sensors and rating plugs from Tables 3.4, 3.5 or 3.6. One current sensor per phase and one
rating plug are included as standard with all fixed and drawout circuit breakers unless a circuit breaker is non-automatic. Select NN for character positions 11 and 12 if the circuit breaker is non-automatic (without integral trip unit protection). Select the current sensor and rating plug rating by circuit
breaker frame size. For 3-pole circuit breaker ground fault applications on 3-phase, 4-wire circuits, external neutral mounted current sensors must be
ordered separately.
Table 3.3 Available Current Sensors and Rating Plugs for Narrow Frame
Catalog Number
Positions
11 and 12
2000A
(Fixed Circuit
Breaker Only)
NN - None
20
16
13
12
10
08
07
06
04
03
05
02
01
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
1600 A
1600
1250
1200
1000
800
630
600
400
300
250
200
100
1200 A
1200
1000
800
630
600
400
300
250
200
100
800 A
800
630
600
400
300
250
200
100
Check Cutler-Hammer for availability of 100 ampere sensor
Table 3.4 Available Current Sensors and Rating Plugs for Standard Frame
Catalog Number
Positions
11 and 12
3200 A
3000 A
2500 A
2000 A
NN - None
32
30
25
20
16
13
12
10
08
07
06
04
03
05
02
01
3200
3000
2500
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
3000
2500
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
2500
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
2000
1600
1250
1200
1000
800
630
600
400
300
250
200
1600 A
1600
1250
1200
1000
800
630
600
400
300
250
200
100
800 A
800
630
600
400
300
250
200
100
Check Cutler-Hammer for availability of 100 ampere sensor
Table 3.5 Available Current Sensors and Rating Plugs for Double Frame
Catalog Number
Positions
11 and 12
NN - None
60
50
40
32
25
20
6000 A
6000
5000
4000
3200
2500
2000
5000 A
4000 A
5000
4000
3200
2500
2000
4000
3200
2500
2000
Check Cutler-Hammer for future availability of sensors on frames indicated
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Factory Configured Circuit Breakers
July 2003
Table 3.6 Factory Installed Trip Unit Option for Fixed or Drawout Circuit Breakers
(Character Positions 13 and 14 of Catalog Number)
Catalog Number
Positions
13 and 14
Digitrip RMS
Trip Unit
Functions
Trip Unit
Power Supply
Voltage
Power Relay
Module Alarm or
Trip Contact
Available on
Magnum
Frame(s)
NN
NN
NN
NN
Non-Automatic
Non-Automatic
Non-Automatic
Non-Automatic
3-Pole ACB
3-Pole ACB
4-Pole ACB
4-Pole ACB
Not Applicable
Not Applicable
Not Applicable
Not Applicable
None
None
None
None
Narrow/Standard
Double
Narrow/Standard
Double
22
220
LI
Not Applicable
None
Narrow/Standard
None
None
All Frames
All Frames
None
High Load Alarm
High Load Alarm
High Load Alarm
None
Ground Trip
Ground Trip
Ground Trip
Ground Alarm
Ground Alarm
Ground Alarm
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
52
5G
520
520
LSI
LSIG
Not Applicable
Not Applicable
M2
MT
MU
MV
MG
MH
MM
MN
ME
MC
MF
520M
520M
520M
520M
520M
520M
520M
520M
520M
520M
520M
LSI
LSI
LSI
LSI
LSIG
LSIG
LSIG
LSIG
LSIA
LSIA
LSIA
Not Applicable
24/48 Vdc
120 Vac
240 Vac
Not Applicable
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
CT
CU
CV
CH
CM
CN
CE
CC
CF
520MC
520MC
520MC
520MC
520MC
520MC
520MC
520MC
520MC
LSI
LSI
LSI
LSIG
LSIG
LSIG
LSIA
LSIA
LSIA
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
High Load Alarm
High Load Alarm
High Load Alarm
Ground Trip
Ground Trip
Ground Trip
Ground Alarm
Ground Alarm
Ground Alarm
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
All Frames
1A
1C
1E
1F
1G
1H
1J
1K
1M
1150
1150
1150
1150
1150
1150
1150
1150
1150
LSI
LSI
LSI
LSIG
LSIG
LSIG
LSIA
LSIA
LSIA
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
24/48 Vdc
120 Vac
240 Vac
Programmable
Programmable
Programmable
Programmable
Programmable
Programmable
Programmable
Programmable
Programmable
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Standard/Double
Digitrip 520MC Trip Unit requires PowerNet Software version 3.2 or higher if PowerNet is used
Power Relay Module mounted integral to circuit breaker receives power from an external customer supplied source wired through the
breaker secondary contacts. The external source powers the trip unit digital display (520M, 520MC and 1150), communications functions
(520MC and 1150) and relays
No Power Relay Module provided for 520M trip unit when this catalog code is selected. The Digital display powered from current sensors
and the circuit breaker must carry 20% rated sensor current to power up the trip unit digital display.
Digitrip 1150 has programmable relay trip or contact A for trip unit protective and high load functions.
The maximum available instaneous interrupting rating for the Magnum DS Standard Frame Non-Automatic Switch is 85kA when the
breaker is used with a suitable external overcurrent protective device with instantaneous protection.
Digitrip 220 Trip Unit
PG01301001E
Digitrip 520 Trip Unit
Digitrip 520M Trip Unit
Digitrip 520MC Trip Unit
For more information visit: www.cutler-hammer.eaton.com
Digitrip 1150 Trip Unit
61
Factory Configured Circuit Breakers
62
57
July 2003
Table 3.7 Factory Installed Shunt Trip (ST) Option
for Fixed or Drawout Circuit Breakers (Character
Position 15 of Catalog Number)
Catalog Number
Position 15
Voltage
(AC: 50/60 Hz)
N
A
R
C
H
None
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
Table 3.8 Factory Installed Motor Operator Option
for Fixed or Drawout Circuit Breakers (Character
Position 16 of Catalog Number)
For electrically operated circuit breakers, select a Motor Operator and
Spring Release Device (SRD) and (if required) a Shunt Trip (ST). The
Motor Operator voltage selected must match the Spring Release
Device (SRD) voltage.
