Operating and installation manual
Humidity and Temperature transmitter with
built-in PI-Control function
MF-HTT
version 3.x
Doc.No: Mi-201gb / 2009-09-18
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
NOTE !
Read the entire instruction carefully before start.
APPLICATION
MF-HTT is a humidity and temperature transmitter/controller for the measurement and indication of
relative humidity, temperature, dewpoint and mixing
ratio. With the four keys , , PGM and ESC the
desired function is selected as well as setting and
scaling is done. The dual row LCD display clearly indicates the selected function
INSTALLATION
MF-HTT is designed to be placed on a wall or for recessed mounting through a wall or cabin door.
When recessed mounting, a mounting kit,
MFM-PANEL is used. The unit is fixed to the wall by
four screws, max 4 mm. The location of the holes is
shown at the back of the enclosure.
Unscrew the four screws of the front cover and use
the bottom screws to attach the front cover on the
upper end of the casing, see Fig 1. This makes installation and electrical connection easier.
Connect power supply according to the electrical
connection.
To each front cover the CPU is mounted, since the
I/O calibration of the main circuit board is stored on
the CPU-board, it is not possible to move the front
cover between different units.
OUTPUT SIGNAL
MF-HTT has two analogue outputs to be used for
RH, Temp, dewpoint, mixing ratio and PI-controller.
VDC or mA output signal must be set by the
DIL-switch (DIL1). The same programming must
then also be done under Outputs.
C1
TREEDIV1
C19
E3
C34
C11
C30
C6
C1
E4
R24
R28
J5
D1
1 2 3 4 5
1 on, 2 off
3 on, 4 off
1 off, 2 on
3 off, 4 on
Ou
Ou
N-
N-
L+
DIL 1:
START MENU
When the power supply is connected a start menu
will be displayed. With it is possible to go
through the different start menus. To always have
the same start menu, the selection is programmed
under System settings. Pressing ESC when some
other menu is displayed returns to the menu programmed under 'Display'.
PROGRAMMING
Press PGM until displayed text disappears. Display
shows parameter group, see table on page 2.
With it is possible to scroll through the parameter groups
1. Current values
2. System settings
5. Temperature
6. Alarms
7. PIR Controller
8. Communication
DIL1
9. Internals
Output/Utsignal
1
volt output 1
volt output 2
mA output 1
mA output 2
Fig 1
Use the front cover bottom screws (marked A) to fix the front
cover at the enclosures top edge during installation.
4. Humidity
PL1
ON
3. Outputs
R18
C29
L3
2
When the parameter group to be programmed is
shown, press PGM.
The parameters are then shown, with select the
parameter to be programmed and press PGM.
Par.no:
Par name
Par.no:
Range
Preset
Par name
19 Source 1
Internals
0 Progver
0,00...9,99
20 Level 1
Current values
100 Humidity
101 Temp
0,0...100,0
-30,0...80,0
102 HR
0,0...25,0
103 Tdp
-30,0...80,0
104 PIR Out
105 PIR CSP
(99) Access code
Outputs
2 Source 1
3 Signal 1
25 Delay 2[s]
0..10V 0..10V
2..10V
0..20mA
4..20mA
-32768...32767 0,0
0...3600 0
PIR Controller
46 Source
OFF OFF
RH
TEMP
HR
TDP
47 Mode
AUTO AUTO
HAND
49 Set point
50 NZ [%]
51 P-band
52 I-time[s]
DIRECT DIRECT
REVERSE
-3276,8...3276,7 0,0
1...50 1
0,0...999,9 0,0
0...999 0
Communication
26 Address
1...247 21
4 Minval 1
-3276,8...3276,7 0,0
27 Location
5 Maxval 1
