Measurenents
ANATYSIS AND PRO1ECTION OF POWER SYSTE}T,S COIIRSE
BUSBAR PROTECTION
BY
G.A.
I{AIII,ET
1.
BUSBAR PROTECTION
1.0
INTRODUCTION
rn the early
of the electricity suppry ind.ustry, protective
equ.ipment
for plants connected. to a busbar instalration
was reried upon to crear
busbar faults' This resulted. in tine-delayed.
fault clearance
days
by time-grad.ed
protections such as distance relays or
overcurrent-tine relays.
with present-day widely meshed power systen
networks with
rine sections
varying in length and nurnerous intermed.iate
infeedsl fault elearance by
zone 2 or zone J of d'istance relay can
be difficult plus the inpossibility
of selective tripping of different br:s sections.
rn order to maintain
systen stability and ninimise da^mag:e due to
high fault levels tine-delayed
tripping for busbar faults is no longer acceptable.
rt is therefore
necessarJr to detect busbar faults selectivery
with a rrnit form of protection
system.
2r0
(i)
rt
must be conpletely
reliable, since the protectlon may only
called to operate once or twi.ce in the rife of the
switchgear
installation and failure to operate under fault eonditions
be
wourd
be unacceptable.
(ii)
rt
raust be absolute].y
stable r:nder all through fault conditi.ons
since failure to stabilise wourd cause unnecessarJr
(ii:.)
interruption of supply.
rt must be capable of comprete d.iscrimination
wid.espread
between sections
of
the busbars to ensr:re that the rninimum nr:nber
of circuit breakers
are tripped. to isolate the fau1t.
.
2.
(i")
It nust
possess high speed
maintaj.n system
fnd.oor
(ii)
outdoor type.
da.rnage and
stability.
There are two main types
(i)
of operation to minlmise
of busbar installation :-
or metalclad type.
Indoor or metalclad switchgear is rnainly used on medium voltage systems,
but with the introduction of sF5 gas as an insulation
med.ir:m,
it is
now
possible to have rnetalclad. busbar installations up to the highest system
voltages. rf the rnetarcrad type is fulry
phase segregated interphase
faults cannot occur and only earth fault protection is required. A1I other
types of busbars should be protected against both phase and earth faults
by varior:s types
of protection
schemes.
1.o
TYPES OF 3US3AR TA.OTECTION SCIfiME
1.1
SASIC CIRCULATING CURRE}IT SCHBIE
This is a sinple form of r.rnit protectlon which compares the current entering
and ]eaving the busbar as shown
in Fig. 1. If the curent transf
orrners were
perfect there would. be no cument through the relay circuj.t. In practice
there will be spill current through the relay circuit, which must not exceed
the relay cunent setting up to the rnarinr:n through fault current.
1.2
BTASFJD
DI$ENEMIAT. CIRCULATTNG CURRnIT
The basic schene using
SCFTN,IE
practical current transforrners cannot provide high
fault stability at the same tine.
A bias feature can be incorporated. The principle of operation is shown
in Fig. 2. The reray used has both bias and operating circuits. ?he
speed operation and guarantee through
former is energi-sed by the arithrnetric sr:m of all the circuit curents
whilst the latter energised by the vector sun. A set of rectifiers
ar:xi1iary sunnation cr:rrent transforners is required.
and
1.
,.1
The
DIRECTTONAT COMPAXISON
principle of operation is
in eurrent in all feeders
During an external
SCIII}E
shown
connected
in Fig. Ja. An internal fault results
to the bus flowing towards the bus.
fault, however, the cr:nent in the faulted
feed.er
will
flow outwards. Contacts from all the d.irectional relays are connected in
series to energise a muLti-contact trip reIay.
An
alternative
amangement
is to use an additional blocking relay.
The
d-irectional relay is to have a changeover output contact. Al-1 the break
contacts are paralleled and connected to the blocking relay. All the make
contacts are paralle1 and connected to the trip relay through a no::nally
crosed contact from the blocking reray. This is sholn in Fig. 1lb.
The d.irectional
relays are arranged to look into the bus. luring
norrnal
load eonditions at least one feed.er will ca^rry outgoing current so that
the blocking relay will nornally be energised. and there will not be contact
race to prevent tripping on an external fauIt.
relay can be provided for this
A tine deIay in the trip
purpose.
PHASE COMPARISON SCHEME
'.4
Fig. 4 shows a simplified single
3.
phase arrangernent using
high
speed.
relays
fault conditions the prinary fault currents are
in phaser but the cr:nent transforrner secondarJr cuxrents are out of phase.
A and
Under external
Soth relays A and B operate, no tripping
occrgs.
Ilnd.er
internal fault
conditionsr the primary currents are out of phase but the secondary cunents
are in phase. Relay A operates in the positive half cycle of the cunent
wavefbr"m
whilst relay 3 operates in the negative half cycle"
4.
1.5
FRII'IE LEAKAGE PROTECTTON
lhis is a sinple
and econonical
fom of
busba^r
protection which is ideal for
the protection of phase seg?egated. ind.oor metalclad. switchgear
where earth
fault protection only is reqr:-ired.. The main basic requirenent
is that
frarne
of the switchgear
mrrst be insulated from
the tn:e earth and
the
between
sections of the switchboard. This provision of insuration
between switchboard
sections is the main disadvantage of this forr of protection plus
the fact
that it is not possible to d.iscriminate between faults on tr*o
sets of busbars
rwrning through
).5.1
cornmon
switchgear fra.meso
Principle of Operation.