Catalog Number
Position 16
Voltage
(AC: 50/60 Hz)
M
N
P
L
K
W
T
Manual Operated
110 - 120 Vac
220 - 240 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
Refer applications requiring capacitor trip
devices to Cutler-Hammer
Table 3.9 Factory Installed Spring Release Device
(SRD) Option for Fixed or Drawout Circuit Breakers
(Character Position 17 of Catalog Number)
Catalog Number
Position 17
Voltage
(AC: 50/60 Hz)
N
A
R
C
H
None
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
Table 3.10 Factory Installed Undervoltage Release
(UVR) or Second Shunt Trip Attachment (STA)
Option for Fixed or Drawout Circuit Breakers
(Character Position 18 of Catalog Number)
Catalog Number
Position 18
Voltage
(AC: 50/60 Hz)
UVR
Release Type
N
A
R
C
H
E
F
G
X
J
K
1
2
3
4
None
110 - 127 Vac
208 - 240 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
32 V dc
380 - 415 Vac
480 Vac
600 Vac
110 - 127 Vac
208 - 250 Vac
24 Vdc
48 Vdc
None
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Second Shunt Trip
Second Shunt Trip
Second Shunt Trip
Second Shunt Trip
Refer requests for Time Delay UVRs to Cutler-Hammer.
Digitrip 1150 Trip Units have an integral adjustable time delay undervoltage trip
function from the line voltage.
An external customer supplied panel mounted Time Delay Undervoltage Relay can
Table 3.11 Factory Installed Auxiliary Switch
Option for Fixed or Drawout Circuit Breakers
(Character Position 19 of Catalog Number)
Catalog Number
Contact Type
Position 19
N
2
4
6
None
2a/2b
4a/4b
6a/6b
Comments
also be applied, wired through the breaker secondary contacts to a Shunt Trip
Attachment for Time Delay Undervoltage protection.
Each second Shunt Trip Attachment includes its own cut-off switch.
Table 3.12 Factory Installed Bell Alarm/OTS Switch
Option for Fixed or Drawout Circuit Breakers
(Character Position 20 of Catalog Number)
This option is for circuit breakers with trip units only, not available on
Non-Automatic Circuit Breakers.
4a/4b maximum on Narrow Frame
6a/6b maximum on Double or Standard Frames
Rfer applications requiring 6a/6b contacts on the Narrow Frame Breaker to CutlerHammer.
Except when a Second Shunt Trip Attachment is selected, which occupies a 2a/2b
contact mounting position.
Catalog Number
Position 20
Mechanical
Trip Indicator
OTS Switch
with 2 Form C Contacts
E
N
Y
No
Yes
Yes
No
No
Yes
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Factory Configured Circuit Breakers
July 2003
Table 3.13 Factory Installed
Padlockable Pushbutton Cover Option for
Fixed or Drawout Circuit Breakers
(Character Position 21 of Catalog Number)
Catalog Number
Position 21
Description
N
M
P
C
H
None
Metal Frame (Open and Close)
Plastic Frame (Open and Close)
Block Close PB Metal Frame
Block Close PB Plastic Frame
Table 3.16 Circuit Breaker and Cassette
Shipping Instructions
(Character Position 24 of Catalog Number)
Configure the drawout cassette and cassette options using Figure 3-2
(Cassette Catalog Number Selections) and its accompanying tables.
Shipment
Description
Drawout ACB
Alone
All Frames
Not
Applicable
Not Wired
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Narrow
No Shutters
Not Wired
Standard
No Shutters
Not Wired
Narrow
No Shutters
Pre-Wired
Standard
No Shutters
Pre-Wired
Narrow
Shutters
Not Wired
Standard
Shutters
Not Wired
Narrow
Shutters
Pre-Wired
Standard
Shutters
Pre-Wired
Fixed or
C
P
P
Table 3.14 Factory Installed Operations
Counter/Key Interlock Provisions Option for
Fixed or Drawout Circuit Breakers
(Character Position 22 of Catalog Number)
Catalog Number
Position 22
Counter Type
Keylock Provision
N
K
C
R
A
Y
L
H
No Counter
No Counter
No Counter
No Counter
Operations Counter
Operations Counter
Operations Counter
Operations Counter
No Lock
Kirk Lock
Castell Lock
Ronis Lock
No Lock
Kirk Lock
Castell Lock
Ronis Lock
S
S
W
W
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Drawout ACB in
Narrow Cassette
Drawout ACB in
Universal Cassette
Shutters
Pre-Wired
Cassette
Secondary
Terminal
Blocks
Double-wide and Standard cassettes ship separately from breakers
Table 3.17 Future Use By Cutler-Hammer
(Character Position 25 of Catalog
Key Interlock provision includes a hole in the front cover with
cap plus provisions hardware kit for customer installation of
customer supplied cylinder lock.
Catalog Number
Position 25
X
Table 3.15 Factory Installed Latch Check
Switch/Metering Trip Unit Configuration
Option for Fixed or Drawout Circuit Breakers
(Character Position 23 of Catalog Number)
The Latch Check Switch monitors the circuit breaker trip latch
and readiness to close.
Catalog Number
Position 23
Latch Check Switch
(LCS) Connection
Metering Trip Unit Line Voltage Connection
N
M
L
Y
C
D
None (Default)
None
Latch Check Switch wired to Spring Release
Latch Check Switch wired to Spring Release
Latch Check Switch for External Wiring (1 Form C)
Latch Check Switch for External Wiring (1 Form C)
Upper Terminal Voltage Connection
Lower Terminal Voltage Connection
Upper Terminal Voltage Connection
Lower Terminal Voltage Connection
Upper Terminal Voltage Connection
Lower Terminal Voltage Connection
(Applicable only when Digitrip RMS 1150 Trip
Unit is selected in Catalog Positions 13 and 14)
Form C contact wired through circuit breaker secondary contacts for external use.
