Easypact MVS: Catalogue
Easypact MVS: Catalogue
EasyPact MVS
LV power circuit breakers and switch-disconnectors
800 to 4000A
Catalogue
2012
Performance
without compromise
Exceptional
reliability,flexibility
and convenience
Buildings
Industry
Panelbuilders
EasyPact MVS
Benefits for every
customer
EasyPact MVS08 to MVS40
Panel builders/
contractors
End Users
Designers
90%
re
ations a
c
li
p
p
a
f
o
covered
ock by
educe st
up to
30%
%
0
0
1
ment to
Commit
quality
At a cost-effective investment
Pay for what you need: Get outstanding durability with
the features you need, with the benefit of easy to order
and stock.
Gain peace of
mind and
optimised cost
for every
installation
EasyPact MVS
General contents
Functions
and characteristics
A-1
Installation
recommendations
B-1
Dimensions
and connection
C-1
Electrical diagrams
D-1
Additional
characteristics
E-1
Catalogue numbers
and order form
F-1
Functions
and characteristics
EasyPact MVS
General overview
A-2
A-4
A-6
Overview of functions
A-8
Detailed contents
MVS08 to MVS40
ET trip system
ETA trip system
ETV trip system
A-2
A-4
A-8
A-10
A-12
A-14
A-14
Connections A-15
Overview of solutions and accessories
Accessories and auxiliaries
A-15
A-16
Locking A-18
On the device
On the chassis
A-18
A-19
Indication contacts
A-20
Remote operation
A-21
Source-changeover systems
A-24
Remote ON / OFF
Remote tripping
Mechanical interlocking
A-21
A-23
A-24
Accessories A-25
Installation recommendations
Dimensions and connection
Electrical diagrams
Additional characteristics
Catalogue numbers and order form
B-1
C-1
D-1
E-1
F-1
A-1
General overview
Functions
and characteristics
Detailed contents
CPB100000
page A-4
ET trip system
page A-8
page A-10
page A-12
Connections
page A-15
bb Ratings:
vv EasyPact MVS 800 to 4000 A
bb Circuit breakers type N, H
bb Switch-disconnectors type NA, HA
bb 3 or 4 poles
bb Fixed or drawout versions
long
time
long time
tr
8
.8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
x In
[Ir
instantaneous
.7
.6
.5
.4
Isd
alarm
alarm
3
2.5
2
1.5
Isd
4 5
x Ir
Ir
long
time
long time
.7
.6
.5
.4
short time
3
2.5
2
1.5
6
8
10
test
.8
x In
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
short time
short time
4 5
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.2
.1
on
on
I t
.2
.1
0off
alarm
alarm
long
time
long time
Ir
.7
.6
.5
.4
instantaneous
Ii
instantaneous
4
3
6
2
8 10
12
15
off
off
x In
test
Isd
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
.8
x In
short time
short time
3
2.5
2
1.5
4 5
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.2
.1
on
on
setting
I t
.2
.1
0off
delay
tg
(s)
(s) .4 .4 .3
D E F
.2
G
.3
C
.1
H
.2
B
I
on.1 2 0off
A
on I t off
ground fault
Ig
alarm
alarm
instantaneous
Ii
instantaneous
4
3
6
2
8 10
12
15
off
off
x In
test
test
ground fault
bb 2I basic protection
bb 5S selective protection
bb 6G selective + earth-fault protection
bb Standard long-time rating plug:
vv Current setting (A) 0.4 to 1 x In
bb External power-supply module
bb Rear connection:
vv Horizontal
vv Vertical
bb Optional accessories:
vv Interphase barriers
vv Safety shutters and shutter locking
blocks
DB101149
Ir
bb 2I basic protection
bb 5S selective protection
bb 6G selective + earth-fault protection
bb Standard long-time rating plug:
vv Current setting (A) 0.4 to 1 x In
bb External power-supply module
E46459
CDB500002
CDB500001
CDB500000
bb 2I basic protection
bb 5S selective protection
bb 6G selective + earth-fault protection
bb Standard long-time rating plug:
vv Current setting (A) 0.4 to 1 x In
Safety shutters
Interphase barriers
A-2
page A-18
DB101109
DB101110
Locking
bb Pushbutton locking by
padlockable transparent cover
bb OFF-position locking by keylock
bb Chassis locking in disconnected
position by keylock
bb Chassis locking in connected,
disconnected and test positions
bb Door interlock (inhibits door
opening with breaker in
connected or test position
DB101112
page A-20
E46438
PB104354A40
Indication contacts
bb Standard:
vv ON/OFF indication (OF)
vv Fault trip indication (SDE)
bb Optional:
vv Additional ON/OFF indication (OF)
vv Ready-to-close contact (PF)
vv Carriage switches for connected
(CE) disconnected (CD) and test
(CT) positions
Ready-toclose contact
OF contact
DB101114
page A-21
DB101113
CPB100003
Remote operation
bb Remote ON/OFF:
vv Gear motor
vv XF closing or MX opening
voltage releases
bb Remote tripping function:
vv MN voltage release
-- Standard
-- Adjustable or non-adjustable
delay
E46669
E46668
page A-25
Escutcheon
Transparent cover
DB101115
CPB100015
Accessories
page A-24
CPB100016
CDB500053
Source-changeover systems
A-3
Functions
and characteristics
Circuit breakers
and switch-disconnectors
MVS08 to MVS40
Common characteristics
Number of poles
Rated insulation voltage (V)
Impulse withstand voltage (kV)
Rated operational voltage (V AC 50/60 Hz)
Suitability for isolation
Degree of pollution
Ui
Uimp
Ue
IEC 60947-2
IEC 60664-1
3/4
1000
12
690
Yes
4
In
at 40C(1)
Icu
220...440V
690 V
% Icu
CPB100000
Basic circuit-breaker
Ics
Icw
1s
3s
220...440 V
690V
440/690V
220...440 V
690 V
CPB100014
Icm
Icw
1s
3s
Maintenance/Connection/Installation
Service life
C/O cyclesx1000
Mechanical
Electrical
Connection
Switch disconnector.
Dimensions (mm)
(H x W x D)
with maintenance
without maintenance
without maintenance
Horizontal
Vertical
Drawout
Fixed
Weight (kg)
(approximate)
A-4
Drawout
Fixed
440 V
690 V
3P
4P
3P
4P
3P/4P
3P/4P
MVS08
MVS10
MVS12
MVS16
MVS20
MVS25
MVS32
MVS40
800
800
800
N
50
42
100%
B
50
42
25
105
88
25
<70
1000
1000
1000
N
50
42
100%
B
50
42
25
105
88
25
<70
1250
1250
1250
N
50
42
100%
B
50
42
25
105
88
25
<70
1600
1600
1600
N
50
42
100%
B
50
42
25
105
88
25
<70
2000
2000
2000
N
50
42
100%
B
50
42
25
105
88
25
<70
2500
2500
2500
N
50
42
100%
B
50
42
25
105
88
25
<70
3200
3200
3200
N
50
42
100%
B
50
42
25
105
88
25
<70
4000
4000
4000
N
55
42
100%
B
55
42
30
121
88
25
<70
H
65
50
65
50
36
143
105
MVS08
NA
800
105
50
25
HA
143
65
36
20
10
6000
4000
Yes
Yes
439 x 441 x 395
439 x 556 x 395
352 x 422 x 297
352 x 537 x 297
70/85
40/50
H
65
50
65
50
36
143
105
MVS10
NA
1000
105
50
25
20
10
6000
4000
HA
143
65
36
H
65
50
65
50
36
143
105
MVS12
NA
1250
105
50
25
20
10
6000
4000
HA
143
65
36
H
65
50
65
50
36
143
105
MVS16
NA
1600
105
50
25
20
10
6000
4000
HA
143
65
36
H
65
50
65
50
36
143
105
MVS20
NA
2000
105
50
25
20
10
6000
4000
HA
143
65
36
H
65
50
65
50
36
143
105
MVS25
NA
2500
105
50
25
20
10
5000
2500
HA
143
65
36
H
65
50
65
50
36
143
105
MVS32
NA
3200
105
50
25
20
10
5000
2500
HA
143
65
36
H
65
50
65
50
36
143
105
MVS40
NA
4000
121
55
30
HA
143
65
36
20
10
5000
2500
90/120
60/80
A-5
Functions
and characteristics
Identifying ET range of
trip system
Dependability
CPB100011
Accessories
Type of protection
bb 2I for basic protection
bb 5S for selective protection
bb 6G for selective + earth-fault protection
Type of measurement
bb ET for basic
bb ETA for Current
bb ETV for Current and Voltage
Protection:
long time
+ instantaneous
DB101117
A-6
DB101118
DB101117
2I
long
time
long time
Ir
tr
8
.8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
x In
[Ir
instantaneous
.7
.6
.5
.4
Isd
ETA
bb I1, I2, I3, IN, Iearth-fault, and maximeter for
these measurements:
vv Fault indications
vv Settings in amperes and in seconds
CDB500028
2I
CDB500000
ET
bb Fault indications
bb Settings in amperes and in seconds
alarm
alarm
x Ir
long
time
long time
tr
8
.8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
x In
[Ir
instantaneous
.7
.6
.5
.4
Ii
4 5
3
2.5
2
1.5
2I
ETA2I
Ir
short time
6
8
10
ETV
bb Incorporates all the rms measurements of ETA trip
unit, plus voltage readings:
vv Calculates the current demand value
vv Quickview function for the automatic cyclical
display of the most useful values
CDB500035
2I
alarm
alarm
4
3
test
long
time
long time
Ir
alarm
alarm
tr
8
.8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
x In
[Ir
instantaneous
.7
.6
.5
.4
instantaneous
8 10
12
15
off
off
2
x In
Ii
instantaneous
8 10
12
4
15
3
off
off
2
x In
6
test
test
long
time
long time
Ir
.7
.6
.5
.4
Isd
.8
x In
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
short time
short time
3
2.5
2
1.5
tsd
(s)
(s) .4 .4 .3
4 5
.3
.2
on.1
6
8
10
x Ir
on
I t
.2
.1
0off
alarm
alarm
long
time
long time
Ir
.7
.6
.5
.4
instantaneous
Ii
instantaneous
4
3
8 10
12
15
off
off
2
x In
Isd
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
.8
x In
short time
short time
2.5
2
1.5
test
5S
ETA5S
4 5
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.