Refer to Fig. 5.
principle of operation of a frame leakage schene is based
on the fact
that any breakd'own of the witchgear lnsulation will raise the potential
T?re
the frame to earth
of
a eunent to flow in the connection between the
fra'me bonding bar and earth. A current transformer
connected. between the
and' cause
bonding bar and earth
operate a protective
CAG12
will therefore
re1ay.
measure thi-s earth
An instantarreous
fault current and.
cunent relay such as type
is sufficient for this application.
current transformer ratio used is not critical provid.ed the
fault setting can be obtained.
The
necessarJr
3.5.2
The switehgear nust be insurated. as a whore, usually
by stantling
concrete, ta-king care that the found.ation bolts
reinforcenent.
connections
that:-
No
d.o
it
on
not touch any steel
other earth connections of any Wpe including incid.ental
to structural steelwork should be present. This is to
ensure
5.
(i)
The
(ii)
No spurious
effective setting of the relay is not raised. by any path shwting
the principal earth connection and cr:*ent transformer,
tripplng will take place for an external earth fault
with current flowing into or out of the switchgear fra.&e.
insulation achieved should be greater than 10 ohns to ensr:re stability
under external fault cond.itions. This is illustrated
by considering Fig.
The
which shows the cuFent distribution for an external
earth fault. The fault
current splits between the switchgear frarne to earth insulation
resistance
and the resistance
of the earthing electrod.e. Since the latter has a value
is norrnarly less than 1 ohn the cu:rent 11 seen by the relay wirl
be
approximately 1CIrt of the total fault cunent. The relay
setting should be
greater than 1CI/o of the maxinun earth fault current to
achieve stability
for external- faults and should. be 1g1/o of the mininr:m earth fault
which
cr:rrent to
ensu.re
fast operation for busbar faults.
0n resistance earthed. systems r*here the earth
fault current is fairly
constant
there is no problern. However on soridly earthed. high vortage
systems the
difference between mininrrn and maxinun ea^rth faurt levers may
be considerable
and
this
may prevent
the use of fra.ne leakage protection
scheme unless
specially high insulation resistance is provided.
A11 cable glands nust be
insulated to prevent circuration of spurior:s cg:rent
produced by higb voltages induced in the cable
sheaths under through fault
conditions causing flashover between grand and srritchgear fr4ne.
on resistance earthed systems it is reconnended to use
a eonmon earthing
electrode for both the power source neutral and the switchgear frame.
rf
separate electrodes are used an internal fault cunent has to
flow thror:gh
both eleetrodes in series. rf either or both are of high resistance
or
inadequate current carrying capacity the fault cunent nay
be linited to
below the relay setting.
6.
If the electrode earthing of the switehgear fra^me is the offender the potential
of the fra.me may be raised to a d.angerous value as a1l the fault curent will
flow through the frane-to-earth insulation resistance.
Fig. 5 shows the preferred arrangenent with the earthing connection from the
switchgear frame rnade between the bottorn of the earthing resistor and the
earthing electrode.
t.r.t
Types
of
Fra.ne Leaka.ee Schelnes.
1.5,1.1 SinEle Susbar with Insulation Saniers on Both
Sides
of 3us Section Circult
The seheme is shown
Sreaker-
in Fig. 5. In this
case sepaxate zones
of protection
are fo::med with complete discrinination between them. Faults on the
on either sid.e
of the bus section brealer outside the bus section
in tripping of the bus section
brealcer and a1I
zones
zone
result
circuit breakers in the fJtea
Zono Faults on the bus section zone result in tripping of all circuit
brea.kers.
1.5.1.2 SinEIe Busbar with Insulation Sarrier
on
a
In this
agangement the bus section brealcer i.s insulated. on one side only
as shor.rn in Fig. 7. There will be a blind spot between the br:.s section
breaker a3d. the insulation bagier.
tr'aults on zone 1 or zone 2 will trip
the bus section breaker and all breakers connected. to the busbaxs in the
faulted Zoneo To cover the blind spot a sequential tripping circuit is
used whieh
is
arranged.
to trip circuit breakers in the non-faulted
if the protection in the faulted
zone
zone including the bus section breaker
remains operated. A time setting 1n the order
of 0.4
seconds
is
used. to
allow for the breakers in the faulted. zone to trip and the protection in
that
zone
to reset (for a genuine fault in that zone) before initiating
tripping of the other
zonse
7.
It is essential that an earthed. source of supply is
connected.
to the side of
the busbar not containing the bus section breaker.
1.5.1.1 Double Susbar.
rt is extremery diffieult to obtain d.iserimination between the two busbars
due to the practical difficurty in insuLating between them and
the fact that
the circuit breakers thenselves must also be includ.ed in the zones of
protection.
The schene shown
in Fig.
illustrates the various
zones arranged.
to trip
all circuit breakers connected to the faulty section of the nain busbars and
al1 breakers connected to the reserve busbars.
3.5.4
Check Feature.
The main
objection to the frame leaka6e protection
scherne
is the faet that
the discrininating relays in the various zones of protection will operate
whenever the cunent in the current transforrner is above their
effective
setting irrespective of whether it is due to a genuine busbar fault or
faults in the secondarSr wiring.
this diffieulty it is conmon practice to add a cheek featr:re
as a second line of d.efence. This takes the fo:m of another ind.epend.ently
operated' relay to detect earth faults. This relay is non-discrj.ni.natory
To overcorne
and operates
for both internal
and external
faul-ts. Both the eheck relay
diserininating relay m'st operate before tripping can occur.
