Relequick is a Spanish company founded in 2003 with 100% Spanish capital,
dedicated to the design, manufacture and sales of systems and electrical
and electronic components, as well as state of the art software for the
control of their products, mainly in the market for industrial automation.
Currently, it has a wide range of over 900 different products developed
and manufactured according to the highest international standards and
approved by the appropriate agencies within each sector in which we
operate, in particular, IEC, VDE, CE , RoHS, UL, ISO-9000, etc..
Innovation is one of the basic pillars of Relequick culture that deeply marks
all its business areas to achieve the highest levels of efficiency, quality and
respect for the environment.
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Index
1.- Relays and socket "T" series
3 - General characteristics
5 - RM-T relays, SM-T sockets
7 - RQ-T relays, SQ-T sockets
9 - RF-T relays, SF-T sockets
11 - RF-PT relays
12 - RVS relays, SVB sockets
13 - RM-FT Power relays
15 - RPA Power relays
2.- Relays and socket Standard series
17 - RM relays, SM sockets
19 - RQ relays, SQ sockets
21 - RF relays, SF sockets
3.- Solid state relays and heat sinks
25 - Zero crossing AC single phase
26 - Random AC single phase
27 - Solid state relay DC single phase
28 - Solid state relays angle switching
29 - DIN single phase solid state relays
30 - Power solid state relays
31 - PCB single phase relays
32 - PCB Single phase power relays
33 - Three phase relays
34 - Motor reversing relays
35 - Heat sinks
4.- Modules and monitoring relays
39 - RFS1SL Programable solid state relays
40 - MQPMM timer and counter module
41 - Slimline timer
42 - Modules standard for SQ/SF
43 - Current moniroting relay
44 - Three phases monitoring relay
45 - GSM modules
47 - Software Devices Programmer
49 - Programmable functions
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
General information
Implementation Rules
In the design and fabrication of Relequick S.A. products described
in this catalog it has been taken into account the European and
International standards (International Electronic Commission)
applicable in each case:
IEC/EN 61810-1, IEC/EN 61810-2, IEC/EN 61810-7 (relays);
IEC/EN 61812-1 (timers);
IEC/EN 60669-1 and IEC/EN 60669-2-1 (control relays, etc);
IEC/EN 50178 (Industrial Use);
IEC/EN 61810-1(thermal conditions, etc.)
Quick-clamp quick connection: The conductor is clamped by
force of a spring made of steel plate without the need for screws.
Compliance with RoHS Directive: RoHS is the acronym for "Restriction
of Hazardous Substances"), European Directive 2002/95/EC of
27.01.2003 regulating substances under restrictions: Lead, Mercury,
Hexavalent Chromium, Polybrominated Biphenyls (PBB),
Polibromobifenilteres (PBDEs), Cadmium (Having exceptions on
contact materials).
Electromechanical relays
General characteristics
Contact specifications
Continuous Operation: Permanent connection of the coil up to
balance thermal relay.
Nomenclature of contacts:
Contatc normally open (Europe = NO, GB = A, USA = n * PST-NO)
Contact normally closed (Europe = NC, GB = B, USA = n * PST-NC)
Changeover contact (Europe = CO, GB = C, USA = n * PDT)
n* = number of poles (single = 1, double = 2, etc)
Electrical life: Represents the duration of normal use of the relay
with a rated resistive load at nominal current AC1 specified for
that relay and a voltage of 250 VAC.
Mechanical life: If the load on the relay contacts is very low
electrical life can approach to mechanical life.
Operating time: Average time (once the coil is energized) until the
closing of NO contact.
Release time: Average time (once the coil has been de-energized)
to the NC contact closure relay changeover contacts, or up to
the opening of NO contact on a open contacts relay.
Ambient temperature: The temperature of the environment in
which the relay can work.
Storage temperature: Room temperature with upper and lower
limits extended by about 10 C.
Protection category: according to EN 60529.
IP 00 = No protection.
IP40 = Protected against solid foreign objects of 1 mm or greater.
No protection against the entry of water.
IP50 = Dust protection in an amount or in some places that may
impair the proper functioning of the relay.
No protection against the entry of water.
IP54 = As IP 50, but protected against splashing water
(limited penetration is allowed).
IP67 = Total protection against dust and protected against the
effects of temporary immersion in water.
Isolation areas: For electromechanical relays isolation areas to
consider are according to IEC 61810-1:
The isolation between the coil and all contacts.
The separation between adjacent contacts in a multipolar relay.
Pollution degree: The EN50178 imposes a pollution degree of 2 to
electronic equipment in power installations. The degree of pollution
2 and 3 are normally required to relays:
1 Without pollution or dry non-conductive pollution.
2 There is only non-conductive pollution.
3 Conductive pollution occurs or dry pollution that becomes
conductive due to condensation.
4 Pollution generates conductivity which is maintained due to dust
that is conductive or atmospheric agents.
Nominal current: Is the highest current that a contact can lead
permanently without exceeding the heating limits and coincides
with the maximum operating current.
Maximum peak current: Is the higher current than the contact can
make for less than second and with a lower RI intermittence 10%
without any degradation.
Nominal voltage: Is the switching voltage associated with the rated
current that determines the rated load AC1.
Maximum switching voltage: The maximum voltage level that can
switch contacts and that can ensure the isolation distances specified
by the rules.
Rated load AC1: The maximum power switchable by contact, for
a resistive load on AC that is able to connect and disconnect
repeatedly. It is used in the tests on electrical life.
Contact resistance: The Ohmic resistance measured between the
contacts of the relay.
Contact material: The alloy of which are made of relay contacts,
normally usually AgNi (PlataNiquel) AgCdO (Silver Cadmium Oxide),
AgSnO2 (Silver Tin Oxide).
Characteristics of the coils
Nominal supply voltage: Voltage planned to be supplied in the coil
of the relay design.
Rated power: Is the DC power on W or the AC apparent power on
VA consumed by coil when is energized with the nominal voltage
at an ambient temperature of 25 C.
Operating range: According to EN 61810-1 our relays are classified
into Class 1: (0.8 ... 1.1) A, both relays with AC coils, like DC, within
the temperature range covered by the standard.
Rated coil resistance: Is the ohmic resistance of the coil (within a
tolerance of 10%) at 25 C ambient temperature.
(02410413)
Vibration Resistance: According To IEC 60068-2-6 The maximum
value of acceleration g can be applied to an relay without opening
contact.
Torque: According to EN 60999 refers to the maximum torque
supported by terminal screws connection on Nm.
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Products features standard information
Solid state relays
Repeatability: Is the maximum difference between two results
obtained by making a sufficient sample time measurements on
specific conditions that can be attributed to the accuracy of the
test method, and that it is given as mean value.
General characteristics
Description: A solid state relay (SSR) is an electronic switch,
that doesnt contains any moving parts. The charging current
is conducted by one or more semiconductors such as
transistors and thyristors or triacs in substitution of metal
contacts. Used for controlling high power loads signals starting
from low voltage control and intensity. Solid state relays are
widely used in test instruments, monitors, appliances, cars, etc.
Time precision Is the absolute percentage error is expressed in % of
the peak value it measures the instrument, and also expressed in %
with respect to the difference between maximum and minimum
value measurable.
Reestablishment time The minimun time necesary before re.starting
the timer function.
In comparison to electromechanical relays are lighter, quieter,
faster and more reliable, do not wear, are immune to shock
and vibration, generate very little interference, switch high
currents and voltages without producing arcs, provide several
kilovolts of isolation between input and output.
Control modules
Three phase monitoring module
Opto-coupler: The opto-coupler in all our solid state relays,
ensures electrical isolation between input and output circuits.
Voltage reading range: Is the read range of voltage that the
module can detect and monitor.
Minimum switching current: Is the minimum current required to
make a proper load switching.
Percentage of asymmetry: It Is given in % and represents the
theoretical phase shift distance of 120 between the phase-phase
phasors voltage on a three-phase.
Maximum load current: Maximum current that can
continuously pass through output terminals using a specific
heatsink.
Hysteresis: Is a % of the value which has been established below
which the control module is reset.
Zero crossing: Circuit which starts the operation when the
voltage at the AC load has a value close to zero.
Current monitoring module.
Current reading range: Is the read range of current that the
module can detect and monitor.
Control current: Is the nominal input current at 23 C for the
rated voltage.
Lock Time: Is the delay time of alarm activation after current
exceeded the set threshold.
Timers
Switch-on delay: this refers to the time taken for the output relay to
energise, following the detection of conditions requiring this.
General characteristics
Timing Adjustment: These are the values that can be established specific timed using timescales of the product or making
a program on it.
Key references
RQ S 4 0 L 230 AC D T
M series
M series
Q series
Q series
Q series
F series
F series
Product series
Type
Contacts number
Contacts material
Led
Coil voltaje
Coil circuit
Series executions
Type
Contact material
S: Change-over
Silver alloy
Standard fol all models
Sockets
SQ B 4 0 D
Model
B: screw terminal
R: Quick Clamp
C: PCB
SFMFRVJDL!T/B/!!
universal 8 pins
universal 11 pins
miniature
miniature
miniature
interface
interface
2 contacts
3 contacts
1 contact
2 contacts
4 contacts
1 contact
2 contacts
Circuit connected to coil
0: without circuit
D: with diode, only DC
8 pins
11 pins
8 faston
8 faston
14 faston
5 faston
8 faston
RVS10N(--)V000 PCB relay *
SVB10D010(---) interface socket 6,2mm **
SVB10D010000V PCB socket weld-on 6,2mm
SVB10D000000V Separator accesory
Connection bridge for SVG
AVP
sockets
MTV
Label for laser marking
* (--) 5/6/9/12/24/48/60 coil voltage
** (---)012/024/110/240 Input voltage
Special executions
0: without special
T: T series
Modules
Details of the references for sockets
M series
M series
Q series
Q series
F series
F series
Colour
0: Relequick grey colour
1: Black
RMS2
RMS3
RQS1
RQS2
RQS4
RFS1
RFS2
Luminous indication
L: with led
N without led
0 0 0
Product series
Model
Contacts number
Colour
Montage type
Form
Module insertion
Range
Slimline relay
Details of the references for relays
SMS2
SMS3
SQS2
SQS4
SFS1
SFS2
Montage type
D: DIN rail 35 mm
C: weld-on PCB
universal 8 pins
universal 11 pins
miniature
miniature
Interface
Interface
Form
0: Interface
1: Standard
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
2 contacts
8 pins
3 contacts
11 pins
1-2 contacts
8 faston
4 contacts
14 pins
1 contacts 5 faston or pins
2 contacts 8 faston or pins
Module insertion
0: yes
1: No
Tel: + 34 91 812 42 84
Range
0: Standard
T: T series
Fax: +34 91 817 85 65
SVT10D010024V SlimLine programmable timer
MQPMM
MMA10
M(--)Q
M(--)F
Programmable multifunction &
mulltivoltage module Q series
Module interface to connect
the MQPMM in the SM sockets
Indication and protection
modules Q series
Indication and protection
modules F series
RFS1SL028(---) Programmable solid state relay
MCU(--)R2
Current control module
MPH(--)R1
Three phase control module
E-mail: info@relequick.com
www.relequick.com
(02410413)
Relays
Relays RM-T series
Features
Universal power relay for general applications.
Available in 2 & 3 change-over contacts with max. current
10 A - 250 VAC1 / 28 VDC1.
Nominal power 1,5 W(DC) & 2,7 VAC.
Available with and without LED for AC/DC relays. Diode only
available for DC.
Socket terminals, 8 pins plug-in for 2 contacts and 11 pins
plug in for 3 contacts.
Insulation: IEC61810-1 - 2,5 KV/3.
Pollution degree: 2.
Approvals: CE, UL.
Protection class: IP40.
European Patent.
Coil ratings
60
Nominal voltage VDC
6 12 24
48
115
Resistance ( 15%) 28,4 100 430 1,5k 2,33K 8,1K
60
Nominal voltage VAC
6 12 24
48
120
4.2 19,5 73,6 284
1,5K
Resistance ( 15%)
220
32,6K
230
6,3K
Coil values at 25C
VDC
0,8 -1,1 Un
15% Un
Operating range
Max. drop-out voltaje
VAC 50HZ
0,8 -1,1 Un
30% Un
Contacts
RMS2-T Relay 8 pins 2 contacts
RMS3-T Relay 11 pins
Wiring diagram RMS2-T
Wiring diagram RMS3-T
Dimensions RMS2-T
33,4 [1.31]
Dimensions RMS3-T
33,4 [1.31]
34,2 [1.34]
2,
8
2,
8
[.1
1
[.1
1
34,2 [1.34]
34,2 [1.34]
52,1 [2.05]
34,2 [1.34]
52,1 [2.05]
3 contacts
Coil temperature
Electrical life
Product series
RM: RM relays series
Type
E: without button
S: with button
(02410413)
Contacts number
2: 2 contacts
3: 3 contacts
Contact material
0: silver alloy
SFMFRVJDL!T/B/!!
Led
L: with LED
N: without LED
Contact arrangement: 2C & 3C.
Max. contact power: 2500 VA / 280 W.
Max. voltage: 250 VAC / 220 DC1.
Max. current:10A ( 250 VAC1 / 28VDC1).
Maximum breaking capacity: 110V DC ---> 0,4A
220V DC ---> 0,15-0,20A
Contact resistance: 50 m.
Contact material: Silver alloy ( AgNi ).
Specification RM
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000M(500VDC)
30ms
1200op/h at nominal load
20ms
2.500VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Atmospheric pressure
Weight
Pack units
10 - 50Hz (Double width 1,5mm)
10g
-40 C +65 C
35% -85% RH
86 - 106 KPa
80 gr
20
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
220: 220V (only DC)
230: 230V (only AC)
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Series features
T: T series
Circuit connect to coil
0: without circuit
D: with diode (only DC)
Coil version
AC: VAC voltage
DC: VDC voltage
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Sockets SM-T series
Features
DIN rail (35 mm, t35) or panel mounting (EN 60715).
DIN/EN sequential numbering.
IEC / EN 61812/1/4 compliant.
Clip and label included.
Electronic modules allowed.
Specifications SMB2-T and SMB3-T
Nominal load
SMB3-T Socket
SMB2-T Socket
Wiring diagram SMB2-T
10 A / 400 VAC
Dielectric strength (Vrms/1min)
Wiring diagram SMB3-T
2,5 KV
Max. screw torque
1,2 Nm
Screws
M3 Steel. Pozi drive
4 mm2 or 2 x 2,25 mm2
Wire in lets capacity: solid wire
Wire in lets capacity: multi-core
Dimensions SMB2-T
22 14 AWG
MAX (1X12 /2X14 AWG)
Weight
Dimensions SMB3-T
60gr
Room temperature
-40C to 70C
Pack Units
,3
[
75 [2.94]
61,8 [2.43]
,3
[ .1
50gr
3]
25,9 [1.02]
38,4 [1.51]
3,7
5
[.1
4,
3
[.1
7]
35 [1.38]
37,1 [1.46]
3,
4 ,3
[.1
7]
5]
[.1
28 [1.09]
25,9 [1.02]
37,1 [1.46]
Weight
61,8 [2.43]
35 [1.37]
38,4 [1.51]
SMB2-T & SMB3-T (short sockets)
29 [1.15]
37 [1.47]
.13
]
IP 20
28 [1.11]
37 [1.47]
35 [1.36]
26 [1.02]
29 [1.15]
37 [1.46]
75 [2.94]
10
Protection category
37 [1.46]
26 [1.02]
35 [1.36]
References socket SMB-T
SMB21D10T
SMB21D11T
Long sockets for RM2 black
Short sockets for RM2 black
SMB20D11T
Short sockets for RM2 grey
SMB31D10T
Long sockets for RM3 black
SMB31D11T
Short sockets for RM3 black
SMB30D11T
Short sockets for RM3 grey
Accesories for relays
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: +34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
(02410413)
Mechanical indication and a wide window.
3-sequential-position test button (free, check, lock).
With colours for an easier identification of coil voltage
(DC Blue, AC Red).
Technical information and coil voltage in frontal side printed.
Relays RQ-T series
Features
Miniature power relays for general and industrial
applications. Available in 1 and 2 change-over contacts
with max. current 16 A - 250 VAC/30 VDC and 10 A - 250
VAC/30 VDC and in 4 change-over with max. current 5 A 250 VAC/30 VDC (AC1/DC1), (1, 2, 4 PDT) contacts.
Nominal coil power 0,9 W(DC) & 1.5 VAC.
Available with and without LED for AC and DC. Diode only
available for DC.
Insulation: IEC61810-1 - 2,5 Kv/3.
Pollution degree 2.
Plug-in terminal faston 1 and 2 contacts (4,8 mm). 4-contact
version with plug-in faston (2,6 mm).
Approvals: CE, UL.
Protection class : IP40
European Patent.
Coil ratings
Nominal voltage VDC
6
40
Resistance ( 15%)
Nominal voltage VAC
6
Resistance ( 15%) 11,5
12
160
12
40
60
24
48
115
220
650 2,6K 3,2K 13,8K 52,3K
60
24
48
120
230
160 700 1,06K 3,6K 12,4K
Coil values at 25C
Wiring diagram RQS1-T
RQS2-T
Relay 2 contacts
Wiring diagram RQS2-T
Dimensions RQS1-T & RQS2-T
35,4 [1.39]
27 [1.08]
35,5 [1.40]
(02410413)
Type
E: without button
S: with button
SFMFRVJDL!T/B/!!