.1
on
on
2
I t
.2
.1
0off
CDB500030
5S
CDB500029
5S
CDB500001
ground fault
alarm
alarm
long
time
long time
Ir
.8
.7
.6
.5
.4
instantaneous
Ii
ETV5S
instantaneous
Isd
8 10
12
4
15
3
off
off
2
x In
x In
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
short time
short time
3
2.5
2
1.5
4 5
x Ir
tsd
(s)
(s) .4 .4 .3
.3
.2
on.1
6
8
10
on
I t
.2
.1
0off
alarm
alarm
instantaneous
Ii
instantaneous
4
3
6
2
8 10
12
15
off
off
x In
test
test
long
time
long time
Ir
.7
.6
.5
.4
Isd
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
.8
x In
short time
short time
3
2.5
2
1.5
4 5
x Ir
6
8
10
setting
tsd
(s)
(s) .4 .4 .3
.3
.2
on.1
on
I t
.2
.1
0off
delay
tg
(s)
(s) .4 .4 .3
D E F
.2
G
.3
C
.1
H
.2
B
I
on.1 2 0off
A
on I t off
ground fault
6G
alarm
alarm
long
time
long time
Ir
instantaneous
Ii
instantaneous
4
3
8 10
12
15
off
off
2
x In
test
test
.7
.6
.5
.4
4 5
3
2.5
2
1.5
Ig
ground fault
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
.8
x In
short time
short time
Isd
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.2
.1
on
on
setting
Ig
D E F
C
B
I t
.2
.1
0off
delay
tg
(s)
(s)
.4 .4 .3
.2
G
.3
.1
H
.2
I
on.1 2 0off
A
on I t off
ground fault
alarm
alarm
instantaneous
Ii
instantaneous
4
3
6
2
8 10
12
15
off
off
x In
test
test
CDB500004
6G
CDB500003
6G
CDB500002
ground fault
long
time
long time
Ir
.7
.6
.5
.4
Isd
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
[Ir
.8
x In
short time
short time
2.5
2
1.5
4 5
x Ir
6
8
10
setting
tsd
(s)
(s) .4 .4 .3
.3
.
.1
on
on
2
I t
.2
.1
0off
delay
tg
(s)
(s) .4 .4 .3
D E F
.2
G
.3
C
.1
H
.2
B
I
on.1 2 0off
A
on I t off
ground fault
alarm
alarm
instantaneous
Ii
instantaneous
4
3
6
2
8 10
12
15
off
off
x In
test
test
Ig
ground fault
ground fault
A-7
Overview of functions
Protection
CDB500002
Functions
and characteristics
ET trip system
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Protects cables (phase and neutral) against overloads
Thermal memory(1): thermal image before and after tripping.
Short-time protection
bb The short-time protection function protects the distribution system against
impedant short-circuits
bb The short-time tripping delay can be used to ensure discrimination with
downstream circuit breaker
bb The I2t ON and I2t OFF options enhance discrimination with a downstream
protection devices
bb Use of I2t curves with short-time protection:
vv I2t OFF selected: the protection function implements a constant time curve
vv I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 lr. Above 10 lr, the time curve is constant
Earth-fault protection on ET6G trip system
Residual earth fault protection.
Selection of I2t type (ON or OFF) for delay.
A ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
function is to eliminate this type of fault.
Type
Residual
Ir
long
time
long time
.7
.6
.5
.4
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
x In
[Ir
.8
short time
short time
Isd
4 5
3
2.5
2
1.5
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.2
.1
on
on
setting
Ig
D E F
C
B
I t
.2
.1
0off
delay
tg
(s)
(s)
.4 .4 .3
alarm
alarm
7
instantaneous
Ii
instantaneous
4
3
8 10
12
15
off
off
2
x In
test
test
.2
G
.3
.1
H
.2
0
.
1
I
on
off
A
2
on I t off
ground fault
ground fault
Description
Instantaneous protection
The Instantaneous-protection function protects the distribution system against solid
short-circuits. Contrary to the short-time protection function, the tripping delay for
instantaneous protection is not adjustable. The tripping order is sent to the circuit
breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI(2) terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
1 Long-time threshold and tripping delay.
2 Overload alarm (LED) at 1,125 Ir.
3 Short-time pick-up and tripping delay.
4 Instantaneous pick-up.
5 Earth-fault pick-up and tripping delay.
6 Earth-fault test button.
7 Long-time rating plug screw.
8 Test connector.
9 Lamp test, reset and battery test.
10 Indication of tripping cause.
A-8
Fault indications
Test
A hand-held test kit may be connected to the test connector on the front to check
circuit-breaker operation. For ET6G trip unit, the operation of earth-fault protection
can be checked by pressing the test button located above the test connector.
ET2I
0.4
Long time
Isd = Ir x
0.9
0.95
0.98
0.5
1
2
4
8
12
12.5 25
50
100 200 300
2
4
8
12
0.7(1) 1
5.5
8.3
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
16
400
16
11
20
500
20
13.8
24
600
24
16.6
1.5
0.6
2.5
10
0.8
0.9
0.95
0.98
0.5
1
2
4
8
12
12.5 25
50
100 200 300
2
4
8
12
0.7(1) 1
5.5
8.3
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
16
400
16
11
20
500
20
13.8
24
600
24
16.6
Isd = Ir x
1.5
2.5
10
Settings
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
Protection
ET5S/ET6G
0.4
Pick-up (A)
Accuracy: 10 %
Time setting tsd (s)
Time delay (ms) at 10 x Ir
(I2t Off or I2t On)
Instantaneous
Pick-up (A)
Accuracy: 10 %
Time delay
Earth fault
Pick-up (A)
Accuracy: 10 %
0.8
Long time
Short time
0.7
ET5S/ET6G
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.5
0.6
0.7
DB101127
Pick-up (A)
Accuracy: 10 %
Time delay
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.5
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
ET6G
A
0.3
0.2
500
0
20
80
B
0.3
0.3
640
0.1
0.1
80
140
C
0.4
0.4
720
0.2
0.2
140
200
D
0.5
0.5
800
0.3
0.3
230
320
DB101128
Instantaneous
ET2I
DB101126
Protection
A-9
Functions
and characteristics
Overview of functions
Ammeter measurements
CDB500003
Protection
14
13
Ir
long
time
long time
.7
.6
.5
.4
tr
8
(s) 4
.9 (s)
12
16
.95 2
.98 1
20
24
1
.5
at 6 Ir
x In
[Ir
.8
short time
short time
Isd
4 5
3
2.5
2
1.5
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.2
.1
on
on
setting
Ig
D E F
C
B
I t
.2
.1
0off
delay
tg
(s)
(s)
G
H
.4 .4 .3
.3
.2
on.1
I
A
on
ground fault
ground fault
I t
alarm
alarm
7
instantaneous
Ii
instantaneous
8 10
12
4
15
3
off
off
2
x In
6
test
test
.2
.1
0off
off
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Protects cables (phase and neutral) against overloads
Thermal memory(1): thermal image before and after tripping.
Short-time protection
bb The short-time protection function protects the distribution system against
impedant short-circuits
bb The short-time tripping delay can be used to ensure discrimination with
downstream circuit breaker
bb The I2t ON and I2t OFF options enhance discrimination with a downstream
protection devices
bb Use of I2t curves with short-time protection:
vv I2t OFF selected: the protection function implements a constant time curve
vv I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 lr. Above 10 lr, the time curve is constant
Earth-fault protection on ETA6G trip system
Residual earth fault protection.
Selection of I2t type (ON or OFF) for delay.
A ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
function is to eliminate this type of fault.
Type
Residual
A-10
Instantaneous protection
The Instantaneous-protection function protects the distribution system against solid
short-circuits. Contrary to the short-time protection function, the tripping delay for
instantaneous protection is not adjustable. The tripping order is sent to the circuit
breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI(2) terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
Fault indications
Test
Note: ETA trip units come with a transparent leadseal cover as
standard.
Description
A hand-held test kit may be connected to the test connector on the front to check
circuit-breaker operation. For ETA6G trip unit, the operation of earth-fault protection
can be checked by pressing the test button located above the test connector.
ETA2I
0.4
Long time
Isd = Ir x
0.9
0.95
0.98
0.5
1
2
4
8
12
12.5 25
50
100 200 300
2
4
8
12
0.7(1) 1
5.5
8.3
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
16
400
16
11
20
500
20
13.8
24
600
24
16.6
1.5
0.6
2.5
0.7
10
0.8
0.9
0.95
0.98
0.5
1
2
4
8
12
12.5 25
50
100 200 300
2
4
8
12
0.7(1) 1
5.5
8.3
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
16
400
16
11
20
500
20
13.8
24
600
24
16.6
Isd = Ir x
1.5
2.5
10
Settings
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
Protection
ETA5S/ETA6G
0.4
Long time
Short time
Pick-up (A)
Accuracy: 10 %
Time setting tsd (s)
Time delay (ms) at 10 x Ir
(I2t Off or I2t On)
Instantaneous
Pick-up (A)
Accuracy: 10 %
Time delay
Earth fault
Pick-up (A)
Accuracy: 10 %
Ammeter
Type of measurements
Instantaneous currents
Current maximeters of
0.8
ETA5S/ETA6G
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.5
0.6
0.7
DB101127
Pick-up (A)
Accuracy: 10 %
Time delay
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.5
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
ETA6G
A
0.3
0.2
500
0
20
80
B
0.3
0.3
640
0.1
0.1
80
140
C
0.4
0.4
720
0.2
0.2
140
200
D
0.5
0.5
800
0.3
0.3
230
320
DB101128
Instantaneous
ETA2I
DB101126
Protection
ETA2I/ETA5S/ETA6G
Range
0.2 x In to 1.2 x In
0.2 x In to In
0.2 x In to 1.2 x In
Accuracy
1.5 %
10 %
1.5 %
A-11
Functions
and characteristics
Overview of functions
CDB500004
Protection
15
14
13
long
time
long time
tr
8
(s) 4
.9 (s)
12
16
.6
.95 2
.5
.98 1
20
24
.4
1
.5
at 6 Ir
x In
[Ir
Ir
.7
.8
short time
short time
Isd
2.5
2
1.5
4 5
x Ir
6
8
10
tsd
(s)
(s) .4 .4 .3
.3
.2
on.1
on
setting
Ig
D E F
C
B
I t
.2
.1
0off
delay
tg
(s)
(s)
.4 .4 .3
Type
alarm
alarm
7
instantaneous
Ii
instantaneous
4
3
8 10
12
15
off
off
2
x In
test
test
.2
G
.3
.1
H
.2
I
on.1 2 0off
A
on I t off
ground fault
ground fault
A-12
Protection thresholds and delays are set using the adjustment dials.
