MAKING MODERN LIVING POSSIBLE
Selection guide
VLT AutomationDrive FC 360
www.danfoss.com/FC360
1968 was the year when
Danfoss presented the first
mass produced frequency
converter in the world
and named it VLT
PERFORMANCE,
RELIABILITY AND
SPEED
Increase quality and efficiency with
energy efficient, user friendly control of
motors from 0.37 to 75 kW.
Built on the success of the tried and tested VLT platform that
Danfoss developed and launched in the 1960s, the VLT AutomationDrive FC 360 shares the same technical heritage as the
popular and versatile VLT AutomationDrive FC 300 series.
Developed to meet a general purpose operation prole the
drive lacks the expandability of its larger sibling, but still delivers
powerful performance out of the box.
Due to the fact that all Danfoss frequency converters follow the
same basic design and operating principle, existing owners and
users of VLT drives will instantly feel at home when operating
the VLT AutomationDrive FC 360.
The VLT AutomationDrive FC 360 is a dedicated industry drive ,
designed for OEMs, that provides precise and ecient motor
control in a wide range of industrial applications.
Built-in features help owners save
Space in installations
Time in setup
Eort in daily maintenance.
The result is a powerful and versatile solution that increases
process eciency and quality in a cost-ecient package
Built-in features provide
high performance and
reduce the need for external
components. This reduces
complexity and makes the
ordering process easier.
REDUCED HARMONICS
A built-in DC choke
reduces harmonics to
less than 43% (ThiD) and
significantly extends
the lifetime of the DC
capacitor.
Designed for challenging environments
Using advanced coating and quality internal
electronics protection, the FC 360 has the rugged
characteristics demanded by the textile, plastics,
rubber, food, beverage and building materials
industries.
Maximize productivity
IP20 standard protection and an easy to use control
panel saves valuable time in commissioning and
maintainance, and enables owners to maximize
uptime and save energy..
Compact design for easy installation
The compact, lightweight design enables owners to
optimize panels space by mounting several drives
side-by-side mounting with zero clearance.
Save time on setup
Easy parameter setup makes the path to energy
savings both short and simple, and can be carried
out with an enhanced numeric LCP or graphical
control panel that supports English and Chinese.
Targeted Application Selections make it easy for
users to set up and commission typical applications.
HIGH RELIABILITY
Coated Printed Circuit Boards
High level 3C3 Printed Circuit Board
(PCB) coating as standard provides
high reliability in harsh environments
to prevent failures and downtime. The
lifetime of the drive is also increased as
a result of the IEC 60721-3-3 conformal
coating.
55C Working Temperature
VLT AutomationDrive FC 360 is
designed to operate at 45-50C ambient
temperature at full load (depending
on model) and 55C with derating. This
means there is no need to install extra
cooling equipment or oversize the drive,
resulting in cost savings.
Efficient heat management
COATED PCB
EASY CLEANING
The VLT AutomationDrive FC 360 is
delivered with a 3C3 class coated PCB as
standard to strengthen reliability.
An easy to remove fan makes it easy to
keep dust from affecting the drives
ventilation.
A unique cooling concept ensures
that there is no forced air ow over
the electronics. This reduces the risk of
downtime, while strengthening stability
in daily operation.
By preventing dust and particles from
accumulating on the small internal
components and legs, the risk of short
circuits is signicantly reduced, especially
in humid environments.
DISPLAY
ENCLOSURE
Customer can select enhanced numerical
display or graphical control panel that
supports English and Chinese (requires
adaptor).
The VLT AutomationDrive FC 360 is
available with an IP 20 enclosure.
Optimized for
industrial applications
Extruders
Escalators
Winders
Material Handling
Palletizer
Conveyor
Draw Bench
Textile Machinery
Hoist
Air Compressor
Printing & Dyeing
Glass Production Line
Centrifuge separators
Pumps
Fans
HIGH PERFORMANCE
CONTROLLER
VLT AutomationDrive
FC 360 has an advanced
controller with high speed
response making high-end,
complicated applications
easy.