PG01301001E
Magnum ACB
Frame Type
Catalog
Number
Position 24
For more information visit: www.cutler-hammer.eaton.com
Description
Future Factory
Option
63
Factory Configured Drawout Cassettes
64
July 2003
Factory Configured Drawout
Cassettes
Step 2: Select Cassette Catalog
Positions 8 through 15 to designate factory installed options
as follows:
Factory configured cassettes for
drawout Magnum DS Power Circuit
Breakers are ordered using a 15digit catalog numbering system.
Cassette configuration is achieved
by using a simple 2-step process.
Catalog Positions 8 and 9 per
Table 3.19 are reserved for a future
option.
Catalog Position 10 establishes if optional shutters are installed
per Table 3.20.
Step 1: Select a 7-Digit
Cassette Catalog Number
Prefix.
Catalog Positions 11 through
13 per Table 3.21 are reserved for
future options.
Choose the cassette prefix from
Table 3.18 based on the following:
Narrow Frame Cassette
(Front View with circuit breaker)
Narrow Frame Cassette
(Rear View)
Magnum Cassette Type
Catalog Positions 14 and 15
establishe if the cassette is prewired per per Table 3.22.
Number of Poles
Magnum Breaker Frame Type
Continuous Current Rating
Magnum Frame Type
Catalog Number Character Positions
1
N
Character
Position
A N N
Description
10 11 12 13 14 15
N N
Character
Position
C
Description
Cassette Family
Future Use
10
Shutters
Continuous Amperes
11
Future Use
Poles
12
Future Use
Rear Terminals
13
Future Use
Arc Hood
14
Cassette Wiring
Future Use
15
Cassette Shipping
3&4
Future Use
Figure 3-2 Drawout Cassette 15-character Catalog Number Selections
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Factory Configured Drawout Cassettes
July 2003
Table 3.18 Cassettes for Drawout Circuit Breakers
(First 7 Character Positions of Catalog Number)
Cassette standard features include an arc hood, provisions for secondary terminal blocks including wiring, and a cell rejection kit. Narrow and Universal Cassettes may be shipped with the circuit breaker by specifying breaker Catalog Character Position 24.
Catalog Number
Positions
1 to 7
Cassette Type
Poles
Magnum
Circuit Breaker
Frame Type
Continuous
Current Rating (A)
at 40C
LN203HA
MN203UA
MN323UA
MN403UA
MN503UA
Narrow
Universal
Universal
Universal
Universal
3 pole
3 pole
3 pole
3 pole
3 pole
Narrow
Standard
Standard
Double
Double
800-1600
800-2000
2500-3200
4000
5000
LN204HA
MN204UA
MN324UA
MN404UA
MN504UA
Narrow
Universal
Universal
Universal
Universal
4 pole
4 pole
4 pole
4 pole
4 pole
Narrow
Standard
Standard
Double
Double
800-1600
800-2000
2500-3200
4000
5000
MN203PA
MN323PA
MN403PA
MN503PA
Basic w/o Stab Kit
Basic w/o Stab Kit
Basic w/o Stab Kit
Basic w/o Stab Kit
3 pole
3 pole
3 pole
3 pole
Standard
Standard
Double
Double
800-2000
2500-3200
4000
5000
MN203CA
MN323CA
MN403CA
MN503CA
Basic w/ Stab Kit
Basic w/ Stab Kit
Basic w/ Stab Kit
Basic w/ Stab Kit
3 pole
3 pole
3 pole
3 pole
Standard
Standard
Double
Double
800-2000
2500-3200
4000
5000
Table 3.20 Cassette Shutters Option
(Character Position 10 of Catalog Number)
Shutters can be factory installed or are also available as a field installation kit for customer installation. For the Basic Cassette, a shutter field kit is recommended rather than factory installed
shutters, since the shutter must be partially removed to assemble bus stabs in the cassette.
Catalog Number
Position 10
Description
Cassette Type
N
S
S
S
No Shutters
Shutters Installed
Shutters Installed
Shutters Installed
All Types
Narrow
Universal & Basic
Universal & Basic
S
S
S
Shutters Installed
Shutters Installed
Shutters Installed
Narrow
Universal
Universal
Magnum
Circuit Breaker
Frame Type
Continuous
Current Rating (A)
at 40C
3 and 4
3 pole
3 pole
3 pole
All Frames
Narrow
Standard
Double
All Ratings
800-1600
800-3200
4000-5000
4 pole
4 pole
4 pole
Narrow
Standard
Double
800-1600
800-3200
4000-5000
Poles
Table 3.23 Pre-wired Cassettes Option
(Character Positions 14 and 15 of Catalog Number)
Pre-wired cassettes include wiring and terminal blocks mounted and wired to secondary contacts
ready to receive the circuit breaker.
Catalog Number
Positions
14 and 15
NC
WC
WC
WC
PG01301001E
Voltage
(AC: 50/60 Hz)
Cassette Type
All Types
Unwired
Pre-wired for circuit breaker
Narrow
Pre-wired for circuit breaker Universal & Basic
Pre-wired for circuit breaker Universal & Basic
Magnum
Continuous
Circuit Breaker Current Rating (A)
Frame Type
at 40C
All Frames
Narrow
Standard
Double
All Ratings
800-1600
800-3200
4000-5000
For more information visit: www.cutler-hammer.eaton.com
Table 3.19 Future Cassette
Option (Positions 8 and 9 of
Catalog Number)
Catalog Number
Positions 8 and 9
NN
Table 3.21 Future Cassette
Option (Positions 11 to 12 of
Catalog Number)
Catalog Number
Positions
11 - 12
NNN
Table 3.22 Future Cassette
Option (Position 13 of
Catalog Number)
Catalog Number
Position 13
Door Escutcheon and
Gasket Kit
X
D
Not Included
Included
65
66
Field Option Kits for Cassettes
July 2003
Table 3.24 Cassette Shutter Field Option Kit
This is a field installable kit for use with drawout cassettes, and is for customer installation.