Contacts
Electrical life RQS4-T
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
220: 220V (only DC)
230: 230V (only AC)
Product series
RQ: RQ relays series
Contact material
0: silver alloy
VAC 50HZ
0,8 -1,1 Un
30% Un
105 cycles
Electrical life
Mechanical life
107 cycles
Insulation resistance
1000M(500VDC)
Operation time
20ms
Operation frequency
1200op/h at nominal load
Release time
20ms
Dielectric strength at 1mA in 1 & 2 contacts
2.000VAC/min(between coil and contacts)
1.200VAC/min(between contacts)
Dielectric strength at 1mA in 4 contacts
1.800VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
10 - 50Hz (Double width 1,5mm)
Shock resistance
10g
Room temperature
-40 C +65 C
Room humidity
35% -85% RH
Armospheric pressure
86 - 106 KPa
Weight
35gr
Pack units
20
Coil temperature RQS4-T
Electrical life RQS1-T & RQS2-T
VDC
0,75 -1,1 Un
10% Un
Specifications RQ-T
2,6 [.10]
Coil temperature RQS1-T & RQS2-T
Operating range
Max. drop-out voltage
Contact arrangement: 1C, 2C and 4C.
Maximum contact power:(230 VAC1/25VDC1)
1C: 4.000 VA / 480 W
1C (1PDT)
2C: 2.500 VA / 300 W
2C (DPDT)
4C: 1.250 VA / 150 W
4C (4PDT)
Maximum voltage: 250VAC, 220VDC.
Maximum current: 16A(1C), 10A(2C), 5A(3C)
(250VAC1/28VDC1)
Maximum breaking capacity: 110V DC ---> 0,4A
220V DC ---> 0,15-0,20A
Contact resistance: 50m.
Contact material: Silver alloy( AgNi).
20,8 [.82]
4,8 [.19]
Wiring diagram RQS4-T
Dimensions RQS4-T
20,8 [.82]
Contacts number
2: 2 contacts
3: 3 contacts
4: 4 contacts
RQS4-T
Relay 4 contacts
28 [1.08]
RQS1-T
Relay 1 contact
Series features
T: T series
Circuit connect to coil
0: without circuit
D: with diode (only DC)
Coil version
AC: VAC voltage
DC: VDC voltage
Led
L: with LED
N: without LED
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Sockets SQ-T series
Features
Interface I/O (Input/Output).
Interchangeable marked labels and clip integrated.
DIN rail (35 mm, T35) or panel mount (EN 60715).
Connection bridges for A2 terminals.
Electronic modules connection.
3-position clip for the subjection to DIN rail.
DIN and sequential numbering(optional).
IEC/EN 61812/1/4 compliant.
Specifications SQB20-T and SQB40-T
SQB2-T
SQB4-T
Socket
Wiring diagram SQB2-T
The SQ-T sockets are produced with module insertion.
Socket
Nominal load
Wiring diagram SQB4-T
16A (SQB2-T); 10A (SQB4-T) 250V
Dielectric strength Vrms/1min
2,5 KV
Max. screw torque
Dimensions SQB2-T
Dimensions SQB4-T interface
1,2 Nm
Screws
M3 Steel. Pozi drive
Wire in lets capacity: solid wire
4 mm2 or 2 x 2,25 mm2
77 [3.01]
Weight
61 [2.39]
46,4 [1.83]
Room temperature
35 [1.39]
35 [1.38]
3,7 [.14]
27 [1.06]
23 [.91]
27 [1.06]
3,6 [.14]
-40C to 70C
10
Protection category
IP 20
Weld-on PCB socket SQC
38 [1.50]
37,4 [1.47]
Weight
83 [3.28]
75 [2.96]
1gr
Pack Units
81 [3.17]
Dimensions SQB4-T
21 [.82]
12 [.46]
25 [.98]
30
43 [1.69]
Dimensions SQC2-T & SQC4-T
28 [1.11]
22 14 AWG
71gr
Pack Units
19 [.75]
81 [3.17]
Wire in lets capacity: multi-core
35 [1.37]
24 [.95]
27 [1.06]
3,8 [.15]
37 [1.47]
75 [2.96]
References
SQB21D10T
Socket for relays 1-2 contacts black
SQB20D10T
Socket for relays 1-2 contacts grey
SQB41D10T
Socket for relays 4 contacts black
SQB40D10T
Socket for relays 4 contacts grey
SQB41D00T
Interface socket for relays 4 contacts black
SQB40D00T
Interface socket for relays 4 contacts grey
SQC21C11T
Weld-on PCB socket for relays 2 contacts black
SQC41C11T
Weld-on PCB socket for relays 4 contacts black
Accessories for relays
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
(02410413)
Led and Mechanical indication and a wide window.
3-sequential-position test button (free, check, lock).
With colours for an easier identification of coil voltage
(DC Blue, AC Red).
Technical information and coil voltage printed in frontal side.
Relays RF-T series
Features
Industrial interface relay for general applications. Available
in 1 & 2 change-over contacts with max. current 10 &16 A
- 250VAC1/30VDC1 and 5A & 8 A - 250 VAC1/30VDC1.
Coil nominal power DC 0,53 W & AC 1,1 VA.
Available with or without led for AC/DC relays.
Diode only available in DC.
Insulation: IEC61810-1 - 2,5 Kv/3.
Pollution degree 2.
Socket 187 (4,75 mm)terminals.
Approvals: CE, UL.
Protection class: IP40.
European Patent.
Coil ratings
Nominal voltage VDC
Resistance ( 10%)
Nominal voltage VAC
Resistance ( 10%)
6
68
6
17
12
259
12
63
24
939
24
250
48
115
4,2K 20,9K
48
120
1,1K 5,17K
230
20K
Coil values at 25 C
Operating range
Max. drop-out voltage
RFS2-T
Relay 1 contact
Wiring diagram RFS1-T
Wiring diagram RFS2-T
Dimensions RFS1-T
Dimensions RFS2-T
27 [1.06]
5 [.20]
5 [.20]
5 [.20]
Coil temperature RFS1-T
Electrical life RFS1-T
Coil temperature RFS2-T
Electrical life RFS2-T
Type
S: change-over
standard for all models
(02410413)
SFMFRVJDL!T/B/!!
Contact resistance: 50 m.
Contact material: Silver alloy (AgNi).
Specifications RF-T
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000M(500VDC)
20ms
1200op/h at nominal load
10ms
5.000VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
Pack units
10 - 50Hz (Double width 1,5mm)
10g
-40 C +65 C
35% -85% RH
86 - 106 KPa
20gr
50
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
230: 230V (only AC)
Product series
RF: RF relays series
Contacts number
1: 1 contact
2: 2 contacts
Contact arrangement: 1C and 2C.
Maximum contact power(230VAC1/28VDC1): 1C:2.500
VA / 300 W, 2C: 1.250VA / 150W.
Maximum voltage: 250 VAC / 220 VDC.
Maximum current: 10 A & 16A 1C and 8 A & 5A 2C
AC1/DC1
Maximum breaking capacity: 110V DC ---> 0,4A
220V DC ---> 0,15-0,20A
29 [1.13]
13 [.49]
5 [.18]
27 [1.06]
29 [1.14]
Contact material
0: silver alloy
VAC 50HZ
0,8 -1,1 Un
30% Un
Contacts
Relay 2 contacts
13 [.49]
RFS1-T
VDC
0,75 -1,1 Un
10% Un
Series features
T: T series
Power Version
0: standard power (10A - 5A)
H: hight power (16A - 8A)
Coil version
AC: VAC voltage
DC: VDC voltage
Led
N: without led
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Socket SF-T series
Features
Interface I/O (Input/Output)
DIN rail (35 mm, T35) or panel mount (EN 60715)
PCB relays and electronic modules allowed
According to IEC(EN 61812/1/4)
DIN/EN sequential numbering
Specifications
Nominal load
SFB1-T
SFB2-T
Socket
Wiring diagram SFB1-T
1C: 16A (250 V); 2C: 8A (250V)
Dielectric strength Vrms/1min
Socket
2,5 KV
Max. screw torque
Wiring diagram SFB2-T
1,2 Nm
Screws
M3 Steel. Pozi drive
Quick Clamp
Dimensions SFB1-T
Stainless steel
Wire in lets capacity: solid wire
Dimensions SFB2-T
mm2
Wire in lets capacity: multi-core
3,
Protection Category
Weight
3gr
Pack Units
100
Weld-ong PCB sockets SFC
30,2 [1.19]
46 [1.79]
44 [1.74]
73 [2.88]
9,5 [.37]
72 [2.83]
References
Reference
Contacts
Connection
SFB11C00T
Socket for relays 1 contact black
SFB10C00T
Socket for relays 1 contact grey
SFC11C11T
Weld-on PCB sockets 1 contact relay black
SFB21C00T
Socket for relays 2 contacts black
SFB20C00T
Socket for relays 2 contacts grey
SFC21C11T
Weld-on PCB sockets 2 contacts relays black
IP 20
12,8 [.50]
75 [2.95]
61 [2.41]
]
. 13
2[
42 [1.67]
,2
3]
[.1
-40C to 70C
20
16 [.61]
35 [1.37]
22 14 AWG
46gr
Room Temperature
Pack Units
16 [.61]
42 [1.67]
61 [2.41]
75 [2.95]
Weight
or 2 x 2,25 mm2
5 [.20]
Series - T modules
31,3 [1.23]
8,6 [.34]
M12-LM-AA
6/230 VDC protection diode (A1-)
M22-LM-AB
6/230 VDC protection diode (A1+)
M32-LM-BC
6/24 VDC protection diode & led (A1-)
M32-LM-BC 6/24 VDC protection diode & led (A1+)
12,5 [.49]
M52-LM-DK
110/230 VAC RC supressor
M62-LM-EM
24/60 VAC/DC with led
M92-LM-EN
110/230 VAC/DC with led
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
10
(02410413)
Series - T modules - diagrams
Relays RF-PT series
Features
Industrial interface relay for general applications.
Available in 1 and 2 change-over contacts with max. current
16 A - 250VAC1/30VDC1 and 8 A - 250 VAC1/30VDC1.
Coil nominal power DC 0,4 W.
Insulation: IEC61810-1 - 2,5 Kv/3.
Pollution degree 2.
Socket 187 (4,75 mm)terminals.
Approvals: CE, UL
Protection class: IP67
European Patent.
Coil ratings
Nominal voltage VDC
Resistance ( 10%)
Nominal voltage VAC
Resistance ( 10%)
6
60
6
16
12
24
48
115
353 1,37K 4,3K 22,8K
12
24
48
120
63 240
1K 6,7K
230
21K
Coil values (at 25 C)
VDC
0,75 -1,1 Un
10% Un
Operating range
Max. drop-out voltage
RFS1-PT Relay 1 contact
RFS2-PT Relay 2 contacts
Wiring diagram RFS1-PT
Wiring diagram RFS2-PT
Dimensions RFS1-PT (mm-inch)
Contact arrangement: 1C and 2C. (230 VAC1/28VDC1)
Maximum contact power: 1C:2.500 VA / 300 W, 2C: 1.250VA
/ 150W.
Maximum voltage: 250 VAC / 220 VDC.
Maximum current: 16A 1C and 8 A 2C AC1/DC1
Maximum breaking capacity: 110V DC ---> 0,4A
220V DC ---> 0,15-0,20A
29 [1.14]
Contact resistance: 50 m.
Contact material: Silver alloy (AgNi).
15 [.60]
5 [.20]
13 [.50]
15 [.60]
13 [.50]
5 [.20]
Contacts
Dimensions RFS2-PT (mm-inch)
29 [1.14]
Specifications RF-PT
4 [.15]
4 [.15]
Coil temperature RFS1-PT
Electrical life RFS1-PT
Coil temperature RFS2-PT
VAC 50Hz
0,8 -1,1 Un
30% Un
Electrical life RFS2-PT
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000 M(500VDC)
20 ms
1200 op/h at nominal load
10 ms
5.000VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
Pack units
10 - 50 Hz (Double width 1,5mm)
10 g
-40 C +70 C
35% -85% RH
86 - 106 KPa
12 gr
100
The sockets for these relays are the SF SERIES page 10.
References RF-PT relays
Example: Relay RF. 1 contact, 24VDC coil voltage.
RF
Product series
RF: RF relays series
(02410413)
Type
S: change-over
standard for all models
Contacts number
1: 1 contact
2: 2 contacts
Contact material
0: silver alloy
11
SFMFRVJDL!T/B/!!
024
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
230: 230V (only AC)
DC
Series features
T: T series
Type
P: power and sealed version
Coil version
AC: VAC voltage
DC: VDC voltage
Led
N: without led
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
RVS SlimLine relays and SVB sockets
Features
Miniature relay for PCB.
Available in 1 change-over contact with max. current
6A(AC1 / 250V; DC1 / 30V).
Nominal power: 5, 6, 9, 12, 18, 24 VDC (170mW);
48 VDC & 60 VDC (210mW).
Miniature, low comsumption, high response and sensitivity relay.
PCB terminals.
Approvals: CE.
Protection class (RVS): IP67
IEC 60664
Coil ratings
77 [3.03]
15 [.58]
5 [.20]
5 [.20]
15 [.58]
90 [3.54]
Contacts
5 [.20]
Control
voltage
32VDC
32VDC
12VDC
24VDC
60VDC
5 [.20]
1 [.04]
6
212
9
12
18
476 816 1,9K
24 VDC/AC
Operating range
Max. drop-out voltage
35 [1.36]
28 [1.10]
5
141
SVB sockets Features
24
48
60
3,3K 10,6K 16.6K
60 VDC/AC
Coil values at 25 C
6 [.25]
28 [1.10]
Nominal voltage VDC
Resistance ( 10%)
Socket input voltage
Reference
RVSDCB032DC240004D
RVSACB032DC240002Z
RVS10N012V000
RVS10N024V000
RVS10N060V000
The relay voltage 5,6,9,18 and 48VDC are under request
Interface I/O (Input/Output) & weld on sockets.
Diferent types depending on the input voltage.
Protection and indication circuit.
Rail DIN (35 mm) and PCB.
DIN / EN secuential numbering.
Protection class: IP20
SVB sockets specifications
Nominal load
Dielectric strength
Screws
Wire in lets capacity solid wire
6 A / 300 VAC
> 3 KV
M3 Steel. Pozi drive
1 x 2,5 mm2
Weight
Pack units
24gr
20
Sockets' references
VDC
0,75 -1,3 Un
5% Un
Contacts
Contact arrangement: 1C and 2C open contacts.
Maximum contact power: 1.500 VA (AC1 LOAD) 250 VAC.
Maximum voltage: 250 VAC.
Maximum current: 30A(AC1 250V), 9A-250VAC3, DC1 load
24V/220V, 140W/40W.
Contact resistance: 50 m.
Contact material: Silver alloy (AgNi).
Specifications RVS
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000 M(500VDC)
8ms
1200op/h at nominal load
4ms
4.000VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Atmospheric pressure
Pollution degree
Weight
Pack units
10 - 55Hz (Double width 1,0mm)
5g
-40 C +85 C
5% -85% RH
86 - 106 KPa
3
5,4gr
50
Sockets reference
SVB10D010024V*
SVB10D010024V
SVB10D010060V
SVB10D010110V
SVB10D010240V
Sockets input voltage
12 VAC/DC
24VAC/DC
60VAC/DC
100-110VAC/DC
220-240 VAC/DC
Relay reference
RVS10N012V000
RVS10N024V000
RVS10N060V000
RVS10N060V000
RVS10N060V000
*The SVB0D010024V socket is also usefull for the 12V
Accesories
Reference
Description
Observations
SVB10D01000V
PCB socket- weld on 6,2mm
Separator accesory
SVB10D000000V
AVP
Connection bridge for SVB sockets 1bridge (20 pins) per unit
Labels set for laser marking
1 set 64 labels
(17410413)
MTV
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
12
Power relays RM-FT
Features
Universal power relays for general applications with faston
terminals, specially designed to have a high resistance to
the wearing down in inductive load applications, for DC
current.
Nominal power 1,5W(DC) & 2,4 VAC.
Low consumption and high response.
Protection class: IP40.
Insulation: IEC61810-1 - 2,5 Kv/3.
Pollution degree: 2.
Contact material: (Ag+ Ni)
European Patent.
Approvals: CE, UL.
RME2-FT & RME3-FT change-over contacts
Available in 2 & 3 change-over contacts with max. current
16 A - 250 VAC / 30 VDC
RMS2-FT & RMS3-FT change-over contacts with LED & button
Available in 2 & 3 change-over contacts with max. current
16 A - 250 VAC / 30 VDC
RMEA2-FT & RMEA3-FT open contacts
Power relay faston terminals, special designed for DC charge
Applications with 1,5 mm GAP.