450 kg force at 0.6 Hz. The high
torque performance of a 0.75
kW VLT AutomationDrive FC
360 fully meets the demands
for tensile testing at Samuya
Technocrates in India.
SPEED
PM motor control
The FC 360 can provide highly ecient
permanent magnet (PM) motor control
in open loop under VVC+ mode in
motors up to 22kW. Using Automatic
Motor Adaptation (AMA) the drive
adapts to the specic characteristics of
the permanent magnet motor.
Smart Logic Control
Smart Logic is a simple and clever way
to keep the drive, motor and application
working together. The smart logic
controller monitors a specic event, and
when it occurs, it triggers a predened
action which is monitored for 20 steps,
before returning to step 1.
The Smart Logic Controller can monitor
any parameter that can be dened as
true or false, providing users with
signicant freedom to tailor the control
strategy to their specic needs. This
includes digital commands and logic
expressions, where sensor outputs can
inuence operation using parameters
such as temperature, pressure, torque,
ow, time, load, frequency, voltage, and
others, combined with the operators
>, <, =, and and or as logical
statements.
With the VLT Encoder Input MCB 102
and VLT Resolver Input MCB 103 the
VLT AutomationDrive FC 360 can
receive encoder feedback from either a
motor or a process.
Time saving setup
VLT Motion Control Tool MCT 10
The FC 360 can be congured and
monitored with Danfoss own VLT
Motion Control Tool MCT 10 software.
This provides plant managers with
a comprehensive overview over the
system at any point in time and a high
level of exibility in conguration and
monitoring.
MCT 10 is a windows based engineering
tool with a clearly structured interface
that provides an instant overview of all
the drives in a system of any size. The
software runs under Windows and
enables data exchange over a traditional
RS 485 interface or eldbus (PROFIBUS).
EASY SETUP VIA PC
Connect the VLT AutomationDrive FC 360
directly to a PC for fast and easy transfer of
settings.
Parameter conguration is possible both
online and oine, and the software can
be congured to link to the systems
electrical diagrams or operating
manuals. This helps to reduce the risk of
incorrect conguration while oering
fast access to troubleshooting.
Expand with control
and feedback modules
Fieldbus communication in VLT
AutomationDrive FC 360 is integrated
in the control card. In addition, the
drive can be expanded with options
for additional control and encoder
feedback.
USE WITH VLT OneGearDrive
The VLT AutomationDrive FC 360 is
designed to work perfectly with permanent
magnet motors, such as the VLT
OneGearDrive, which is widely used in
Danfoss VLT FlexConcept.
7
FEATURES DESIGNED TO
MEET INDUSTRIAL NEEDS
The VLT AutomationDrive FC 360 is designed to provide
maximum uptime and reliability in a wide range of environments.
Built-in Brake Chopper
A built-in brake chopper up to 22kW
saves money and panel space.
Pulse Input as Speed Reference
VLT AutomationDrive FC 360 oers the
capability to convert pulse input as a
speed reference, avoiding the need to
purchase an analog signal module for
PLC.
Center Winder
FC 360 supports center winder
functionality, eliminating the need for
a special module in the programmable
logic control (PLC).
3
1
Built-in PID Controller
The built in PID controller calculates an
error value as the dierence between a
measured process variable and a desired
setpoint.
Built-in RFI Filter
Built-in lters not only save space, but also
eliminate additional costs for tting, wiring,
and material. The most important
advantage is the perfect EMC conformance
and cabling of integrated lters.