Magnum
Circuit Breaker
Frame
Cassette Type
Poles
Continuous
Current Rating (A)
Catalog Number
Narrow
Standard
Double
Narrow
Universal and Basic
Universal and Basic
3 pole
3 pole
3 pole
800-1600
800-3200
4000-5000
MDNSHTR3P
MDSHTR332
MDSHTR350
Narrow
Standard
Double
Narrow
Universal
Universal
4 pole
4 pole
4 pole
800-1600
800-3200
4000-5000
MDNSHTR4P
MDSHTR432
MDSHTR450
Table 3.25 Cassette Cell Switch Field Option Kit
This is a field installable kit for use with drawout cassettes and is for customer installation. The
switch changes position when the circuit breaker is levered to the CONNECT position. The kit
includes the switch, mounting bracket and hardware. The switch kit also includes pre-installed
wiring for easy field installation to cassette cell secondary terminal blocks.
Magnum Breaker
Frame and
Cassette Types
Catalog Number
Description
Type
Narrow
Standard & Double
Standard &Double
Standard & Double
MD4CSN
MSCELLSW1
MD4CS
MD8CS
4 Form C Contacts
4 Form C Contacts
4 Form C Contacts
8 Form C Contacts
Kit with Mounting Bracket
Switch Only
Kit with Mounting Bracket
Kit with Mounting Bracket
Table 3.26 Cassette Cell Lock
Provision Field Option Kit
This is a field installable kit for use with drawout cassettes and is for customer installation.
The kit includes mounting provisions for single
or multi-cylinder Kirk or Castell locks provided
and fitted to the cassette by the customer.
Catalog Number
Lock
MCASSPRL
MCASSPRR
Left Side
Right Side
Table 3.27 Secondary Contact Wiring
Field Option Kit
This is a field installable kit for use in wiring fixed circuit breakers or drawout circuit
breaker cassette secondary contacts or for adding option kits in the field. Each kit can be
used to complete as many as three circuit breakers or more, depending on the number
and type of accessories required for the the circuit breaker.
Description
Catalog Number
Kit Contents
Secondary Terminal Block Kit
Secondary Terminal Wire Kit
Secondary Terminal Wiring Kit
Secondary Terminal Repair Kit
with Extraction Tool
MSECBK
MSECWR
MKW40
MSECTOOL
Ouantity 15 6-Point Terminal Blocks with Labels
Quantity 90 Wires for Connecting Secondary Blocks
Quantity 30 Wires 40 Inches Long for Fixed Circuit Breaker
Quantity 2 6-Point Terminal Blocks, Quantity 2 Secondary
Disconnect Blocks, AMP Removal Tool and and
Miscellaneous Wires
Pin Removal Tool can be purchased directly from AMP, Inc. under Part Number 3205183
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Field Option Kits for Circuit Breakers
July 2003
Table 3.28 Shunt Trip (ST)
Field Option Kit
Table 3.33 Undervoltage Release (UVR)
Field Option Kit
This is a field installable kit for fixed or drawout circuit breakers. The
kit includes a shunt trip (ST), a cut-off switch and instructions. Refer
applications requiring capacitor trip devices to Cutler-Hammer.
This is a field installable kit for fixed or drawout circuit
breakers.
Voltage
(AC:50/60Hz)
Catalog Number
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
MST1
MST2
MST3
MST4
Table 3.29 Motor Operator
Field Option Kit (For Charging Closing Spring)
This is a field installable kit for fixed or drawout circuit breakers.
The kit includes a motor operator assembly, which includes a
motor cut-off switch, and instructions.
Voltage
(AC:50/60Hz)
Catalog Number
110 - 120 Vac
220 - 250 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
MMOTN
MMOTP
MMOTL
MMOTK
MMOTW
MMOTT
This is a field installable kit for fixed or drawout circuit breakers. The
kit includes spring release device (SRD) assembly and instructions.
Catalog Number
110 - 127 Vac/dc
208 - 250 Vac/dc
24 Vdc
48 Vdc
MSRA
MSRR
MSRC
MSRH
Catalog Number
UVR Release
Type
110 - 127 Vac
208 - 240 Vac
24 Vdc
48 Vdc
110 - 125 Vdc
220 - 250 Vdc
32 Vdc
380 - 415 Vac
480 Vac
600 Vac
MUVRA
MUVRR
MUVRC
MUVRH
MUVRE
MUVRF
MUVRG
MUVRX
MUVRJ
MUVRK
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
Instantaneous
On applications requiring Time Delay Undervoltage Protection,
refer requests for Time Delay UVRs to Cutler-Hammer..
Digitrip 1150 Trip Units have an integral adjustable time delay undervoltage trip function.
An external panel mounted Time Delay Undervoltage Relay can also
be applied with a Shunt Trip Attachment for Time Delay
Undervoltage protection.
Table 3.34 Trip Indicator and Bell
Alarm/Overcurrent Trip Switch (OTS)
Field Option Kit
Table 3.30 Spring Release Device (SRD)
Field Option Kit
Voltage
(AC:50/60Hz)
Voltage
(AC:50/60Hz)
This is a field installable kit for fixed or drawout circuit breakers. It
is a manual reset only device and is for circuit breakers with trip
units only (not available on Non-Automatic Circuit Breakers).
Mechanical Pop-out Trip Indicator
Bell Alarm/OTS with Mechanical Trip Indicator
Bell Alarm/OTS contact
Catalog Number
Description
MLSC1
MLSC2
Latch Check Switch for Wiring Internally to Spring Release
Latch Check Switch with 1 Form C Contact for Remote indication.
Table 3.35 Operations Counter
Field Option Kit
This is a field installable kit for fixed or drawout circuit
breakers.
Kit Type
Catalog Number
Mechanical Counter
MCOUNT
Table 3.32 Auxiliary Switch
Field Option Kit
This is a field installable kit for fixed or drawout circuit breakers. Note that
a maximum of 6a/6b contacts apply to the Standard and Double Frames.
