User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
1Summary
With high performance MPU, the GAC608 diesel generator set controller is provided
with many advantages, such as impacted structuresmall floor spaceeasy to connection
high reliability and so on. Additionally, based on overall control, realize all kinds of
automatic protection and site parameter adjustment, and so this device is widely used for
the automatic control system in all kinds of diesel generator set.
2Performance and characteristics
Automatic start/stop the generator set, alarm and stop the generator set for high
water temperaturelow oil pressureover speedlow speed, etc.
Built-in ATS control unit.
Built-in main power detection unit.
Detect and display the speed of diesel engine voltage of battery as well as
running time.
Built-in speed/frequency detect unitcan judge the states such as crank success ,
rated running , over speed and low speed.
Built-in preheating and pre-oil supply control.
Can output two different kinds of control signals for oil-break at the simultaneously,
so suitable for different models diesel engine.
With four gun control models which are high-speed start three-wire solenoid
valveservo motor and electric speed regulation , etc. So suitable for different gun
control mechanism.
Power supply range8~35Vsuitable for different voltage environment.
Built-in watch dog can never be dead halt , ensuring smooth program execution .
3Specification
Power supply: 8~35V DC
Input voltage (main power or generator set): 0~300V AC.
Working conditions: Temperature 0~50
Humidity (20~90)%
Storage condition: Temperature range -20~+60
Power consumption: <3W
4Parameter setting content
P00 Rated speed: 01500
11800 23000 33600
P01
Crank success conditions: 0Generator frequency
1Magnetic Pickup +
generator frequency
P02
Calculated value for the number of teeth of flywheel.
P03
Set value for the number of teeth of flywheel: 70255 (Default 125)
P04
Rated voltage: 80-255
P07
Gun control mode: 0Fixed gun
2Electromagnet control
1Servo motor control
3Electric speed regulation
P08
Time confirm for start signal: 1255S (Default 2S)
P09
Number of start: 19 (Default 3)
P10
Cranking time: 115 (Default 5S)
P11
Crank rest time: 560 (Default 10S)
P12
Idle running time: 0255 (Default 30S)
-1-
User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
P13
Oil bypass delay time: 10255 (Default 15S)
P14
Time confirm for stop signal: 1-255 (Default 2S)
P15
High speed cooling time: 10255 (Default 120S )
P16
Idle speed cooling time: 0255 (Default 30S)
P17
Stop time : 1025 (Default 10S)
P18
Pre-heating time: 090
P19
Transfer rest time: 2255 (Default 2S)
P20
Generator set switch delay time: 5255 (Default 5S)
P21
Main power switch delay time: 1255 (Default 2S)
P22
Calibration point for battery voltage: (12V DC)
P23
Calibration point for battery voltage: (24V DC)
P24
Calibration point for main power voltage: (220V AC)
P25
Main power voltage display
P26
Calibration point for generator voltage: (220V AC)
(Default 0S)
P27 Generator voltage display
5Operating
a. Operation panel
MODEL: GAC608
Crank Failure
Cooling
Low Oil Pressure
High Water Temperature
Low Speed
Over speed
Emergency Stop /Stop Failure
Remote Signal
Fault Signal for Extension
Generator
-2-
Voltage Abnormal
User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
Speed Display
Battery Voltage Display
Run time Display
Main power
Generator set
Manual
Setting/Reset
Manual turn off
Manual main power turn on
Load
Auto
Manual generator turn on
Manual Start
Manual Stop
b. There are manualautomatic and parameter setting models for choose. When under
manual or automatic mode, if press the
setting mode, while re-press
c. Manual operation
key by 3S, the machine enters into parameter
key by 3S, exit from parameter setting mode.
Startupwhen under manual state, continues to press
by 3Sthe generator set
shall be started, and judge that if the starting is successful ,rise up to high-speed for running
automatically. After oil bypass delay time, the generator set enters into normal running.
Within oil bypass delay time, the controller carries out detection for running conditions of
generator set without alarm and stop. In the normal running state , if there is any fault, the
generator set shall speed down and stop..
StopAfter the generator set enters into normal running, press
by 3s for normal
stop, then the generator set enters into standby state after high-speed and idle speed cooling. If
the generator set has not entered into normal running, it stops immediately.
ATS Manual operationContinues to press
key by 3sthe generator set turn on
while continues to press
key by 3sthe main power turn onContinues to press
by 3sif the ATS is three-section typethe ATS returns to middle positionif two-section
typereturns to main power turn on state.
d. Generator set automatic operation
Under automatic mode, if there is any abnormal condition for main power(Power-off
overvoltage or low voltage)all these shall be confirmed by starting signal delay, enter into
starting procedure then enter into normal running after starting idle speed delay
speed-up and oil bypass delay. When the starting signal disappears, the generator set
enters into stop procedure after stop signal delay confirmation, and enter into standby state
after high and idle speed cooling.
e. ATS Automatic operation
Under automatic mode, the generator set enters into running state and provide normal
voltage if the start signal is normal, and carry out automatic switching the generator set on
load after generator set switch delay, if there is failure, switch the main power on load
before generator set stop automatically. When the stop signal is completed with delay
confirmation, switch the main power on load automatically.