Available in 2 & 3 open contacts with max. current 16A 250 VAC / 30 VDC & 1A - 220 VDC
RM2-FT
RM3-FT
Relay 2 contacts
Wiring diagram RME20N
2 change-over contact
Wiring diagram RMS20L
2 change-over w. button
Wiring diagram RME2AN
2 open contact
Wiring diagram RME30N
3 change-over contact
Wiring diagram RMS30L
3 change-over w. button
Wiring diagram RME3AN
3 open contact
Relay 3 contacts
Wiring diagram RMED1
1 contact double make
Wiring diagram RMET1
1 contact triple make
In 1 contact triple make
is absolutely necesary
use the socket
* SMB31D11TFT
RMED-FT 1 open contact with double and triple make
universal power relay faston 1 open contact double and
triple make, designed with higher GAP to obtain more
switching capacity for DC current in inductive charges.
RMED 1 Double make
1 open contact with double make 3A/220 VDC1 GAP 3mm.
Available in 1 contact with max. current 16A
(250VAC/30VDC)
RMET 1 Triple make
1 open contact with triple make 3A/220 VDC1 GAP 4,5mm.
Available in 1 contact with max. current 16A
(250VAC/30VDC)
*Triple make use with socket SMB31D11TFT only.
Coil ratings
Dimensions RM2-FT & RM3-FT (mm-inch)
Nominal voltage VDC
Resistance ( 15%)
Nominal voltage VAC
Resistance ( 15%)
34 [1.34]
8 [.32]
52 [2.03]
37 [1.46]
(02410413)
13
SFMFRVJDL!T/B/!!
12
96
12
17
24
430
24
78
48
1,6K
48
305
115
9,8K
120
1,2K
220
39,7K
230
6,4K
Coil values (at 25 C)
4,8 [.19]
Coil temperature
6
23,5
6
3,9
Operating range
Max. drop-out voltaje
VDC
0,8 -1,1 Un
15% Un
VAC 50HZ
0,8 -1,1 Un
30% Un
Electrical life
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Power relays RM-FT
Contacts
RME
RMS
Change over contacts
2C and 3C
Gap
Max. contact power
Change over contacts Change over contacts
with led and button
RMEA
RMED
RMET
Open contacts
Contact double make
Contact triple
make
2C and 3C
2C and 3C
1C
1C
1,5mm
1,5mm
1,5mm
3,5mm
4,5mm
4.000VA / 480W
4.000VA / 480W
4.000VA / 480W
4.000VA / 480W
4.000VA / 480W
16A (250VAC1)
16A (250VAC1)
16A (250VAC1)
16A (250VAC1/30VDC1) 16A (250VAC1/30VDC1)
3A (220 VDC1)
5A (220 VDC1)
1A (220 VDC1)
110V DC -> 0,4A
110V DC -> 0,4A
110V DC -> 0,4A
110V DC -> 0,4A
110V DC -> 0,4A
220V DC -> 0,15-0,20A 220V DC -> 0,15-0,20A 220V DC ->0,15-0,20A 220V DC -> 0,15-0,20A 220V DC->0,15-0,20
Max. current
Maximum
breaking capacity
Contact resistance
30m
30m
30m
30m
30m
Contact material
Silver alloy
Silver alloy
Silver alloy
Silver alloy
Silver alloy
Specifications RF-PT
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000M(500VDC)
30ms
1200op/h at nominal load
20ms
4.200VAC/min(between coil and contacts)
1.200VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
Pack units
10 - 50Hz (Double width 1,5mm)
10g
-40 C +65 C
35% -85% RH
86 - 106 KPa
72gr
20
Product series
RM: RM relays series
Type
S: with button
E: without button
Contacts number
1: 1 contact double or triple make
2: 2 contacts
Contact material
3: 3 contacts
A: open contacts
D: double make one contact
T: triple make one contact
0: change over contact
LED
L: witht LED
N: without LED
Series features
FT: FT series power relays
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
220: 220V (only DC)
230: 230V (only AC)
Coil version
AC: VAC voltage
DC: VDC voltage
Sockets SMB-FT
Features
35 [1.38]
,3
[ .1
3]
35,4 [1.39]
41,2 [1.62]
82,4 [3.24]
References sockets SMB-FT
SMB31D11FT000
Long black socket for 2 & 3 contacts relays
SMB31D11TFT00
Long black socket special for triple make
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Specifications SMB-FT
10A / 400VAC
2,5KV
1,2Nm
Nominal load
Dielectric strenght
Max. screw torque
Screws
Wire in lets capacity: solid wire
M3 Steel. Pozi drive
2
2
4 mm or 2 x 2,25 mm
Wire in lets capacity: multi-core
Weight
Pack units
22 14 AWG
67gr
10
(02410413)
26,1 [1.03]
DIN rail (35 mm) or panel mounting, T35 (EN 60715).
DIN/EN sequential numbering.
IEC / EN 61812/1/4 compliant.
Clip and label included.
Electronic modules allowed.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
14
Power relays RPA
Features
High power relay designed for strong current load
applications.
1 & 2 open contacts used for up to 30A / 25A.
Available with flanges for panel or DIN rail, and faston or
screw terminals.
Nominal power 1,9 W(DC) & 2,5 VAC.
Insulation: IEC61810-1 - 2,5 Kv/3.
Pollution degree: 2
Approvals: CE, UL.
Protection class: IP20.
European patent.
Coil ratings
Nominal voltage VDC
Resistance ( 10%)
Nominal voltage VAC
Resistance ( 10%)
6
19
6
17
12
75
12
65
24
300
24
275
48
1,2K
48
1,1K
115
6,4K
120
4,7K
230
21K
Coil values (at 25 C)
RPA1
RPA2
Relay 1 contact
Wiring diagram RPA1
Relay 2 contacts
VDC
0,75 -1,1 Un
15% Un
Operating range
Max. drop-out voltage
Wiring diagram RPA2
VAC 50HZ
0,8 -1,1 Un
30% Un
Contacts
Dimensions RPA- Faston-flanges
Dimensions RPA faston-DIN
40 [1.58]
35 [1.38]
6,3 [.25]
60 [2.36]
44 [1.72]
33 [1.31]
33 [1.29]
40 [1.59]
6,3 [.25]
Contact resistance: 50 m.
Contact material: Silver alloy (AgNi).
50 [1.97]
68 [2.67]
68 [2.67]
51 [1.99]
50 [1.98]
Specifications RF-PT
Dimensions Screw terminals - DIN
51 [2.00]
44 [1.72]
40 [1.58]
35 [1.38]
33 [1.31]
47 [1.84]
M4
51 [1.99]
Coil temperature
Contact arrangement: 1C and 2C open contacts.
Maximum contact power: 7.500 & 6.250 VAC (AC1).
Maximum voltage: 250 VAC.
Maximum current: 30A (1C) & 25A (2C)
AC1 250V-9A-250VAC3
Maximum breaking capacity: 7500 VA/840W,
AC1 250/ DC1 30V
Electrical life
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
5x106 cycles
1000M(500VDC)
30ms
1200op/h at nominal load
30ms
4.000VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
10 - 50Hz (Double width 1,5mm)
10g
-40 C +65 C
35% - 85% RH
86 - 106 KPa
91gr faston terminals
123gr screw terminals
10
Pack units
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
115: 115V (only DC)
120: 120V (only AC)
230: 230V (only AC)
Product series
RF: RF relays series
(02410413)
Contacts number
1: 1 contact
2: 2 contacts
15
SFMFRVJDL!T/B/!!
Contact
A: open contacts for
all models
Series features
T: T series
Connection features
F: faston terminals & flanges
H: faston terminal & DIN rail
T: screw terminal & DIN rail
Coil version
AC: VAC voltage
DC: VDC voltage
Led
N: without led
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
STANDARD
SERIES
RELAYS
16
Relays RM series
Features
Universal power relay for general applications.
Available in 2 & 3 change-over contacts with max. current
10 A - 250 VAC1 / 28 VDC1.
Nominal power 1,5 W(DC) & 2,7 VAC.
Available with and without led for AC/DC relays.
Diode only available for DC.
Socket terminals, 8 pins plug-in for 2 contacts and 11 pins
plug-in for 3 contacts.
Insulation: IEC61810-5 - 2,5 KV.
Approvals: CE, UL.
Class protection: IP40
European patent.
Coil ratings
Nominal voltage VDC
Resistance ( 15%)
Nominal voltage VAC
Resistance ( 15%)
6
23,9
6
3,9
12
96
12
17
24
430
24
62,5
48
115
1,6K 7,4K
48
120
305 1,2K
220
29K
230
5,1K
Coil values at 25C
Operating range
Max. drop-out voltage
VDC
0,8-1,1 Un
15% Un
VAC 50HZ
0,8 -1,1 Un
30% Un
Contacts
RMS2
Relay 8 pins 2 contacts
RMS3
Wiring diagram RMS2
Wiring diagram RMS3
Dimensions RMS2
Dimensions RMS3
Coil temperature
35 [1.37]
Electrical life
Product series
RM: RM relays series
(02410413)
Type
S: change-over
standard for all models
17
SFMFRVJDL!T/B/!!
Specifications RM
34 [1.35]
57 [2.25]
35 [1.37]
58 [2.27]
34 [1.35]
Contacts number
2: 2 contacts
3: 3 contacts
Contact arrangement: 2C & 3C.
Max. contact power: 2.500 VA / 280 W.
Max. voltage: 250 VAC / 220 DC1.
Max. current:10A - 250 VAC1 / 28VDC1
Maximum breaking capacity: 110V DC ---> 0,4A
220V DC ---> 0,15-0,20A
Contact resistance: 50 m.
Contact material: Silver alloy.
Relay 11 pins 3 contacts
Contact material
0: silver alloy
Led
N: without led
L: with led
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000M(500VDC)
30ms
1200op/h at nominal load
20ms
2.500VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
Pack units
10 - 50Hz (Double width 1,5mm)
10G
-40 C +65 C
35% -85% RH
86 - 106 KPa
80gr
10
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
220: 220V (only DC)
230: 230V (only AC)
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Series features
0: without special feature
Circuit connect to coil
0: without circuit
D: with diode (only DC)
Coil version
AC: VAC voltage
DC: VDC voltage
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Sockets SM series
Features
DIN rail (35 mm,T35) or panel mounting (EN 60715).
DIN/EN sequential numbering.
IEC / EN 61812/1/4 compliant.
Clip and label included.
Electronic modules allowed.
Specifications SMB2 and SMB3
10A / 400VAC
2,5KV
1,2Nm
Nominal load
Dielectric strenght
Max. screw torque
Screws
SM2
SM3
Socket
Wiring diagram SM2
Socket
Wiring diagram SM3
35 [1.36]
35 [1.36]
37 [1.47]
,3
[
Wire in lets capacity: multi-core
Protection class
Room temperature
Weight
22 14 AWG
IP20
-40 to 70
59gr
Pack units
10
75 [2.94]
37 [1.47]
.13
]
M3 Steel. Pozi drive
2
2
4 mm or 2 x 2,25 mm
29 [1.15]
29 [1.15]
37 [1.46]
75 [2.94]
37 [1.46]
26 [1.02]
Dimensions SM3 (mm- inch)
26 [1.02]
Dimensions SM2 (mm- inch)
Wire in lets capacity: solid wire
,3
[.1
3]
References sockets SM
SMB20D1000000
Long grey socket for 2 contacts relays
SMB30D1000000
Long grey socket for 3 contacts relays
Accesories
Mechanical indication and a wide window.
3-sequential-position test button (free, check, lock).
Colours for an easier identification of coil voltage (DC Blue, AC
red).
Technical information and coil voltage in frontal side,
laser printed.
Interchangeable marking labels.
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
18
(02410413)
AME
Relays RQ series
Features
Miniature power relays for general and industrial
applications.
Available in 1 and 2 change-over contacts with max. current
16A - 250 VAC/30 VDC and 10A - 250 VAC/30 VDC and in
4 change-over with max. current 5A - 250 VAC/30 VDC
(AC1/DC1).
Nominal coil power 0,9 W(DC) & 1.5 VAC.
Available with and without LED for AC and DC. Diode only
available for DC.
Pollution degree: 2.
Insulation: IEC61810-1 - 2,5 Kv/3.
Protection class: IP40.
Plug-in terminal faston 1 and 2 contacts (4,8 mm). 4-contact
version with plug-in faston (2,6 mm).
Approvals: CE, UL.
European patent.
Coil ratings
Nominal voltage VDC
Resistance ( 10%)
Nominal voltage VAC
Resistance ( 10%)
6
40
6
11,5
12
160
12
40
24
650
24
160
48
115
220
2,5K 13,2K 52K
48
120
230
600
3k
12,4K
Coil values at 25C
Operating range
Max. drop-out voltage
RQS1Relay 1 contact
Wiring diagram RQS1
RQS3 Relay 2 contacts
RQS4 Relay 4 contacts
Wiring diagram RQS2
Wiring diagram RQS4
29 [1.12]
4,8 [.19]
29 [1.12]
21 [.83]
37 [1.47]
Dimensions RQS4 (mm- inch)
21 [.83]
37 [1.46]
Dimensions RQS1 -RQS2 (mm-inch)
VAC 50HZ
0,8 -1,1 Un
30% Un
Contacts
Contact arrangement: 1C, 2C and 4C.
Maximum contact power: (230 VAC1 / 28VDC1)
1C: 4000VA / 480 W.
1C (1PDT)
2C: 2500VA / 300 W.
2C (DPDT)
4C: 1250VA / 150 W.
4C (4PDT)
Maximum voltage: 250 VAC, 220 VDC.
Maximum current: 16A, 10A, 5A. (250 VAC1/ 30 VDC1)
Maximum breaking capacity: 110V DC ---> 0,4A
220V DC ---> 0,15-0,20A
Contact resistance: 50m.
Contact material: Silver alloy (AgNi).
Specifications RQ
2,8 [.11]
Coil temperature RQS1-RQS2
VDC
0,7 - 1,1 Un
10% Un
105 cycles
Electrical life
Mechanical life
107 cycles
Insulation resistance
1000M(500VDC)
Operation time
20ms
Operation frequency
1200op/h at nominal load
Release time
20ms
Dielectric strength at 1mA in 1 & 2 contacts
Coil temperature RQS4
2.000VAC/min(between coil and contacts)
1.200VAC/min(between contacts)
Dielectric strength at 1mA in 4 contacts
Electrical life RQS1-RQS2
1.800VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Electrical life RQS4
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
Pack units
Product series
RQ: RQ relays series
(02410413)
Type
S: change-over
standard for all models
Contacts number
1: 1 contact
2: 2 contacts
4: 4 contacts
19
SFMFRVJDL!T/B/!!
Contact material
0: silver alloy
LED
N: without LED
L: with LED
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
220: 220V (only DC)
230: 230V (only AC)
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
10 - 50Hz (Double width 1,5mm)
10g
-40 C +65 C
35% -85% RH
86 - 106 KPa
35gr
10
Series features
0: without special feature
Circuit connect to coil
0: without circuit
D: with diode (only DC)
Coil version
AC: VAC voltage
DC: VDC voltage
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Sockets SQ series
Features
Interface I/O (Input/Output).
Interchangeable marked labels and clip integrated.
DIN rail (35 mm, T35) or panel mount (EN 60715).
Connection bridges for A2 terminals.
Electronic modules connection.
3-position clip for DIN rail subjection.
DIN and sequential numbering(optional).
IEC/EN 61811/2/4 compliant.
SQ2
SQ4
Socket
Wiring diagram SQ2
Socket
Specifications SQ
Wiring diagram SQ4
The SQ sockets are produced in 2 versions with or without
MQ-series module insertion (see modules pages).
Dimensions SQ4 (mm-inch)
69 [2.70]
69 [2.70]
Dimensions SQ2 (mm-inch)
[.1
3,
5
[.1
3,5
4]
23 [.92]
35 [1.39]
4]
23 [.92]
35 [1.39]
32 [1.26]
91 [3.58]
16A (SQB2,SQR2); 10A (SQB4, SQR4) 250V
Nominal load
2,5KV
Dielectric strenght
Max. screw torque
1,2Nm
Screws
M3 Steel. Pozi drive
2
Wire in lets capacity: solid wire
4mm or 2 x 2,25mm
Wire in lets capacity: multi-core
22 14 AWG
Protection class
Room humidity
Weight
IP20
-40 to 70
72gr
Pack units
10
32 [1.26]
91 [3.58]
References sockets SQ
Reference
Contacts
Connection
onnection
Module
SQB20D010
1 or 2
Screw
ew terminals
No
SQR20D010
1 or 2
Quick
uick Clamp
No
SQB20D000
1 or 2
Screw
ew terminals
Yes
SQR20D000
1 or 2
Quick
uick Clamp
Yes
SQB40D010
Screw
ew terminals
No
SQR40D010
Quick
uick Clamp
No
SQB40D000
Screw
ew terminals
Yes
SQR40D000
Quick
uick Clamp
Yes
Accesories
AQE
SFMFRVJDL!T/B/!!
AQP
Ctra. Mntrida a Aldea del Fresno
esno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
20
(02410413)
ow.
Mechanical indication and a wide window.
heck, lock).
3-sequential-position test button (free, check,
Colours for an easier identification of coill voltage
(DC blue, AC red).
n frontal part, laser printed.
Technical information and coil voltage in
Interchangeable marking labels. They can
n be easily interchanged
or replaced, enabling the relays and sockets
ckets identification.
Connection bridges allow the connection
tion of A2 coil terminal
contacts in Q & F series, thus reducing wiring
iring
g time and effort.
Relays RF series
Features
Industrial interface relay for general applications. Available
in 1 & 2 change-over contacts with max. current 10 A 250VAC1/30VDC1 and 5 A - 250 VAC1/30VDC1.