See the interactive presentation
and video at www.danfoss.com/
fc360
4
DESIGNED FOR A WIDE
RANGE OF POWER
SUPPLY CONDITIONS
VLT AutomationDrive
FC 360 can operate at
-15% of supply voltage
8
Designed for use in ambient
temperatures up 45-50C without
derating. Max. ambient temperature
55C
No forced air over PCB for whole
power range (0.37 to 75kW)
Class C3C coated components for
increased reliability in harsh environments (IEC 60721-3-3)
Removable fan
EMC compliant. Meets class C3 with
limit A2 (EN 55011) as standard
Built-in brake chopper up to 22 kW
Fieldbus embedded in control card
(PROFIBUS)
I/0 number and functions
- 7DI / 2AI / 2AO / 2 DO
- Pulse input as speed reference
- Pulse feedback and 24V encoder
feedback
- 24V (100 mA)
- 12V
Display options
- Graphic LCP
- Enhanced numeric LCP
- Blind cover
Full automatic motor adaptation
(AMA) optimizes compatibility
between frequency converter and
motor in VVC+ mode
Built-in Smart Logic Controller
RFI Swtich
9
7
* Not visible on picture
SPECIFICATIONS
(Basic unit without extensions)
Analogue output
Main supply (L1, L2, L3)
Supply voltage
380480 V -15%/+10%
50/60 Hz 5%
Programmable
analogue outputs
Displacement power factor
(cos )
> 0.98
Current range at
analogue output
0/4 20 mA
Switching on input supply
L1, L2, L3
0.37-7.5 kW maximum 2 times/min.
11-75 kW maximum 1 time/min.
Supply frequency
Harmonic disturbance
Meets EN 61000-3-12
Output data (U, V, W)
Output voltage
0 100% of supply voltage
Output frequency
0-500 Hz
0-200 Hz under VVC+ Mode
Switching on output
Ramp times
Unlimited
0.05-3600 sec
Note: 160% current can be provided for 1 minute.
Higher overload rating is achieved by oversizing the drive.
Digital inputs
Programmable digital inputs
Changeable to digital output
2 (Terminal 27,29)
Logic
PNP or NPN
Voltage level
0 24 V DC
Maximum voltage on input
Input resistance, Ri
Scan interval
28 V DC
Approx. 4 k
Control card
RS485 interface
Up to 115 kBaud
Max. load (10 V)
15 mA
Max. load (24 V)
100 mA
Relay output
Programmable relay outputs
Max. terminal load (AC)
on 1-3 (break), 1-2 (make),
4-6 (break) power card
250V AC, 3 A
Max. terminal load (AC) on
4-5 (make) power card
250V AC, 3 A
Min. terminal load on
1-3 (break), 1-2 (make),
4-6 (break), 4-5 (make)
power card
250V AC, 0.2 A
Enclosure
2
Voltage or current
IP20
Vibration test
Max. relative humidity
1.0 g
5-95% (IEC 60721-3-3; Class 3K3 (noncondensing) during operation
Voltage level
0 to +10 V
(scaleable)
Ambient temperature
max. 55C with derating
Current level
0/4 to 20 mA (scaleable)
Galvanic isolation of all
I/O supplies according to PELV
Accuracy of analog inputs
Max. error 0.5% of full scale
Programmable pulse/
encoder inputs
Voltage level
Pulse input accuracy
(0.1 1 kHz)
Encoder input accuracy
2/1
0 24 V DC (PNP positive logic)
Max. error: 0.1% of full scale
4Hz-32kHz
* Utilize some of the digital inputs
Digital outputs
Programmable
digital/pulse outputs
Voltage level at
digital/frequency output
Max. output current
(sink or source)
Maximum output frequency
at frequency output
Accuracy on frequency
output
* Utilize 2 digital inputs
Aggressive environment
Class 3C3
Fieldbus communication
Pulse/encoder inputs
10
Max. error: 0.8 % of full scale
Surroundings/external
Analog inputs
Modes
Accuracy on analogue
