Transformer Specifications to invite Quotations.
Specifications
Sr.No.
Content
M/s Voltamp Transformers
M/s Raychem RPG
M/s Crompton Greaves
Specifications.
Rating
1000 KVA, Oil Filled
Confirm
Confirm
Confirm
On Load Tap Changer, Oil Filled.
OLTC with RTCC & ARV
Confirm
Confirm
Confirm
No Load Voltage Ratio.
11/0.433 KV
Confirm
Confirm
Confirm
Winding Material
Electrolytic Copper Wound
Confirm
Confirm
Confirm
Type
Core Type / IS : 2026; IS:1180
Confirm
Confirm
Confirm
Vector Group
Dyn11
Confirm
Confirm
Confirm
Phases
Confirm
Confirm
Confirm
Frequency
50 Hz
Confirm
Confirm
Confirm
Primary
Delta Connected
Confirm
Confirm
Confirm
10
Secondary
Star Connected
Confirm
Confirm
Confirm
11
Tapping range
Plus 5% to Minus 15%, in the steps of
2.50%.
Confirm
Confirm
Confirm
12
OLTC Tapping Steps / HV Side.
Confirm
Confirm
Confirm
13
Termination HV
Bare Bushing
Confirm
Confirm
Confirm
14
Termination LV
To be confirmed
To be confirmed
To be confirmed
15
Duty
Out Door
Confirm
Confirm
Confirm
16
Temp. Rise (Oil / Wdg.)
50 / 55 Deg Cen.
Confirm
Confirm
40-45 deg
17
Insulation Level :
17 (i)
a) HV (KVp/KVrms)
75 KVp/28 KVrms.
Confirm
Confirm
Confirm
17 (ii)
b) LV
03KVrms
Confirm
Confirm
Confirm
18
Type of Cooling
ONAN
Confirm
Confirm
Confirm
19
Type of Breather
Silica Jel Breather with Oil Seal.
Confirm
Confirm
Confirm
20
Paint
Epoxy Paint (Shade # 631 of IS 5)
Confirm
Confirm
Confirm
21
Accessories :
21 (i)
a) Buchholz Relay (Main Tank & OLTC)
With Alarm & Trip & Shut off Valve.
Confirm
Confirm
Confirm
21 (ii)
b) OTI
Dia-6" with MRP, Alarm & Trip
Confirm
Confirm
Confirm
21 (iii)
c) WTI
Dia-6" with MRP, Alarm & Trip
Confirm
Confirm
Confirm
21 (iv)
d) Marshalling Box
d) Marshalling Box
Confirm
Confirm
Confirm
21 (v)
e) Set of Radiators
e) Set of Radiators
Confirm
Confirm
Confirm
21 (vi)
f) Conservator Tank
f) Conservator Tank with MOLG
Confirm
Confirm
Confirm
21 (vii)
e) Explosion vent with diaphram
e) Explosion vent with diaphram
Confirm
Confirm
Confirm
22
Transformer Oil / First filling of Oil in Party
As per IS : 335 of 1983
scope, including Cooling Fins.
Confirm
Confirm
Confirm
23
No load Losses of Transformer
Less than 3KW
Confirm
Confirm
Confirm
24
Load Losses at rated current.
Less than 9 KW
Confirm
Confirm
Confirm
25
Test
All routine (IS : 2026) Test in supplier scope,
Type test cgargeable, If reqd.
Confirm
Confirm
Confirm
26
Guarantee, from date of commissioning.
12 Months
27
Commissioning
In Supplier Scope
28
Qty.
01 No.
29
Quoted price (Lacs Rs.)
30
Delivery
31
Other condition If any.
Contacted Person.
2 Months
Confirm
Confirm
Confirm
Additional Charges
Additional Charges
Additional Charges
Confirm
Confirm
Confirm
16.15
10.45
21.50
10 - 12 Weeks.
10 - 12 Weeks.
10 - 12 Weeks.
Suchita/02025650612-103
Mr. Purushottam Patel / 097115 66576
/ 098112 35849
Mr. Srijan Kr Gpta / 096541
25252
Technically seek O.K
Technically seek O.K
Technically seek O.K
No.
32
33 AMRI Remarks