Coil nominal power 0,53 W(DC) & 1,1 VAC.
Available with or without LED for AC/DC relays.
Diode only available in DC.
Insulation: IEC61810-1 - 2,5 Kv/3.
Pollution degree 2.
Socket 187 (4,75 mm)terminals.
Protection class: IP40
Approvals: CE, UL.
European Patent.
Coil ratings
Nominal voltage VDC
Resistance ( 10%)
Nominal voltage VAC
Resistance ( 10%)
6
68
6
16
12
270
12
63
24
48
115
1,1K 4,1K 22,4K
24
48
120
230
240 1,06K 5,37K 21,18K
Coil values at 25C
RFS1
RFS2
Relay 1 contact
Wiring diagram RFS1
Relay 2 contacts
Wiring diagram RFS2
Dimensions RFS1
30 [1.19]
36 [1.40]
Contact resistance: 50 m.
Contact material: Silver alloy (AgNi).
20 [.79]
20 [.78]
5 [.20]
2,5 [.10]
VAC 50HZ
0,8 -1,1 Un
30% Un
Contact arrangement: 1C and 2C.
Maximum contact power (230BAC1 / 28 VDC1):
1C: 2.500VA / 300W
2C: 1.250VA / 150W
Maximum voltage: 250VAC / 220VDC.
Maximum current: 10A and 5A. (250AC1/30DC1)
Maximum breaking capacity: 110VDC ---> 0,4A
220VDC ---> 0,15-0,20A
13 [.51]
30 [1.19]
36 [1.42]
4,8 [.19]
VDC
0,75-1,1 Un
10% Un
Contacts
Dimensions RFS2
13 [.49]
5 [.20]
Operating range
Max. drop-out voltage
Specifications RM
Coil temperature RFS1
Electrical life RFS1
Electrical life
Mechanical life
Insulation resistance
Operation time
Operation frequency
Release time
Dielectric strength at 1mA
105 cycles
107 cycles
1000M(500VDC)
20ms
1200op/h at nominal load
10ms
5.000VAC/min(between coil and contacts)
1.000VAC/min(between contacts)
Coil temperature RFS2
Electrical life RFS2
Vibration resistance
Shock resistance
Room temperature
Room humidity
Armospheric pressure
Weight
Pack units
10 - 55Hz (Double width 1,5mm)
10g
-40 C +65 C
35% -85% RH
86 - 106 KPa
22gr
10
References RF relays
Example: Relay RF. 2 contacts, 230VAC coil voltage, with LED, and with diode.
RF
Product series
RF: RF relays series
(02410413)
Type
S: change-over
standard for all models
Contacts number
1: 1 contacts
2: 2 contacts
21
SFMFRVJDL!T/B/!!
Contact material
0: silver alloy
230
Coil voltage
006: 6V
012: 12V
024: 24V
048: 48V
060: 60V
115: 115V (only DC)
120: 120V (only AC)
230: 230V (only AC)
AC
Series features
0: without special feature
Circuit connect to coil
0: without circuit
D: with diode (only DC)
Coil version
AC: VAC voltage
DC: VDC voltage
Led
N: without led
L: with led
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Sockets RF series
Features
Interface I/O (Input/Output).
Interchangeable marked labels option, and clip integrated
DIN rail (35 mm, T35) or panel mount (EN 60715).
Connection Bridges for A2 terminals.
Industrial faston or PCB relay mount.
3-position clip for subjection to DIN Rail.
DIN/EN sequential numbering (optional).
According to IEC/EN61810.
SF1
SF2
Socket
Wiring diagram SF1
Socket
Wiring diagram SF2
Dimensions SF2 (mm - inch)
69 [2.70]
69 [2.70]
Dimensions SF1 (mm - inch)
35 [1.39]
The SF sockets are produced in 2 versions with or without MF-series
module insertion (see the modules pages).
Nominal load
Dielectric strenght
Max. screw torque
Screws
Quick Clamp
Wire in lets capacity: solid wire
1C;16A (250V); 2C: 8A (250V)
2,5KV
1,2Nm
M3 Steel. Pozi drive
Stainless steel
2
2
4mm or 2 x 2,25mm
Wire in lets capacity: multi-core
Protection class:
Room Humidity
22 14 AWG
IP20
-40 to 70
Weight
Pack units
49gr
10
3,
5
[.1
4]
16 [.62]
3,
5
[.1
4]
16 [.63]
35 [1.39]
Specifications SFB10SFR10, SFB20SFR20
39 [1.52]
39 [1.52]
91 [3.58]
91 [3.58]
References
Reference
Contacts
Connection
SFB10D010
Screw terminals (Faston or PCB)
SFR10D010
Quick Clamp (Faston or PCB)
SFC11C110
Pin terminals (Faston)
SFB20D010
Screw terminals (Faston or PCB)
SFR20D010
Quick Clamp (Faston or PCB)
SFC21C110
Pin terminals (Faston)
Accessories for relays
Mechanical indication and a wide window.
3-sequential-position test button (free, check, lock).
Colours for an easier identification of coil voltage
(DC blue, AC red).
Technical information and coil voltage in frontal part, laser printed.
Interchangeable marking labels.
They can be easily interchanged or replaced, enabling the relays
and sockets identification.
Connection bridges allow the connection of A2 coil terminal
AFE
SFMFRVJDL!T/B/!!
AFP
Ctra.
a. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
22
(02410413)
contacts in the Q & F series, thus reducing wiring time and effort.
SFMFRVJDL!T/B/!!
SFMFRVJDL!T/B/!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
SOLID STATE RELAYS
www.relequick.com
24
Zero crossing AC SSR
Load current vs. ambient temperature
Single phase relay - 25 A
Single phase relay - 60 A
40 - 440 VAC
90 - 250 VAC
RS1A0P032DC440060Z
-30
20
40
60
40
WITHOUT HEAT SINK
20
0
80
-30
RSH-039 HEAT SINK
80 A
RS1A0P032DC440080Z
RSH-038
100 A
RS1A0P032DC440100Z
RSH-039
25 A
RS1A0P250AC440025Z
RSH-061
60 A
RS1A0P250AC440060Z
RSH-038
80 A
RS1A0P250AC440080Z
RSH-038
100 A
RS1A0P250AC440100Z
RSH-039
Load current (A)
Load current (A)
60
40
-30
80
100
RSH-038 HEAT SINK
60
Single phase relay - 100 A
80
RSH-038
40
RS1A0P032DC440060Z
RS1A0P250AC440060Z
Single phase relay - 80 A
20
20
Ambient temperature ( C)
RS1A0P032DC440025Z
RS1A0P250AC440025Z
Operational Operational
Reference
Reference
voltage
heat sink
current
25 A
RS1A0P032DC440025Z RSH-061
60 A
10
WITHOUT HEAT SINK
RSH-038 HEAT SINK
60
Ambient temperature ( C)
References
3 - 32 VDC
RSH-061 HEAT SINK
20
Single phase 2 input ranges: 3-32VDC and 90-250VAC.
Maximum load current (AC1 at 25 C): 25, 60, 80, 100A.
Operational ratings: 40 - 440 VAC.
Frequency range: 50- 60 Hz.
Maximum non-repetitive peak voltage: 930 Vp.
LED indicator.
Clip on protective cover for greater safety (IP 20).
Control
voltage
30
80
Load current (A)
Load current (A)
40
WITHOUT HEAT SINK
20
40
60
75
50
25
0
80
Ambient temperature ( C)
-30
WITHOUT HEAT SINK
20
40
60
80
Ambient temperature ( C)
RS1A0P032DC440080Z
RS1A0P250AC440080Z
RS1A0P032DC440100Z
RS1A0P250AC440100Z
Dimensions (mm-inch)
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Rth junction to case
Ambient humidity
CE marking
2,500 VAC
-25 C to 70 C
-35 C to 85 C
2,5 C/W (25 A)
0,65 C/W (60 A)
0,5 C/W (80 A)
0,3 C/W (100 A)
Operating: up to 85 %
Yes
Input specifications
VDC input
VAC input
Control voltage range
3 - 32 VDC
90 - 250 VAC
Input current (max)
10/16 mA @= 5 V/24 V 29 mA @= 220 VAC
Pick-up voltage
1,9 VDC
70 VAC
Drop-out voltage
1,9 VDC
70 VAC
Maximum reverse voltage
32 VDC
Max. response time pick-up
cycle
1 cycle
Max. response time drop-out
cycle
2 cycles
Diagrams
Output specifications
Maximum load current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
25, 60, 80, 100 A
5, 15, 18, 20 A
40 - 440 VAC
50 - 60 Hz
930 Vp
350 Ap / 25 A 910 Ap / 80 A
Max. non-repetitive peak current (t=10ms)
630 Ap / 60 A 1100 Ap / 100 A
10 mArms
Maximum off state leakage current
200 V / seg
Minimum off state dv / dt
<1,6 VAC
Maximum on state voltage
Minimum load current
0,1 Arms
2
625 A s (25 A) 4.225 A2s (80 A)
I2t (10 ms) (orientative data)
2
2.025 A s (60A) 6.050 A2s (100A)
(02410413)
Housing specifications
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
25
SFMFRVJDL!T/B/!!
57 x 44 x 23
150 gr max.
Aluminum, nickel-plated
1,2 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Random AC SSR
Load current vs. ambient temperature
Single phase relay - 25 A
Single phase relay - 60 A
30
10
20
40
60
WITHOUT HEAT SINK
20
0
80
-30
RSH-039 HEAT SINK
RS1A0P032DC480060R RSH-038
80 A
RS1A0P032DC480080R RSH-038
100 A
RS1A0P032DC480100R RSH-039
25 A
RS1A0P280AC480025R RSH-061
60 A
RS1A0P280AC480060R RSH-038
80 A
RS1A0P280AC480080R RSH-038
100 A
RS1A0P280AC480100R
Load current (A)
Load current (A)
60 A
80
Single phase relay - 100 A
RSH-038 HEAT SINK
40
-30
60
100
60
40
RS1A0P032DC480060R
RS1A0P250AC480060R
Single phase relay - 80 A
20
20
Ambient temperature ( C)
80
Operational Operational
Reference
Reference
voltage
heat sink
current
25 A
RS1A0P032DC480025R RSH-061
90 - 280 VAC
40
RS1A0P032DC480025R
RS1A0P250AC480025R
References
40 - 480VAC
-30
WITHOUT HEAT SINK
RSH-038 HEAT SINK
60
Ambient temperature ( C)
Two input ranges: 3-32 VDC and 90-280 VAC.
Maximum load current (AC1 at 25 C): 25, 60, 80, 100A.
Operational ratings: 40 - 480 VAC.
Frequency range: 50- 60 Hz.
Maximum non-repetitive peak voltage: 930 Vp.
LED indicator.
Clip on protective cover for greater safety (IP 20).
3 - 32 VDC
RSH-061 HEAT SINK
20
Control
voltage
80
Load current (A)
Load current (A)
40
WITHOUT HEAT SINK
20
40
60
75
50
25
0
80
Ambient temperature ( C)
-30
WITHOUT HEAT SINK
20
40
60
80
Ambient temperature ( C)
RS1A0P032DC480080R
RS1A0P250AC480080R
RS1A0P032DC480100R
RS1A0P250AC480100R
Dimensions (mm-inch)
RSH-039
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Rth junction to case
Ambient humidity
CE marking
Input specifications
2,500 VAC
-30 C to 80 C
-35 C to 85 C
2,5 C/W (25 A)
0,65 C/W (60 A)
0,5 C/W (80 A)
0,3 C/W (100 A)
Operating: up to 85 %
Yes
VDC input
Control voltage range
3 - 32 VDC
Input current (max)
13/16 mA @= 5 V/24 V
Pick-up voltage
1,9 VDC
Drop-out voltage
1,9 VDC
Maximum reverse voltage
32 VDC
Max. response time pick-up
1 ms
Max. response time drop-out
cycle
VAC input
90 - 280 VAC
29 mA @= 220 VAC
70 VAC
70 VAC
-
Diagrams
Output specifications
Maximum load
current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
Max. non-repetitive peak current
(t=10ms)
Maximum off state leakage current
Minimum off state dv / dt
Maximum on state voltage
Minimum load current
I2t (10 ms) (orientative data)
25, 60, 80, 100 A
5, 15, 18, 20 A
40 - 480 VAC
50 - 60 Hz
930 Vp
910 Ap / 80 A
350 Ap / 25 A
630 Ap / 60 A 1100 Ap / 100 A
8 mArms
200 V / seg
1,6 VAC
0,05 Arms
625 A2s (25 A) 4.225 A2s (80 A)
2.025 A2s (60A) 6.050 A2s (100A)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
SFMFRVJDL!T/B/!!
57 x 44 x 23
150 gr max.
Aluminum, nickel-plated
1,2 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
26
(02410413)
Housing specifications
Single phase SSR (DC load)
Load current vs. ambient temperature
Single phase relay - 25 A
Single phase relay - 40 A
40
40
Load current (A)
Load current (A)
RSH-036 HEAT SINK
30
RSH-061 HEAT SINK
20
10
0
-30
WITHOUT HEAT SINK
20
40
60
30
20
WITHOUT HEAT SINK
10
0
80
-30
Ambient temperature ( C)
RS1D0P015DC600025D
DC solid state relay.
Input range: 3 - 15 VDC.
Maximum load current (AC1 at 25 C): 25, 40, 60, 80A.
Operational ratings: 12 - 600 VDC.
LED indicator.
Clip on protective cover for greater safety (IP 20).
Control voltage
Reference
heat sink
25 A
RS1D0P015DC600025D
RSH-061
40 A
RS1D0P015DC600040D
RSH-036
60 A
RS1D0P015DC600060D
RSH-038
80 A
RS1D0P015DC600080D
RSH-038
3 - 15 VDC
RSH-038 HEAT SINK
Load current (A)
60
40
20
0
-30
80
80
RSH-038 HEAT SINK
Reference
60
Single phase relay - 80 A
80
Operational current
40
RS1D0P015DC600040D
Single phase relay - 60 A
Load current (A)
References
20
Ambient temperature ( C)
WITHOUT HEAT SINK
20
40
60
60
40
20
0
80
Ambient temperature ( C)
-30
WITHOUT HEAT SINK
20
40
60
80
Ambient temperature ( C)
RS1D0P015DC600060D
RS1D0P015DC600080D
Dimensions (mm-inch)
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Rth junction to case
Ambient humidity
CE marking
1,500 VDC
-40 C to 80 C
-45 C to 85 C
2,5 C/W (25 A)
0,65 C/W (60 A)
0,5 C/W (80 A)
Operating: up to 85 %
Yes
Input specifications
Control voltage range
Input current (max)
Pick-up voltage
Drop-out voltage
Maximum reverse voltage
Max. response time pick-up
Max. response time drop-out
3 - 15 VDC
2/30mA@= 3 V/15 V
1,5 VDC
1,5 VDC
15 VDC
5ms
0,2ms
Diagrams
Output specifications
Maximum load current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
25, 40, 60, 80A
5, 10, 15, 18A
12 - 600 VDC
Maximum off state leakage current
1mA
Minimum off state dv / dt
200V / seg
Maximum on state voltage
Minimum load current
1,4 VDC
0,1A
Housing specifications
(02410413)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
27
SFMFRVJDL!T/B/!!
60 x 45 x 22
150gr max.
Aluminum, nickel-plated
1,2Nm
2,4Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
AC & load analog switching/pahse angle SSR
Load current vs. ambient temperature
Load adjusting voltage (%)
100
Control Operational Operational
voltage
current
voltage
25 A
240 VAC
40 A
2 - 10VDC
60 A
380 VAC
80 A
240 VAC
4 - 20mA
380 VAC
Reference
Ref.
heat sink
RS1APV010DC240025R
RSH-060
RS1APV010DC240040R
RSH-061
RS1APV010DC380060R
RSH-038
RS1APV010DC380080R
RSH-038
100 A
25 A
RS1APV010DC380100R
RS1API420mA240025R
RSH-039
RSH-060
40 A
RS1API420mA240040R
RSH-061
60 A
80 A
RS1API420mA380060R
RS1API420mA380080R
RSH-038
RSH-038
100 A
RS1API420mA380100R
RSH-039
RS1APV010DC380060R
40
RS1APV010DC380080R
20
RS1APV010DC380100R
2
Control input (VDC)
100
Load adjusting voltage (%)
References
RS1APV010DC240040R
60
Analog switching AC solid state relay.
Two input ranges: 4 - 20 mA and 2 - 10 VDC.
Maximum load current (AC1 at 25 C): 25, 40, 60, 80, 100 A.
Operational ratings: 0 - 380 VAC.
Frequency range: 50 - 60 Hz.
Maximum non-repetitive peak voltage: 850 Vp.
Clip on protective cover for greater safety (IP 20).