The various nethod.s of obtaining a check feat're &Te !(i)
Neutral cheek provided by a relay energised. from a single cugent
transforner in the pouer systen neutral.
(ii)
Residual check proirid.ed by a relay energised fron residually
and
connected cr:rrent transforuers on the incoming
busbarso
circuits to
the
8.
(:.ii)
Residr:ar vortage check provided. by a voltage
reray energised from
an open delta voltage transforner supply.
cheek relays should' be
self reset to eliminate the need to manuarly reset
the relay after each external fault.
Fig. 9 shows a typical tripping and alarn circuit
for a frame leakage
protection schene with a eheck feature.
1.5
Tlris is a r:nit type protective scheme in which
cunents entering an. reaving
the busbar installation a-re compared continuously.
The object is to provide
fast operation at a 1ov fault setting on interraal faults
and. yet retain
stability up to the highest possible value of short circu:it
current on
through
faults'
cr:rrent transfonners on each of the busbar
circuits are
eonnected in paraller whlch will produee
a resultant cr:nent to operate a
relay for internal busbar faults onry. Theoreticarl_y
such a systen is
unaffected by through faults, but in practice
the associated. cu*ent
transfo::ners may not behave ideally when the
cu:rent exceed.s a certain vaIue.
Errors in transfo::station dr.rs to saturation of the
current transfo::mer cores
nay be sufflcient to cause rnaloperation if special preeautions
are not taken.
1
.5.1
consider Fig. 10. under external fault conditions
the current in relay R
should theoretically be zQToo However, if one
of the cr:nent transfo:mers
becones fu11y saturated' d'ue to high flux
in its core, its
secondanlr
becones zero and
this
can be represented by a short
e.n.f.
circuit acrosg its
magnetising impedance. This is the worst condition
for stability of the
relay and the high inped.ance principle is used to
ensure that the relay
circuit inped.anee is sufficientry high to prevent
its operation.
9.
Assuming
that CT rXf
becomes
ful1y saturated and ignoring the nagnetising
culrent in CT rYr r the secondarJr current Iy will split up betveen ttre relay
circuit
and the saturated current
transforrner. The relay circuit
inpedance
is adjusted so that the current flowing through the relay is less than its
cunent setting. The necessary inpedance can be calculated with a slight
safety nargin by assuming the cu:rent Iy flows th:ough the saturated. cunent
transformer only. This will develop a voltage Vj given by
vp = Iy
Ttre
relay circuit
(Rcr
* Ru)
irnped.ance
is then adjusted so that the
necessary voltage
to operate the relay is greater than the voltage Vp. This voltage
the setting voltage is given by
Yg =
fhus
where
rnR
Vg ca11ed
Ip = relay current setting.
R = relay circuit inp,edance.
Vg
i.er
iRR
.t.
> Iy (Rcr + RpE)
-1R
In order to obtain the required. value of R it is usually
an additional
relay coil
.'.
resistor called stabilising resistor
Rg1
necessary
to
use
in series with the
Rp.
Required value
of stabilising resistor :
Rst = R-RR
fault at tr' as shown in Fig. 11 the current transfolsners
will attenpt to transfom the fu1I fault cur'rent and. pass this through
the relay circuit. The voltage output Vp fron ttre current transformers
required to pass this cunent through the relay will be given by:For an internal
Vp =
fF.R
= fr'.a (na* + nr;)
fp
10.
relative values of relay setting fp and fault cunents
rp and ry the value of vp can be many KV. rt is not possibre for any
Depending on the
practical current transforners to develop such a high value an6 severe
saturation will oecu!. The saturated output consists of spikes of very
high voltage around the points of zero f1ux. To enable fast relay oper-
ation the curent transformer should have a knee-point voltage equal to at
least twice the relay voltage setting Vg.
1.5.2 Fau1t SettinEs.
Fig.
again. With a given relay current setting fp the overall
fault setting of the scheme is higher than Ip due to the magnetising cugent
Consider
11
taken by the curent transformers. This overall fault setting or the
effective setting Ig (referred. to cu:rent transformer secondary
amperes)-
is given by :
rs=rP+Zrm
vhere I,
is the magnetising cr:rrent
taken by one current transforroer
at the setting voltage Vg.
0r in terms of prinary cr:rrent the effective prinarJr current setting fp is
given by
rp
where
r =
= l:,1- + 2rm)
For a busbar installation with n circuits
transforner c'*ent
;"::
rp = r(rn+nr6).
In addition to the relay there may be a voltage limiting d.evice, a fault
setting resistor and supervision relay connected across the relay circuit.
These
will be discussed in later sections. Therefore, in generar,
effective prima:ry cur-rent setti.ng can be expressed as
fp = t (In + nI, + Iy + fSR + Iv)
the
11.
where r14
= currrent taken by voltage limiting
at Vg volts.
device
rsn = current taken by faurt setting resistor at
Vg volts.
Iv = cunent taken by supervi.sion relay at Vg volts.
The value of rp shoul-d' be in the order of
tq" of minimr:m fault cu*ent
available' This is to ensure sufficient fault cunent frowing
through
the relay under internal fault eonditions for high
speed. operation.
3.5.1
Throueh Fau1t
Stabilitv.
stabilj'ty lini't of a busbar protection scheme is based on the
naximun
through fault curent. rn general this takes the
value of the associated.
The
switchgear ratj-ng irrespective
of the existing or anticipated fauLt 1eve1s.