-3-
User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
f. Fault removal
In the processing of running, if there is any failure, generator set will stop by speed
down immediately, and the corresponding indicator is on. Then press the set/reset key
the generator set will be reseted from the failure state.
g. Parameter display
Under auto and manual state, the four-digital nixietube can display speed of
generator setvoltage of battery and running time, and the data shall be updated every 1.5s,
you may press
or
key for parameter selection. If under setting state, the
four-digital nixietube is used for displaying parameter number and value.
h. Parameter setting
Continues to press
key by 3sthe controller enters into parameter setting mode,
and the nixietube displays the parameter number like PSuch as P01P02here, press
or
key for parameter selection, if the parameter number is selected, press
keythe nixietube shall display the corresponding parameter value, and the controller shall
make the corresponding digital flicker. If the hundreds'digit flickerspress
value shall be reduced by 100press
key, add 100; if the tensdigit flickers press
key, the value is added with 10, while press
the units'digit
flickers press
key, reduced 1.
Press
units'digit flickers, press
key , the
key, the value shall be reduced by 10; if
key, the value shall be added with 1while press
for choosing the digit of flickering display, when
keyreturn to display status of parameter number. Continues
to press
key by 3sexit from parameter setting state and save the parameter value.
I. Setting for the number of flywheel teeth
When crank success conditions (P01)
select 1 ( Magnetic Pickup
generator
frequency), must set the number of flywheel teeth. If the number of wheel teeth is known,
you may set the number of flywheel according to P03. If unaware of the number of flywheel
teeth, there is automatic test function for choose. You may test and set the number of
flywheel teeth by the steps as follows:
Continues to press
Press
key by 3s, enter into parameter setting status.
for slecting P02 then press
key for displaying the number of
flywheel teeth by auto calculation.
Press
key for starting the generator setthen release
after start.
-4-
key immediately
User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
Use the AC voltage meter to detect the output voltage of magnetic speed sensor
generally, it should be in the range of 3V~30V, if not, adjust the clearance
between the magnetic speed sensor and flywheel.
If the generator set is working normally, the nixietube can display the number of
flywheel teeth by auto calculation.
When the number display is stable, press
keythen press
keythe number
shall flickers, this means the number of flywheel teeth is effective and saved into
P03.
Continues to press
key by 3s, the system shall quit from parameter setting
state and save the parameters.
6Typical Application
The typical diagram for GAC608 is shown as follows:
Load U V W N
U
U
V
W
N
V
W
N
10 13
14
16
15 12
11
GAC608
4 5
Speed Sensor
K5
Oil Pressure Sensor
K4
7
Oil Temperature Sensor
Raise Speed Relay
K3
Stop Relay
K2
Drop Speed Relay
K1
Alarm
6
Water Temperature Sensor
Crank Motor
Heater
K1
Fuel Valve
Emer. Stop
Battery+
K2
Stop solenoid
K5
Heat Relay
21 24 23 22 20 19 18 17
Crank Relay
Battery-
Meter Power
7Installation
The controller is designed to panel installation mode , and it is fixed by clamps when it is
installed. The overall dimension and panel tapping dimension are given as follows:
-5-
Utility
Generator
ATS
User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
8Test run
Before operation, inspections that are recommended as follows should be carried out:
a. Check and assure that all connections are correct , and that diameter of wire is
suitable ;
b. The DC power supply of controller is equipped with fuse ,and the positive
supply (+Ve) and the negative supply (-Ve) connected with battery are connected
correctly ;
c. The emergency stop input is connected with the positive supply (+Ve) of the
battery though the NC terminal and fuse of emergency stop button.
d. The suitable operation should be taken to prevent the engine from crank
success (such as dismantling the connection of crank motor),check and assure that it
is correct , then connect with battery ,select manual mode ,the controller will execute
program .
e. Press down start button
the generator set will crank , after starts have been
carried out according to setting crank numbers ,the controller sends the signal that
indicates crank failure ; Press key
to make the controller resetting ;
f. Restore the measure that prevents the generator set from crank success( such
as restoring the connection of crank motor ); Press start button
again the
generator set will crank , if crank is normal , the generator set will operate from idle
state (if idle has been set ) to normal state . In the meantime observe the running
condition of engine as well as voltage and frequency of AC generator. If there is
abnormal , stop the generator set ,then check connections of each part according to
this hand book ;
g. Choose auto state thought the front panelthen turn on the main power ,the
controller switches over ATS (if it exist) to mains on load after pass through the main
power normal delay , after cooling time , and then shut down to go into standby state
until the main power is abnormal again;
h. After the main power is abnormal again, the generator set will crank into normal
running state, and then switch the ATS to generator set on load. If not, you may check
the connections of ATS according to this hand book
f. For more information, please contact our technicists in time.
-6-
User's manual for GAC608 controller
Fujian Fu'an Deppblue Electronic Co.,Ltd.
9Troubleshooting
Fault Symptom
Possible measures
1.Check the battery
2.Check the connection of controller
3.Check the DC fuse
The controller is not work
Generator set
1.Check if the water temperature is over high
2.Check the voltage of generator
3.Check DC fuse
1.Check if the emergency button is normal
2. Check if the positive pole of battery has been connected
to emergency stop button correctly
3.Check if there is opening or short in connection
stop
Controller emergency stop
Lower oil pressure alarm after Check the oil pressure sensor input and its connection
crank success
High water temperature
alarm after crank success
Check the water temperature sensor input
connection
Failure to crank
1. Check the actuator and its connection
2. Check fuel
3. Check the battery voltage
4. Check magnetic and its connection