-3276,8...3276,7 100,0
28 Protocol
COMLI COMLI
6 Source 2
RH TEMP
TEMP
HR
TDP
PIR
29 Baud
600 b 4800 b
1200 b
2400 b
4800 b
9600 b
7 Signal 2
0..10V 0..10V
2..10V
0..20mA
4..20mA
8 Minval 2
-3276,8...3276,7 -30,0
9 Maxval 2
-3276,8...3276,7 80,0
Humidity
10 0% RH[V]
0,500...1,100 0,800
11 75.3%RH[V]
2,834...3,434 3,134
12 Cal Tbl
FACTORY FACTORY
USER 2P
USER 1P
13 UsrCalPt 1
0,0...100,0 0,0
14 UsrCalPt 2
0,0...100,0 75,3
15 SinglePt
0,0...100,0 0,0
Temperature
16 Temp Unit
71 Offset Adj
C C
F
K
-99,0...99,0 0,0
Alarms
18 Alarm 1
RH RH
TEMP
HR
TDP
48 Output
RH RH
TEMP
HR
TDP
PIR
0...3600 0
23 Source 2
24 Level 2
0...9999 0000
-3276,8...3276,7 0,0
OFF OFF
HIGH
LOW
-3276,8...3276,7
RH T+RH
TEMP
T+RH
T+HR
T+TDP
RH+PIR
T+PIR
HR+PIR
TDP+PIR
Preset
RH RH
TEMP
HR
TDP
22 Alarm 2
0,00...100,00
System settings
1 Display
21 Delay 1[s]
Range
OFF OFF
HIGH
LOW
30 Protect
0...32767 0
NO NO
YES
Digit programming
Every digit is separately programmed. Press for
1...9, after 9 if negative values are accepted -9...0.
Digit to be changed is flashing . When all digits are
programmed press PGM and the entire row will
flash. To stop incorrect programming press ESC
and then PGM to execute new programming.
Unit or value programming
Press to change unit/value. When selected
press PGM then the entire row will flash.
Press ESC to return to parameter group.
Press ESC to leave the parameter group and return
to start menu. NOTE ! It is always possible to cancel
an incorrect programming with the ESC-key if you
have not pressed PGM after the last digit or
unit/value selection.
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
PARAMETER LIST
1. CURRENT VALUES
100
Humidity
0,0...100,0
101
Temp
-30,0...80,0
102
HR
0,0...25,0
103
Tdp
-30,0...80,0
104
PIR Out
0,00...100,00
105
PIR CSP
-3276,8...3276,7
Displays actual values of Humidity, Temperature,
Mixing ratio, Dew point and PI-controller.
2. SYSTEM SETTINGS
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
99
(hidden)
Display
Access code
RH
TEMP
T+RH
T+HR
T+TDP
RH+PIR
T+PIR
HR+PIR
TDP+PIR
q Minval and Maxval allow scaling of the measurement range to achieve 0-100% output signal.
Measuring values Minval equals 0 % output
signal.
Measuring values Maxval equals 100% output signal.
The values for 'Minval' and 'Maxval' are entered in
their corresponding engineering units.
q Humidity = % RH
q Temperature = C / F / K.
q Mixing ratio = g / kg.
q Dew point = C / F / K.
q Control signal = %
4. HUMIDITY
10
0% RH[V]
0,500 .. 1,100
11
75.3%RH[V]
2,834 .. 3,434
12
Cal Tbl
FACTORY
USER 2P
USER 1P
13
UsrCalPt 1
0,0 .. 100,0
14
UsrCalPt 2
0,0 .. 100,0
15
SinglePt
0,0 .. 100,0
0...9999
Programme the preferred start menu under the parameter 'Display'.
For activating or inactivating the Key lock function in
parameter 'Access code', see page 7.
Source 1
Signal 1
0..10V
2..10V
0..20mA
4..20mA
Minval 1
-3276,8...3276,7
Calibration of the Humidity Sensor
HTT is equipped with a humidity sensor with an accuracy of +/- 2% RH.
The sensor is delivered with a calibration protocol
which state two reference voltage values which are
programmed in parameters '0% RH' and
'75,3% RH'.
Calibration table FACTORY must have been selected.
If the sensor is exchanged the new reference values
for the new sensor are programmed for 0 % RH and
75.3 % RH.
Maxval 1
-3276,8...3276,7
NOTE Save the sensor calibration protocol.