Overload protection
True rms long-time protection.
Protects cables (phase and neutral) against overloads
Thermal memory(1): thermal image before and after tripping.
Short-time protection
bb The short-time protection function protects the distribution system against
impedant short-circuits
bb The short-time tripping delay can be used to ensure discrimination with
downstream circuit breaker
bb The I2t ON and I2t OFF options enhance discrimination with a downstream
protection devices
bb Use of I2t curves with short-time protection:
vv I2t OFF selected: the protection function implements a constant time curve
vv I2t ON selected: the protection function implements an I2t inverse-time curve up to
10 lr. Above 10 lr, the time curve is constant
Earth-fault protection on ETV6G trip system
Residual or source ground return earth fault protection.
Selection of I2t type (ON or OFF) for delay.
A ground fault in the protection conductors can provoke local temperature rise at
the site of the fault or in the conductors. The purpose of the ground-fault protection
function is to eliminate this type of fault.
Residual
Description
Instantaneous protection
The Instantaneous-protection function protects the distribution system against solid
short-circuits. Contrary to the short-time protection function, the tripping delay for
instantaneous protection is not adjustable. The tripping order is sent to the circuit
breaker as soon as current exceeds the set value, with a fixed time delay of
20 milliseconds.
Neutral protection
On three-pole circuit breakers, neutral protection is not possible.
On four-pole circuit breakers, neutral protection may be set using a three-position
switch: neutral unprotected (4P 3d), neutral protection at 0.5 Ir (4P 3d + N/2), neutral
protection at Ir (4P 4d).
Zone selective interlocking (ZSI)
A ZSI(2) terminal block may be used to interconnect a number of control units to
provide total discrimination for short-time and earth-fault protection, without a delay
before tripping.
Overload alarm
A yellow alarm LED goes on when the current exceeds the long-time trip threshold.
Fault indications
Test
A hand-held test kit may be connected to the test connector on the front to check
circuit-breaker operation. For ETV6G trip unit, the operation of earth-fault protection
can be checked by pressing the test button located above the test connector.
ETV2I
0.4
Long time
Isd = Ir x
0.9
0.95
0.98
0.5
1
2
4
8
12
12.5 25
50
100 200 300
2
4
8
12
0.7(1) 1
5.5
8.3
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
16
400
16
11
20
500
20
13.8
24
600
24
16.6
1.5
0.6
2.5
0.7
10
0.8
0.9
0.95
0.98
0.5
1
2
4
8
12
12.5 25
50
100 200 300
2
4
8
12
0.7(1) 1
5.5
8.3
0.7(2) 0.69 1.38 2.7
20 minutes before and after tripping
16
400
16
11
20
500
20
13.8
24
600
24
16.6
Isd = Ir x
1.5
2.5
10
Settings
I2t Off
I2t On
tsd (max resettable time)
tsd (max break time)
0
20
80
0.1
0.1
80
140
0.2
0.2
140
200
0.3
0.3
230
320
0.4
0.4
350
500
Ii = In x
10
12
15
off
E
0.6
0.6
880
0.4
0.4
350
500
F
0.7
0.7
960
G
0.8
0.8
1040
H
0.9
0.9
1120
J
1
1
1200
Protection
ETV5S/ETV6G
0.4
Long time
Short time
Pick-up (A)
Accuracy: 10 %
Time setting tsd (s)
Time delay (ms) at 10 x Ir
(I2t Off or I2t On)
Instantaneous
Pick-up (A)
Accuracy: 10 %
Time delay
Earth fault
Pick-up (A)
Accuracy: 10 %
Energy
Type of measurements
Instantaneous currents
Current maximeters of
Demand currents of
Voltages
0.8
ETV5S/ETV6G
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.5
0.6
0.7
DB101127
Pick-up (A)
Accuracy: 10 %
Time delay
tr (s)
1.5 x Ir
6 x Ir
7.2 x Ir
0.5
I2t Off
I2t On
tg (max resettable time)
tg (max break time)
ETV6G
A
0.3
0.2
500
0
20
80
B
0.3
0.3
640
0.1
0.1
80
140
C
0.4
0.4
720
0.2
0.2
140
200
D
0.5
0.5
800
0.3
0.3
230
320
ETV2I/5S/6G
Range
0.2 x In to 1.2 x In
0.2 x In to In
0.2 x In to 1.2 x In
0.2 x In to 1.2 x In
100 to 690 V
DB101128
Instantaneous
ETV2I
DB101126
Protection
Accuracy
1.5 %
10 %
1.5 %
1.5 %
0.5 %
A-13
Functions
and characteristics
DB101524
External sensors
PB101026-32A
The external power-supply module makes it possible to use the display (ETA and
ETV trip systems) even if the circuit breaker is open or not supplied (for the exact
conditions of use, see the electrical diagrams part of this catalogue).
Characteristics
bb Power supply:
vv 110/130, 200/240, 380/415 V AC (+10 % -15 %)
vv 24/30, 48/60, 100/125 V DC (+20 % -20 %)
bb Output voltage: 24 V DC 5 %, 1 A
bb Ripple < 1 %
bb Dielectric withstand : 3.5 kV rms between input/output, for 1 minute
bb Overvoltage category: as per IEC 60947-1 cat. 4
PB100775-32
Spare parts
Lead-seal cover.
Lead-seal covers
A lead-seal cover controls access to the adjustment dials.
When the cover is closed:
bb It is impossible to modify settings using the keypad unless the settings lockout pin
on the cover is removed
bb The test connector remains accessible
bb The test button for the earth-fault protection function remains accessible
Characteristics
bb Transparent cover for all trip units
Spare battery
A battery supplies power to the LEDs identifying the tripping causes.The healthiness
of the battery to be checked periodically. A test button on the front of the control
unit is used to check the battery condition. The battery may be replaced on site
when discharged.
Test equipment
CDB500038
A-14
Connections
Rear connection
Horizontal
PB104354A40
PB104355A40
Vertical
PB104359A40
Mixed
CPB100010
PB104364A50
Safety shutters VO
Mounted on the chassis, the safety shutters automatically block access to the
disconnecting contact cluster when the device is in the disconnected or test positions
(degree of protection IP 20) When the device is removed from its chassis, no live
parts are accessible.
The shutter-locking system is made up of a moving block (optional device) that can
be padlocked (padlock not supplied). The block:
bb Prevents connection of the device
bb Locks the shutters in the closed position
For EasyPact MVS08 to MVS40
A support at the bottom of the chassis is used to store the blocks when they are
not used:
bb 2 blocks for MVS08 to MVS40
Note: EasyPact MVS circuit breakers can be connected indifferently with bare-copper, tinnedcopper and tinned-aluminium conductors, requiring no particular treatment.
A-15
Interphase
barriers
Type of accessory
DB101149
Functions
and characteristics
Optional
Optional
DB101153
Safety shutters
Standard
E46460
Safety shutters
locking blocks
Optional
E46452
Door interlock
E46666
E46666
Optional
Optional
CDB500039
CDB500039
Optional
Pushbutton
locking device
Optional
Optional
E46451
Disconnected
position locking
A-16
E46689
E46689
Optional
Optional
CDB500040
Standard
E46689
Standard
CDB500040
Additional ON/OFF
indication contacts(OF)
E46689
Optional
ON/OFF indication
contacts(OF)
Standard
Standard
Type of accessory
Connected, disconnected,
test position
indication
contact(CE,CD,CT)
Auxiliary
terminal shield(CB)
E46438
E46668
DB125617
Standard
Optional
Optional
E46670
E46668
Standard
Optional
Optional
E46458
Escutcheon
blanking plate
Optional
DB125617
Mechanical operation
counter(CDM)
Optional
E46670
Escutcheon(CDP)
E46438
Optional
Ready to close
contact(PF)
E46669
Optional
Transparent
cover (IP54)
Optional
A-17
Locking
Functions
and characteristics
CDB500006
On the device
1
2
3
4
5
6
7
8
9
ET6G
System
Syste
Trip
Trip
ET6G
MVS08
alarm
alarm
Ir
8 12
time tr
time
long
long
16
(s) 4
(s)
.7
.8 .9.95
.6
.98
.5
1
.4 x In
setting
Ig D
C
B
.5 at 6IrIr
20
24
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
2
1
E F
.2
.1
(s)
(s)
.3
.2
.1
on
on
I t
0off
-2 50/60H
60947
instantane
Ii
instantane
4
3
6
2
ous
8 1012
15
off
off
x In test
test
delay
. 4 .3 2
tg
(s)
.
.4
(s)
G
H
IEC
ous
.1
.3
.
on.1
2
I
on
A
fault
fault
ground
I t
off
0off
ground
PB100811-32
The transparent cover blocks access to the pushbuttons used to open and close
the device.
It is possible to independently lock the opening button and the closing button.
The locking device is often combined with a remote operating mechanism.
The pushbuttons may be locked using either:
bb Three padlocks (not supplied)
bb Lead seal
bb Two screws
PB100810-32
The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
bb Using keylocks (one or two keylocks, supplied)
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
bb One keylock
bb One keylock mounted on the device + one identical keylock supplied separately
for interlocking with another device
A locking kit (without locks) is available for installation of one or two keylocks (Ronis,
Profalux).
CPB100007
CDB500036
Profaulx
Ronis
Mounted on the right or left-hand side of the chassis, this device inhibits opening of
the cubicle door when the circuit breaker is in connected or test position. It the
breaker is put in the connected position with the door open, the door may be closed
without having to disconnect the circuit breaker.
CPB100008
This option discharges the springs before the breaker is removed from the chassis.
Door interlock.
A-18
On the chassis
CDB500007
The connected, disconnected and test positions are shown by an indicator and
are mechanically indexed. The exact position is obtained when the racking handle
blocks. A release button is used to free it.
6
3
Door interlock.
Keylock locking.
Padlock locking.
Position indicator.
Chassis front plate (accessible with cubicle door closed).
Racking-handle entry.
Release button.
Racking-handle storage.
CPB100006
1
2
3
4
5
6
7
8
Mounted on the chassis and accessible with the door closed, these devices lock the
circuit breaker in the disconnected position in two manners:
bb Using padlocks (standard), up to three padlocks (not supplied)
bb Using keylocks (optional), one or two different keylocks are available
Profalux and Ronis keylocks are available in different options:
bb One keylock
bb Two identical key locks - one keylock mounted on the device + one identical
keylock supplied separately for interlocking with another device
A locking kit (without locks) is available for installation of one or two keylocks
(Ronis, Profalux).