RS1APV010DC240025R
80
80
RS1API420mA240025R
60
RS1API420mA240040R
RS1API420mA380060R
40
RS1API420mA380080R
20
0
RS1API420mA380100R
5
10
15
20
Control input (VDC)
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
Dimensions (mm-inch)
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Rth junction to case
Ambient humidity
CE marking
Input specifications
2.500 VAC
-40 C to 80 C
-45 C to 85 C
2,5 C/W(25A)
0,5 C/W(80A)
1,25 C/W(40A)
0,3 C/W(100A)
0,65 C/W(60A)
Operating: up to 85 %
Yes
VDC input
Current
Control voltage range
2 - 10 VDC
4 - 20 mA
And control mA range
13/16 mA @= 5 V/24 V 29 mA @= 220 VAC
1,9 VDC
70 VAC
Pick-up voltage
1,9 VDC
70 VAC
Drop-out voltage
32 VDC
Maximum reverse voltage
1 ms
Max. response time pick-up
cycle
Max. response time drop-out
Diagrams
Output specifications
Maximum load
current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
Max. non-repetitive peak current
(t=10ms)
Maximum off state leakage current
Minimum off state dv / dt
Maximum on state voltage
Minimum load current
I2t (10 ms) (orientative data)
25, 40, 60, 80, 100 A
5, 15, 18, 20 A
0 - 240VAC / 0 - 380 VAC
50 - 60 Hz
850 Vp
350 Ap / 25 A
910 Ap / 80 A
500 Ap / 40 A
630 Ap / 60 A 1100 Ap / 100 A
8 mArms
200 V / seg
1,6 VAC
0,15 - 0,25Arms
2
625 A s (25 A) 4.225 A2s (80 A)
1.250 A2s (40A)
6.050 A2s (100A)
2.025 A2s (60A)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
SFMFRVJDL!T/B/!!
57 x 44 x 23
160 gr max.
Aluminum, nickel-plated
1,2 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
28
(02410413)
Housing specifications
DIN-rail single phase SSR
Load current vs. ambient temperature
DIN-rail solid state relay (AC, 25 A)
DIN-rail solid state relay (AC, 60 A)
80
Load current (A)
Load current (A)
40
30
20
10
0
-30
20
40
60
60
40
20
0
80
-30
Ambient temperature ( C)
20
40
60
80
Ambient temperature ( C)
RS1A0R024DC480025Z
RS1A0P024DC480060Z
Dimensions (mm. inch)
AC zero crossing solid state relay.
Input range: 5 - 24 VDC.
Maximum load current (AC1 at 25 C): 25, 60 A.
Operational ratings: 48 - 480 VAC.
Frequency range: 50 - 60 Hz.
Maximum non-repetitive peak voltage: 1.000 Vp.
Two LEDs indicators (input / output).
Clip on protective cover for greater safety (IP 20).
Heat sink included.
Can be mounted directly on a DIN-rail with a clip for DIN-rail.
Control
voltage
5 - 24 VDC
Operational
voltage
48 - 480 VAC
Operational
current
25 A
RS1A0R024DC480025Z
60 A
RS1A0P024DC480060Z
92 [3.63]
98 [3.88]
References
Reference
13 [0.51]
102 [4.02]
22 [0.88]
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Ambient humidity
CE marking
2.500 VAC
-40 C to 80 C
-45 C to 85 C
Operating: up to 85 %
Yes
68 [2.69]
Control voltage range
Input current (max)
Pick-up voltage
Drop-out voltage
Maximum reverse voltage
Max. response time pick-up
Max. response time drop-out
121 [4.77]
5 - 24 VDC
16/18 mA @= 5 V/24 V
2,2 VDC
2,2 VDC
24 VDC
10 ms
10 ms
Output specifications
Maximum load current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
Max. non-repetitive peak current (t=10ms)
Maximum off state leakage current
Minimum off state dv / dt
Maximum on state voltage
Minimum load current
I2t(10 ms) (orientative data)
80 [3.15]
Input specifications
25, 60 A
5, 15 A
48 - 480 VAC
50 - 60 Hz
1.000 Vp
350 Ap / 25 A
630 Ap / 60 A
3 mArms
500 V / seg
<1,2 VAC
0,1 Arms
625 A2s (25 A)
2.025 A2s (60A)
Diagram
Housing specifications
(02410413)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
29
SFMFRVJDL!T/B/!!
75 x 35 x 100
80 x 70 x 105
200 gr
340 gr
Aluminum, nickel-plated
1,2 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Single phase power relay SSR
Load current vs. ambient temperature
Single phase relay - 100 A
Single phase relay - 250 A
100
240
RSH-039 HEAT SINK
Load current (A)
Load current (A)
RSH-039 HEAT SINK
75
50
25
0
-30
WITHOUT HEAT SINK
20
40
60
180
120
WITHOUT HEAT SINK
60
0
80
Ambient temperature ( C)
-30
20
40
60
80
Ambient temperature ( C)
RS1A0PP32DC440100Z
RS1A0PP32DC440250Z
Dimensions (mm. inch)
AC Solid state relay, zero crossing.
Input range: 3 - 32 VDC.
Maximum load current (AC1 at 25 C): 100, 150, 250 A.
Operational ratings: 40 - 400 VAC.
Frequency range: 50 - 60 Hz.
Maximum non-repetitive peak voltage: 930 Vp.
LED indicator.
References
Control
voltage
Operational Operational
Reference
Reference
heat sinks
voltage
current
RSH-039
RS1A0PP32DC440100Z
100 A
3 - 32 VDC 40 - 440 VAC
150 A
RSH-039
RS1A0PP32DC440150Z
250 A
RS1A0PP32DC440250Z
RSH-039
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Ambient humidity
CE marking
2.500 VAC
-30 C to 80 C
-45C to 85 C
Operating: up to 85 %
Yes
Input specifications
Control voltage range
Input current (max)
Pick-up voltage
Drop-out voltage
Maximum reverse voltage
Max. response time pick-up
Max. response time drop-out
(50Hz)
(50Hz)
Diagram
3 - 32 VDC
6/35 mA @= 3 V / 32 V
3 VDC
1 VDC
32 VDC
10 ms
10 ms
Output specifications
Maximum load current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
100, 150, 250 A
5, 15, 18, 20 A
40 - 440 VAC
50 - 60 Hz
930 Vp
1.100 Ap/100 A
Max. non-repetitive peak current (t=10ms)
2.200 Ap/250 A
1450 Ap/150 A
10 mArms
Maximum off state leakage current
500 V / seg
Minimum off state dv / dt
1,6 VAC
Maximum on state voltage
0,05 Arms
Minimum load current
6.050 A2s (100A) 24.200 A2s
I2t (10 ms) (orientative data)
(250A)
10.500 A2s (150A)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
SFMFRVJDL!T/B/!!
94 x 34 x 43
235 gr
Aluminum, nickel-plated
1,0 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
30
(02410413)
Housing specifications
PCB single phase SSR
Load current vs. ambient temperature
PCB mounting relay, 4 A
PCB mounting relay, 5 A
8
Load current (A)
Load current (A)
8
6
4
2
0
-30
20
40
60
6
4
2
0
-30
80
Ambient temperature ( C)
20
40
60
80
Ambient temperature ( C)
RS1ACB032DC440004Z
RS1AMB032DC440004Z
RS1AMB032DC440005Z
Dimensions (mm. inch)
AC Solid state relay, zero crossing.
Input range: 3 - 32 VDC.
Maximum load current (AC1 at 25 C): 4, 5 A.
Operational ratings: 40 - 400 VAC.
Frequency range: 50 - 60 Hz.
Maximum non-repetitive peak voltage: 1.200 Vp.
RS1ACB032DC440004Z
References
Control
voltage
Operational
voltage
3 - 32 VDC
40 - 440 VAC
Operational
current
Reference
RS1ACB032DC440004Z
4A
RS1AMB032DC440004Z
5A
RS1AMB032DC440005Z
RS1AMB032DC440004Z
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Ambient humidity
CE marking
500 VAC
-30 C to 80 C
-30 C to 85 C
Operating: up to 85 %
Yes
Input specifications
Control voltage range
Input current (max)
Pick-up voltage
Drop-out voltage
Maximum reverse voltage
Max. response time pick-up
Max. response time drop-out
3 - 32 VDC
9/16 mA @= 5 V/24 V
1,5 VDC
1,5 VDC
32 VDC
<1 ms
<1 ms
(50Hz)
(50Hz)
RS1AMB032DC440005Z
Output specifications
Maximum load current
(AC51 @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
Max. non-repetitive peak current (t=10ms)
Maximum off state leakage current
Minimum off state dv / dt
Maximum on state voltage
Minimum load current
4A, 5A
40 - 440 VAC
50 - 60 Hz
1.200 Vp
7 Ap / 5 A
10mA
200 V / seg
<1,6 VAC
0,1 Arms
Housing specifications
Dimensions (L x W x H mm)
(02410413)
Weight
Baseplate
31
43 x 26 x 12
22 gr
SFMFRVJDL!T/B/!!
34x26x16
43 x 31 x 20
34 gr
78 gr
Aluminum, nickel-plated
Diagram
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
PCB single phase power relay SSR
Load current vs. ambient temperature
Single phase power relay, 4 A
Single phase power relay, 2 A
8
Load current (A)
Load current (A)
8
6
4
2
0
-30
20
40
60
6
4
2
0
-30
80
Ambient temperature ( C)
20
40
60
80
Ambient temperature ( C)
RVSDCB024DC024004D
RVSACB024DC240002Z
Housing specifications
Optically Isolated
Low On-state Resistance
Low Input Power Consumption
TTL and CMOS compatible
RC networks (VAC)
UL requested
Dimensions (L x W x H mm)
22x5x15
Weight
Baseplate
AC
DC
Dielectric insulation (between input & output) 4KVrms, 1min 3750Vrms
Dimensions (mm. inch)
-20 C to 80 C
-25 C
-40 C
to 80 C
to 100 C
Operating: up to 85%
220 C (10sec)
Yes
Operating temperature
Storage temperature
Ambient humidity
Maximum Soldering Heat
CE marking
28 [1.10]
15 [.58]
General specifications
4g
-
24VDC
18 - 32VDC
9/16 mA @= 5V/24V
7,7mA
3000
1V
32VDC
Nominal Voltage
Control voltage range
Input current (max)
Control current
Impedance
Release voltage
Maximum reverse voltage
Output specifications
AC
Maximum load current
(AC51 @ Ta = 25 C)
Load voltage
Frequency range
Max. non-repetitive peak voltage
Max. non-repetitive peak current (t=10ms)
Maximum off state leakage current
Minimum off state dv / dt
DC
5 [.20]
5 [.20]
Input specifications
Diagram
4A, 2A
24V
50 - 60Hz
600V
60V
80A
7A
<1,5mA
<1mA
500V/s
0.24V
1,2V
(at IL=2A)
50mA
1mA
100s
50s
1/2 cicle
600s
+1ms
Maximum on state voltage
Minimum load current
Turn On Time (at nominal voltage)
Turn Off Time (at nominal voltage)
36V
-
Breakdown voltage
Static output on- Resistance (at IL=2A)
Peak power dissipation
50s
600W
References
AC
032
DC
Output voltage type
AC: VAC voltage
DC: VDC voltage
240
Output voltage
24: 24V (only DC)
48: 48V (only DC)
100: 100V (only DC)
240: 240V (only AC)
002
Printed circuit
Control voltage
Relay type
Z: zero crossing
R: random
D: DC
Amps
002: 2A (only AC)
004: 4A (only DC)
Control voltage type
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
32
(02410413)
RVS
Product series
RVS: RVS relays series
Three phase SSR
Load current vs. ambient temperature
Three phase relay - 25 A
Three phase relay - 60 A
40
80
10
40 - 440 VAC
90 - 250 VAC
60 A
RS3A0P032DC440060Z
RSH-038
80 A
RS3A0P032DC440080Z
RSH-038
120 A
RS3A0P032DC440120Z
RSH-039
25 A
RS3A0P250AC440025Z
RSH-035
60 A
RS3A0P250AC440060Z
RSH-038
80 A
RS3A0P250AC440080Z
RSH-038
100 A
RS3A0P250AC440100Z
RSH-039
20
40
60
2.500 VAC
-25 C to 70 C
-35 C to 85 C
Operating: up to 85 %
Yes
Input specifications
VDC input
VAC input
Control voltage range
3 - 32 VDC
90 - 250 VAC
Input current (max)
5/25 mA @= 3 V/32 V 5/30 mA @= 90/250 V
3 VDC
Pick-up voltage
70 VAC
1 VDC
Drop-out voltage
70 VAC
32 VDC
Maximum reverse voltage
10 ms
Max. response time pick-up
10 ms
Max. response time drop-out
WITHOUT HEAT SINK
20
0
80
-30
80
100
RSH-039 HEAT SINK
Load current (A)
RSH-038 HEAT SINK
60
40
-30
60
Three phase relay - 100 A
80
40
RS3A0P032DC440060Z
RS3A0P250AC440060Z
Three phase relay - 80 A
20
20
Ambient temperature ( C)
WITHOUT HEAT SINK
20
40
60
75
50
25
0
80
-30
Ambient temperature ( C)
WITHOUT HEAT SINK
20
40
60
80
Ambient temperature ( C)
RS3A0P032DC440080Z
RS3A0P250AC440080Z
RS3A0P250AC440100Z
Three phase relay - 120 A
120
RSH-039 HEAT SINK
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Ambient humidity
CE marking
40
RS3A0P032DC440025Z
RS3A0P250AC440025Z
Operational Operational
Reference
Reference
voltage
heat sink
current
25 A
RS3A0P032DC440025Z RSH-035
3 - 32 VDC
Load current (A)
Control
voltage
-30
WITHOUT HEAT SINK
60
Ambient temperature ( C)
Load current (A)
References
RSH-035 HEAT SINK
20
Three phase AC solid state relay, zero crossing.
Two input ranges: 3 - 32 VDC and 90 - 250 VAC.
Maximum load current (AC1 at 25 C): 25, 60, 80, 100, 120 A.
Operational ratings: 40 - 440 VAC.
Frequency range: 50- 60 Hz.
Maximum non-repetitive peak voltage: 930 Vp.
LED indicator.
Clip on protective cover for greater safety (IP 20).
Load current (A)
Load current (A)
RSH-038 HEAT SINK
30
90
60
30
0
-30
WITHOUT HEAT SINK
20
40
60
80
Ambient temperature ( C)
RS3A0P032DC440120Z
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
Dimensions (mm. inch)
Output specifications
Maximum load current
(AC51 @ Ta = 25 C)
(AC53a @ Ta = 25 C)
Load voltage range
Frequency range
Max. non-repetitive peak voltage
25, 60, 80, 100, 120 A
5, 15, 18, 20, 21 A
40 - 440 VAC
50 - 60 Hz
930 Vp
350 Ap/ 25 A
1.100 Ap/100 A
Max. non-repetitive peak current (t=10ms) 630 Ap/ 60 A
1.400 Ap/120 A
910 Ap/ 80 A
10 mArms
Maximum off state leakage current
300 V / seg
Minimum off state dv / dt
Maximum on state voltage
1,6 VAC
0,1 Arms
Minimum load current
625 A2s (25 A) 6.050 A2s (100A)
I2t (10 ms) (orientative data)
2.025 A2s (60A)
9.800 A2s (120A)
4.225 A2s (80 A)
Diagrams
Housing specifications
(02410413)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
33
SFMFRVJDL!T/B/!!
106 x 75 x 32
150 gr max.
Aluminum, nickel-plated
1,2 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Motor reversing SSR
Load current vs. ambient temperature
Motor reversing relay - 1 KW
Motor reversing relay - 5 KW
40
80
Load current (A)
Load current (A)
RSH-039 HEAT SINK
30
RSH-038 HEAT SINK
20
10
0
-30
WITHOUT HEAT SINK
20
40
60
This relay is used to invert the turn
direction of an engine, which will
depend on the input circuit.
If the system is powered between the
terminals F and GND, the triphase
network will work in a direct way; if it
is powered between R and GND,
the direction of the engine will be
inverted.
GND - R
10 - 30 VDC
Reference
Reference
heat sink
RS1ARP030DC5301K3Z
RSH-38
RS1ARP030DC5305K3Z
RSH-39
RS1ARP115AC5305K3Z
RSH-39
Operational Max. Load
voltage
Power
1 KW
24 - 530 VAC
90 - 115 VAC
5 KW
-30
20
40
60
80
RS1ARP030DC5305K3Z
RS1ARP115AC5305K3Z
Over 10 A load a heat sink must be used. The use of a heat sink will make
the lifetime of the relay up to four times longer, even when using it with
load currents lower than 10 A.
References
Control
voltage
WITHOUT HEAT SINK
20
Ambient temperature ( C)
RS1ARP030DC5301K3Z
Input control Output connection
GND - F
40
80
Ambient temperature ( C)
Motor reversing solid state relay, AC.
Two input ranges: 10 - 30 VDC and 90 - 115 VAC.
Maximum load power: 1 KW and 5 KW.
Operational ratings: 24 - 530 VAC.
Frequency range: 50- 60 Hz.
Maximum non-repetitive peak voltage: 1.200 Vp.
LED indicator (green: forward; yellow: reverse).