output
500
1 ms
* 2 can be used as digital outputs
Analogue inputs
Max. load to common at
analogue output (clamp 30)
2
0 24 V DC
40 mA
4Hz to 32 kHz
Max. error: 0.1% of full scale
Standard built-in
FC Protocol
Modbus RTU
Fieldbus built-in control card
variants
PROFIBUS
CONNECTION EXAMPLES
The numbers represent the terminals on the drive
3 Phase
power
input
91 (L1)
92 (L2)
93 (L3)
95 PE
(U) 96
(V) 97
(W) 98
(PE) 99
Switch Mode
Power Supply
10Vdc
24Vdc
15mA
100mA
+10V DC
50 (+10 V OUT)
0/-10V DC 0/4-20 mA
53 (A IN)
0/-10V DC 0/4-20 mA
54 (A IN)
130BC438.11
3)
Motor
(-UDC) 88
(+UDC) 89
Brake
resistor
(BR) 81
relay1
03
02
55 (COM A IN)
01
relay 2 2)
12 (+24V OUT)
06
P 5-00
05
18 (D IN)
24V (NPN)
0V (PNP)
19 (D IN)
24V (NPN)
0V (PNP)
20
(COM D IN)
27
(D IN/OUT)
(A OUT) 45
24V (NPN)
0V (PNP)
(D IN/OUT)
24V
5V
24V (NPN)
0V (PNP)
S801
0V
1
2
3
4
5
Analog Output
0/4-20 mA
ON=Terminated
OFF=Open
ON
1 2
0V
240V AC, 2A
04
(A OUT) 42
24V
29
240V AC, 2A
32 (D IN)
24V (NPN)
0V (PNP)
33 (D IN)
24V (NPN)
0V (PNP)
31 (D IN)
24V (NPN)
0V (PNP)
RS-485
Interface
0V
(N RS-485) 69
RS-485
(P RS-485) 68
(COM RS-485) 61
(PNP) = Source
(NPN) = Sink
Built-in braking chopper available from 0.37 - 22 kW
Relay 2 is 2 pole for J1-J3 and 3 pole for J4-J7. Relay 2 of
J4-J7 with terminal 4,5,6, same NO/NC logic as Relay 1.
Dual DC choke in 30-75 kW
Switch S801 (bus terminal) can be used to enable termination on the RS-485 port (terminals 68 and 69).
Terminal 81 not available from 30 - 75kW
The diagram shows the port terminals
of the VLT AutomationDrive FC 360.
The numbers indicated refer to the
terminal numbers of the drives.
Users can set the mode of the analogue
inputs 53 and 54 by setting software
parameters.
The FC 360 features a RS485 interface
as standard. The RS485 terminations are
integrated in the drive (S801).
To switch from NPN to PNP logic for the
digital signals, use parameter 5-00.
PROFIBUS DP can be specied by
conguring dierent control cassette
when ordering.
11
POWER, CURRENTS, ENCLOSURES
AND ORDERING TYPE CODE
1.1
1.6
2.1
2.8
3.4
4.8
6.3
8.2
11
14
21
27
34
40
52
65
80
96
124
[1]
FC-360
[1] Application
360
VLT AutomationDrive FC 360
Power size [kW]
0.37-2.2
3.0-5.5
Dimensions
[mm]
12
J4
7.5
11-15
B
b
J5
J6
J7
18.5-22
30-45
55-75
J2
J3
J4
Height A
210
272.5
272.5
317.5
410
515
550
Width B
75
90
115
133
150
233
308
Depth C
(with option B)
168 (181)
168 (181)
168 (181)
245 (258)
245 (258)
241
323
198
260
260
297.5
390
495
521
b
Mounting screw
60
70
90
105
120
200
270
M4
M5
M5
M6
M6
M8
M8
J5
J6
Mounting holes
J7
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[3] AC Line Voltage
T4
[2] Power Size
HK37
HK55
HK75
H1K1
H1K5
H2K2
H3K0
H4K0
H5K5
H7K5
H11K/
Q11K See ratings data on page 11
H15K/ for power ratings
Q15K
H18K/
Q18K
H22K/
Q22K
H30K/
Q30K
H37K/
Q37K
H45K/
Q45K
H55K/
Q55K
H75K/
Q75K
J3
J1
[2]
J2
130BC449.10
1.2
1.7
2.2
3.0
3.7
5.3
7.2
9.0
12
15.5
23
31
37
42.5
61
73
90
106
147
J1
440-480V
0.37
0.55
0.75
1.1
1.5
2.2
3.0
4.0
5.5
7.5
11
15
18
22
30
37
45
55
75
Frame size
380-480 V
A
a
kW
HK37
HK55
HK75
H1K1
H1K5
H2K2
H3K0
H4K0
H5K5
H7K5
H11K/Q11K
H15K/Q15K
H18K/Q18K
H22K/Q22K
H30K/Q30K
H37K/Q37K
H45K/Q45K
H55K/Q55K
H75K/Q75K
Dimensions [mm]
IP 20 /Chassis
FC 360
380-439V
T4 380 480 V
(High and normal overload)
Amp.