Padlock
Circuit breaker in disconnected
position.
Keylock
Turn the key(s).
CPB100017
A-19
Functions
and characteristics
Indication contacts
PB100807-20
Supplied as standard
Optional contact
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
MVS
Standard
V AC
V DC
240/380
480
690
24/48
125
250
1 (4 C/O)
1 (4 C/O)
Minimum load: 100 mA/24 V
10/6 (1)
10/6 (1)
6
10/6 (1)
10/6 (1)
3
PB100818-16
Supplied as standard
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
MVS
Standard
V AC
V DC
240/380
480
690
24/48
125
250
1
Minimum load: 100 mA/24 V
5
5
3
3
0.3
0.15
PB100817-32
Three series of optional auxiliary contacts are available for the chassis:
bb Changeover contacts to indicate the connected position CE
bb Changeover contacts to indicate the disconnected position CD. This position
is indicated when the required clearance for isolation of the power and auxiliary
circuits is reached
bb Changeover contacts to indicate the test position CT. In this position, the power
circuits are disconnected and the auxiliary circuits are connected
Additional actuators
A set of additional actuators may be installed on the chassis to change the functions
of the carriage switches.
Contacts
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
CE, CD and CT connected/
disconnected/test position
carriage switches.
A-20
MVS
Standard
Standard
V AC
V DC
240
380
480
690
24/48
125
250
CE/CD/CT
3
3
3
Minimum load: 100 mA/24 V
8
8
8
6
2.5
0.8
0.3
Remote operation
Remote ON / OFF
The remote ON / OFF function is used to remotely open and close the circuit breaker.
It is made up of:
bb An electric motor MCH equipped with a springs charged limit switch contact CH
bb Two voltage releases:
vv A closing release XF
vv An opening release MX
PB104349A68
DB111783
A-21
Functions
and characteristics
Remote operation
Remote ON / OFF
PB100808-32
The electric motor automatically charges and recharges the spring mechanism when
the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible
following opening. The spring-mechanism charging handle is used only as a backup
if auxiliary power is absent.
The electric motor MCH is equipped as standard with a limit switch contact CH that
signals the charged position of the mechanism (springs charged).
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating threshold
Consumption (VA or W)
Motor overcurrent
Charging time
Operating frequency
CH contact
DB117037
Characteristics
Power supply
V AC 50/60 Hz
V DC
Operating threshold
Consumption (VA or W)
XF
MX
PB100809-16
MX voltage releases.
XF voltage release.
PB100818-16
Characteristics
Maximum number
Breaking capacity (A)
p.f.: 0.3
AC12/DC12
Standard
V AC
V DC
A-22
240/380
480
690
24/48
125
250
1
Minimum load: 100 mA/24 V
5
5
3
3
0.3
0.15
Remote tripping
DB100809-16
The MN release instantaneously opens the circuit breaker when its supply voltage
drops to a value between 35 % and 70 % of its rated voltage. If there is no supply on
the release, it is impossible to close the circuit breaker, either manually or electrically.
Any attempt to close the circuit breaker has no effect on the main contacts. Circuit
breaker closing is enabled again when the supply voltage of the release returns to
85% of its rated value.
Characteristics
Power supply
MN voltage release.
V AC 50/60 Hz
V DC
Operating threshold Opening
Closing
Consumption (VA or W)
MN consumption
with delay unit (VA or W)
Circuit-breaker response time at Un
MN delay units
056422N
Power supply
V AC 50-60 Hz /DC
Operating threshold
MN delay unit.
Non-adjustable
100/130 - 200/250
Adjustable
48/60 - 100/130 - 200/250 - 380/480
Opening
0.35 to 0.7 Un
Closing
0.85 Un
Pick-up: 200 (200 ms)
Hold: 4.5
Non-adjustable
0.25 s
Adjustable
0.5 s - 0.9 s - 1.5 s - 3 s
A-23
Functions
and characteristics
Source-changeover systems
Mechanical interlocking
CPB100009
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side. The interlocked devices may be fixed or drawout, three-pole or fourpole, and have different ratings.
Interlocking between two devices
This function requires:
bb An adaptation fixture on the right side of each device
bb A set of cables with no-slip adjustments
bb The use of a mechanical operation counter CDM is compulsory
The maximum distance between the fixing planes (vertical or horizontal) is 2000 mm.
Interlocking between three devices
This function requires:
bb A specific adaptation fixture for each type of interlocking, installed on the right side
of each device
bb Two or three sets of cables with no-slip adjustments
bb The use of a mechanical operation counter CDM is compulsory
The maximum distance between the fixing planes (vertical or horizontal) is 1000 mm.
Installation
The adaptation fixtures, sets of cables and circuit breakers or switch-disconnectors
are supplied separately, ready for assembly by the customer.
Installation conditions for cable interlocking systems:
bb Cable length: 2.5 m
bb Radius of curvature: 100 mm
bb Maximum number of curves: 3
Possible combinations of Normal and Replacement source circuit breakers
Normal N
Replacement R
MVS08 to MVS40
b
MVS08 to MVS40
Ratings 800...4000A
MVS08 to MVS40
b
All combinations of two or three EasyPact MVS devices are possible, whatever the
rating of the devices.
A-24
Accessories
PB104740
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
DB101173
PB104382A32
The operation counter sums the number of operating cycles and is visible on the
front panel. It is compatible with manual and electrical control functions.
This option is compulsory for all the source-changeover systems.
Escutcheon CDP
Standard equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP 40 (circuit breaker installed free standing: IP30) .
It is available in fixed and drawout versions.
Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet
equipped with a device. It may be used with the escutcheon for both fixed and
drawout devices.
PB100776-42
Optional equipment mounted on the escutcheon, the cover is hinged and secured by
a screw. It increases the degree of protection to IP54, IK10. It adapts to drawout
devices.
A-25
Installation
recommendations
EasyPact MVS
Installation recommendations
A-1
Operating conditions
B-2
Installation in switchboard
B-3
B-5
Control wiring
B-6
Power connection
B-7
B-9
Busbar sizing
B-10
Temperature derating
Power dissipation
B-12
C-1
D-1
E-1
F-1
B-1
Operating conditions
Installation
recommendations
Ambient temperature
ET6G
EasyPact MVS devices can operate under the following temperature conditions:
bb The electrical and mechanical characteristics are stipulated for an ambient
temperature of -5C to +60C
bb Circuit-breaker closing is guaranteed down to -35C
Storage conditions are as follows:
bb -40 to +85C for a Easypact MVS device without its control unit
bb -25C to +85C for the control unit
System
System
Trip
Trip
ET6G
MVS08
alarm
alarm
8 12
time tr
time
long
long
16
(s) 4
(s)
.8 .9.95
Ir
.6.7
.98
.5
1
.4 x In
2
1
.5 at 6IrIr
20
24
.2
.1
(s)
(s)
.3
.
.1
on
on
2
I t
IEC
60947-2
50/60H
instantaneous
Ii
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
instantaneous
4
3
8 1012
6
2
0off
15
off
off
x In test
test
delay
setting
.4 .3 2
tg
(s)
.
(s) .4
E F
.1
.3
G
.2
off
0off
CD
H
on.1 I2t
B
I
on
A
fault
fault
ground
Ig
CDB500011
ground
Altitude
(m)
2000
At altitudes higher than 2000 metres, the modifications in the ambient air (electrical
resistance, cooling capacity) lower the following characteristics as follows:
Altitude (m)
Impulse withstand voltage uimp (kV)
Rated insulation voltage (Ui)
Maximum rated operationnal
voltage 50/60 Hz Ue (V)
ET6G
System
System
Trip
Trip
ET6G
MVS08
alarm
alarm
8 12
time tr
time
long
long
16
(s) 4
(s)
.8 .9.95
Ir
.6.7
.98
.5
1
.4 x In
2
1
.5 at 6IrIr
20
24
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
.2
.1
(s)
(s)
.3
.
.1
on
on
2
I t
0off
delay
setting
. 4 .3 2
tg
(s)
.
(s) .4
E F
.1
.3
G
.2
off
0off
CD
H
on.1 I2t
B
I
on
A
fault
fault
ground
Ig
ground
IEC
instantaneous
Ii
instantaneous
4
3
6
2
8 1012
15
off
off
x In test
test
60947-2
50/60H
CDB500012
ET6G
System
System
Trip
Trip
ET6G
MVS08
alarm
alarm
8 12
time tr
time
long
long
16
(s) 4
(s)
.8 .9
.95
.6.7
.98
.5
1
.4 x In
Ir
2
1
.5 at 6IrIr
20
24
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
.2
.1
(s)
(s)
.3
.
.1
on
on
2
I t
0off
delay
setting
.4 .3.2
tg
(s)
(s) .4
E F
.1
.3
G
.2
off
0off
CD
H
on.1 I2t
B
I
on
A
fault
fault
ground
Ig
ground
B-2
IEC
instantaneous
Ii
instantaneous
4
3
6
2
8 1012
15
off
off
x In test
test
60947-2
50/60H
3000
11
900
590
890
0.99 x In
Electromagnetic disturbances
Isd
2000
12
1000
690
1000
1 x In
Installation in switchboard
ET6G
CDB500015
CDB500013
CDB500014
Possible positions
System
System
Trip
Trip
ET6G
MVS08
alarm
alarm
IEC
8 12
time tr
time
long
long
16
(s) 4
(s)
.8 .9
.95
.6.7
.98
.5
1
.4 x In
Ir
2
1
.5 at 6IrIr
20
24
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
.2
.1
(s)
(s)
.3
.
.1
on
on
2
I t
0off
60947-2
50/60H
instantaneous
Ii
instantaneous
4
3
6
2
8 1012
15
off
off
x In test
test
delay
setting
.4 .3.2
tg
(s)
(s) .4
E F
.1
.3
G
.2
off
0off
CD
H
on.1 I2t
B
I
on
A
fault
fault
ground
Ig
ground
Power supply
CDB500016
EasyPact MVS devices can be supplied either from the top or from the bottom
without reduction in performance, in order to facilitate connection when installed
in a switchboard.
ET6G
System
System
Trip
Trip
ET6G
MVS08
alarm
alarm
IEC
8 12
time tr
time
long
long
16
(s) 4
(s)
.8 .9
Ir
.95
.6.7
.98
.5
1
.4 x In
2
1
.5 at 6IrIr
20
24
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
.2
.1
(s)
(s)
.3
.