60
Dimensions (mm. inch)
General specifications
Dielectric insulation (between input & output)
Operating temperature
Storage temperature
Rth junction to case
Ambient humidity
CE marking
Input specifications
Control voltage range
Input current (max)
Pick-up voltage
Drop-out voltage
Maximum reverse voltage
Max. response time pick-up
Max. response time drop-out
2,500 VAC
-30C to 80 C
-35C to 85 C
0,25 C/W
0,22 C/W
Operating: up to 85 %
Yes
VDC
10 - 30 VDC
30 mA
8 VDC
4 VDC
30 VDC
cycle
cycle
VAC
90 - 115 VAC
35 mA
85 VAC
30 VAC
-
Diagram
Output specifications
Maximum load current
Load voltage range
Frequency range
Max. non-repetitive peak voltage
Max. non-repetitive peak current (t=10ms)
Maximum off state leakage current
Minimum off state dv / dt
Maximum on state voltage
Minimum load current
I2t (10 ms) (orientative data)
VDC
1 KW
25 A
VAC
5 KW
60 A
24 - 530 VAC
50 - 60 Hz
1.200 Vp
350 Ap / 25 A
850 Ap / 60 A
8 mArms
500 V / seg
1,6 VAC
1,8 VAC
0,1 A
2
625 A s (25 A)
3.600 A2s (60A)
Dimensions (L x W x H mm)
Weight
Baseplate
Control terminal (M3x6) torque
Power terminal (M5x9) torque
SFMFRVJDL!T/B/!!
106 x 75 x 32
430 gr Max.
Aluminum, nickel-plated
1,2 Nm
2,4 Nm
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
34
(02410413)
Housing specifications
Heat-sinks
Over 10 A load a heat-sink must be used. The use of a heat-sink will make the lifetime of the relay up to four times longer, even when using
it with load currents lower than 10 A. The following is a list of Relequicks available heat-sinks, a full range that covers the requirements of
all our solid state relays.
(Notation on mm-inch)
RSH-035
Current < 35A
Rh=1,7 K/W
79 [3.12]
7]
150 [5.91]
[.0
35 [1.38]
71 [2.80]
R2
32 [1.26]
90 [3.54]
90 [3.54]
80 [3.15]
RSH-036
Current < 50A
Rh=1,25 K/W
71 [2.80]
99 [3.90]
80 [3.15]
130 [5.12]
-6
92 [3.62]
-6
.8
8
x0.
130 [5.12]
M4x0.7 - 6H
M5
.7
x0
92 [3.62]
x0
M5
M4
150 [5.91]
48 [1.89]
-6
H
RSH-037
Current < 55A
Rh=1,15 K/W
183 [7.19]
RSH-038
Current < 80A
Rh=0,9 K/W
105 [4.13]
79 [3.11]
105 [4.15]
174 [6.83]
-6
108 [4.27]
125 [4.92]
150 [5.91]
42 [1.65]
90 [3.54]
5x
0.
-6
260 [10.24]
140 [5.51]
113 [4.45]
91 [3.58]
8
0.
5x
M
115 [4.54]
135 [5.31]
50 [1.95]
48 [1.89]
48 [1.89]
RSH-059
Current < 20A
Rh=2,9 K/W
RSH-039
Current < 180A
Rh=0,6 K/W
44 [1.73]
77 [3.04]
115 [4.54]
135 [5.31]
105 [4.15]
105 [4.13]
79 [3.11]
108 [4.27]
46 [1.81]
125 [4.92]
(02410413)
35
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
73 [2.85]
200 [7.87]
M4
x0.
7
-6
47 [1.83]
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Heat-sinks
RSH-060
Current < 25A
Rh=2,15 K/W
79 [3.12]
7]
150 [5.91]
[.0
50 [1.97]
99 [3.90]
80 [3.15]
92 [3.62]
8
x0.
130 [5.12]
M4x0.7 - 6H
M5
72 [2.83]
.7 - 6H
71 [2.80]
R2
71 [2.80]
52 [2.04]
M4x0
90 [3.54]
80 [3.15]
61 [2.40]
83 [3.27]
RSH-061
Current < 40A
Rh=1,42 K/W
-6
H
RSH-062
Current < 45A
Rh=1,38 K/W
100 [3.94]
RSH-063
Current < 50A
Rh=1,32 K/W
100 [3.94]
51 [2.01]
51 [2.01]
124 [4.88]
M4 x 0
180 [7.09]
80 [3.15]
- 6H
110 [4.33]
x0.7
110 [4.33]
M4
49 [1.93]
49 [1.93]
113 [4.45]
M 5x
.7 - 6H 0.8 - 6H
113 [4.45]
124 [4.88]
RSH-MR
Current 5A
81 [3.19]
48 [1.87]
6H
6H
7-
8-
x0.
x0 .
M4
M5
65 [2.56]
8 [.32]
44 [1.75]
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
36
(02410413)
34 [1.34]
MODULES
RFS1SL Programmable solid state relay
Features
This module have 9 different time functions. The program
range is from 0,1 second to 999 hours timing.
There are RFS1 modules in VAC output (zero crossing and
random) and other in VDC output (with different polarities).
The led allows to see the relay status.
Our free software DEVICES PROGRAMMER* allows to
make a chain of time and PWM functions in a very easy
way.
This electronic module (plug and play in our sockets SF) is a solid state
relay that can be programmed with diferent time functions and PWM.
References
Reference
Polarity output
Output voltage
RFS1SL028DC0P
DC positive common
RFS1SL028DCNP
DC negative common
RFS1SL028AC0P
AC random
RFS1SL028ACZP
AC zero cross switching
5 - 50VDC
1,5 - 250VAC
Nominal values
Supply voltage
Programming time range
Time precision
Repeatability
Reestablishment time
Indicator(indicates the state relay output)
5 - 28 VDC
1ms - 999Hours
0,05% of set time
0,01% of set time
>300ms
Green led
Input ratings
Input current (max)
Pick-up voltage
Drop-out voltage
Max. reverse voltage
Max. response time pick-up
Max. response time drop-out
10 - 20 mA
5 VDC
3 VDC
28 VDC
1 ms
2 ms
Specifications
Functions
The RFS1 have different functions easy to program:
- Timing functions: simple or cycles.
- Control PWM.
For more information look the page 48.
Room humidity
Supply frecuency (AC)
Load current / temperature
Output relay
13 [.50]
Load current (A)
36 [1.42]
20 [.78]
Socket solid state relay (AC load)
RFS1SL028ACZP/0P
Dimensions
Working T
-20 C to 60 C
Storage T
-20 C to 100 C
5% to 85 %
50 - 60 Hz
Maximum load current
3 A(AC)
(AC51 @ Ta = 25 C)
2 A(DC)
1.5 - 250 VAC
Load voltage range
5 - 50 VDC
Maximum non-repetitive 250 VAC
peak voltage
150 VDC
Maximum non-repetitive
20 Ap
peak current (t = 5 ms)
Maximum off state
1 mA
leakage current
Min. off state dA / dt 5 A / 350 s
Room temperature
Max. on state voltage
Ambient temperature ( C)
Min. load current
Load current (A)
RFS1SL028DC0P/NP
Socket solid state relay (DC load)
4,8 [.19]
30 [1.19]
Ambient temperature ( C)
Uses and applications
All program timing functions at very fast switching time, because
it is a Solid state relay, with relay output 250VAC (3A) or 50VDC (2A).
I2t (5 ms)
(orientative data)
Insulation dielectric strength
(between input & output)
Mounting
Dimensions
Weight
CE- marking
Protection class
Pack Units
<1.5 VAC
<1.5 VDC
0.1 A
1 A 2s
3,750 KV
Faston standard form
29x13x40
23 gr
yes
IP20
10
Circuit diagrams
(02410413)
Accesories
To program by usb is required cable ref CPCD01.
39
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
MQPMM Timer and counter module
Features
This module has 21 programmable functions, the timing range is
from 0,1 second to 999 hours and a counting capacity until 999
cycles with high precission.
It can be used with different relay models because the MQPMM
has a wide range of charges (24-230VAC, 12-115VDC). The LCD
allows to see the program status and the relay activity.
Our free software DEVICES PROGRAMMER* allows to make a
chain of time and count in a very easy way.
This electronic module (plug and play in our sockets SQ and SM) can
be programmed to control the relay that is connected in the socket
and work according with the program working in many ways.
It allows that one standard relay works like an output miniPLC with a
wide range of current and voltages.
It is possible to program the MQPMM with the buttons without the
PC.
The B conection in the socket allows a external signal, from a PC,
sensor, push button etc... allowing to change the relay status.
Nominal values
Reference
Reference
Type
MQPMM (easy control)
plugin timer module
Functions
The MQPMM has different functions easy to program:
- Timing functions: simple or cycles.
- Counter: simple or cycles.
- External signal: timing or counting according with the program.
For more information look at the pages 49 and 50.
Dimensions (mm-inch)
Supply voltage (U)
Timing range
VAC (50 / 60 Hz)
VDC
24 - 230
12 - 115
0,1seconds - 999 hours
Counter range
1 - 1000000
Timing precision
0.05 % of set time
Repeatability
0.01 % of set time
Reestablishment time
Minimum B signal duration
Maximum counter frequency
> 300 ms
> 23 ms (VDC) - 50 ms (VAC)
21Hz (VDC)-10 Hz (VAC)
(125 Hz under request)
program mode and relay output state
Indicator(LCD)
43 [1.71]
Specifications
Room temperature
Room humidity
24 [.94]
Supply frecuency (AC)
Nominal power AC/DC (W)
Mounting
22 [.86]
Uses and applications
Working T
Storage T
-10 C to 60 C
-20 C to 60 C
5% to 85 %
50 - 60 Hz
0.1 W (12 VDC) - 0.5 W (115 VDC)
Interface in SQ series and SM series sockets
43,5x24x21,8mm
11gr
Yes
Dimensions
Weight
CE - marking
Protection class
Pack Units
IP20
1
Switching and programming the module in our socket, you get more
advantages in your applications.
Example: you can have a timer and a counter for resistive or inductive
charges with a relay output 230VAC, 16A only switching our MQPMM in
the SQ socket with the adecuate relay.
Accesories
- It is necessary to program, use the cable ref: CPCD01.
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
40
(02410413)
- Interface MMA10 to use the MQPMM in the socket SM.
SVT10D010024V SlimLine timer
Features
Programmable multi function electronic device. Up to 6
functions can be configured with 3 trimmers and using 6
different time scales:
[0,05 - 1] [0,5 - 10] [5 - 100] seconds
[0,5 - 10] [5 - 100] minutes
[0,5 - 10] hours
Compact design (6,22 mm), easy mounting and wiring.
SPDT 1-relay output with switching capacity of 6A.
Rail DIM 35mm (T35).
Timing range: 0,05 seconds to 10 hours.
LED indication of relay excitation.
One model covers the whole tension range 12 - 24AC/DC.
Easy programming: This timer can be programmed using a
lower scale to adjust their values better. Once the value is
the electronic programmable module has been specifically designed for
timing and controlling 5,08 mm PCB relays. The module can be mounted
on a DIN-rail and thanks to its 6,22 mm width and compact design it will
take up minimum space on any control panel.
programmed, the scale can be changed to the adequate
level to be used in operating mode.
Numbering identification label relay.
Retaining clip relay, Anti Shake.
With its 6 different functions and the wide timing range available (from 0,05
Nominal values
seconds to 10 hours) the module offers great control versatility within a
Supply voltage
reduced space.
from 0,8 to 1,1Un (12-24
VAC/DC)
Rated power
0,5W
Programming timing range
Functions
Operation time
Function
On pulse
(switch-off delay)
Asymmetrical cycle
(start ON)
Output relay
1 SPDT relay with 6A switching
capacity
(AC1 / 250 V - DC1 / 30V)
Breaking capactity
6/0,2/0,15 (DC1 30/110/220V)
applications and buildings. With our programmable timer
module it is possible to adjust how the system must works,
and its different programmable functions make it useful in
U
a wide range of possible environments.
R
U
Specifications
t
t/2
t/2
Room temperature
-10 C to 60 C
-20 C to 70 C
5% to 85 %
50 - 60 Hz
Resistive load 6A at 250VAC (cos =1)
6A at 30VDC (L/R = 0 ms)
1A at 250VAC (cos=0.4)
Inductive load
1A at 30VDC (L/R = 7 ms)
Electrical life 104cycles
7
Mechanical life 10 cycles
Max. screw torque
Mounting
Dimensions
1 [.04]
35 [1.38]
6 [.25]
15 [.58]
76 [2.99]
(02410413)
Working T
Storage T
Room humidity
Supply frecuency (AC)
Output relay
5 [.20]
Green LED
It is often useful in all kind of systems, from industrial
Dimensions (mm-inch)
28 [1.10]
Relay excited
Uses and applications
0.5 sec
Symmetrical cycle
(start OFF)
+ 1% of set time
Indicators
U
Symmetrical cycle
(start ON)
0,01 seconds
Timing precission
Diagram
On delay
(switch-on delay)
Fixed pulse
0,05 seconds to 10 hours
0.6Nm
DIN-rail
6,22 x 90 x 76 mm
Weight
CE - marking
23 gr
Yes
Protection class
Pack Unit
IP20
20
This timer can be used with 12VDC and 24VDC relays.
41
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Modules Standard SQ/SF
The use of indication and protection modules increases the relays
life and verifies their state.
Dimensions (mm-inch)
Use them to avoid the destructive effects from the
peaks produced by the variation of current when the relays are
used with inductive charges.
SF module
Free-wheeling diodes, varistors, or RC (snubber circuits)
are very useful in these cases.
SQ module
Functions
Operating Range
ByPass Module
Code
SF
SQ
(110-230VAC)
M11F
M11Q
(6 -24 VDC)
M12F
M12Q
(48 - 60 VDC)
M22F
M22Q
(110-230VDC)
M32F
M32Q
(6 -24 VDC)
M13F
M13Q
(48 - 60 VDC)
M23F
M23Q
(110-230VDC)
M33F
M33Q
(6 -24 VAC/VDC)
M14F
M14Q
(48 - 60 VAC/VDC)
M24F
M24Q
(110-230VAC/VDC)
M34F
M34Q
(6 -24 VAC/VDC)
M15F
M15Q
(48 - 60 VAC/VDC)
M25F
M25Q
(110-230VAC/VDC)
M35F
M35Q
(6 -24 VAC)
M16F
M16Q
(48- 60 VAC)
M26F
M26Q
(110-230VAC)
M36F
M36Q
(6 -24 VAC)
M17F
M17Q
(48- 60 VAC)
M27F
M27Q
Led + Diode
module
standard polarity
Led + Diode
module
inverse polarity
Led module
RC module
Led + Varistor
module
Rectifier + LED
module
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Description
Diagrams
Bypass module is used between 110-230VAC.
The module prevent the residual currents that may arise,
affecting the relays coil.
LED + Diode Module is used in VDC, if the led is
lit, the relay is energized. The negative peak voltages
are shorted by the diode in parallel.
The positive is connected to A1 contact.
LED + Diode Module is used in VDC, if the led is lit, the
relay is energized. The negative peak voltages are
shorted by the diode in parallel.
The positive is connected to A2 contact.
LED Module is used in VAC/VDC, if the led is lit the relay
is energized, for the VDC it should be noted that the
positive must be connected to A1 contact.
RC Module is used in VAC/VDC. The RC circuit protect
the coil from the voltage spikes.
LED + Varistor Module is used in VAC relays, the varistor
limits the voltage spikes that can reach the relay coil.
The LED indicates if the relay is energized. For VDC be
noted that the positive must be connected to A1.
Rectifier + LED Module is used in VDC, The module
rectifies the AC input to allow excite coils with currents
in DC. The LED indicates if the relay is energized.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
42
(02410413)
Function
MCU Current monitoring relay
Features
The module can be used in two different ways:
Manual mode: configure the function n 0 only using the
trimmer.
Programming mode: With our Devices Programmer
software* it is possible to program easily up to different
functions.
Over, under and window current monitoring with a
measuring range from 0,5 to 10A.
Adjustable switch-on/off delay. LED indication of power and
alarm.
There are 2 models, with different power supply voltage.
Nominal values
from 0,8 to 1,1Un12 - 24 VAC/VDC
Supply voltage
This electronic current monitoring relay has been specially designed to
control the intensity on single-phase AC/DC circuits. It compares the set
intensity value to the real intensity supported by the circuit, activating the
alarms and outputs of the relevant relays in order to protect the system
against over and undercurrent between 0,5 and 10A (250 V). For currents
greater than 10A a transformer is used (view diagram).
References
Modules Reference
Imput voltage
12/24VAC/DC
MCU230R2
110/230VAC/DC 2 relay: 6A (250VAC/30VDC)
Accesories Reference
CPCD01
DEVICES
PROGRAMMER
Current reading range
Current precision
Switch-on delay
Programming time range
Time accuracy
Repeatability
Indicators
Output relays
MCU024R2
from 0,8 to 1,1Un110 - 230 VAC/VDC
0,5 - 10 A (AC/DC; without transformer)
20- 200 A with commercial CT
AC
+ 5% of full scale
DC
+ 5% of full scale
AC
0,02 seconds
DC
0,2 seconds
0,1 seconds -999 hours
+ 1% of full scale error
0,01% of set time
Alarm
Red LED
Supply
Green LED
Specifications
2 relay: 6A (250VAC/30VDC)
Working T
Room
Temperature
Type
special cable USB<-->mini-USB
Software
Storage T
Room humidity
Supply frequency (AC)
Overcurrent transient
(burst) - 100 ms
Functions
Output relays
Max. screw torque
Mounting
Dimensions
Weight
CE marking
Protection class
-10 C to 45 C (24 V)
-10 C to 60 C (230 V)
-40 C to 70 C
25% to 85%
50 / 60Hz 5Hz
50A
6 A at 250 VAC (cos =1)
Resistive load
6 A at 30 VDC (L / R = 0 ms)
1 A at 250 VAC (cos =0,4)
Inductive load
1 A at 30 VDC (L / R = 7 ms)
7
10 cycles
Mechanical Life
Electrical Life
3 x 104 cycles
0,8 Nm
DIN-rail (35 mm)
22,5 x 76 x 105 mm
115 gr
Yes
IP20
Connection diagrams
Uses and applications
Protection of engines against over- and/or undercurrent.