Contact Cutler-Hammer if more than 4a/4b contacts are required on the
Narrow Frame.
2a/2b Contacts
MAUX2
PG01301001E
MDTRIND
MDTRINDBA
MOTS
already installed.
This is a field installable kit for fixed or drawout circuit breakers. The
kit includes a LCS assembly 1 Form C contact, plug-in wires and
instructions.
Catalog Number
None
2 Form C
2 Form C
For use with breakers having mechanical pop-out trip indicator option
Table 3.31 Latch Check Switch (LCS)
Field Option Kit
Switch Type
Contacts Catalog Number
Trip Indication Description
For more information visit: www.cutler-hammer.eaton.com
67
68
Field Option Kits for Circuit Breakers
July 2003
Table 3.36 Padlockable Pushbutton Cover
Field Option Kit
Table 3.38 Sensor/Rating Plug
Field Change-out Kit
This is a field installable kit for fixed or drawout circuit
breakers. Padlocks are not included and must be provided
by customer. The cover can be configured to block the
breaker CLOSE and OPEN pushbuttons or only the CLOSE
pushbutton.
This is a field installable kit for changing the sensor/rating plug rating
on fixed or drawout circuit breakers. Narrow and Standard Frame kits
include 1 rating plug plus 3 sensors for 3-pole or 4 sensors for 4-pole
circuit breakers. Double Frame kits include 1 rating plug plus 6 sensors
for 3-pole or 8 sensors for 4-pole circuit breakers. The rating plug rating and the sensor rating in the kit match. The sensor ampere rating
selected cannot exceed the circuit breaker frame and ampere rating.
Note: For 3 pole breaker ground fault applications on 3 phase, 4 wire
circuits, externally mounted sensors must be ordered separately.
Cover Type
Catalog Number
Plastic Frame (Blocks Open and Close Buttons)
MCOVH
Metal Frame (Blocks Open and Close Buttons)
MCOVC
Magnum Frame
Table 3.37 Breaker Key Lock Provisions
Field Option Kit
This is a field installable kit for fixed or drawout
circuit breakers. The kit includes mounting
hardware and brackets to mount single cylinder
lock for locking circuit breaker in the Open
position. The cylinder lock and key are not
included and must be supplied by customer.
Key Type Catalog Number
Castell
Ronis
Kirk
MBRLCKC
MBRLCKR
MBRLCKK
Use with Customer Supplied Lock & Key #
Castell # FGCL4008
Ronis # 1104A
Kirk Lock # KC40---10 & Lock KC4
Table 3.39 Neutral Current Sensor
This is a field installable external accessory for use with fixed
or drawout circuit breakers. The fourth sensor is for mounting on enclosure neutral in 3-pole circuit breaker ground fault
applications on 3-phse, 4-wire systems.
Magnum Frame
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Narrow or Standard
Double
Double
Sensor
Rating
Sensor Qty.
Required per
3-Pole Breaker
Catalog Number
100
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3200
4000
5000
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
Contact C-H
9253C03H01
9253C03H02
9253C03H03
9253C03H04
9253C03H05
9253C03H14
9253C03H06
9253C03H07
9253C03H08
9253C03H15
9253C03H09
9253C03H10
9253C03H11
9253C03H12
9253C03H13
9253C03H10
9253C03H11
Sensor Rating
(A)
3-Pole
Catalog Number
4-Pole
Catalog Number
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
Narrow
100
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
M3NRG0100
M3NRG0200
M3NRG0250
M3NRG0300
M3NRG0400
M3NRG0600
M3NRG0630
M3NRG0800
M3NRG1000
M3NRG1200
M3NRG1250
M3NRG1600
M3NRG2000
M4NRG0100
M4NRG0200
M4NRG0250
M4NRG0300
M4NRG0400
M4NRG0600
M4NRG0630
M4NRG0800
M4NRG1000
M4NRG1200
M4NRG1250
M4NRG1600
M4NRG2000
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
100
200
250
300
400
600
630
800
1000
1200
1250
1600
2000
2500
3000
3200
M3SRG0100
M3SRG0200
M3SRG0250
M3SRG0300
M3SRG0400
M3SRG0600
M3SRG0630
M3SRG0800
M3SRG1000
M3SRG1200
M3SRG1250
M3SRG1600
M3SRG2000
M3SRG2500
M3SRG3000
M3SRG3200
M4SRG0100
M4SRG0200
M4SRG0250
M4SRG0300
M4SRG0400
M4SRG0600
M4SRG0630
M4SRG0800
M4SRG1000
M4SRG1200
M4SRG1250
M4SRG1600
M4SRG2000
M4SRG2500
M4SRG3000
M4SRG3200
2000
2500
3000
3200
4000
5000
M3RRG2000
M3RRG2500
M3RRG3000
M3RRG3200
M3RRG4000
M3RRG5000
M4RRG2000
M4RRG2500
M4RRG3000
M4RRG3200
M4SRG4000
M4SRG5000
Double
Double
Double
Double
Double
Double
Subject to future availability. Contact Cutler-Hammer.
Fixed Narrow Frame Breaker only
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Field Option Kits for Circuit Breakers
July 2003
Table 3.40 Primary Terminal Adapter Field
Option Kits for Fixed Circuit Breakers
This field installation kit is for changing fixed circuit breakers to the desired bus configurations.