.1
on
on
2
I t
0off
60947-2
50/60H
instantaneous
Ii
instantaneous
4
3
6
2
8 1012
15
off
off
x In test
test
delay
setting
.4 .3.2
tg
(s)
(s) .4
E F
.1
.3
G
.2
off
0off
CD
H
on.1 I2t
B
I
on
A
fault
fault
ground
Ig
ground
CDB500018
CDB500017
It is important to distribute the weight of the device uniformily over a rigid mounting
surface such as rails or a base plate.
This mounting plane should be perfectly flat (tolerance on support flatness: 2 mm).
This eliminates any risk of deformation which could interfere with correct operation
of the circuit breaker.
EasyPact devices can also be mounted on a vertical plane using the
special brackets.
ET6G
System
System
Trip
Trip
ET6G
ET6G
alarm
alarm
8 12
time tr
time
long
long
16
(s) 4
(s)
.8 .9.95
.7
.6
.98
.5
1
.4 x In
Ir
.5 at 6IrIr
20
24
.2
.1
(s)
(s)
setting
. 4 .3 2
tg
(s)
.
.4
Ig D
C
B
2
1
time
shorttime tsd .4 .4 .3
short
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
E F
.3
.
.1
on
on
2
G
H
0off
.1
.3
.
on.1
I
on
A
fault
fault
ground
ground
I t
delay
(s)
I t
off
0off
IEC
s
instantaneou
Ii
instantaneous
4
3
6
2
System
System
Trip
Trip
ET6G
MVS08
8 1012
15
off
off
x In test
test
60947-2
MVS08
50/60H
alarm
alarm
8 12
time tr
time
long
long
16
(s) 4
.8 .9.95 (s)2
20
.7
1
24
.6
.98
.5 at 6IrIr
.5
1
.4 x In
time
shorttime tsd .4 .4 .3
short
(s)
.2
(s)
.1
.3
.2 2 0off
.1 I t
on
on
IEC
Ir
4 5
3
6
8
2.5
2
10
1.5 Ir
x
Isd
setting
Ig D
C
B
E F
G
H
60947-2
50/60H
s
instantaneou
Ii
instantaneous
4
3
6
2
8 1012
15
off
off
x In test
test
delay
. 4 .3 2
tg
(s)
.
(s) .4
.1
.3
.
on.1
2
I
on
A
fault
fault
ground
I t
off
0off
ground
Mounting on rails.
B-3
Installation in switchboard
Partitions
DB101434
Installation
recommendations
Busbars
DB117045
DB101436
Interphase barrier
CDB500041
DB101439
DB101435
453
B-4
CDB500034
DB117044
Dimensions (mm)
Type
MVS08-40 (3P)
MVS08-40 (4P)
(1)
215
330
(2)
215
215
Breaker in connected
or test position
Breaker in disconnected
position
Door can be opened
DB102194
DB103819
83
103
B-5
Installation
recommendations
Control wiring
During pick-up, the power consumed is approximately 150 to 200 VA. For low control
voltages (12, 24, 48 V), maximum cable lengths are imposed by the voltage and the
cross-sectional area of cables.
Recommended maximum cable lengths (meter).
MN
MX-XF
U source 100 %
U source 85 %
U source 100 %
U source 85 %
12 V
2,5 mm2
21
10
1,5 mm2
12
6
24 V
2,5 mm2
58
16
115
75
1,5 mm2
35
10
70
44
48 V
2,5 mm2
280
75
550
350
1,5 mm2
165
45
330
210
24 V DC power-supply module
B-6
DB101452
DB101453
Busbars connections
DB101451
DB101450
DB101449
Cables connections
DB101448
Power connection
Electrodynamic stresses
The first busbar support or spacer shall be situated within a maximum distance from
the connection point of the breaker (see table below). This distance must be
respected so that the connection can withstand the electrodynamic stresses
between phases in the event of a short circuit.
Maximum distance A between busbar to circuit breaker connection and the first busbar
support or spacer with respect to the value of the prospective short-circuit current.
Isc (kA)
Distance A (mm)
30
350
50
300
65
250
B-7
Power connection
Installation
recommendations
DB101454
Clamping
1
2
3
4
5
6
DB101457
DB101456
DB101455
Tightening torques
(mm)
(mm)
Nominal
Drilling
10
37.5
11
DB101460
DB101459
DB101458
Busbar drilling
Examples
DB101461
Isolation distance
Dimensions (mm)
Ui
600 V
1000 V
X min
8 mm
14 mm
DB101462
Busbar bending
When bending busbars maintain the radius indicated below(a smaller radius would
cause cracks).
Dimensions (mm)
e
5
10
B-8
Radius of curvature r
Min
5
15
Recommended
7.5
18 to 20
CDB500042
MVS40
CDB500055
CDB500054
DB101465
DB101464
DB101474
DB101463
DB101476
CDB500043
CDB500056
MVS40
DB101477
B-9
Busbar sizing
Installation
recommendations
Basis of tables:
bb Maximum permissible busbars temperature: 100C
bb Ti: temperature around the circuit breaker and its
connection
bb Busbar material is unpainted Copper/ Aluminium
PB104347A55
Unpainted Copper
EasyPact
MVS08
MVS10
MVS12
Maximum
service
current
800
1000
1250
MVS16
MVS20
MVS25
MVS32
MVS40
1600
2000
2500
3200
4000
Unpainted Aluminium
EasyPact
Maximum
service
current
Ti : 40C
No. of 5 mm
thick bars
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
3b.80 x 5
3b.100 x 5
4b.100 x 5
6b.100 x 5
Ti : 40C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.40 x 10
2b.63 x 10
2b.80 x 10
2b.100 x 10
3b.100 x 10
5b.100 x 10
No. of 10 mm
thick bars
Ti : 50C
No. of 5 mm
thick bars
2b.50 x 5
3b.50 x 5
3b.50 x 5
2b.80 x 5
3b.80 x 5
3b.100 x 5
4b.100 x 5
8b.100 x 5
Ti : 50C
No. of 5 mm
thick bars
Example
Conditions:
bb Drawout version
bb Horizontal busbars
bb Ti: 50C
bb Service current: 2000 A
Solution:
For Ti = 50C, use an MVS20 which can be connected
with 3 bars - 100x5mm (or) 2 bars - 80x10mm.
Note: The values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
B-10
No. of 10 mm
thick bars
1b.50 x 10
2b.50 x 10
2b.50 x 10
2b.63 x 10
2b.80 x 10
2b.100 x 10
3b.100 x 10
5b.100 x 10
No. of 10 mm
thick bars
Ti : 60C
No. of 5 mm
thick bars
2b.50 x 5
3b.63 x 5
3b.63 x 5
3b.80 x 5
3b.100 x 5
4b.100 x 5
Ti : 60C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
1b.63 x 10
2b.50 x 10
2b.50 x 10
3b.50 x 10
3b.63 x 10
3b.80 x 10
4b.100 x 10
6b.100 x 10
No. of 10 mm
thick bars
Basis of tables:
bb Maximum permissible busbars temperature: 100C
bb Ti: temperature around the circuit breaker and its
connection
bb Busbar material is unpainted Copper/ Aluminium
DB101487
Unpainted Copper
EasyPact
MVS08
MVS10
MVS12
MVS16
MVS20
MVS25
MVS32
MVS40
Maximum
service
current
800
1000
1250
1600
2000
2500
3200
4000
Unpainted Aluminium
EasyPact
Maximum
service
current
Ti : 40C
No. of 5 mm
thick bars
2b.50 x 5
2b.50 x 5
2b.63 x 5
3b.63 x 5
3b.100 x 5
4b.100 x 5
6b.100 x 5
Ti : 40C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
1b.50 x 10
1b.50 x 10
1b.63 x 10
2b.50 x 10
2b.63 x 10
2b.80 x 10
3b.100 x 10
4b.100 x 10
No. of 10 mm
thick bars
Ti : 50C
No. of 5 mm
thick bars
2b.50 x 5
2b.50 x 5
3b.50 x 5
3b.63 x 5
3b.100 x 5
4b.100 x 5
6b.100 x 5
Ti : 50C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
1b.50 x 10
1b.50 x 10
2b.40 x 10
2b.50 x 10
2b.63 x 10
2b.80 x 10
3b.100 x 10
4b.100 x 10
No. of 10 mm
thick bars
Ti : 60C
No. of 5 mm
thick bars
2b.50 x 5
2b.63 x 5
3b.50 x 5
3b.80 x 5
3b.100 x 5
4b.100 x 5
Ti : 60C
No. of 5 mm
thick bars
No. of 10 mm
thick bars
1b.50 x 10
1b.63 x 10
2b.40 x 10
2b.63 x 10
2b.80 x 10
3b.80 x 10
4b.100 x 10
4b.100 x 10
No. of 10 mm
thick bars
Example
Conditions:
bb Drawout version
bb Vertical connections
bb Ti: 60C
bb Service current: 1250 A
Solution :
For Ti = 60C use an MVS12 which can be
connected with 3 bars - 50x5mm (or) 2 bars - 40x10mm.
Note: The values indicated in these tables have been extrapolated from test data and theoretical
calculations. These tables are only intended as a guide and cannot replace industrial experience
or a temperature rise test.
B-11
Temperature derating
Power dissipation
Installation
recommendations
Temperature derating
MVS (50kA)
MVS08N
MVS10N
MVS12N
MVS16N
MVS20N
MVS25N
MVS32N
MVS40N
MVS (65kA)
MVS08N
MVS10N
MVS12N
MVS16N
MVS20N
MVS25N
MVS32N
MVS40N
Drawout
Fixed
Rear horizontal
Rear vertical
Rear horizontal
Rear vertical
40 C 45 C 50 C 55 C 60 C 40 C 45 C 50 C 55 C 60 C 40 C 45 C 50 C 55 C 60 C 40 C 45 C 50 C 55 C 60 C
800
1000
1250
1600
2000
2500
3200
4000
1900 1800
2450
3100 3000 2900
3900 3750 3650
800
1000
1250
1600
2000
1900
2500 2450 2400 2300
3200
3100 3000
4000
3900 3750
1800
2200
2900
3650
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
1900 2000
2500
3200
3900 4000
800
1000
1250
1600
1920 2000
2500
3200
3900 3800 4000
800
1000
1250
1600
2000
2500
3200
4000
800
1000
1250
1600
1900 2000
2450 2400 2300 2500
3200
3900 4000
800
1000
1250
1600
1920 2000
2500
3200
3900 3800 4000
Power dissipation
MVS08N
MVS10N
MVS12N
MVS16N
MVS20N
MVS25N
MVS32N
MVS40N
65kA
MVS08H
MVS10N
MVS12N
MVS16N
MVS20N
MVS25N
MVS32N
MVS40N
B-12
Draw-out
Power loss (W)
Fixed
Power loss (W)
120
180
280
460
470
600
670
900
60
100
140
200
250
260
420
650
100
150
230
390
470
600
670
900
42
70
100
170
250
260
420
650
B-13
Dimensions
and connection
EasyPact MVS
A-1
B-1
C-2
C-6
C-2
C-4
C-6
C-8
AccessoriesC-10
External modules
Electrical diagrams
Additional characteristics
Catalogue numbers and order form
C-11
D-1
E-1
F-1
C-1
Dimensions
and connection
CDB500019
DB101267
Dimensions
DB101270
Mounting detail
DB101269
Insulated
parts
A
B
0
0
: Datum.