Detection of resistor failures on heating systems.
Current consumption control.
Security applications for the industry, buildings, lighting etc.
Dimensions (mm-Inch)
(07410413)
Functions 0 to 14 can be configured on a PC with our Devices Programmer software. The user can then load them
onto the module with the cable( CPCD01 ) provided by Relequick, S. A.
43
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
MPH 3-ph loss, asymetry, sequency monitoring
Features
The module can be used in two different ways:
Manual mode: configure the function n 1 only using the trimmer.
Programming mode: With our Devices Programmer software it is
possible to program easily different functions, as the percentage
values of asymmetry and time delay.
The powering of the module is the same three-phase voltage to
be monitirized.
The module can detect asymmetry fails from 2% to 22% of
nominal voltage, the voltage range from 200 to 480VAC.
Adjustable switch-on/off delay.
Led indications of power, status relay and alarm.
Models with 2 different voltage range of power supply.
Nominal values
200 - 240 VAC
Supply voltage
This electronic digital programmable relay has been specially,
designed to monitor the voltage asymmetry, loss of phases
sequence and loss of phase for three -phase power systems.
From 2% until 22% of nominal voltage
+ 2% of full scale
Voltage reading precission
Switch-on delay
0,02 seconds
0,1 seconds -145 seconds
Programming time range
References
Modules Reference
Input and measure voltage
MPH240R1
MPH480R1
Time accuracy
+ 1% of set time
Repeatability
0,01% of set time
Red LED
200 to 240 VAC
380 to 480 VAC
Accesories Reference
CPCD01
DEVICES
PROGRAMMER
380 - 480 VAC
Voltage asymetry range
Indicators
Alarm
Supply
Green LED
Relay status
Yellow LED
Type
special cable USB<-->mini-USB
Specifications
Software
Room
Temperature
Functions
Working T
-10 C to 60 C
Storage T
-40 C to 70 C
Room humidity
25% to 85%
Supply frequency (AC)
50 / 60Hz 5Hz
Burst current 100 ms.
400 A, 100 ms max.
Resistive load
Output relays
Functions 0 to 3 can be configured on a PC with
our Devices Programmer software. The user can
then load them onto the module with the cable
( CPCD01 ) provided by Relequick, S. A.
Max. screw torque
Mounting
Dimensions
Weight
CE marking
Protection class
Inductive load
Mechanical Life
Electrical Life
6 A at 250 VAC (cos =1)
6 A at 30 VDC (L / R = 0 ms)
1 A at 250 VAC (cos =0,4)
1 A at 30 VDC (L / R = 7 ms)
7
10 cycles
3 x 104 cycles
0,8 Nm
DIN-rail (35 mm)
22,5 x 76 x 105 mm
150 gr (5.29 Oz)
Yes
IP20
Connection diagrams
3
2
1
ON
SELECTORS
Uses and applications
Dimensions mm (Inch)
The asymmetry, sequence detection and phase loss monitoring has
great applications in industry, buildings, and all kinds of electrical
installations, both in load monitoring, as in protection of machines
or small installations.
Protection and prevention due to an imbalance of the asymmetric
or one phase loss or the inverse of sequency power in any kind of
three phase motors.
Preventing damages or overheating in the engines.
Motors, pumps, compressors, forklifts, generators... all of them may
be protected with this device in case of phase failures.
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
44
(07410413)
Some common applications are the following:
SMX-T80 GSM module
Features
SMX-80 module is the solution for the remote monitoring and control of the
temperature.
The SMS temperature information will be received in the mobile phone,
also the variations of all values, installation state and fails.
The mobile phone sends a SMS to the module programming the relays
output and control the device.
The Kit has SMX-T80 antenna FME and power supply.
Functions
Programmed by SMS and protected by password.
Information reforwarding without further configuration.
Two switch-buttons for the manual control of the relays.
Manual push button to recharge the temperature advices
programmed. Reset push button to return factory
program.
Two output relays are prepared for control for Switch-on or
off and timing.
One relay can be adjusted as a thermostat (adjustable
hysteresis) with two working ways:
Hot mode: Close when T is lower than the T
programmed.
Cool mode: Close when T is upper than the T
programmed.
Any change on the relay 2 when there are an advice of
temperature change can be made in three ways:
Automatic: reestablish the alarm when the temperature
return to the programmed values.
Forced: Maintain fix the last advice produced.
Timing: Avoid a large number of alarm messages (SMS).
Nominal values
Supply voltage
Output relay control by SMS, (2 output relays).
Battery supply option to avoid electricity fails. Inform of power supply
failure by SMS.
Inform of the temperature changes according with the program by SMS.
Inform of connection fail or failure of the temperature sensor by SMS.
First relay can be programmed to work as a thermostat.
Second relay can be programmed according with the temperature
value setting.
Communication
Supply not battery charging
Cinterion modem MC55i
Modem reboot
delay in case
of signal failure
10 seconds
0,02 seconds
Switch-on delay
Indicators
Led
Status
Dimensions (mm-inch)
66 [2.59]
Room
Temperature
40 [1.57]
Power supply
80 [3.14]
45 [1.78]
105 [4.13]
Accesories
Temperature sensor SMX-TEM.
The external temperature sensor has a range between -25 C to 85C.
Battery SMX-BAT.
Plum battery of 2V with 800mA, in box format with jack connector for
SMX-T80.
Antennas SMX-AN1 and SMX-AN2.
(02410413)
Rail DIN accessory SMX-DIN.
SFMFRVJDL!T/B/!!
System switch on
System without alarm
Yellow blinking
Green alarm
Red alarm
Waiting program
Lower temperature
Temperature alarm
Green led
GSM communication
Working T
Storage T
-5C to 50 C
-10C to 60 C
Working
5% to 85%
Storage
5% to 85%
Max. comsuption (during Battery charge) 5 W
1-4 terminals allows 12VDC of supply for other device
Supply frequency
(AC)
Output relays
45
Yellow regular
Yellow
Specifications
Room humidity
95 [3.74]
10 - 28V
Supply battery Charging
17 -28V
GSM 4 bands 800/900/1.800/1.900 MHz
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
50 / 60 Hz
Resistive load
5 A at 250 VAC (cos = 1)
5 A at 30 VDC (L / R = 0 ms)
Inductive load
1 A at 250 VAC (cos = 0,4)
1 A at 30 VDC (L / R = 7 ms)
Mechanical Life
10 cycles
Electrical Life
3 x 104 cycles
Mounting
Pannel mounting with accesory for rail DIN SMX-DIN
Dimensions
146 x 105 x 45 mm
Weight
166 gr
IP protection
IP 40
CE marking
Yes
Uses and applications
Monitoring in real time and programming the temperature.
Food warehouses.
Heating and freezing systems.
Cold stores.
Computer installations.
Laboratories.
In every place where the temperature is important to
control.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
SMX-G50 GSM module
Features
Functions
Nominal values
Supply not battery charging
Supply voltage
Communication
Output relay control by SMS, (Two output relays).
Battery supply option to avoid electricity fails. Inform of power
supply failure by SMS.
Inform of the temperature changes according with the
program by SMS.
Inform of connection fail or failure of the temperature sensor by
SMS.
Two alarms input that advice by SMS when they open or close
according with the program.
Control the output realy using X10 module.
The relays 2 and 3 can be controlled for switch-on or switch-off
and timing.
It can send orders to any X10 device.
Dimensions (mm-inch)
10 seconds
0,02 seconds
Switch-on delay
Led
Status
Yellow regular
Yellow
System switch on
System without alarm
Yellow blinking
Green alarm
Red alarm
Waiting program
Lower temperature
Temperature alarm
Green led
GSM communication
Specifications
Room
Temperature
Room humidity
66 [2.59]
Cinterion modem MC55i
Modem reboot
delay in case
of signal failure
Indicators
Power supply
Working T
Storage T
-5C to 50 C
-10C to 60 C
Working
5% to 85%
Storage
5% to 85%
Max. comsuption (during Battery charge) 5 W
1-4 terminals allows 12VDC of supply for other device
40 [1.57]
Supply frequency
(AC)
Output relays
80 [3.14]
95 [3.74]
45 [1.78]
105 [4.13]
Accesories
Temperature sensor SMX-TEM.
The external temperature sensor has a range between -25 C to
85C.
Battery SMX-BAT.
Plum battery of 2V with 800mA, in box format with jack connector for SMX-G50.
10 - 28 V
Supply battery Charging
17 -28 V
GSM 4 bands 800/900/1.800/1.900 MHz
50 / 60 Hz
Resistive load
5 A at 250 VAC (cos = 1)
5 A at 30 VDC (L / R = 0 ms)
Inductive load
1 A at 250 VAC (cos = 0,4)
1 A at 30 VDC (L / R = 7 ms)
Mechanical Life
10 cycles
Electrical Life
3 x 104 cycles
Mounting
Pannel mounting with accesory for rail DIN SMX-DIN
Dimensions
146 x 105 x 45 mm
Weight
166 gr
IP protection
IP 40
CE marking
Yes
Uses and applications
This remote control module can be used in all the industrial and
domotic instalations in special cases that the electrical system
needs to be controlled in an easy way and in distance.
Antennas SMX-AN1 and SMX-AN2.
Garage doors.
External control of temperature systems.
Cooling and heating systems.
Domotic and industrial automation.
Rail DIN accessory SMX-DIN.
In every place where the temperature is important to control.
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
46
(02410413)
SMX-G50 module is the solution for the remote monitoring and
control the temperature.
The SMS temperature information will be received in the mobile
phone, also the variations of all values, installation state and fails.
The mobile phone sends a SMS to the module programming the
relays output and control the device.
The Kit has SMX-G50, antenna FME, RS232 cable, and power
supply.
Programmable by SMS and Gplus software free. Protected by
password.
Information return without programming necessities.
Two digital Inputs one to connect a external thermostat.
Connection with X10 devices.
Three output relays are controlled for Switch-on or off and timing.
Manual push button control the relay 1 allowing pass from switch-on to switch-off only pushing time to time.
Reset push button to return factory program.
Control the relay 1 output to X10 adress working like a heatting
system according with the thermostat input allowing switch-on or
switch-off and timing and fix a value with the external thermostat.
Alarm of Max and Min. temperature.
the alarms can be sent to 3 mobile phones.
Indication LED state of the heating system and GSM communication.
Software Devices Programmer
Devices Programmer is a software for easy configuration to use with a
friendly graphic in which can be selected the different functions for each
module.
Devices Programmer is a tool that allows to edit, compile and download
the implemented program into the modules memory.
The software has a main menu and each function has a
short description about it.
It is possible to select the language among English,
French, Spanish and German.
The software can be downloaded from our website
www.relequick.com, freely.
Always to program our modules, you need to use our
cable converter series - USB CPCD01.
Easy selection among the different modules.
This software can be use to program the following
modules:
MQPMM, RFS1, MCU and MPH. Sooner in
more modules.
Note: you must disconnect the power supply of the
module before connecting it with the PC.
To create a program is simple and intuitive in that software, allowing the
development of complex programs with our modules.
You can save the program in your computer, so you can load the
program developed in all the modules you want.
Programming modules RFS1 and MQPMM
The program allows you to select the appropriate functions in an easy
way through various windows and drawings for each function.
All functions are placed in the main window in order to easily see the
program that you are editing.
The program is developed as a flow diagram in the workspace for an
easy understanding
"Devices Programmer" allows to program many functions in the same
module making chains of functions and jumping between them.
Allows to change the functions programmed only with a Click.
The flow diagram of the program finalizes with the word End or with a
(02410413)
flowchart jump making a loop.
47
SFMFRVJDL!T/B/!!
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Software Devices Programmer
Programming modules MCU and MPH
-The module has a factory program installed that may be
programmed by selectors. The sofware allows program different
functions by the USB cable. It also allows back to factory mode.
- The function programmed by the software gets more accuracy
than the program made by the potentiometers.
- The programs of these modules are shown so that understanding is easy and intuitive .
- Allows to change the functions programmed only with a Click
Programming the modules
Once the program is finished, it can be donwloaded into the module in three very easy steps:
1. Create a connection with the module:
- Choice the USB communications port in Programming > Port.
- Establish the communication Click in the icon
and the signal of the connection will change to green.
2. Compile the program.
- Compile the program Click in the next icon:
3. Download the program in the module memory.
- Download the program Click in the next icon:
Note: you must turn-off the power supply of the module before to connect the module with the PC.
Functions of RFS1 solid state relay programmable
Switch-on delay
Switch-off delay
Pulse delay
Initial state
CO
NO
CO
NO
CO
NO
Diagram
U
NO
Symmetric timing
cycle (starting open)
CO
NO
Asymmetric timing
cycle (starting closed)
CO
NO
CO
NO
PWM progressive disconnection
ramp (for DC loads)
SFMFRVJDL!T/B/!!
t2
t1
R
U
Once the module is powered a symmetric cycle
begins, being the relay closed for a t timelapse and
open during the next t interval.
Once the module is powered a symmetric cycle
begins, being the relay open for a t timelapse and
closed during the next t interval.
t1
t2
t1
t2
t1
Once the module is powered an asymmetric cycle
begins, being the relay closed for a t1 timelapse and
open during a t2 interval.
t1
t2
t1
t2
t1
Once the module is powered an asymmetric cycle
begins, being the relay open for a t1 timelapse and
closed during a t2 interval.
R
CO
CO
NO
NO
R
U
After a t1 delay the relay is switched on, and keeps
on for a t2 lapse. The delay begins when the module
is powered.
t2
t1
Delay timing (t time) to the disconnection of the relay.
CO
PWM progressive connection
ramp (for DC loads)
R
U
Symmetric timing
cycle (starting closed)
Asymmetric timing
cycle (starting open)
Description
Delay timing (t time) to the connection of the relay.
The relay is connected slowly as a progressive
connection ramp (PWM). It is completed during the
specified time t.
The relay is disconnected slowly as a progressive
disconnection ramp (PWM). It is completed during
the specified time t.
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
48
(02410413)
DC load regulation Symmetric and asymmetric cycle timing functions
Simple timer
Function name
Software Devices Programmer
Functions MQPMM timer and counter module
F0:CONNECTION DELAY
Once the system is supplied with a voltage U, after
a time t, the relays R1 and R2 will be activated
simultaneously. ( the relay R2 is only available for
models MTIR2 and MTIR2 MODBUS )
A - SIMPLE TIMER
U
R1
R2
F1:DISCONNECTION DELAY
Once the system is supplied with a voltage U, after
a time t, the relays R1 and R2 will be deactivated
simultaneously. ( the relay R2 is only available for
models MTIR2 and MTIR2 MODBUS )
A - SIMPLE TIMER
U
t
R1
R2
F2:CONNECTION DELAY BY FLANK
Once the system is supplied with a voltage U,
when an up flank of the signal B1 is produced, the
relays R1 and R2 will be activated simultaneously
after a time t. In the modules that have input B2, as
MTIR2, the state of this signal B2 is irrelevant in this
function. (the relay R2 is only available for models
MTIR2 and MTIR2 MODBUS ).
B - TEMPORIZED WITH SIGNAL B1
U
B1
R1
R2
F3:ACTIVATION WITH U AND DISCONNECTION
DELAY BY FLANK EDGE OF SIGNAL B1
Once the system is supplied with a voltage U, the
relays R1 and R2 will be activated. When an up
flank of the signal B1 is produced, the relays R1 and
R2 will be deactivated simultaneously after the
programmed time t. In the modules that have
input B2, as MTIR2, the state of this signal B2 is
irrelevant in this function. (the relay R2 is only
available for models MTIR2 and MTIR2 MODBUS ).
B - TEMPORIZED WITH SIGNAL B1
U
B1
t
R1
R2
B - TEMPORIZED WITH SIGNAL B1
U
t1
B1
t2
t3
t+t1+t2+t3
R1
c
t+t1+t2+t3
R2
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
t2
R1
t1
R2
t1
t2
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
B1
t2
R1
t2
t1
t1
t2
R2
t2
t1
t1
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
F4:DISCONNECTION DELAY BY DOWN FLANK , WITH
RELAY CONNECTION BY UP FLANK OF SIGNAL B1
Once the system is supplied with a voltage U,
When an up flank of the signal B1 is produced,the
relays R1 and R2 will be activated simultaneously.
With the flank down of the same pulse, a time t
starts and at the end of that time the relays R1 and
R2 will be deactivated simultaneously. If before the
end of time t there is a new pulse of the signal B1,
a new time t will begin with the down flank of the
second B1 and at the end ot this time t the relays
R1 and R2 will be deactivated simultaneously and
so forth. In the modules that have input B2, as
MTIR2, the state of this signal B2 is irrelevant in this
function. (the relay R2 is only available for models
MTIR2 and MTIR2 MODBUS).