As shol'n previowly the stability limit is governed.
by the relay clrcuit
setting voltage. This must not be less than the stability
voltage of
the
systen, which is caleulated by assuming that the maxinr:rn through
fault
current flows in through one cilrrent transforrner and out
through a second.
onet the latter being assumed to be the most remote (in
terrns of secondarxr
Lead resistance) from the
further
asswaed
relay associated with the zone concerned. rt is
that the d.c. conponent of the offset prina:ry fault c'rrent
completely saturates the second. cr:nent transforraer whirst
the
continues to transforn perfeetly.
first
one
1.5.4 Fault SettinE Resistors.
to increase the effective primary fault setting by creating
a shunt resistance across the relay circuit as shown in Fig. ,rz,
They are
These are used
useful where a standard relay with a given setting
for arl the
busbar installations to achieve a given primary faurt
setting throughout.
i_s used.
12.
1.5.5
Cheek Feature
A second
line of
defence
is considered
good
practice in most
schemes
busbar protection, not
of
to give security against maroperation of the
prirnarSr protection d'ue to inherent
defects but to prevent incorrect tripping
as a resurt of damage to wiring and equipment
from
extra'eous sourees.
A check feature
is
provid.ed by duph_cation
of the primary protection using
a second set of curzent transforners on all circuits
other than bus section
and coupler units. The check systern is
ananged in a sinilar
manner to
the prinary protection but fozns one zone
only covering the whole of the
busbars and does not discriminate between
faults in the various
of the
sections
busbars.
under i'n-zone
faurt eonditi.ons, the high impedance relay circuit
constitutes
aJl excessive burden to the eu:rent transformers,
leading to the developnent
of a high voltage the waveform of which will be highly
distorted with a peak
value many tines the nominal saturation voltage.
AD approximate forrnula
based on experimental results conmonly used
for checking the magnitude
the
of
voltages vp deveroped by a current transformer
und.er internal
fault eonditions is gi.ven by :
peal<
Yp = 2rmvFEf
where
v6 =
eurrent transfor:mer
knee-point r.m.s.
voltage.
Vp =
maximurn ?orDrso
voltage
that would be produced
if the cunent transforser
did not saturate.
13.
This fornula does not hold for the open eircuit
condition and is inaccurate
for very high burd'en resi'stance values that approximate
ft only appl_ies for values of
to an open circuit,
V6 less than
v.F. ft should therefore be
used
2
as a guide to the possible peak voltage.
rf there are a number of current transformess in parallel
the peak voltage
vp as caleulated above for a single transforuer
wi]] be reduced by the shunt
conductance of the other current transformers.
The
insulation of the cu:=ent transformel
second.ary winding and
reray will
not be abre to withstand the very high voltages
that can be produced..
where neeessary the voltage is rinited
to less than ]kv peak by the use of
non-linear resistors caLled metrosirs eonnected
in paraller with the relay
circuit as shown in Fig.
The voltage/current
v = crp
1J.
characteristic of a netrosir is given by :
where the voltage
and current
are
peak values.
I(rms) = o.52I
C=
a constant depending on the
metrosi.l construction i.e. the
size and
number
of individ.ual
dises used in the metrosil
and.
whether connected. in series or
para11e1.
F = a constant in the range O.2 to
O.25.
14.
The values
of c
F are chosen so that the voltage across the metrosil is
linited to less than lkv peak at the maximr:n fault current. The value of c
and
nust al'so be sufficiently high to restriet the current tal<en by the netrosil
at the relay setting voltage Vg so as not to ad.versely affect the primary
fault setti.ng. Acceptable metrosil cuments are approxinately JgmA for use
with 1A current transforrners and. 1OOrnA for use with 5A cu:rent transfomers.
An approximate value
caLculated from
,fr
vs
of r(rms) at relay setting voltage vg(rms) can be
= c ((r(*");F
0.52
)
Suitable metrosils are chosen
(i)
(ii)
based.
on
relay setting voltage.
rated. cunent transformer second.arxr current
i.e. required prirnary-
cunent setting.
(:-ii)
rnaxirm:m
J.6.7
Open
eurrent transfo:rner
second.arxr
current under fault eonditions.
Circuited Current Transformers and Wiring
a cur=ent transformet secondary wind.ing or corueections between current
transfor:ners and the relay cireuit become open circuited, the resultalt
when
out-of-balanee current will flow through the paralleI combination of relay,
metrosilr fault setting resistor and cu:rent transfoxmer magnetising
inpedance. This nay cause the proteetion to operate for load. or through
fault conditions dependi.ng on the effective primary setting.
The
condition of an open circuit can be d.etected. by neasr.rring the voltage
across the relay circuit by a sensitive voltage-operated. relay as shown in
Fig. 14. This eelay is set to operate when the out-of-balance cument
equals about
2!
1U/o
of the least loaded feeder
amperes whichever
is the greater.
conneeted.
to the busbars or
'15.
rf accr:rate details of current transformer nagnetising
characteristics
available, the required setting ean be calculated..
Checks
should be
on
site to
ensuee
that the relay will not operate due to
are
done
normar unbalance
with the system and protection healthy.
operation of the supervision relay is arranged
to give an ala* that the
busbar protection is faulty and to short
circuit the buswires if this is
neeessarJr to prevent danage to the protective
relay and stabirising resistors.
when the busbar protection has a
faurt setting
fulr road of the
connected feeders it is very 1ike1y to
operate .ue to an open circuit
current transforrner' rn this case a check feature
is required to prevent
tripping. At the sarae tine it is inportant that
below
the buswires are short
circuited via the supervisi-on relay to prevent
therrnar damage to
protecti've relay and' stabilising resistors
which woul-d othe::wise
the
renain
continuously picked up und.er road conditions.