Terminal
Adapter
Kit Type
Fixed
Magnum
Frame Type
Breaker
Poles
Continuous
Current
(A)
Short Circuit
Rating
(kA)
Catalog Number
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Narrow
Standard
Standard
Standard
Double
Double
3 pole
3 pole
3 pole
3 pole
3 pole
3 pole
800 - 2000
800 - 1600
Up to 2000
2500 - 3200
4000
5000
Up to 65
Up to 65
Up to 100
All
All
All
MVADP320N
MVADP16
MVADP20
MVADP32
MVADP40
MVADP50
Vertical
Vertical
Vertical
Vertical
Vertical
Vertical
Narrow
Standard
Standard
Standard
Double
Double
4 pole
4 pole
4 pole
4 pole
4 pole
4 pole
800 - 2000
800 - 1600
Up to 2000
2500 - 3200
4000
5000
Up to 65
Up to 65
Up to 100
All
All
All
MVADP420N
MVADP416
MVADP420
MVADP432
MVADP440
MVADP450
Front Mount
Front
Front
Front
Front
Front
Front
Narrow
Narrow
Standard
Standard
Standard
Double
Double
3 pole
3 pole
3 pole
3 pole
3 pole
3 pole
3 pole
800 - 1200
1600 - 2000
800 - 1200
1600 - 2500
3200
4000
5000
Up to 65
Up to 65
Up to 100
Up to 100
All
All
All
NFC312KT
NFC320KT
SFNTC312
SFNTC325
SFNTC332
Contact C-H
Contact C-H
Front
Front
Front Mount
Front Mount
Front Mount
Front Mount
Front Mount
Narrow
Narrow
Standard
Standard
Double
Double
Double
4 pole
4 pole
4 pole
4 pole
4 pole
4 pole
3 pole
800 - 1200
1600 - 2000
800 - 1200
1600 - 2500
3200
4000
5000
Up to 65
Up to 65
Up to 100
Up to 100
All
All
All
NFC412KT
NFC420KT
SFNTC412
SFNTC425
SFNTC432
Contact C-H
Contact C-H
Table 3.41 Primary Terminal Adapter Field
Option Kits for Drawout Circuit Cassettes
This field installation kit is for changing drawout cassettes to the desired bus configurations.
Terminal
Adapter
Kit Type
Kit Qty.
Required Per
Cassette
Drawout
Magnum
Frame Type
Drawout
Cassette
Type
Breaker
Poles
Continuous
Current
(A)
Catalog Number
Vertical
Narrow
Narrow
3 pole
800 - 1600
MVADP320N
Vertical
Narrow
Narrow
4 pole
800 - 1600
MVADP420N
L-Bus
L-Bus
L-Bus (with Heat Sinks)
Heat Sink Kit (No Bus)
L-Bus
1
1
1
1
2
Standard
Standard
Standard
Standard
Double
Universal
Universal
Universal
Universal
Universal
3 pole
3 pole
3 pole
3 pole
3 pole
800 - 2000
2500 - 3000
3200
3200
4000 - 5000
MUBADP316
MUBADP330
MUBADP332
MUBHS332
MUBADP330
L-Bus
L-Bus
L-Bus (with Heat Sinks)
Heat Sink Kit (No Bus)
L-Bus
1
1
1
1
2
Standard
Standard
Standard
Standard
Double
Universal
Universal
Universal
Universal
Universal
4 pole
4 pole
4 pole
4 pole
4 pole
800 - 2000
2500 - 3000
3200
3200
4000
MUBADP416
MUBADP430
MUBADP432
MUBHS432
MUBADP430
Vertical Bus Stab
Vertical Bus Stab
Vertical Bus Stab
Vertical Bus Stab
1
1
1
1
Standard
Standard
Double
Double
Basic
Basic
Basic
Basic
3 pole
3 pole
3 pole
3 pole
800 - 2000
2500 - 3200
4000
5000
Contact C-H
Contact C-H
Contact C-H
Contact C-H
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
69
70
Field Option Kits for Circuit Breakers
July 2003
Table 3.42 Mechanical Interlock Assembly Kits
This is an external field installation kit for fixed or drawout circuit breakers. Select a Mechanical
Interlock Kit and Rod or Cable Kits (Table 3.43) for complete assembly as indicated.
Configuration
of Interlocked
Breakers
Type of Breaker
Interlock Kit
Type
Catalog Number
of Kit
Comments
2 Way
2 Way
3 Way
3 Way
3 Way
Fixed
Fixed
Fixed
Fixed
Fixed
Rod Type 2
Cable Type 2
Cable Type 31
Cable Type 32
Cable Type 33
MI2FR
MI2FC
MI31FC
MI32FC
MI33FC
Kit also requires 1 Rod Kit
Kit also requires 1 Cable Kit
Kit also requires 2 Cable Kits
Kit also requires 3 Cable Kits
Kit also requires 3 Cable Kits
2 Way
2 Way
3 Way
3 Way
3 Way
Drawout
Drawout
Drawout
Drawout
Drawout
Rod Type 2
Cable Type 2
Cable Type 31
Cable Type 32
Cable Type 33
MI2DR
MI2DC
MI31DC
MI32DC
MI33DC
Kit also requires 1 Rod Kit
Kit also requires 1 Cable Kit
Kit also requires 2 Cable Kits
Kit also requires 3 Cable Kits
Kit also requires 3 Cable Kits
Table 3.43 Rod or Cable Kits
This is an external field installation kit for fixed or drawout circuit
breakers. It is required for the assembly of Mechanical Interlock
Assembly Kits (Table 3.42)
Kit Type
Catalog Number
of Kit
Comments
Rod Type
Cable Type
Cable Type
Cable Type
Cable Type
MIR
MIC5
MIC6
MIC8
MIC10
Includes 2 Rods 3 feet long (910 mm) each
Includes 2 Cables 5 feet long (1520 mm) each
Includes 2 Cables 6 feet long (1830 mm) each
Includes 2 Cables 8 feet long (2440 mm) each
Includes 2 Cables 10 feet long (3050 mm) each
For more information visit: www.cutler-hammer.eaton.com
Cassette-Mounted 2-Way Cable
Interlock
PG01301001E
Miscellaneous Accessories
July 2003
Table 3.44 Miscellaneous Accessories
Description
Levering Device
Lifting Yoke (3-pole Narrow Frame)
Lifting Yoke (3-pole Standard Frame)
Lifting Yoke (3-pole Double Frame)
Lifting Yoke (4-pole Narrow Frame)
Lifting Yoke (4-pole Standard Frame)
Lifting Yoke (4-pole Double Frame)
Roll on Floor Lifting Device
Magnum Test Cabinet
Catalog Number
Kit Contents/Accessory Function
Breaker Maintenance and Handling
None Required
Special levering device not required. Use 10 mm socket and drive set
8651C91G09
Fits 3-pole Narrow Frame Circuit Breaker
8651C91G02
Fits 3-pole Standard Frame Circuit Breaker