C-2
DB101273
CDB500020
DB101271
Safety clearances
Metal
parts
0
0
Energised
parts
100
60
Connections
DB101278
DB101277
Detail
DB101276
DB101274
DB101282
DB101287
Detail
DB101280
DB101279
View A detail.
C-3
Dimensions
and connection
CDB500021
DB101289
Dimensions
DB101292
Mounting detail
DB101291
A
B
0
0
: Datum.
C-4
Metal
parts
0
0
DB101295
DB101293
Insulated
parts
DB101294
Door cutout
CDB500022
Safety clearances
Energised
parts
0
60
Connections
DB101278
DB101298
Detail
DB101297
CDB500044
DB101282
DB101307
Detail
DB101301
CDB500045
View A detail.
C-5
Dimensions
and connection
CDB500021
DB101267
Dimensions
DB101270
Mounting detail
DB101269
Door cutout
Insulated
parts
A
B
0
0
: Datum.
C-6
DB101273
DB101271
CDB500020
Safety clearances
Metal
parts
0
0
Energised
parts
100
60
Connections
DB101309
DB101276
15
400(3P)
DB101315
CDB500049
CDB500049
DB101311
Detail
DB101313
DB101312
DB101314
DB101287
Detail
C-7
Dimensions
and connection
CDB500019
DB101289
Dimensions
DB101292
Mounting detail
DB101291
Insulated
parts
A
B
0
0
: Datum.
C-8
Metal
parts
0
0
DB101295
DB101294
Door cutout
CDB500022
DB101293
Safety clearances
Energised
parts
0
60
Connections
CDB500046
DB101297
400(3P)
15
DB101315
DB101311
CDB500050
CDB500050
Detail
DB101314
DB101319
CDB500047
View A detail.
DB101307
Detail
C-9
Accessories
Dimensions
and connection
DB101360
DB125695
MVS08 to MVS40
Rear view
Escutcheon
Drawout device
DB101366
DB101365
EasyPact MVS
Fixed device
: Datum.
C-10
External modules
DB101368
DB101367
DB102076
DB102077
DB117025
DB101375
C-11
External modules
Dimensions
and connection
DB117024
Dimensions
400/2000 A (MVS08 to MVS20)
DB101386
Installation
400/2000 A (MVS08 to MVS20)
C-12
C-13
Electrical diagrams
EasyPact MVS
Electrical diagrams
A-1
B-1
C-1
EasyPact MVS08 to 40
D-2
EasyPact MVS
D-4
Additional characteristics
Catalogue numbers and order form
E-1
F-1
D-2
D-4
D-5
D-6
D-1
Electrical diagrams
Remote operation
Close
Open
Stop
Fault
V3
V2
V1
VN
Charged
Readyto-close
Power
ET trip system
E89955
NCT
UC1
UC2
UC1
UC2
UC3
Remote operation
E60067A
E60066A
SDE
MN
MX
XF
PF
MCH
F2+
84
D2
C2
A2
254
B2
C3
A3
252
B3
C1
A1
251
B1
Z5
Z5
Z3 Z4 T3 T4
Z3
Z4
T3
T4
VN
82
Z1 Z2 T1 T2
Z1
Z2
T1
T2
F1-
81
E46137A
E60065A
E89956
ET trip system
E46136A
UC2 :
T1, T2, T3, T4=external neutral
UC3 :
F2+, F1-: external 24 V DC power supply
VN: external voltage connector (must be
connected to the neutral CT with a 3P
circuit breaker equipped with ETV trip system)
D1
Remote operation
SDE:
MN:
MX:
XF:
PF:
MCH:
E47477
D-2
The rating of the sensor (CT) must be compatible with the rating of the circuit
breaker:
1. MVS08 to MVS20: CT 400/2000;
2. MVS25 to MVS40: CT 1000/4000;
Chassis contacts
DB101409
Indication contacts
Indication contacts
OF4
OF3
OF2
OF1
OF14
OF13
OF12
OF11
44
34
24
14
144
134
124
42
32
22
12
142
132
41
31
21
11
141
131
Standard
CD3
CD2
CD1
CE3
CE2
CE1
CT3
CT2
CT1
114
834
824
814
334
324
314
934
924
914
122
112
832
822
812
332
322
312
932
922
912
121
111
831
821
811
331
321
311
931
921
911
Optional
Indication contacts
OF4
OF3
OF2
OF1
Standard
ON/OFF
Indication contacts
Chassis contacts
Optional
Chassis contacts
OF 14
OF 13
OF 12
OF 11
Optional
ON/OFF
Indication contacts
CD3 Disconnected
CD2 Position
CD1 Contacts
CE3 Connected
CE2 Position
CE1 Contacts
CT3 Test
CT2 Position
CT1 Contacts
Key:
Drawout device only
XXX SDE1, OF1, OF2, OF3, OF4 supplied as standard
Interconnected connections
(only one wire per connection point)
D-3
EasyPact MVS
Electrical diagrams
Earth-fault protection
Neutral Protection
VN
DB125601
ET/ETA/ETV 6G
External
Neutral CT
Neutral protection
bb Three pole circuit breaker:
vv Neutral protection is impossible
bb Four pole circuit breaker:
vv The current transformer for external neutral is not
necessary
D-4
VN
Shield Drain
DB101420
Fault 1.
Only circuit breaker A detects the fault. Because it receives no
signal from downstream, it opens immediately, regardless of its
tripping delay set to 0.3.
Fault 2.
Circuit breakers A and B detect the fault. Circuit breaker A
receives a signal from B and remains closed for the full duration
of its tripping delay set to 0.3. Circuit breaker B does not
receive a signal from downstream and opens immediately, in
spite of its tripping delay set to 0.2.
Wiring
bb Maximum impedance: 2.7 W / 300 m
bb Capacity of connectors: 0.4 to 2.5 mm2
bb Wires: single or multicore
bb Maximum lenght: 3000 m
bb Limits to device interconnection:
vv The common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)
can be connected to a maximum of 10 upstream device
vv A maximum of 100 downstream devices may be connected
to the common ZSI - IN (Z3) and to an input ZSI - IN CR ( Z4)
or GF (Z5)
D-5
Electrical diagrams
EasyPact MVS
bb The 24 V DC external power-supply (AD module) for the ET Trip system (F1- F2+)
is not required for basic protections LSIG
bb With ETA/ETV, it is recommended to connect 24 V DC external power-supply
(AD module) to the Micrologic control unit (F1- F2+) in order to keep available the
display and the energy metering, even if Current < 20 % In
Note: In case of using the 24 V DC external power supply (AD module), maximum cable length
between 24 V DC (G1, G2) and the control unit (F1-, F2+) must not exceed 10 meters.
The internal voltage taps are connected to the bottom side of the circuit breaker.
Connection
The maximum length for each conductor supplying power to the trip unit is 10 m.
Do not ground F2+, F1-, or power supply output:
bb The positive terminal (F2+) on the trip unit must not be connected to earth ground
bb The negative terminal (F1-) on the trip unit must not be connected to earth ground
bb The output terminals (- and +) of the 24 V DC power supply must not be grounded
Reduce electromagnetic interference:
bb The input and output wires of the 24 V DC power supply must be physically
separated as much as possible
bb If the 24 V DC power supply wires cross power cables, they must cross
perpendicularly. If this is not physically possible, the power supply conductors
must be twisted together
bb Power supply conductors must be cut to length. Do not loop excess conductor
D-6
D-7
Additional
characteristics
EasyPact MVS
Additional characteristics
A-1
B-1
C-1
D-1
Tripping curves
E-2
F-1
E-1
Tripping curves
Additional
characteristics
DB105112
DB105113
E-2
DB101505
(1)
Ig = In x...
In y 400 A
400 A < In y 1000 A
In u 1250A
0.3
0.2
500
0.3
0.3
640
0.4
0.4
720
0.5
0.5
800
0.6
0.6
880
0.7
0.7
960
0.8
0.8
1040
0.9
0.9
1120
1
1
1200
E-3
Catalogue numbers
and order form
EasyPact MVS
Catalogue numbers
and order form
Functions and characteristics
Installation recommendations
Dimensions and connection
Electrical diagrams
Tripping curves
A-1
B-1
C-1
D-1
E-2
Nomenclature F-2
EasyPact MVS 800 to 4000A
F-3
EasyPact MVS
F-8
F-3
F-4
F-5
F-7
Connection F-8
ET Trip System & accessories
F-9
Remote operation
F-10
Chassis locking and accessories
F-12
Clusters F-13
Circuit breaker locking and accessories
F-14
Mechanical interlocking for source changeover
F-15
Indication contacts
F-16
Instructions F-17
Order form
F-18
F-1
Nomenclature
Catalogue numbers
and order form
Range
Current rating Type
Pole
Operating mechanism Installation
EasyPact MVS (from 800 to 4000A) Icu=Ics=Icw (1 sec)=50kA & 65kA
MVS
08
N
3
M
F
10
H
4
N
W
12
O
16
P
20
Q
25
R
32
S
40
T
L
A
V
D
L
A
V
D
2
5
6
0
F
W
M
N
O
P
Q
R
S
T
3P
4P
N
H
08
10
12
16
20
25
32
40
Example 1
MVS
EasyPact
MVS
Example 2
MVS
EasyPact
MVS
F-2
11 digits
Type
Basic protection
Protection+current metering
Protection+voltage metering
Switch disconnector
Protections No.