The supervision relay must have a tine
delay to prevent its operation due
to genui.ne busbar faults. A time delay of about
J seeonds is used.
1.5.8
3.5.9.1
inportant advantage of wing high impedance relay
in a circurating
current systen is the ability to predict the protective
An
scheme performance
in terus of prirnary fault setting
fault stability by calculation
without heary-cuEent eonjunctive tests. The
valid.ity of the eal-culation
is based on the assumpti-on that all the current
transforuers Lre of lowreactance type' A 1ow-reactance cunent transformer
is d.efined as one of
which a lcror+Iedge of the seconda:qr exciting
eu*ent, secondarxr winding
resi'stance and turns ratio is sufficient for
an assessnent of its performance.
and through
This covers current transformers with uniformly
distributed windings or
whose core leakage flux is negligiblq.
16.
1.6.8.2
l{1th hi-gh inpedance circulating current schemes, it is
of the utmost
importance that the l-ead. burdens between the various sets
of cu*ent
transformer be kept as low as possibre in order to obtain
the required
stability
sensi-ti-vity. rt is therefore ad.visable to run the buswires
in the forrn of a closed' ring between all the cireuit breaker control
cabinets.
and
This avoids the need for numerous radial loops between the
current transfo'mers
and the bus zone panel which would be required if the buswires
were formed in
the bus zone panel.
A closed
ring consisting of cores in multicore cables affords
increased
security against maloperation which may result from unbalancing
of the
protection due to inadvertent d.isconnection of bus
wires. rt also provid_es
easy extensicn of the protection when new circuits
are to be connected into
the protection zone.
of rwrning a nulti-core cable ring in the
arrangeinent is as fol1ows :
(i)
current transforrners to marshalling kiosk.
An example
(ii)
marshal-1ing
case
of a double busbar
kiosk to ar.rxiliary switches in the busbar serector
isolators.
(iii.)
The
loop between marshalling kiosks.
size of conductor
Howevet,
for the interconnecting pilots is 2.5rr2.
it is occasionally necessanxr to use para11e1 cores to reduce the
no::ma11y used
bu.rd.en.
j.6.9.1
rn a lot of
cases such as a d.ouble bus amangement where on-load
transfer of
a circuit is posslble, current transfonner outputs are switched. to
the
correct buswires by means of auxili-ary switches on the selecting
isolators.
These auxiliary srvitches should close before
the mai-n isolator closes and
should' open
after the main isolator
operati.on. This is
shorvn
in Fig.
opens
15.
to
ensure
stability during sr+itching
18.
The reserve busbar
is then included within the
feed.er
protection.
The
discrininating zone current transforrners on the bus coupler for the reserve
bars are no longer required and are used to replace the check zone current
transfor^mers on the
line circuit breaker.
additional cunent
Sometimes an
transforner may be provided on the bus coupler specifically for this pgrpose,
in which case the reserve bar discrirninating eurrent transformers
can be
short circuited. during bypass cond"itions.
1.5.8,) Current Transformer Locatj,on.
The three
alternative arrangements as shown in Fig. 18 are :
curent transfo:mers for feeder and busbar protection overlapping
the circuit breaker.
(i)
(u)
(
ii.i
(i)
all current transformers on rine side of circuit breaker.
alr cument transforiners on the busbar sid.e of circuit breaker.
rn this
arrangerrent
faults at F1 and F2 are cleared correctly by
the busbar and feeder protection respectively. Faults at
between the
forrners
F3
circuit breaker and feeder protection current trans-
will be creared by the busbar protection
by the remote end. of the feeder protection. No
and possibly also
'nneeessary
disruption to loads will result from this.
Faults at F4 will be seen by the feeder protection but also by the
busbar protection resurting in unnecessarJr tripping of the br:sbars
for what is essentially a feeder fault.
of this anrangement.
(ii)
This is the uost
This is the nain disad.vantage
cortrnon amangement where
all the current trassformers
are on the feeder side of the circuit breaker. However, there is
a blind spot at point F, where faults are seen by busbar protection
but not seen by the feed.er proteetion. With this arrangernent it is
therefore required to intertrip the renote circuit breaker when busbar
protection operates.
19.
fntertripping
can be achieved, by
and ean be instantaneous
unstabilising the feeder protection
or tirne delayed to
a1low clearance of
faults on the busbar sid.e of the circuit breaker before intertripping.
Alternatively an interlocked. overcurrent relay can be used. to intertrip
the renote circuit breaker. fhis relay in the form of a polyphase
induction disc is interlocked. wittr the br:sbar protection by means
of a shading
operates
(iii)
\,r,hen
wind.ing which
when the busbar protection
all the current transformexs are located on the busbar
of the circuit
and
is closed
brealcer a
sid.e
fault al T1 betveen the current trarrsformers
circuit breaker will continue to
be fed.
fron the busbars after
the circuit breaker has been tripped by the feed.er protection.
4n
interlocked overculrent relay whieh is interlocked with the feeder
protection is required to ensure that the busbars are only tripped
for this condition
and not
for faults on the feeder.
1.6.9 Typi.cal Susbar Protection Using High
I_grpedance
Circulating Cr:gent
Scheme
Figure 1! shows the current transfoxmer cireuits for a typical busbar
station layout comprising
breakers.
one bus section and two bus coupler
The busbar arrangment enables three zones
cireuit
of protection to
be obtained, and the cr:rrent transfoxme?s a"re connected
to provide over-
lapping at the bus section and bus coupler circuit breakers.