3 x 380/480 V AC (High overload)
3 x 380/480 V AC (Normal overload)
[4] Enclosure
For cabinet mounting:
E20
IP 20/Chassis
[5] RFI Filter (EN 55011)
H2
RFI-Filter class A2
[6] Braking
X
No brake IGBT
B
Built-in brake IGBT
* 0.37-22kW built-in; 30-75kW not
[7] Display (Local Control Panel)
X
No LCP, blind cover
* Following accessories available: NLCP, GLCP and blind
cover
[8] Conformal Coating (IEC 721-3-3)
C
Conformal coating on all PCBs
[11]
[12]
SXX X
[13]
[14]
[9] Mains Input
D
Load sharing terminals
[10] Cable
X
Standard Cable Entry
[13] Fieldbus embedded in control cassette
AX
No fieldbus option
A0
PROFIBUS
[14] B Option (Application)
BX
No application option
* VLT Encoder Input MCB102 and VLT Resolver Input
MCB 103 available as accessories
Please note that not all combinations are
possible. Find help for configuring your drive
with the online configurator at
driveconfig.danfoss.com
380 480 VAC
Enclosure
Typical Shaft Output
Typical Shaft Output at 460 V
IP 20
HO
[kW]
[HP]
HK37
0.37
0.5
HK55
0.55
0.75
HK75
0.75
1
J1
H1K1
1.1
1.5
H1K5
1.5
2
H2K2
2.2
3
H3K0
3
4
J2
H4K0
4
5.5
H5K5
5.5
7.5
J3
H7K5
7.5
10
Output Current
(3 x 380 440 V)
Continuous
[A]
1.2
1.7
2.2
3.7
5.3
7.2
12
15.5
Output Current
(3 x 441 480 V)
Continuous
[A]
1.1
1.6
2.1
3.4
4.8
6.3
8.2
11
14
[A]
1.9
2.7
3.5
4.8
5.9
8.5
11.5
14.4
19.2
24.8
Intermittent
(60 s overload)
Output Power
(400 V AC)
Continuous
[kVA]
0.8
1.2
1.5
2.1
2.6
3.7
5.0
6.2
8.3
10.7
Output Power
(460 V AC)
Continuous
[kVA]
0.9
1.3
1.8
2.5
2.8
5.2
6.8
9.2
11.6
Max. cable size
(Mains, motor, brake and load sharing)
[mm ]
([AWG])
4 mm2
Max. Input Current
(3 x 380 440 V)
Continuous
[A]
1.2
1.6
2.1
2.6
3.5
4.7
6.3
8.3
11.2
15.1
Max. Input Current
(3 x 441 480 V)
Continuous
[A]
1.2
1.8
2.9
3.9
4.3
6.8
9.4
12.6
Intermittent
(60 s overload)
[A]
1.9
2.6
3.4
4.2
5.6
7.5
10.1
13.3
17.9
24.2
Max. pre-fuses
Environment
Estimated power loss at rated max. load
Weight
IP 20
Efficiency
[A]
10
[W]
20.8
25.1
30
[kg]
2.3
0.96
2.3
2.3
IP 20
Enclosure
52.9
73.9
94.8
115.5
157.5
192.8
2.3
2.3
2.5
3.6
3.6
0.98
3.6
4.1
0.97
J4
32
40
J5
J6
H11K
(Q11K)
H15K
(Q15K)
H18K
(Q18K)
[kW]
[HP]
11
15
15
20
18
25
22
30
HO
(NO)
Typical Shaft Output
Typical Shaft Output at 460 V
25
H22K
H30K
(Q22K) (Q30K)
J7
H37K
(Q37K)
H45K
(Q45K)
H55K
(Q55K)
H75K
(Q75K)
30
40
37
50
45
60
55
75
75
100
Output Current
(3 x 380 440 V)
Continuous
[A]
23
31
37
42.5
61
73
90
106
147
Output Current
(3 x 441 480 V)
Continuous
[A]
21
27
34
40
52
65
80
96
124
[A]
34.5
(25.3)
46.5
(34.1)
55.5
(40.7)
63.8
(46.8)
91.5
(67.1)
109.5
(80.3)
135
(99)