LI protection
LSI protection
LSIG protection
No protection for switch disconnector
Type of installation
Fixed
Withdrawable/drawout
Operating mechanism
Manually operated ACB/SD
Electrical 200/240 VAC
Electrical 110/130 VAC
Electrical 380/415 VAC
Electrical 200/250 VDC
Electrical 100/125 VDC
Electrical 48/60V DC
Electrical 24/30V DC
MCH + XF + MX
MCH + XF + MX
MCH + XF + MX
MCH + XF + MX
MCH + XF + MX
MCH + XF + MX
MCH + XF + MX
Number of poles
3 Poles
4 Poles
Current rating
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
MVS32N4NW6L
32
N
3200A
4 Pole
Electrical operated
240V AC
MVS16H3MF0D
16
H
1600A
3 Pole
Manual operated
Fixed
No protection
Switch disconnector
50kA
65kA
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
ET2I
MVS08N3MF2L
MVS10N3MF2L
MVS12N3MF2L
MVS16N3MF2L
MVS20N3MF2L
MVS25N3MF2L
MVS32N3MF2L
MVS40N3MF2L
MVS08N3NF2L
MVS10N3NF2L
MVS12N3NF2L
MVS16N3NF2L
MVS20N3NF2L
MVS25N3NF2L
MVS32N3NF2L
MVS40N3NF2L
ET5S
MVS08N3MF5L
MVS10N3MF5L
MVS12N3MF5L
MVS16N3MF5L
MVS20N3MF5L
MVS25N3MF5L
MVS32N3MF5L
MVS40N3MF5L
MVS08N3NF5L
MVS10N3NF5L
MVS12N3NF5L
MVS16N3NF5L
MVS20N3NF5L
MVS25N3NF5L
MVS32N3NF5L
MVS40N3NF5L
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
MVS08N3MF0D
MVS10N3MF0D
MVS12N3MF0D
MVS16N3MF0D
MVS20N3MF0D
MVS25N3MF0D
MVS32N3MF0D
MVS40N3MF0D
MVS08N3NF0D
MVS10N3NF0D
MVS12N3NF0D
MVS16N3NF0D
MVS20N3NF0D
MVS25N3NF0D
MVS32N3NF0D
MVS40N3NF0D
ET6G
MVS08N3MF6L
MVS10N3MF6L
MVS12N3MF6L
MVS16N3MF6L
MVS20N3MF6L
MVS25N3MF6L
MVS32N3MF6L
MVS40N3MF6L
MVS08N3NF6L
MVS10N3NF6L
MVS12N3NF6L
MVS16N3NF6L
MVS20N3NF6L
MVS25N3NF6L
MVS32N3NF6L
MVS40N3NF6L
4P
ET2I
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ET5S
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ET6G
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
4P
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
F-3
Catalogue numbers
and order form
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
ET2I
MVS08H3MF2L
MVS10H3MF2L
MVS12H3MF2L
MVS16H3MF2L
MVS20H3MF2L
MVS25H3MF2L
MVS32H3MF2L
MVS40H3MF2L
MVS08H3NF2L
MVS10H3NF2L
MVS12H3NF2L
MVS16H3NF2L
MVS20H3NF2L
MVS25H3NF2L
MVS32H3NF2L
MVS40H3NF2L
ET5S
MVS08H3MF5L
MVS10H3MF5L
MVS12H3MF5L
MVS16H3MF5L
MVS20H3MF5L
MVS25H3MF5L
MVS32H3MF5L
MVS40H3MF5L
MVS08H3NF5L
MVS10H3NF5L
MVS12H3NF5L
MVS16H3NF5L
MVS20H3NF5L
MVS25H3NF5L
MVS32H3NF5L
MVS40H3NF5L
CDB500048
Manual
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
MVS08H3MF0D
MVS10H3MF0D
MVS12H3MF0D
MVS16H3MF0D
MVS20H3MF0D
MVS25H3MF0D
MVS32H3MF0D
MVS40H3MF0D
MVS08H3NF0D
MVS10H3NF0D
MVS12H3NF0D
MVS16H3NF0D
MVS20H3NF0D
MVS25H3NF0D
MVS32H3NF0D
MVS40H3NF0D
F-4
ET6G
MVS08H3MF6L
MVS10H3MF6L
MVS12H3MF6L
MVS16H3MF6L
MVS20H3MF6L
MVS25H3MF6L
MVS32H3MF6L
MVS40H3MF6L
MVS08H3NF6L
MVS10H3NF6L
MVS12H3NF6L
MVS16H3NF6L
MVS20H3NF6L
MVS25H3NF6L
MVS32H3NF6L
MVS40H3NF6L
4P
ET2I
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
4P
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ET5S
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ET6G
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
ET2I
MVS08N3MW2L
MVS10N3MW2L
MVS12N3MW2L
MVS16N3MW2L
MVS20N3MW2L
MVS25N3MW2L
MVS32N3MW2L
MVS40N3MW2L
MVS08N3NW2L
MVS10N3NW2L
MVS12N3NW2L
MVS16N3NW2L
MVS20N3NW2L
MVS25N3NW2L
MVS32N3NW2L
MVS40N3NW2L
ET5S
MVS08N3MW5L
MVS10N3MW5L
MVS12N3MW5L
MVS16N3MW5L
MVS20N3MW5L
MVS25N3MW5L
MVS32N3MW5L
MVS40N3MW5L
MVS08N3NW5L
MVS10N3NW5L
MVS12N3NW5L
MVS16N3NW5L
MVS20N3NW5L
MVS25N3NW5L
MVS32N3NW5L
MVS40N3NW5L
ET6G
4P
ET2I
ET5S
ET6G
ETA6G
4P
ETA2I
ETA5S
ETA6G
MVS08N3MW6L
MVS10N3MW6L
MVS12N3MW6L
MVS16N3MW6L
MVS20N3MW6L
MVS25N3MW6L
MVS32N3MW6L
MVS40N3MW6L
MVS08N3NW6L
MVS10N3NW6L
MVS12N3NW6L
MVS16N3NW6L
MVS20N3NW6L
MVS25N3NW6L
MVS32N3NW6L
MVS40N3NW6L
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
ETA2I
MVS08N3MW2A
MVS10N3MW2A
MVS12N3MW2A
MVS16N3MW2A
MVS20N3MW2A
MVS25N3MW2A
MVS32N3MW2A
MVS40N3MW2A
MVS08N3NW2A
MVS10N3NW2A
MVS12N3NW2A
MVS16N3NW2A
MVS20N3NW2A
MVS25N3NW2A
MVS32N3NW2A
MVS40N3NW2A
ETA5S
MVS08N3MW5A
MVS10N3MW5A
MVS12N3MW5A
MVS16N3MW5A
MVS20N3MW5A
MVS25N3MW5A
MVS32N3MW5A
MVS40N3MW5A
MVS08N3NW5A
MVS10N3NW5A
MVS12N3NW5A
MVS16N3NW5A
MVS20N3NW5A
MVS25N3NW5A
MVS32N3NW5A
MVS40N3NW5A
MVS08N3MW6A
MVS10N3MW6A
MVS12N3MW6A
MVS16N3MW6A
MVS20N3MW6A
MVS25N3MW6A
MVS32N3MW6A
MVS40N3MW6A
MVS08N3NW6A
MVS10N3NW6A
MVS12N3NW6A
MVS16N3NW6A
MVS20N3NW6A
MVS25N3NW6A
MVS32N3NW6A
MVS40N3NW6A
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
MVS08N4MW2A
MVS10N4MW2A
MVS12N4MW2A
MVS16N4MW2A
MVS20N4MW2A
MVS25N4MW2A
MVS32N4MW2A
MVS40N4MW2A
MVS08N4NW2A
MVS10N4NW2A
MVS12N4NW2A
MVS16N4NW2A
MVS20N4NW2A
MVS25N4NW2A
MVS32N4NW2A
MVS40N4NW2A
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
MVS08N4MW5A
MVS10N4MW5A
MVS12N4MW5A
MVS16N4MW5A
MVS20N4MW5A
MVS25N4MW5A
MVS32N4MW5A
MVS40N4MW5A
MVS08N4NW5A
MVS10N4NW5A
MVS12N4NW5A
MVS16N4NW5A
MVS20N4NW5A
MVS25N4NW5A
MVS32N4NW5A
MVS40N4NW5A
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
MVS08N4MW6A
MVS10N4MW6A
MVS12N4MW6A
MVS16N4MW6A
MVS20N4MW6A
MVS25N4MW6A
MVS32N4MW6A
MVS40N4MW6A
MVS08N4NW6A
MVS10N4NW6A
MVS12N4NW6A
MVS16N4NW6A
MVS20N4NW6A
MVS25N4NW6A
MVS32N4NW6A
MVS40N4NW6A
F-5
Catalogue numbers
and order form
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
ETV2I
MVS08N3MW2V
MVS10N3MW2V
MVS12N3MW2V
MVS16N3MW2V
MVS20N3MW2V
MVS25N3MW2V
MVS32N3MW2V
MVS40N3MW2V
MVS08N3NW2V
MVS10N3NW2V
MVS12N3NW2V
MVS16N3NW2V
MVS20N3NW2V
MVS25N3NW2V
MVS32N3NW2V
MVS40N3NW2V
ETV5S
MVS08N3MW5V
MVS10N3MW5V
MVS12N3MW5V
MVS16N3MW5V
MVS20N3MW5V
MVS25N3MW5V
MVS32N3MW5V
MVS40N3MW5V
MVS08N3NW5V
MVS10N3NW5V
MVS12N3NW5V
MVS16N3NW5V
MVS20N3NW5V
MVS25N3NW5V
MVS32N3NW5V
MVS40N3NW5V
ETV6G
MVS08N3MW6V
MVS10N3MW6V
MVS12N3MW6V
MVS16N3MW6V
MVS20N3MW6V
MVS25N3MW6V
MVS32N3MW6V
MVS40N3MW6V
MVS08N3NW6V
MVS10N3NW6V
MVS12N3NW6V
MVS16N3NW6V
MVS20N3NW6V
MVS25N3NW6V
MVS32N3NW6V
MVS40N3NW6V
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
MVS08N3MW0D
MVS10N3MW0D
MVS12N3MW0D
MVS16N3MW0D
MVS20N3MW0D
MVS25N3MW0D
MVS32N3MW0D
MVS40N3MW0D
MVS08N3NW0D
MVS10N3NW0D
MVS12N3NW0D
MVS16N3NW0D
MVS20N3NW0D
MVS25N3NW0D
MVS32N3NW0D
MVS40N3NW0D
F-6
4P
ETV2I
MVS08N4MW2V
MVS10N4MW2V
MVS12N4MW2V
MVS16N4MW2V
MVS20N4MW2V
MVS25N4MW2V
MVS32N4MW2V
MVS40N4MW2V
MVS08N4NW2V
MVS10N4NW2V
MVS12N4NW2V
MVS16N4NW2V
MVS20N4NW2V
MVS25N4NW2V
MVS32N4NW2V
MVS40N4NW2V
4P
MVS08N4MW0D
MVS10N4MW0D
MVS12N4MW0D
MVS16N4MW0D
MVS20N4MW0D
MVS25N4MW0D
MVS42N4MW0D
MVS40N4MW0D
MVS08N4NW0D
MVS10N4NW0D
MVS12N4NW0D
MVS16N4NW0D
MVS20N4NW0D
MVS25N4NW0D
MVS42N4NW0D
MVS40N4NW0D
ETV5S
MVS08N4MW5V
MVS10N4MW5V
MVS12N4MW5V
MVS16N4MW5V
MVS20N4MW5V
MVS25N4MW5V
MVS32N4MW5V
MVS40N4MW5V
MVS08N4NW5V
MVS10N4NW5V
MVS12N4NW5V
MVS16N4NW5V
MVS20N4NW5V
MVS25N4NW5V
MVS32N4NW5V
MVS40N4NW5V
ETV6G
MVS08N4MW6V
MVS10N4MW6V
MVS12N4MW6V
MVS16N4MW6V
MVS20N4MW6V
MVS25N4MW6V
MVS32N4MW6V
MVS40N4MW6V
MVS08N4NW6V
MVS10N4NW6V
MVS12N4NW6V
MVS16N4NW6V
MVS20N4NW6V
MVS25N4NW6V
MVS32N4NW6V
MVS40N4NW6V
CDB500048
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
ET2I
MVS08H3MW2L
MVS10H3MW2L
