Merlin Gerin PRD - Datasheet

Surge arresters are devices designed to limit transient overvoltages to a non-dangerous value for electrical installations and switchgear. The document discusses removable surge arresters (PRD) and self-contained surge arresters (PF) that provide protection for different voltage levels and risk levels. It provides technical specifications for various surge arrester models including their maximum discharge current, rated discharge current, and remote indication functions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views7 pages

Merlin Gerin PRD - Datasheet

Surge arresters are devices designed to limit transient overvoltages to a non-dangerous value for electrical installations and switchgear. The document discusses removable surge arresters (PRD) and self-contained surge arresters (PF) that provide protection for different voltage levels and risk levels. It provides technical specifications for various surge arrester models including their maximum discharge current, rated discharge current, and remote indication functions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

Surge arresters

PRD draw out, PF, EM/RM remote indication


Application
A surge arrester is a device designed to limit transient overvoltages to a
non-dangerous value for the installation and electrical switchgear.

Common technical data

80

Permanent operating full withstand current


(Uc): permissible r.m.s. value that can be
continuously applied to the surge arrester's
terminals without affecting its operation.
It must be higher than the system rated voltage,
including variations:
For protection between active conductors
and the earth:
TT: Uc 1.5 Uo,
TN: Uc 1.1 Uo (1.5 Uo in France),
IT: Uc e Uo.
For protection between phases and the neutral:
TT, TN, IT: Uc 1.1 Uo.
Residual voltage (Ures): the peak value of the
voltage that appears at surge arrester terminals
when a discharge current runs through them.
Simple system voltage (Uo): the voltage
between phase and neutral.
System rated voltage (Un): value of the
reference voltage which designates the network
Level of protection (Up): voltage that
characterises the protection performance of a
surge arrester at In.
Full discharge current (Imax): maximum
peak value of the discharge current with a
8/20s wave form which the surge arrester
can withstand one time.
Rated discharge current (In): peak value of the
discharge current with a 8/20s wave form used
to designate a surge arrester.
Permanent operating current (Ic): current that
circulates in the surge arrester, when it is supplied
under permanent operating full withstand current
(Uc) in the absence of a fault.
Common mode overvoltages (MC):
overvoltages that appear between active
conductors and protective conductor.
Differential mode overvoltages (MD):
overvoltages that appear between active
conductors (phase/neutral).

New

Surge arresters

New

PRD draw out


PRD
Application
PRD removable surge arresters allow the rapid replacement of damaged
cartridges. Removable surge arresters PRD 65r, PRD 40r have a remote
indication function.
Uc voltage depends on:
The earthing system.
The protection mode (MC/MD).

16561

Each surge arrester in the range has a specific


use:
Incomer end protection:
The PRD 65r is recommended for a very high risk
level (highly exposed site),
PRD 40r/PRD 40 are recommended for a high
risk level,
The PRD 15 is recommended for a low risk level.
Secondary protection:
The PRD 8 ensures secondary protection of loads
to be protected and is placed in a cascading
configuration with surge arresters at the incomer
end.

Common technical data for PRDs

Frequency: 5060Hz.
Ic:
1P and 3P: < 800A,
1P+N and 3P+N: 0A.
Operation indication by means of a
mechanical indicator:
White: normal operation,
White/red: cartridge replacement to be scheduled
in the near future,
Red: cartridge must be immediately replaced.
Disconnection of the short circuited surge arrester
to be conducted with a circuit breaker.
Permissible internal short circuit current for
PRD 8 and PRD 15:
1P+N, 3P and 3P+N: 10kA,
1P (230 V): 10kA,
1P (400): 3kA.
Permissible internal short circuit current for
PRD 40 and PRD 65:
1P+N, 3P and 3P+N: 25kA,
1P (230 V): 10kA,
1P (400): 3kA.
Downstream and upstream terminal
connection:
2.5 to 16mm2 flexible cable,
2.5 to 25mm2 rigid cable,
10mm2 flexible or rigid cable if installation with
lightning conductor.
Operating temperature: -25C, +60C.
Storage temperature: -40C, +70C.
Protection class:
IP20 at terminals,
IP40 on front panel.
Weight (g):
1P: 90,
1P+N: 180,
3P: 395,
3P+N: 460.