Source 2
RH
TEMP
HR
TDP
PIR
Signal 2
3. OUTPUTS
RH
TEMP
HR
TDP
PIR
0..10V
2..10V
0..20mA
4..20mA
Minval 2
-3276,8...3276,7
Maxval 2
-3276,8...3276,7
Calibration tables
MF-HTT include three tables to store different calibrations, default calibration table 'FACTORY' and
two user programmable tables 'USER 2P' and
'USER 1P' for field calibration.
Factory calibration
The table 'FACTORY' must be selected to apply the
calibration from factory.
Select engineering unit, type of output signal and
scaling for both Output 1 and Output 2.
q Source determines the source used for the
output signal (Humidity RH, Temperature
TEMP, Mixing ratio HR or Dew point TDP).
q Signal determines the type of output signal to
be used for the output (Volt/mA).
Note ! In addition to the programmed output signal, the DIL-switch on the main circuit board
must be set for the same output type.
3
2 point calibration:
Normally this type of calibration is done with a salt
solution with predefined humidity content.
q Select Cal Tbl = USER 2 P
q Place the probe in a chamber with defined humidity for the lower calibration point.
q Programme the defined value in % RH into the
parameter UsrCalPt1.
When programming is finished by pressing the
PGM-key the calibration starts for the lower calibration point.
It is important that the sensor is exposed to the
same humidity level during the entire measuring cycle that is programmed in UsrCalPt 1.
1 point calibration:
This type of calibration is possible to do with a reference instrument or similar
q Select Cal Tbl = USER 1P
q Programme the parameter SinglePt with the
value in % RH indicated by the reference instrument.
q When programming is finished by pressing the
PGM-key the calibration starts.
The text Calibration-Measuring is shown
Calibration
Measuring
When Calibration is completed the following display
appear.
The text Calibration-Measuring is shown.
Calibration
Measuring
When Calibration for the lower calibration point is
completed the following display appear.
Calibration
DONE
Continue with the higher calibration point
q Place the probe in a chamber with defined humidity for the higher calibration point.
q Programme the defined value in % RH into the
parameter UsrCalPt2.
When programming is finished by pressing the
PGM-key the calibration starts for the higher calibration point. Display during calibration is the same
as described for the lower point.
Each point can be recalibrated separately if necessary.
Calibration
DONE
All three calibration tables are stored separately
which makes it possible to switch between the tables if they have been programmed with valid data.
5. TEMPERATURE
16
Temp Unit
C
F
K
71
Offset Adj
-99,0 .. 99,0
Select the preferred unit for temperature.
Under certain conditions the indicated temperature
may differ from a reference measurement reading.
By programming the difference in parameter 'Offset
Adj' the HTTs reading can be adjusted to conform
with the reference measurement.
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
Field calibration
HTT may be calibrated in field during operation.
Calibration may be performed in 1 or 2 calibration
points.
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
6. ALARMS
18
Alarm 1
OFF
HIGH
LOW
19
Source1
RH
TEMP
HR
TDP
20
Level 1
21
Delay 1[s]
22
Alarm 2
OFF
HIGH
LOW
23
Source2
RH
TEMP
HR
TDP
24
Level 2
25
Delay 2[s]
4.
Enter a suitable value for the desired set point
in parameter "Set point".
5.
To achieve a stable control around the set
point, a neutral zone, NZ, can be programmed. Min value is 1% of the selected
source range. The neutral zone is equal on
both sides of the set point.
6.
Select a suitable value for the "P-band". If the
value is set to 0 %, the P-band is deselected
and the I-time is calculated using a P-band of
100 %.
7.
Enter a suitable I-time in seconds in parameter "I-time", 0...999 seconds.
-3276,8 .. 3276,7
0 .. 3600
-32768 .. 32767
Manual operation of the PI-controller
Manual operation is selected in the start menu.
Scroll using the -keys until HAND/AUTO
menu is displayed.
0 .. 3600
The MF-HTT is equipped with a visual alarm.