Discrininating Featureo
Three cunent transformers axe
and also on both sides
The
of the
fitted on all incoming and outgoing circuits
br:s section and bus coupler
circuit breakers.
star points of all the current transformers are connected. to a'buswire
which
is
earthed.
via a removable 1ink.
The other terminals
of the current
transformers in the same zone are connected to three more buswires, all
current transfo::mers in the
same phase bei.ng connected
thus giving a set of three busvires per zone and a
for all the three
zoneso
to the
eommon
sarne buswires,
neutral buswire
20.
One
triple pole re1ayl type
(device 8l) and stabilising resistor is
connected across the busr,rires to give phase and earth fault protection.
CAGJ4
rf a fault occrus outsid'e the protected. zone, the currents entering
an6
leaving the zone are equal and the current transfor:mers affected. will
circulate cu:=ent through the buswires. The schene is so designed. that
the voltage necessary to operate the relay is greater than the voltage
across the buswires under maxj.mum through fault cond"itlons, so that
the
rel-ay
will not operate
'nder such circumsta'ces.
rf a fault oceurs insid"e the protected. zone, the balance of seeond.arxr cu:rent
will be disturbed and the relay will operate.
fiscrininative tripping is obtained by the introd.uction of isoLator auxiliary
switches into the current transforrner circuits.
The auxiliaqy switch contaets
are silver plated, with two switches in paraller per phase, in order
to
mj-n:inise the possibility of high arr:riIiary switeh contact
resistance.
Check Feature.
This is simil-ar in operating principle to the d.iscrfuninating feature,
but
no current transfolsners are fitted. on the bus section and bus coupler
circuits,
and the cornplete busbar
installation is considered as one overaLl
zorlr The crrFent transfonners are fitted on all i.nconing and outgoing
circuits and' again all the current transfo::ners in each phase are paralleled
onto the buswires.
A triple pole relayr type cAci4 (device BJ) and stabilising resistor
is
connected across the buswires.
Continuous Buswire Supervision.
possibirity of faults in the cerent transfo:rners
wiring and interconnecting pi.lots a static relay type VTX
To guard against the
secondar;r
(device 95) is connected. across the busbar protection zone
busr.rires.
C1
Lta
The relay has a voltage
setting ad.justable
between
2 and 1d vo1ts, and an
inherent time delay of J seconds. Operation of the llr'IX relay
alarn
and.
sound.s an
takes the affected zone out of service by shorting the appropriate
buswires.
The
following faults are covered
Open
l+
Broken eurrent transfor.ner
Crossed
eircu-ited current transformers.
pilots.
current transfo:rner pilots.
Tripping Circuj-ts.
tripping circuits are arranged. so that the accidental operation of any
one of the circulating current relays (d.evice 8l) does not cause inad.vertent
The
tripping of a group of cireuit breaters. Both the rDiscrirainatingr
rCheckf high imped^ance voltage
and
differential relays must be energised before
the respective nain tripping relays (deviee )6) arc energised. one ma-in
tripping relay is required for each feed.er circuit breakerr altd two such
relays are required. for each bus section and each bus coupler circuit breaker.
This method presents several advantages
Spare contacts are always available on the arr:riliary
can be used when required
The zone
of protection
tripping relays,
and.
for intertripping duties.
rnay be
easily extended to cover additional circuit
breakets.
The
front
appearance
of the busbar protection panel is not
dependent on
the nwrber of circuit breakers in the zone.
Alarm Circuits.
Audible and visual alarrns are given under the following cond.itions
Busbar
Busbar protecti.on faulf,y.
fauIt.
tt Battery voltage
low.
22.
The r3usbar Proteetion Faultyr alarm
is
time delayed
to prevent
such an alarrn
being given und.er busbar fault condltions.
Figure 20 shows a WpicaL arrangement of the d.c. tri.ppingr alarrn and
indicating circr:-its.
1.6.10
Busbar protection Using Separate
Relavs &rg Each Circlrit Brea]<er.
Differential
J.6.10.1 laslg_Sgbgg.
Fig. 21 shows the basic arrangement. This
for
use where individ.ual
ation j.n U.K.
on a
is particularly suitable
relay roons are used on the 400kV busbar install-
Each room acconmodates both
per-circuit basis.
scheme
Each
the feeder and busbar protection
circuit breaker has its
own
individual
discrirninating and check high impedance relays, coincident operati.on of
which
trips the breaker.
battery. 0n this
Each breaker also has
basi.s buswire selection
its
onn individ.ual
is limited to the a.c. circuits
with no isolator switches in the d.c. trip circuits.
This will provide
greater secr:rity against mal-tripping and greater reliability
Another axrangement shown
in Fig.
trippihg
22 uses two
tripping routes for
circuit breaker. Direct tripping from the high
with each circuit breaker ls via a discrete
of tripping.
inpedance relays associated
busbax
protection trip relay.