159
(116.6)
220.5
(161.7)
Intermittent
(60 s overload)
Output Power
(400 V AC)
Continuous
[kVA]
15.9
21.5
25.6
29.5
42.3
50.6
62.4
73.4
101.8
Output Power
(460 V AC)
Continuous
[kVA]
17.5
22.5
28.3
33.3
43.2
54
66.5
79.8
103.1
[mm2]
([AWG])
6Max. cable size
(Mains, motor, brake)
16 mm2
50 mm2
85 mm2
Max. Input Current
(3 x 380 440 V)
Continuous
[A]
22.1
29.9
35.2
41.5
57
70.3
84.2
102.9
140.3
Max. Input Current
(3 x 441 480 V)
Continuous
[A]
18.4
24.7
29.3
34.6
49.2
60.6
72.2
88.6
120.9
Intermittent
(60 s overload)
[A]
33.2
(24.3)
44.9
(32.9)
52.8
(38.7)
62.3
(45.7)
85.5
(62.7)
105.45
(77.3)
126.3
(92.6)
154.35
(113.2)
210.45
(154.3)
Max. pre-fuses
Environment
Estimated power loss at rated max. load
Weight
IP 20
Efficiency
[A]
50
80
160
250
[W]
289.5
393.3
402.8
467.5
630
848
1175
1300
1507
[kg]
9.4
9.5
12.3
12.5
22.4
0.98
22.5
22.6
37.3
38.7
13
OPTIONS AND ACCESSORIES
PROFIBUS DP-V1
VLT Resolver Input MCB 103
VLT Control Panel LCP 21
Operating the frequency converter
via a eldbus lets you reduce the
cost of your system, communicate faster and more eciently,
and benet from an easier user
interface.
Supports resolver feedback for
asynchronous motors.
The numerical control panel features an excellent user interface to
the drive.
PROFIBUS DP-V1 gives you wide
compatibility, a high level of
availability, support for all major
PLC vendors, and compatibility
with future versions
Fast, ecient communication,
transparent installation, advanced diagnosis and parameterisation and auto-conguration
of process data via GSD-le
A-cyclic parameterisation using
PROFIBUS DP-V1, PROFIdrive or
Danfoss FC prole state machines, PROFIBUS DP-V1, Master
Class 1 and 2
VLT Encoder Input MCB 102
A universal option for connection
of encoder feedback from either a
motor or a process. Feedback for
asynchronous motors.
Primary Voltage:
2 8 Vrms
Primary Frequency:
2.0 kHz 15 kHz
Primary current max:
50 mA rms
Secondary input voltage:
4 Vrms
Ordering number:
132B0283
VLT Brake Resistors
MCE 101
Energy generated during braking
is absorbed by the resistors,
protecting electrical components
from heating up. Danfoss brake
resistors are optimized for the
FC-series.
General versions for horizontal and
vertical applications are also
available.
Status messages
Quick menu for easy
commissioning
Parameter setting and
adjusting
Hand-operated start/stop function or Automatic mode select
Reset function
Ordering number:
132B0254
Graphical LCP Adapter
for FC 360
The converter between FC 360 and
the graphical control panel of VLT
AutomationDrive FC 300 series.