8651C91G05
Fits 3-pole Double Frame Circuit Breaker
8651C91G10
Fits 4-pole Narrow Frame Circuit Breaker
8651C91G07
Fits 4-pole Standard Frame Circuit Breaker
8651C91G08
Fits 4-pole Double Frame Circuit Breaker
6727D63H20
Lifts breaker fitted with lofting yoke from above
Contact C-H
For testing electrical operation of circuit breaker
Breaker Trip Unit Test Devices and Accessories
Magnum Trip Unit Tester
Auxiliary Power Module
Secondary Injection Adapter Cable
Triplink Cable
Door Escutcheon and Gasket Kit
Door Cut-out Cover
IP54 Door Cover Kit
Cassette Rejection Bracket Kit
Capacitor Unit for Breaker Capacitor Trip
CT Shorting and Jumper Terminal Block Kit
CT Jumper Block Kit
CT Shorting Block Kit
MTST1
PRTAAPM
MTADPTC
5720B59G01
Hand-Held Tester fpr Digitrip 220, 520, 520M and 520MC Trip Units
Provides 32 Vdc auxiliary power to Digitrip 520M, 520MC and 1150 Trip Units
Adapter cable to test Magnum trip unit with DS-II test kit
Downloads Trip Unit Settings from one Digitrip RMS 1150 Trip Unit to another
Miscellaneous Breaker and Enclosure Accessories
MDES
Escutcheon, Gasket and Mounting Hardware
MDCC
Covers door cavity for future breaker compartments
MDESC
IP54 Cover, Gasket and Mounting Hardware
MCELLREJBK
Circuit Breaker Cell Rejection Bracket Kit (Cassette Mounting)
Contact C-H
Enclosure Mounted AC Capacitor Unit for circuit breaker Capacitor Trip
MSJB
One CT jumper block and one CT shorting block with mounting hardware
MJB
One CT jumper block with mounting hardware
MSB
One CT shorting block with mounting hardware
Peripheral Devices
MODBUS Mint Translator
Digital Relay Accessory Module
PG01301001E
MMINT
DRAM
Translates INCOM for up to 32 Communicating Trip Units to Modbus
Used with Accessory Bus on Digitrip 1150 Trip Unit
For more information visit: www.cutler-hammer.eaton.com
71
72
Appendix
July 2003
Engineering Data Reference Chart
Sections
Reference #
Product Description
For Use with or Installation of
Breaker Instruction
Book
2C12060H05
2C13060H03
Magnum DS Fixed/Drawout Power Circuit Breakers (ANSI)
Magnum Fixed/Drawout Power Circuit Breakers (IEC)
Installation, Operation and Maintenace
Installation, Operation and Maintenace
Trip Unit IL
70C1036H03
70C1037H04
70C1080H02
Digitrip Models 1150 & 1150i Trip Units (includes 1150P)
Digitrip Models 220, 220+, 520, 520i, 520Mi, 520MC & 520MCi Trip Units
Ground Fault Alarm Power Supply
2A11799G40 - G44
2A11799G01 - G33
7802C83G01/G02
Breaker Accessory
and Field Option Kit
2C14766H01
2C14761H01
2C14762H01
2C14760H01
2C13769H02
2C13769H01
2C12769H01
2C12769H02
2C12865H01
2A11851H10
2C12895H01
2C13761H01
2C13763H01
2C13760H01
2C13766H01
2C13795H03
2C13820H01
2C14763H01
2C14764H01
2C14765H01
2C12894H01
2C14767H01
2C13764H01
Breaker Auxiliary Switch Field Option Kit
Breaker Spring Release Field Option Kit
Breaker Shunt Trip Field Option Kit
Breaker Undervoltage Release Field Option Kit
Breaker Motor Operator Field Option Kit (For Narrow, Standard & Double Frame)
Breaker Motor Operator Field Option Kit (For Standard & Double Frame Only)
Latch Check Switch for use with Spring Release Field Option Kit
Latch Check Switch (accessible) Field Option Kit
Charging Handle Replacement Kit
Center Pull Handle Replacement Parts Kit
Pushbutton Cover Field Option Kit
Breaker Kirk Key Interlock Provision Field Option Kit
Breaker Castell Key Interlock Provision Field Option Kit
Breaker Ronis Key Interlock Provision Field Option Kit
Breaker Pop-out Trip Indicator with Switches Field Option Kit
Fixed Breaker Secondary Terminal Mounting Bracket Field Option Kit
Front Mounted Standard Terminal Field Option Kit
800-1600A Vertical Adapter Field Option Kit
2000A Vertical Adapter Field Option Kit
3000-3200A Vertical Adapter Field Option Kit
Door Escutcheon with Gasket Field Option Kit
Breaker Operations Counter Field Option Kit
Non-Auto Breaker Trip Unit Cover Field Option Kit
2A11796
2A11792
2A11791
2A11793
2A11794G41 - G46
2A11794G22 - G35
2C13797G01
2C13797G02
2A10892
2A11851
2C12890
2C12891G01
2C12891G02
2C12891G03
1B93491
2C13794
2A10820
2A11795G01, G11 & G41
2A11795G02, G12 & G42
2A11795G48, G49, G53, G54, G56 G58
2C12893
2A10890
2A11797
Cassette Accessory
and Field Option Kit
2C12093H01
2C12093H02
2C13768H01
2C13765H01
2C13860H01
2C14691H01
2C14694H01
2C14694H02
2C14696H01
3 Pole ANSI Cassette Shutters Field Option Kit
4 Pole ANSI Cassette Shutters Field Option Kit
IEC 800-3200A Cassette Shutters Field Option Kit
IEC 4000-6300A Cassette Shutters Field Option Kit
Cassette Universal Bus Adapter Field Option Kit
Cassette Key Interlock Provision Field Option Kit
ANSI Cassette Cell Switch Field Option Kit
IEC Cassette Cell Switch Field Option Kit
Cassette CT Shorting & Jumper Block Field Option Kit
2C12998
2C12998
1B93096
1B93098
2A10670
1B93091
1B93090
2C13793
1B93094
Miscellaneous
Accessories
2C12766H01
2C12767H01
2C12768H01
2C12860H01
2C12861H01
2C12862H01
2C12863H01
2C12864H01
2C13790H01
2C14695H01
2C12896H01
2C12896H02
2C12898H01
Fixed Breaker 2-Way Cable Interlock Field Option Kit