The other route uses separate contacts on the individr:a1
check and dj.scrininating high-imped.ance relays
each
circult
breaker
to energise a second trip
relay associated with each circuit-breaker. fn this case the separate
contacts on all the high-impedance check relays ate connected in parallelt
the combination of which is in series with a single contact on the individual
high-impedance discriminating
relay associated. with each circuit breaker.
a7
-.)o
1.6.10.2 Basie Scheme with Ad.d.itional DiscriminatinE
and
a
Fig. 2) shows the
anangement
in a simplified forn.
increase the tripping reliability"
The additional relays
A sectionalised back tripping systern
with check and discrininating back tripping bus wj-res (each double pole
switched.) is incorporated which operates onto the ind.ivid.uaL busbar
protection trip relays. Operatj.on of the zone check and discrirninating
relays energise the back trip receive relay through the back trip buswires
and busbar selector
isolator aiuiliary switches.
TLre
receive relays in
turn pick up the busbar protection trip relay to trip the breaker.
I'urther reliability
back
of the tripping circuits is obtained by using
trip receive trip relays as
shor,m
in Fig. 24o This
provid.es
separate
virtual
dupli.cation of the fault detection and tripping functions apart fron curent
transformers and associated bus wiring"
1.5.10.1 Cheek Zone Sectionalisation
Provision of a single check zone covering all the br:sbars has the advantage
of relative simplicity
and economy.
At large busban stations having a
large mrmber of circuits it nay be necessary to depart from this
due
approach
to the difficulty i.n obtaining a suitable primary fault setting. fn
these cases sectionalised check zones are
greater security and flexibility
used. This provision leads to
during construction, naJ.ntenance
and
cornnissionlng. It requi.res additional cunent transforrners at the sectioning
points and separate high
impedance
relays per check
zonr
I+
bCTERNAL
trAU UT
rNTER-NAL EAUr-l
FIC,
BASTC CIRCULATING CURR.ENT STHLME
L5
BIAS
COILS
OPERATING COIL
EXTERNAL FAULT
INTERNAL FAULT
BIAS CURRENT CO|L 'o'
OPERATING CURRENT
BIAS CURRENT COIL.b,
FIGURE
LOW IMPEDANCE BIASED DIFFERENTIAL SCHEME
LXTLRNAL trhULT
NEGATIVE HALF
POSITIVE HETT CYCLE
CYCLE
t-
TRAN
SEEONDAR\ C\'RR.ENT
CTJRRENT
KELNY OPEBATI3I.I
FE-E.DE.R
FTeDER
INTE.RNAL
-(
FA.ULT
POqITIVE HALF CYCLE
<-<--
l
|
cuRRetr
TRANSFOF.t,tER
SEcON!ARy
A
FlG.4
CTTR.F.ENT
R.ELAY oPERATI0N
PHA:E coMPARi tON SCHEME
trEEXER
f-9
1r =I,+12
ar+Iz
swffc.HGEAg F('nmf
---T
-t
GErJ6(A'ro(
_l-
-J
gY9{6r,1 AGrH|rJG
BoIJDTNG 8AR.
RgsrsrAxcE
REr-AY
EACTH
I,+12
8AR
EAP:nrrrJG
tttict|aD
(sr3rAPeE
FrG.5. OPERATTNG
PRINCIPLE OF FRAME LEAKAGE PROTTCIIQN
lr.lsutAfioN
?*:t
Z.ONE Z
BePPR
Zot'tE 3
-t
-l
I
I
I
jl-
L/1
t_
-s/t-
l'
i----r-l
TRIP
t.
I
I
h'
t?rp'B'
FIG.6 FRAME LEAKAGE 5CHEMI \\IITH DOUBLE
INSULATION BARRIER
2ct
INSULATION BARRIER
ZONE
r---
- -1
0.2-1SEC.
-rTRtP
t,
FIGURE 7
FRAME - LEAKAGE SCHEME
INSULATION BARR IER
WITH SINGLE
fo
/,vSazaVaat B.sfPeR
Za*s./
ZavaZ
Z.va J
I
t'
I
'T
l
I
I
---
-d
./
.xF Y'
I
Zz
,11
(,
!. + )/L
(L
c(L\
l_
:
lG.8
f.<'fiyt - / aar4rr ^trfrZt
/6r< 4>a',Qz{'78
ta; @s
3t
IN
lr
ouT
Etod
I css'zt
I
r* olrr
rl
6+22-l
E:4
t t css-zz
TPtp
SUPPLY
SuPlvtSro^/
64Cl{-Z
AIRn
64zl_2
?alv
61a2-Z
74-
td
LAHP
OIJT
tu"zl
Arierr
Sv?6
FlG.g. TYPICAL TRIP
AN
ALARM
suPft.Y
tvl 6 rotJ
CIRCUI@
WITH DOUBLE INSULATION BARRIER ANb
CI{ECK
FEATURE
LTAl(AG
)4.
Q.et
Rr-v
Rsr
i
t
I
le
)*.
VR =
rv (R.r*Prr)
Vs>Ve
Ia R > .Ty (.x* R"r)
R > rv (Rr.x+(cr)
Ig
Psr =
R- Re
F'IG TO PRINCIPLE OF HIGH
IMPEDANCE
PROTECTION
3f
7,n
utl
I
I
FIG.1I INTE-RI{AL FAULT Ot.\ !\IGH MCI\EME
Vr=It'R
(R.. * R'*)
= r,' - !L
Is
E{(e.ct.\v<. Setti^q
Is=I(r2lm
-- Ietn I^
tJ'rL\
'^rit\
Cr r c,.l'i
tS
c-irtr"\tt
?r\'^o*., eftecL\,.re sett\^1
ip
or
: T'(r*+nI*)
tp =
T.(I**oI^+Im
i.* + lu)
c(-
lop = r** lae
FTG-12 USE Dtr FAULT SETTTNG RESISToR
35
t
I
ia
i
I
Ftc -13
t3
Met"osiI c\'ovoctertstic
l'
!:
V=
fiV*
,t/Z Vs
rr.l
o-s2
^FVs =
[s]F
16
- -T
_rl
{r4t',Crt
7*,
r-
)ll
)l
_l
t-
-j
ri
Jr-
cTr
6Ta-
1r
I,:L.+1,+I.