The alarm is indicated in normal state with a green
light emitting diode (LED) and in alarm state with a
red LED. There are two separate alarms for high or
low limit with a separate time delay function in each
one.
If both alarm are used the red LED will lit when the
first alarm state occurs.
In alarm state the red LED is lit and when the time
delay has passed the LED starts flashing.
7. PIR CONTROLLER
46
Source
OFF
RH
TEMP
HR
TDP
47
Mode
AUTO
HAND
48
Output
49
Set point
50
NZ [%]
1...50
51
P-band
0,0...999,9
52
I-time[s]
Humidity 38.2 %
AUTO
28.18 %
The top row display the control source and value and
on the bottom row display HAND or AUTO together with the current control output signal.
Press the PGM-key to switch between HAND and
AUTO position.
Press the ESC-key to select an other view, the manual operation mode is still active.
HAND/AUTO -mode can also be turned On and Off
by programming parameter "Mode" in parameter
group "PIR Controller".
DIRECT
REVERSE
-3276,8...3276,7
0...999
MF-HTT with programme version 3.x or later is
equipped with a PI-control function for one selected
measuring value. The PI-controller output signal is
selected in parameter group "Outputs".
1.
Select source, "Source", for the controller.
The source can be RH, TEMP, HR or TDP.
2.
Select "Hand" or "Auto" in parameter "Mode"
3.
Select the direction for the output signal in
group "Outputs", it can be either DIRECT or
REVERSE.
e.g. Selecting REVERSE will result in a decreasing control signal if the actual value is
above the set point value.
Display text:
RH = Humidity %
HR = Mixing ratio g/kg
Temp = Temperature C, K, F Tdp = Dewpoint C, K, F
Humidity 48.5 %
Temp
23.4 C
Scroll in the opposite direction
Scroll between start menus
Humidity 48.5 %
HR
8.6 g/kg
Humidity 48.5 %
11.7 C
Tdp
AB MICATRONE
Humidity 48.5 %
AB MICATRONE
Temp
23.4 C
Note. Serial number is also visible when scrolling the different start menus
MF-HTT
PROGRAM-MENU
Press key until text MF-HTT PROGRAM-MENU is displayed
Current values
Scroll between parameter groups
Temperature
Scroll in the opposite direction
example
System settings
Outputs
Alarms
PIR Controller
Humidity
Communication
Internals
example
Outputs
Source 1
RH
Outputs
Signal 1
0-10V
Outputs
Minval 1
010,0
Outputs
Maxval 1
090,0
MF-HTT
(PGM) Opens parameter group and allows the parameters to be selected.
Changes between the parameters
according to the parameter list.
(PGM)
Programming position for Unit/Value (Flashes).
Selection of Unit/Value.
(PGM)
Programming of new value. Parameter Unit/Value is flashing.
When programming a number value, each digit is
programmed seperately, until all digits have stopped flashing.
(ESC)
Leaves parameters and returns to Parameter group.
(ESC)
Leaves the parameter group and returns to startmenu.
Always note the programmed data beside the parameter
in the programming protocol for future reference
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
(PGM)
KEY LOCK
Key lock is a hidden parameter if the function is activated and no code has been entered. This function
is available from program version 2.10 or higher.
3. The first digit (0) is flashing to indicate that the
first digit of the code must be entered by using
the arrow-keys. Press the PGM-key to jump to
the second digit, etc.
The key lock is to be used when then transmitters
settings must be protected from unwanted alteration. The 4-digit code must be entered before accessing the program and function menu. For
Micaflex with built-in control function the code must
also be entered to switch between AUTO and
HAND operation.
4. When all four digits are entered press a final
time the PGM-key. The entered code is now
compared with the settings in the parameter
'Access code'. If they match the program menu
is accessed.
Current values
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
Indication of the measured values and operating
state is accessible without entering the code.
At delivery the code is programmed to "0000" unless nothing else is agreed to. With factory default
code "0000" the key lock is in-active. I.e no protection for alternating the settings.
Activating the key lock
To activate the key lock settings must be programmed into the parameter 'Access code' which is
found below the parameter group 'System settings'.