Fixed Breaker 2-Way Rod Interlock Field Option Kit
Drawout Breaker 2-Way Rod Interlock Field Option Kit
Drawout Breaker 2-Way Cable Interlock Field Option Kit
Drawout Breaker MI31 3-Way Cable Interlock Field Option Kit
Fixed Breaker MI31 3-Way Cable Interlock Field Option Kit
Drawout Breaker MI32 3-Way Cable Interlock Field Option Kit
Fixed Breaker MI32 3-Way Cable Interlock Field Option Kit
Secondary Wiring Kit to 6 Point Termination Block Field Option Kit
6 Point Terminal Block Field Option Kit
Drawout Breaker 1100V Arc Hood Barrier Field Option Kit
Fixed Breaker 1100V Arc Hood Barrier Field Option Kit
Fixed Breaker Arc Hood Barrier Field Option Kit
2A11857G02, 2A11858G01
2A11856G02, 2A11859G02
2A11856G01, 2A11859G01
2A11857G01, 2A11858
2A11857G03/G07, 2A11858
2A11857G04/G08, 2A11858
2A11857G05, 2A11858
2A11857G06, 2A11858
1B93093
1B93092
2A10800G02
2A10800G12
2C12898
Renewal Parts Kit
2C12760H01
2C12761H01
2C12762H01
2C12763H01
2C12764H01
2C12866H01
2C12867H01
2C13762H01
2C12061H02
2C12897H01
2C12899H01
2C13767H01
2C15860H01
Breaker Stationary Contact Replacement Kit
Breaker Moving Contact Replacement Kit
Breaker Secondary Disconnect Block Replacement Kit
Breaker Terminal Block Replacement Kit
Breaker Accessory Tray Replacement Kit
Levering Mechanism Assembly Replacement Kit
Levering Door Mechanism Assembly Replacement Kit
Breaker Current Sensor & Rating Plug Replacement Kit
Hatchet Assembly Replacement Parts Kit
Drawout 2500-3200A Breaker Vertical Adapter Replacement Kit
Drawout Breaker Standard/Double Frame Rejection Bracket Replacement Kit
Cassette Standard/Double Frame Rejection Bracket Replacement Kit
Drawout Breaker Narrow Frame Rejection Bracket Replacement Kit
2A10896
2C12761
2A10899
2A10854
2A10891
2A10855
2A10894
2A11798
2A11855
2A11795G48-49 & G53-54
2A11893G01, G02
1B92695G01, G02 & G51
2A11893G92-G94
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
73
74
Appendix
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
75
76
Appendix
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
77
78
Appendix
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
79
80
Appendix
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
81
82
Appendix
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
83
84
Appendix
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
85
86
Appendix
July 2003
Connection Diagram Digitrip 220/520/520i/520M/520Mi/520MC/520MCi (100-3200A)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
Connection Diagram Digitrip 520/520i/520M/520Mi/520MC/520MCi (5000A ABCABC Phasing)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
87
88
Appendix
July 2003
Connection Diagram Digitrip 520/520i/520M/520Mi/520MC/520MCi (5000A AABBCC Phasing)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
SEE NOTE 16
16. JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE
REVERSE POWER CONDITION.
Connection Diagram Digitrip 1150, 1150i (100-3200A)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
89
90
Appendix
July 2003
15. JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE
REVERSE POWER CONDITION.
SEE NOTE 15
Connection Diagram Digitrip 1150/1150i (5000A ABCABC Phasing)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
PG01301001E
15. JUMPERING B-3 (NPOW) TO B-7 TERMINAL WILL ELIMINATE
REVERSE POWER CONDITION.
SEE NOTE 15
Connection Diagram Digitrip 1150/1150i (5000A AABBCC Phasing)
For more information visit: www.cutler-hammer.eaton.com
91
92
Appendix
July 2003
Narrow Frame Cassette Overall Dimensions (3 and 4 pole, 800-2000A)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
Standard Frame Universal Cassette Overall Dimensions (3 and 4 pole, 800-3200A)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
93
94
Appendix
July 2003
Double Wide Frame Universal Cassette Overall Dimensions (6 and 8 pole, 4000-5000A)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
Standard Frame Basic Cassette Overall Dimensions (3 pole, 800-3200A)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
95
96
Appendix
July 2003
Double Wide Frame Basic Cassette Overall Dimensions (3 pole, 4000-5000A)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
Narrow Frame Fixed Overall Dimensions (3 and 4 pole, 800-2000A)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
97
98
Appendix
July 2003
Standard Frame Fixed Overall Dimensions (3 and 4 pole, 800-1600A)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
Standard Frame Fixed Overall Dimensions (3 and 4 pole, 2000A)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
99
100
Appendix
July 2003
Standard Frame Fixed Overall Dimensions (3 and 4 pole, 3200A)
For more information visit: www.cutler-hammer.eaton.com
PG01301001E
Appendix
July 2003
Double Wide Frame Fixed Overall Dimensions (3 and 4 pole, 4000-6300A)
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
101
July 2003
PG01301001E
For more information visit: www.cutler-hammer.eaton.com
108
July 2003
For more information visit: www.cutler-hammer.eaton.com
PG01301001E