MVS12H3MW2L
MVS16H3MW2L
MVS20H3MW2L
MVS25H3MW2L
MVS32H3MW2L
MVS40H3MW2L
MVS08H3NW2L
MVS10H3NW2L
MVS12H3NW2L
MVS16H3NW2L
MVS20H3NW2L
MVS25H3NW2L
MVS32H3NW2L
MVS40H3NW2L
ET5S
MVS08H3MW5L
MVS10H3MW5L
MVS12H3MW5L
MVS16H3MW5L
MVS20H3MW5L
MVS25H3MW5L
MVS32H3MW5L
MVS40H3MW5L
MVS08H3NW5L
MVS10H3NW5L
MVS12H3NW5L
MVS16H3NW5L
MVS20H3NW5L
MVS25H3NW5L
MVS32H3NW5L
MVS40H3NW5L
ET6G
MVS08H3MW6L
MVS10H3MW6L
MVS12H3MW6L
MVS16H3MW6L
MVS20H3MW6L
MVS25H3MW6L
MVS32H3MW6L
MVS40H3MW6L
MVS08H3NW6L
MVS10H3NW6L
MVS12H3NW6L
MVS16H3NW6L
MVS20H3NW6L
MVS25H3NW6L
MVS32H3NW6L
MVS40H3NW6L
Manual
Electrical
240V AC(1)
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
800A
1000A
1250A
1600A
2000A
2500A
3200A
4000A
3P
MVS08H3MW0D
MVS10H3MW0D
MVS12H3MW0D
MVS16H3MW0D
MVS20H3MW0D
MVS25H3MW0D
MVS32H3MW0D
MVS40H3MW0D
MVS08H3NW0D
MVS10H3NW0D
MVS12H3NW0D
MVS16H3NW0D
MVS20H3NW0D
MVS25H3NW0D
MVS32H3NW0D
MVS40H3NW0D
4P
ET2I
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ET5S
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
ET6G
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
4P
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
F-7
Catalogue numbers
and order form
EasyPact MVS
Connection
Connection
3P
4P
47964
47964
47966
47966
47968
47970
47965
47965
47967
47967
47969
47971
E46446
E46445
Horizontal mounting.
Installation manual
MVS21735
E46446
E46445
Horizontal mounting.
Installation manual
47964
47964
47966
47966
47968
47970
47965
47965
47967
47967
47969
47971
MVS21735
Connection accessories
F-8
48599
48600
MVS21735
48599
48600
Trip units
E95540
Battery + cover
65477
65478
67479
65577
65578
65579
MVS15501
MVS15502
MVS15503
Battery (1 part)
Cover (1 part)
33593
33592
menu
E46671
External sensors
DB105360
CDB500038
400/2000 A
1000/4000 A
34035
34036
24-30 V DC
48-60 V DC
100-125 V DC
110-130 V AC
200-240 V AC
380-415 V AC
54440
54441
54442
54443
54444
54445
33594
F-9
Catalogue numbers
and order form
EasyPact MVS
Remote operation
Remote operation
Gear motor
E95172
MCH (1 part)
AC 50/60 Hz
E95171
E95169
DC
Fixed.
100/130 V
200/240 V
380/415 V
24/30 V
48/60 V
100/125 V
200/250 V
For fixed circuit breaker
For drawout circuit breaker
Drawout.
Installation manual
E95170
E95171
E95169
Fixed.
Drawout.
E95170
E95171
E95169
F-10
Installation manual
Drawout.
MVS21736
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
380/480 V AC
For fixed circuit breaker
For drawout circuit breaker
Installation manual
Fixed.
47893
47894
47896
47888
47889
47890
47891
47074
47849
33659
33660
MVS15511
MVS15512
MVS15513
47074
47849
MVS21736
24/30 V DC, 24 V AC
48/60 V DC, 48 V AC
100/130 V AC/DC
200/250 V AC/DC
380/480 V AC
For fixed circuit breaker
For drawout circuit breaker
33659
33660
33661
33662
33664
47074
47849
MVS21736
Remote operation
E95171
E95169
E95170
Undervoltage release MN
Fixed.
E46694
MN delay unit
Drawout.
33668
33669
33670
33671
33673
47074
47849
Installation manual
MVS21736
Installation manual
48/60 V AC/DC
100/130 V AC/DC
200/250 V AC/DC
380/480 V AC/DC
33684
33685
Rr (adjustable)
33680
33681
33682
33683
MVS21736
F-11
Catalogue numbers
and order form
EasyPact MVS
Chassis locking
By padlocks
VCPO
Standard
64934
64935
42888
42878
48564
Installation manual
64937
64938
41940
41950
48564
MVS21737
47914
Installation manual
MVS21737
By Profalux keylocks
Profalux
By Ronis keylocks
Ronis
E46452
Chassis accessories
800/4000 A
3P
4P
64942
48596
Installation manual
800/4000 A
MVS21737
3P
4P
48721
48723
Installation manual
MVS21737
E46460
48591
Installation manual
MVS21737
F-12
3P
4P
48433
48434
Clusters
E95538
Clusters
33166
E95561
Racking handle
Racking handle
EasyPact MVS(3P)
N
H
NA
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
24
12
24
36
36
36
42
42
42
HA
12
12
12
12
12
12
36
42
EasyPact MVS(4P)
N
H
NA
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
32
16
32
48
48
48
56
56
56
HA
16
16
16
16
16
16
48
56
47944
F-13
EasyPact MVS
Catalogue numbers
and order form
By padlocks
48536
Installation manual
MVS21736
By Profalux keylocks
Profalux
By Ronis keylocks
Ronis
64928
64929
42888
42878
64925
64931
64932
41940
41950
64925
MVS21736
Installation manual
DB125617
48535
Installation manual
MVS21736
Escutcheon
E46670
E46669
E46668
Cover
Escutcheon
Transparent cover (IP 54)
Escutcheon blanking plate
Blanking plate
Fixed
48601
48605
Installation manual
MVS21736
CDB500058
MVS21808
Installation manual
MVS21736
E95536
47940
Installation manual
MVS21736
CDB500059
F-14
Drawout
48603
48604
48605
3P
3 x MVS21807
3 x MVS21807
4P
4 x MVS21807
4 x MVS21807
MVS21736
47926
47926
33209
Installation manual
MVS21738
CDB500060
48610
48609
48608
MVS21738
F-15
Catalogue numbers
and order form
EasyPact MVS
Indication contacts
Indication contacts
Installation manual
MVS21736
E46438
47080
47074
47849
Installation manual
MVS21736
Changeover contacts
Installation manual
F-16
47887
47074
47849
6 A - 240 V
33170
MVS21736
47849
47850
47900
Instructions
Instructions
MVS21734
MVS21735
MVS21736
MVS21737
MVS21738
F-17
EasyPact MVS
Catalogue numbers
and order form
EasyPact MVS
Date:
Product ref no:
Indication contacts
OF - ON/OFF indication contacts
Standard
1 block of 4 OF
10 A-240/380V AC
Additional
1 block of 4 OF
6 A-240/380V AC
Quantity
Standard
1 SDE
5A -240/380V AC
Optional
Rating
Carriage switches
Circuit breaker
N/ H
CE - Connected position
Max. 3
qty
Switch Disconnector
NA/HA
CT - Test position
Max. 3
qty
Number of poles
3 or 4
CD - Disconnected position
Max. 3
qty
Type of equipment
Fixed
Remote tripping
Operating Mechanism
8 A-240/380V AC
0.25s
Manual Operated
0.5s3s
Electrical Operated
400/2000A
XF - Closing coil
1000/4000A
5A-240/380V AC
Locks
2I
5S
6G
2I
5S
6G
VSPO - Device locking in OFF position by key lock (Only one key lock per ACB possible)
2I
5S
6G
Standard
0.4 to 1 Ir
Connection
Profalux
Ronis
1 key lock
Profalux
Ronis
Profalux
Ronis
Profalux
Ronis
1 key lock
Profalux
Ronis
Profalux
Ronis
Horizontal
Top
Bottom
Vertical
Top
Bottom
Accessories
VO - Safety shutters on chassis
Standard
CDP - Escutcheon
Standard
Notes:
Customer can provide only the reference no. of the product for the listed references. Kindly refer to product catalogue for list of references.
Customer to fill this order form for non-listed references.
All breakers will be provided with 1 OF (4 c/o contacts), 1 SDE (trip contact), Escutcheon (Panel sealing frame) as standard.
All draw-out type devices will be supplied with Chassis & safety shutter.
For Electrical operated devices, indicate the voltage ratings of MCH,XF & MX
Refer to product catalogue for available voltage ratings of MCH/XF/MX/MN & AD Module
The orientation of customer connecting terminals can be changed at site from Horizontal to vertical or vice-versa.
F-18
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
This document has been printed on ecological paper
Design: Schneider Electric
Photos: Schneider Electric
Printed:
06-2012