Characteristics
ABL6TS250U
voltage transformer - 230..400 V - 1 x 230 V 2500 VA
Range of product
Phaseo Optimum
Product or component
type
Safety and isolation transformer
Rated power in VA
2500 VA
Input voltage
230 V AC single phase , terminal(s): N-L1
400 V AC phase to phase , terminal(s): L1-L2
Output voltage
230 V AC
Secondary winding
Single
Protective cover
Without
Complementary
Input voltage limits
207...253 V
360...440 V
Network frequency limits
47...63 Hz
Input voltage tolerance
+/- 15 V
Efficiency
96 %
Power dissipation in W
104.2 W
Output sustained overvoltage
3 % (no load, hot state)
Voltage drop at rated load
0%
No load losses
23.4 W
Short-circuit voltage
8.73 %
Output protection type
Against overload , protection technology: external
Against overvoltage , protection technology: external
Against short-circuits , protection technology: external
Connections - terminals
Screw type terminals for input connection , connection capacity: 8 x 4 mm AWG
gauge11
Screw type terminals for input ground connection , connection capacity: 1 x 4
mm AWG gauge11
Screw type terminals for output connection , connection capacity: 2 x 4 mm
AWG gauge11
Marking
CE
Fixing mode
By 4 screws , screw(s) # = 10 mm on vertical panel , operating position: vertical
By 4 screws , screw(s) # = 10 mm on vertical panel , operating position:
horizontal
By 4 screws , screw(s) # = 10 mm on horizontal panel with derating to 90 %
Electrical insulation class
Class F
Product weight
27.4 kg
Environment
Product certifications
UR
IP degree of protection
IP20 conforming to EN/IEC 60529
Protective treatment
TC
Ambient air temperature for operation
-20...50 C
Ambient air temperature for storage
-40...80 C
Class of protection against electric shock
Class I conforming to VDE 0106-1
Dielectric strength
2000 V between winding and ground
4000 V between primary and secondary
RoHS EUR conformity date
0623
RoHS EUR status
Compliant
7/11/2011
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.