I.IEALTHY CD}.T}\T TA}J
vlt
i
CTr OPEN CIRCU lT , Lr FLo$rs THRDUGH MAGNET|STUG
IuFgUnUCE AN} g"EL$Y CIRIUIT IN PARALLLL
trIC.I4
SUFER.VISION AGAINST OPEN
a --
Voltac,.
m"o's.rrel
by
C\RCUITE} C.T..g
supe.rvisicn te,la1
y : l, (R ll zma ll zH3 il4.,o)
lC supervision
ra\a.1
seLl',*..
Crt-o{-bo.lo.,.ce. cr,rrrc-nt-
to
V.o
opc-vate
t\'
*9
l:s
L: )4'"
?-r'q7
4,
{
vsP
supetvls't6n Ta\ai
97
NORMAL
CIPER
ATIhIG
.(-oNAr-r,r qN
i\
.-- + \
f4ain s< reserve
zon-g
ultinate/y pr"lleled by
fsefvg b.rsbar se.\ectot
a*rihory
switches
ON-LoN} TRANSFER
FIC.15 BUSBAR SELECTOR A\-n.(ILIARY SWITCHES RECUIREMETIT
38
.<
4
{J
*
2
A.c
6ursx-=S
C/t/
FIG.15. CIRCUIT BREAKTR
BYPA5S.
/7
2
A.C.
tl/
EttswrRS
<//
FIG.IT.. CIRCUIT BREAIR, AND C.T.
BYPASS.
CreorrT
??o-tgiost
Co) oV&APPTNG c.-rs.
&lsgA
Pf.reer,o^t.
Crerrrf
e?org"",ot
(b) ArL c.ts ov t-r^/ sr0e
oF c'Perrff 6CsAEEl?
.
Sr.rs8t{?
{Xor6ctrroU
rrvrnLoc,1gFb
ove!uClN?
Qgtlv.
$WEir.D
orrtlerArrr
es.A\,
ClectrtT
(C). Al,t
c.Tj
oC G,lrsgAe
Eo'recrro{
gurBAe
P"lSeTorr,
FIG.IB IFFECT OF
C.T. LOCATION
srbE
oF crlevrT &f;eAglQ,
ON BUSBAR PRO]ECTION
PIRFORI4ANCE
+o
t1
IE
u3
6q
N;
aarJasr.r=<a(,e
:Y
1g
r-
a<(J
(r!
ff
:<
sg
zz
o<
NVt
2
U
.E
uE
=ct
iol
3=U
a.E<
>5(J
;3i
oEd
t(JE
!
o
a
a
3s
fJ
vrc
-le
-lJz- U
o
N=
!
a=
-GC
-3
tg
N;
:E
z=
RE
xB
(,
-)
C)o
3g
sV,
(
l
v,
I
-lu (,
-lE u,
U
2tn
ra
(,
g
th
TJ
fs
t>
ar>
5?
sU
z2
o<
N('
an
:<
d(J
Jp
gA
< ar.,
6E
!-
! i
?5:
-at
cEa
?-o
EEA
-o3
i;3
EIe
Qr
MlM2N
87CH-1
css-r'f2
ll
a7e-1
ll
al
css-R
o.c. BuswtREs
87CH-2
87M1
ssMf
93M2-1
95R-
-2
-t
1
95CH-l
30Mr
-'r
30[v''|-1
74-l
30R-l
95Mlx-1
EUZZER
93M2X-t
95R.X-1
95CnX-1
l3
30
Zonc indrcating rcl.y typ VAA
74
Alarm cancrllarion rclay rypc VAK
80
D.c. vohs rupcrvision rclay rypc VAX
87
95
95X Zooc bus wirec ahorting rctay rypc VAJHI3
l2
High impcdencc circularing currcnt relay rype CAG 34
8ur wircl supcrvision rclay rypc VTX 3l
FlG.20. DOUBLE BU5BAR scnEne.orve
CSS Conrrol schcror :wirch
tl
L2
lndicering lemp protcction in scrvic:
lndicating larnp protecrion out ol servicc
RerRv pEe.zorue .
o.c.crrcurrs.
+1_
h_-.
e*js-r
1i
z_--aT o-G)
s---olo-{F)
Eil
lrn
IY
tl @
@*r
;r @
@;r
6,
FIG.ZI
2o
BUSBAR. PROTECTION WITH SEPARATE RELAYS PEF.
CIRCUIT BITEAKtR
z--rre
\---o..F
io-rO
I
:IHE!I3
-:.\::i
ry-r
I
o-*is
a?
.?
f+-f
?
I
5s__ _ _
ol
Flc.2?
TRIPPI.NG ROUTE
gr@
.l
,1
tr
t
.J,
v3
OI
bl
,J
FlG
. 23
crRcU_!_a_F
fto- .1-
v-olo_,
I
-l:
@-*.].H
2t
ry
lr
i'
A,
FtG .24
O-- r-:r
CIRCUIT BREAKER .BAsIc sc}IEME WIT.H ADBITID\IAL
REunvs pgn znxE ANn.BhqK TRtpplNG rActL!.TlELJdtrH
SEPARATE TRIP R.ELAYS