The code must be different from "0000" unless the
lock will be in-active. After programming a 4-digit
code into the parameter this code must be used to
access the program and function menus.
In-activating the key lock
The key lock can be in-activated by setting the value
of parameter 'Access code' to "0000". Since the setting is done from the program menu the already
programmed code must be known to inactivate the
key lock.
Contact Micatrone if the code has been lost!
Entering code
To access the program or function menu or to switch
between AUTO-HAND function the code must be
entered.
Example to access the program menu:
1. Press the PGM-key to open the program menu.
Keep the key pressed until following screen appears.
MF-xxx
PROGRAM-MENU
The menu is accessible until the ESC-key is
pressed one or several times and the preset
start menu is displayed. Example:
AB MICATRONE
Temp
23.4 C
5. If the code does not match the programmed settings following screen appears
INVALID CODE
PROGRAM-MENU
for a period of 2 second before shifting to the
"Enter code" screen again.
ENTER CODE: 0***
PROGRAM-MENU
6. By pressing the ESC-key during the operations
the programming of the code is aborted and the
preset start menu is displayed.
AB MICATRONE
Temp
23.4 C
Instead of the text 'xxx' the actual model for the
present type is indicated.
2. Release the PGM-key. If the key lock is activated the following screen appears.
ENTER CODE: 0***
PROGRAM-MENU
Power supply:
Power
consumption:
Measurement range,
- Temp:
- Humidity
- Dew point:
- Mixing ratio:
Accuracy,
- Humidity:
- RH stability:
Temperature:
Response time:
Outputs:
Ambient
temperature:
Alarm (visible):
Housing class:
Electric connections,
- rigid wire:
- flexible wire:
Cable entry:
Dimensions[WxHxD]:
Weight:
Alphanumeric LCD
2 rows, 2x16 characters
24 15 % VAC
20...32 VDC
Max 3 VA (24 VAC)
-30...80 C
0...100 % not condensing
-30...80 C
0...25 g/kg
2 % RH
1 % typical at 50% RH
in 5 year
0.3 C
30 seconds in slow moving
air
Two analogue outputs
0/2...10 VDC, 0/4...20 mA
selectable and scalable
0...50 C
Two separate alarms,
high&low
Red LED alarm indication
IP 65
DELIVERY OPTIONS SENSOR MF-HTT:
Art no
Probe
Cable
Note
60-5462-1
100 mm
0m
"ROOM SENSOR"
60-5462-20
100 mm
2m
60-5462-21
200 mm
2m
60-5462-30
100 mm
5m
60-5462-31
200 mm
5m
60-5462-40
100 mm
10 m
60-5462-41
200 mm
10 m
ACCESSORIES
q Duct mounting plate
q Wall mounting bracket
q Kit for recessed mounting
q External transformer 24, 115, 230 VAC
1 x 2.5 mm2 / terminal
1 x 1.5 mm2 / terminal
2 pcs M16x1.5mm
(cable glands not included)
120 x 122 x 60 mm
0.5 kg
ELECTRICAL CONNECTION
24 VAC, 20...32 VDC
34
35
GREEN+SHIELD [AGND]
GREY [+PT]
33
BROWN [+RH]
32
WHITE [+5V]
31
YELLOW [-PT]
Nt
Out 2
N-
ELECTRICAL CONNECTION
Sensor
Out 1
24 VAC
20...32 VDC
8
SERVICE
Measurement in dirty applications, clean the
sintered filter.
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
TECHNICAL DATA
Indicator:
60.0
52.0
30,0
52.0
60,0
40,0
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
MOUNTING KITS
Duct mounting kit
Wall mounting kit
90 (x4)
mm.
2,8 (x4)
22
mm.
4,0 (x3)
AB MICATRONE 2009-09-18 [H:\ Apps \ Typeset \ Mima \ mi-201gb_090918.vp]
AB Micatrone
ldermansvgen 3
SE-171 48 SOLNA
SWEDEN
Telephone:
Fax:
Internet:
E-mail:
+46 8-470 25 00
+46 8-470 25 99
www.micatrone.se