Supports Chinese and English
display (requires rmware 1.11 or
newer)
Ordering number:
132B0281
Enclosure protection as IP20
and up to IP65
Encoder module supports:
Incremental encoders
SinCos encoders as Hyperface
Power supply for encoders
RS422 interface
Connection to all standard 5 V
incremental encoders
Ordering number:
132B0282
Built-in thermo switch
Versions for vertical and hori-
zontal
mounting
UL-recognized only types for
vertical mounting
VLT Control Panel LCP 102
functions for FC 360
14
English and Chinese display
Status messages
Quick menu for easy
commissioning
Parameter setting and explanation of parameter function
Adjusting of parameters
Full parameter backup and copy
function
Alarm logging
Hand-operated start/stop, or
Automatic mode selection
Reset function
Other accessories
Blind Cover, FC 360
Ordering number: 132B0262
Remote Mounting Kit for LCP
Ordering number: 132B0102
Graphical LCP
Adapter for FC 360
VLT Control Panel LCP 21
Decoupling plate mounting kit
- J1
Ordering number: 132B0258
Decoupling plate mounting kit
- J2, J3
Ordering number: 132B0259
Decoupling plate mounting kit
- J4, J5
Ordering number: 132B0260
Decoupling plate mounting kit
- J6
Ordering number: 132B0284
Decoupling plate mounting kit
- J7
Ordering number: 132B0285
Terminal Cover for MCB - J1
Ordering number: 132B0263
VLT Brake Resistors MCE 101
Terminal Cover for MCB - J2
Ordering number: 132B0265
VLT Control Panel LCP 102
Terminal Cover for MCB - J3
Ordering number: 132B0266
Terminal Cover for MCB - J4
Ordering number: 132B0267
Terminal Cover for MCB - J5
Ordering number: 132B0268
15
What VLT is all about
Danfoss VLT Drives is the world leader among dedicated drives providers
and still gaining market share.
Environmentally
responsible
VLT products are manufactured
with respect for the safety and
well-being of people and the
environment.
All frequency converter factories
are certified according to ISO 14001
and ISO 9001 standards.
All activities are planned and
performed taking into account
the individual employee, the work
environment and the external environment. Production takes place
with a minimum of noise, smoke or
other pollution and environmentally safe disposal of the products
is pre-prepared.
UN Global Compact
Danfoss has signed the UN Global
Compact on social and environmental responsibility and our
companies act responsibly towards
local societies.
Dedicated to drives
Dedication has been a key word since
1968, when Danfoss introduced the
worlds first mass produced variable
speed drive for AC motors and
named it VLT.
Twenty five hundred employees
develop, manufacture, sell and service
drives and soft starters in more than
one hundred countries, focused only
on drives and soft starters.
Intelligent and innovative
Developers at Danfoss VLT Drives
have fully adopted modular principles
in development as well as design, production and configuration.
Tomorrows features are developed in
parallel using dedicated technology
platforms. This allows the development of all elements to take place in
parallel, at the same time reducing
time to market and ensuring that
customers always enjoy the benefits
of the latest features.
Rely on the experts
We take responsibility for every
element of our products. The fact that
we develop and produce our own
features, hardware, software, power
modules, printed circuit boards, and
accessories is your guarantee of
reliable products.
Local backup globally
VLT motor controllers are operating
in applications all over the world and
Danfoss VLT Drives experts located in
more than 100 countries are ready to
support our customers with application advice and service wherever they
may be.
Danfoss VLT Drives experts dont stop
until the customers drive challenges
are solved.
Impact on energy savings
One years energy savings from our
annual production of VLT drives
will save the energy equivalent
to the energy production from a
major power plant. Better process
control at the same time improves
product quality and reduces waste
and wear on equipment.
Danfoss VLT Drives, Ulsnaes 1, DK-6300 Graasten, Denmark, Tel. +45 74 88 22 22, Fax +45 74 65 25 80
www.danfoss.com/drives, E-mail: info@danfoss.com
DKDD.PB.304.A3.02
VLT is a trademark of Danfoss A/S
PE-MMSC 2014.01