B - TEMPORIZED WITH SIGNAL B1
U
B1
R1
R2
B - TEMPORIZED WITH SIGNAL B1
F5:DISCONNECTION DELAY BY UP FLANK OF SIGNAL
B1
Once the system is supplied with a voltage U,
When an up flank of the signal B1 is produced, the
relays R1 and R2 will be activated simultaneously
for a time t. In the modules that have input B2, as
MTIR2, the state of this signal B2 is irrelevant in this
function. (the relay R2 is only available for models
MTIR2 and MTIR2 MODBUS).
U
B1
R1
R2
F6:DISCONNECTION DELAY BY FLANK DOWN OF
SIGNAL B1
Once the system is supplied with a voltage U,
When a down flank of the signal B1 is produced,
the relays R1 and R2 will be activated
simultaneously for a time t. In the modules that
have input B2, as MTIR2, the state of this signal B2 is
irrelevant in this function. (the relay R2 is only
available for models MTIR2 and MTIR2 MODBUS).
B - TEMPORIZED WITH SIGNAL B1
U
B1
R1
R2
B - TEMPORIZED WITH SIGNAL B1
F7:DISCONNECTION DELAY BY UP OR DOWN FLANK
OF SIGNAL B1
Once the system is supplied with a voltage U,
When a up flank of the signal B1 is produced, the
relays R1 and R2 will be activated simultaneously
for a time t. If before the end of time t there is a
down flank of the signal B1, the relays R1 and R2
will remain active again a time t from the down
flank of the signal B1. In the modules that have
input B2, as MTIR2, the state of this signal B2 is
irrelevant in this function.
U
t
B1
R1
R2
R1
R2
(02410413)
B1
t1
t2
t+t1+t2
R1
R2
t+t1+t2
49
SFMFRVJDL!T/B/!!
F8:DISCONECTION DELAY INTERRUPTIBLE BY UP
FLANK OF SIGNAL B1
Once the system is supplied with a voltage U, and
after the programmed time t, the system will start
to count the time of duration t1 when the firt pulse
of B1 is finished. It will count for a time a, it will be
interrupted by a second pulse of B1 of duration t2
and at the end of the second pulse the system will
start to count for a time b, once the time b is
finished lthe relays R1 and R2 will be activated
simultaneously and remain active while power is
supplied. So the total delay will be the sum of t + t1
+ t2 etc., also t will be the sum of a+b+c...+n
interruptions. In the modules that have input B2, as
MTIR2, the state of this signal B2 is irrelevant in this
function.
t
t
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
t
R1
t
t
R2
F10:PULSE DELAY
Once the system is supplied with a voltage U,
after a programmed time delay t1, the relays R1
and R2 will be activated simultaneously for a time
t2.
F11:PULSE DELAY WITH SIGNAL B1
Once the system is supplied with a voltage U,
after an up flank of the signal B1, It starts a delay
time t1 after which the relays R1 and R2 will be
activated simultaneously for a time t2. In the
modules that have input B2, as MTIR2, the state of
this signal B2 is irrelevant in this function.
F12:SYMMETRIC TIMING CYCLE (INITIALLY
ACTIVATED)
Once the system is supplied with a voltage U, a
symmetric timing cycle starts with time value t
for the activation and time t for the deactivation
until supply termination. The relays R1 and R2 are
initialy activated.
F13:SYMMETRIC TIMING CYCLE (INITIALLY
DEACTIVATED)
Once the system is supplied with a voltage U, a
symmetric timing cycle starts with time value t
for the activation and time t for the deactivation
until supply termination. The relays R1 and R2 are
initialy deactivated.
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
t1
t1
R1
t2
t2
t1
t1
R2
t2
t2
F14:ASYMMETRIC TIMING CYCLE (INITIALLY
ACTIVATED)
Once the system is supplied with a voltage U, an
asymmetric timing cycle starts with time value
t1 for the activation and time t2 for the
deactivation until supply termination. The relays
R1 and R2 are initialy activated.
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
F15:ASYMMETRIC TIMING CYCLE (INITIALLY
DEACTIVATED)
Once the system is supplied with a voltage U, an
asymmetric timing cycle starts with time value
t1 for the activation and time t2 for the
deactivation until supply termination. The relays
R1 and R2 are initialy deactivated.
U
t2
R1
t2
t1
t1
t2
R2
t2
t1
t1
E - SIMPLE COUNTING
U
1 23
B1
56
7 . . . n
R1
R2
E - SIMPLE COUNTING
U
1 23
B1
56
7 . . . n
R1
R2
G - SYMMETRIC / ASYMMETRIC COUNTING
U
1 2 3 . .n
B1
B - TEMPORIZED WITH SIGNAL B1
t
t
F9:CONNECTION DELAY INTERRUPTIBLE BY DOWN
FLANK OF SIGNAL B1
Once the system is supplied with a voltage U, and
after a programmed time delay t, this shall begin
with the start of the first pulse duration B1 "a", will
be interrupted by the down flank of the first pulse
B1, it will be stopped a time t1 to start again with
the second pulse duration B1 "b", will be
interrupted by the down flank of the second
pulse B1 and it will be stopped a time t2 to start
again with the third pulse duration B1 "c", and
elapsed a time t3 relays R1 and R2 will be
activated until supply termination. The total
retarded time will be the sum of t+t1+t2+t3 etc.,
also t will be the sum of a+b+c...+n pulse times. In
the modules that have input B2, as MTIR2, the
state of this signal B2 is irrelevant in this function.
1 2 3 . .n
R1
R2
Index
category
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
F16:COUNTER TO CONNECTION BY "N" UP FLANKS
OF SIGNAL B1
Once the system is supplied with a voltage U,
when the system recieves n pulses of the signal B1
the relays R1 and R2 will be activated in the up
flank of the n pulse of the signal B1 and will remain
ativated until supply termination. In the modules
that have input B2, as MTIR2, the state of this
signal B2 is irrelevant in this function.
F17:COUNTER TO DISCONNECTION BY "N" UP
FLANKS OF B1
Once the system is supplied with a voltage U,
when the system recieves n pulses of the signal B1
the relays R1 and R2 will be deactivated in the up
flank of the n pulse of the signal B1. In the
modules that have input B2, as MTIR2, the state of
this signal B2 is irrelevant in this function.
F18:SYMMETRIC COUNTER CYCLE BY "N" UP
FLANKS BY B1(INITIALY ACTIVATED)
Once the system is supplied with a voltage U, the
relays R1 and R2 will remain active until the arrival
of n pulses of signal B1. When the up flank of the
pulse n of the signal B1 arrives, the relay R1 and R2
will be disconnected. The relays will remain on
that state until the arrival of new n pulses of signal
B1, activating the relays with the up flank of the
pulse n of the signal B1 arrives. In the modules that
have input B2, as MTIR2, the state of this signal B2
is irrelevant in this function.
Category description
Index
category
Category description
Simple timer
Simple counter
Temporized functions with signal
B1
Temporized functions with signal
B1 and B2
Temporized
symmetric/asymmetric
Complex counter
Counter Asymmetric /Symmetric
Load controls DC (pwm)
C
D
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
E-mail: info@relequick.com
www.relequick.com
Software Devices Programmer
U
B1
1 2 3 . .n
1 2 3 . .n
R1
R2
G - SYMMETRIC / ASYMMETRIC COUNTING
U
B1
1 2 3 . . n1
1 2 3 4 . . n2
R1
R2
B - TEMPORIZED WITH SIGNAL B1
U
B1
R1
R2
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
B1
t
R1
R2
A - SIMPLE TIMER
t
R2
C - TEMPORIZED WITH SIGNAL B1 AND B2
U
B1
B2
R1
R2
t2
t1
t2
t1
F - COMPLEX COUNTING
F28:SYMMETRIC COUNTING FOR "N" DOWN
FLANKS OF SIGNAL B1(INITIALY DEACTIVATED)
AND "N" DOWN FLANKS OF SIGNAL B2
Once the system is supplied with a voltage U,
the relays R1 and R2 will remain inactive until the
arrival of n pulses of the signal B1. With the down
flank of the pulse number n of the signal B1 the
relays R1 and R2 will be activated. The relays will
remain activated until the arrival of an up flank
of signal B2. With the arrival of the up flank of the
pulse n of the signal B2, the relays R1 and R2 will
be deactivated. This function is available for
MTIR2.
U
1 2 3 . .n
B1
1 2 3 . .n
B2
R1
R2
F20:ASYMMETRIC COUNTER CYCLE BY "N1" AND F - COMPLEX COUNTING
N2 UP FLANKS OF SIGNAL B1(INITIALY ACTIVATED)
U
Once the system is supplied with a voltage U, the
1 2 3 . . n1
relays R1 and R2 will remain active until the arrival
B1
of n1 pulses of signal B1. When the up flank of the
1 2 3 . . n2
B2
pulse n1 of the signal B1 arrives, the relays R1 and
R2 will be deactivated. The relays will remain on
R1
that state until the arrival of new n2 pulses of signal
B1, activating the relays with the up flank of the
R2
pulse n2 of the signal B1 arrives. In the modules
that have input B2, as MTIR2, the state of this signal
B2 is irrelevant in this function.
F21: UP FLANK DELAY NEST-ABLE BY SIGNAL B1
Once the system is supplied with a voltage U, with
the up flank of a signal B1 is initiated a disconnection delay of the relay R1 and R2 with time t. If
before the end of it is received another pulse of
signal B1, then the relays will be activated a time t
from the flank edge of this second pulse of signal
B1. In the modules that have input B2, as MTIR2,
the state of this signal B2 is irrelevant in this
function.
F29:ASYMMETRIC COUNTING FOR "N1" DOWN
FLANKS OF SIGNAL B1(INITIALY DEACTIVATED)
AND "N2" DOWN FLANKS OF SIGNAL B2
Once the system is supplied with a voltage U,
the relays R1 and R2 will remain inactive until the
arrival of n1 pulses of the signal B1. With the
down flank of the pulse number n1 of the signal
B1 the relays R1 and R2 will be activated. The
relays will remain activated until the arrival of an
up flank of signal B2. With the arrival of the up
flank of the pulse n2 of the signal B2, the relays
R1 and R2 will be deactivated. This function is
available for MTIR2.
B - TEMPORIZED WITH SIGNAL B1
F30:UP FLANK DELAY OF SINGAL B1 BETWEEN
RELAY CONNECTIONS OF R1 AND R2
Once the system is supplied with a voltage U,
with the up flank of a signal B1 the relay R1 will
be activated for a programmed time t. Elapsed
this time, the relay R1 will be deactivated and
the relay R2 will be activated until supply
termination. the state of this signal B2 is irrelevant
in this function. This function is available for
MTIR2.
U
B1
t
R1
R2
F22:LOCKING AND CUTTING CYCLE WITH SIGNAL B1 D - TEMPORIZED SYMMETRIC / ASYMMETRIC
Once the system is supplied with a voltage U,
U
when an up flank of the signal B1 a connection
t1
delay with time t is initiated for the relays R1 and
R1
R2, after de up flank of the signal B1, a disconnect2
R2
tion delay with time t is initiated for the relays R1
and R2. In the modules that have input B2, as
MTIR2, the state of this signal B2 is irrelevant in this
function.
F23: CONNECTION DELAY BETWEEN RELAYS R1 AND
R2
Once the system is supplied with a voltage U, the
relay R1 will be activated, after a time t, the relay
R1 will be deactivated and the relay R2 will remain
activated until supply termination. This function is
available for MTIR2.
U
R1
F19:SYMMETRIC COUNTER CYCLE BY "N" UP FLANKS
BY SIGNAL B1(INITIALY DEACTIVATED)
Once the system is supplied with a voltage U, the
relays R1 and R2 will remain inactive until the
arrival of n pulses of signal B1. When the up flank
of the pulse n of the signal B1 arrives, the relays R1
and R2 will be activated. The relays will remain on
that state until the arrival of new n pulses of signal
B1, deactivating the relays with the up flank of the
pulse n of the signal B1 arrives. In the modules that
have input B2, as MTIR2, the state of this signal B2 is
irrelevant in this function.
F24:CONNECTION DELAY BY UP FLANK OF SIGNAL
B1 AND DISCONNECTION DELAY BY UP FLANK OF
SIGNAL B2
Once the system is supplied with a voltage U, with
the up flank of signal B1 is initiated a connection
delay of the relays R1 and R2 with time t1. The
relays will remain active until the arrival of a up
flank of signal B2, which it will start a disconnection
delay of the relays R1 and R2 with time t2. This
function is available for MTIR2.
F32:PULSE DELAY FOR UP FLANK OF B1 (INITIALY
R1 ACTIVATED AND R2 INITIALY DEACTIVATED)
Once the system is supplied with a voltage U,
after the up flank of the signal B1, a connection
delay of the relays R1 with programmed time t1
is initiated. Elapsed this time, the relay R1 will be
deactivated and the relay R2 will be activated,
then a disconnection delay of the relay R2 with
programmed time t2 will be initiated. the state
of this signal B2 is irrelevant in this function. This
function is available for MTIR2.
B - TEMPORIZED WITH SIGNAL B1
U
B1
t1
R1
t2
R2
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
t
R1
R2
D - TEMPORIZED SYMMETRIC / ASYMMETRIC
U
C - TEMPORIZED WITH SIGNAL B1 AND B2
U
B1
B2
t2
R1
t1
R2
t1
t2
C - TEMPORIZED WITH SIGNAL B1 AND B2
U
B1
B2
t2
R1
t1
R2
t1
t2
F25:CONNECTION DELAY BY DOWN FLANK OF
SIGNAL B1 AND DISCONNECTION DELAY BY DOWN
FLANK OF SIGNAL B2
Once the system is supplied with a voltage U, with
the down flank of signal B1 is initiated a
connection delay of the relays R1 and R2 with time
t1. The relays will remain active until the arrival of a
down flank of signal B2, which it will start a
disconnection delay of the relays R1 and R2 with
time t2. This function is available for MTIR2.
F26:CONNECTION DELAY BY UP FLANK OF SIGNAL
B1 AND DISCONNECTION DELAY BY DOWN FLANK
OF SIGNAL B2
Once the system is supplied with a voltage U, with
the up flank of signal B1 is initiated a connection
delay of the relays R1 and R2 with time t1. The
relays will remain active until the arrival of a down
flank of signal B2, which it will start a disconnection
delay of the relays R1 and R2 with time t2. This
function is available for MTIR2.
t1
R1
t1
U
B1
B2
t2
R1
t1
R2
t1
t2
F27:CONNECTION DELAY BY DOWN FLANK OF
SIGNAL B1 AND DISCONNECTION DELAY BY UP
FLANK OF SIGNAL B2
Once the system is supplied with a voltage U, with
the down flank of signal B1 is initiated a
connection delay of the relays R1 and R2 with time
t1. The relays will remain active until the arrival of
an up flank of signal B2, which it will start a
disconnection delay of the relays R1 and R2 with
time t2. This function is available for MTIR2.
Ctra. Mntrida a Aldea del Fresno s/n. 45930 Mntrida. Toledo. Spain.
t2
Pot.
R1
U
t
F37:PWM DOWN OF PULSE WIDTH FOR DC LOADS
Once the system is supplied with a voltage U, a
modulation connection pulse width starts in
relay R1, decreasing the pulse width on ramp
edge during a t time.
H - LOADS CONTROL DC (PWM)
U
t
Index
category
A
B
C
F34: ASYMMETRIC CYCLE TIMED(R1 INITIALY
ACTIVATED)
Once the system is supplied with a voltage U, an
asymmetric cycle timed is initiated with
programmed times t1 and t2. The first relay to be
activated is the relay R1. This function is
available for MTIR2.
F36:PWM EDGE OF PULSE WIDTH FOR DC LOADS
Once the system is supplied with a voltage U, a
modulation connection pulse width starts in
relay R1, increasing the pulse width on ramp
edge during a t time.
H - LOADS CONTROL DC (PWM)
R1
F33: SYMMETRIC CYCLE TIMED(R1 INITIALY
ACTIVATED)
Once the system is supplied with a voltage U, a
symmetric cycle timed is initiated with a
programmed time t. The first relay to be
activated is the relay R1. This function is
available for MTIR2.
F35: LOAD CONTROLS ON DC WITH POTENTIOMETER REGULATOR
Once the system is supplied with a voltage U,
when you insert the potentiometer regulator in
the RFS1LS connector, you can control the DC
load with a generated PWM signal.
SFMFRVJDL!T/B/!!
t2
H - LOADS CONTROL DC (PWM)
R1
C - TEMPORIZED WITH SIGNAL B1AND B2
t1
t1
t2
R2
F31: PULSE DELAY (R1 INTIALY ACTIVATED AND R2
INTIALY DEACTIVATED)
Once the system is supplied with a voltage U, a
connection delay of the relays R1 with programmed time t1 is initiated. Elapsed this time, the
relay R1 will be deactivated and the relay R2 will
be activated, then a disconnection delay with
programmed time t2 will be initiated for relay R2.
This function is available for MTIR2.
Category description
Temporized functions with signal B1
Temporized functions with signal
B1 and B2
Temporized
symmetric/asymmetric
Tel: + 34 91 812 42 84
Fax: +34 91 817 85 65
Index
category
E
Simple timer
Category description
Simple counter
Complex counter
Counter Asymmetric /Symmetric
Load controls DC (pwm)
E-mail: info@relequick.com
www.relequick.com
50
(02410413)
G - SYMMETRIC / ASYMMETRIC COUNTING