Specific technical data


PRD 65r

Imax (8/20 s): 65kA.


In (8/20 s): 20kA.
Operating back-up indicator on front panel.
Remote indication contact:
Electrical data:
DC: 12V, 10mA,
AC: 250V, 1A.
Connection using 0.5mm2 to 1.5mm2 cable.

PRD 40r/PRD 40

Imax (8/20 s): 40kA.


In (8/20 s): 15kA.
The PRD 40r includes:
Operating back-up indicator on front panel.
Remote indication contact:
Electrical data:
DC: 12V, 10mA,
AC: 250V, 1A.
Connection using 0.5mm2 to 1.5mm2 cable.

PRD 15

Imax (8/20 s): 15kA.


In (8/20 s): 5kA.

PRD 8

Imax (8/20 s): 8kA


In (8/20 s): 2kA.

Spare cartridges

40, 15, 8kA and neutral cartridges.


The C65r, C40r and C neutral r cartridges have
operating back-up.

Auxiliaries

Adaptable remote indication modules, EM/RM.

standards

IEC 61643-11 class 2 test.


NF C 61740/95.

81

Surge arresters

New

PRD draw out


Type
PRD
1P

PRD 65r
PRD 40r

PRD 40
PRD 15
PRD 8

Un
(V)
230
230
230
230
230
230
230
230
230
230

Uc MC
(V)
440
275
440
275
440
275
440
275
440
275

Up
(kV)
2
1.5
1.8
1.2
1.8
1.2
1.8
1.2
1.8
1.2

Width in 18mm
SP ways
1
1
1
1
1
1
1
1
1
1

Part No.

Uc MC/MD
(V)
440/275
440/275
440/275
440/275
440/275

Up
(kV)
1.2 (1)
1.2
1.2
1.2
1.2

Width in 18mm
SP ways
2
2
2
2
2

Part No.

Uc MC
(V)
440
440
440
440
440

Up
(kV)
2
1.8
1.8
1.8
1.8

Width in 18mm
SP ways
3
3
3
3
3

Part No.

16555
16556
16560
16561
16565
16566
16570
16571
16575
16576

16561

Type
PRD
1P+N

Un
(V)
PRD 65r
230
PRD 40r
230
PRD 40
230
PRD 15
230
PRD 8
230
(1) Up: L/
=1.5kV
L/N=1.5kV

L
N

16557
16562
16567
16572
16577

16562

Type
PRD
3P

PRD
PRD
PRD
PRD
PRD

L3
L2
L1

L1

82

L2

L3

65r
40r
40
15
8

Un
(V)
400
400
400
400
400

16558
16563
16568
16573
16578

Surge arresters

New

PRD draw out


Type
PRD
3P+N

Un
(V)
PRD 65r
400
PRD 40r
400
PRD 40
400
PRD 15
400
PRD 8
400
(1) Up: L/
=1.5kV.
L/N=1.5kV.

L3
L2
L1
N

L1

L2

Uc MC/MD
(V)
440/275
440/275
440/275
440/275
440/275

Up
(kV)
1.2 (1)
1.2
1.2
1.2
1.2

Width in 18mm
SP ways
4
4
4
4
4

Part No.

Uc MC
(V)
440
275
440
275
440
275
440
275
440
275
440
440

Up
(kV)
2
1.5
1.8
1.2
1.8
1.2
1.8
1.2
1.8
1.2
1.2
1.2

Width in 18mm
SP ways
1
1
1
1
1
1
1
1
1
1
1
1

Part No.

16559
16564
16569
16574
16579

L3

Replacement spare
cartridges
C65r-440
C65r-275
C40r-440
C40r-275
C40-440
C40-275
C15-440
C15-275
C8-440
C8-275
C neutral r
C neutral

16580
16581
16582
16583
16584
16585
16586
16587
16588
16589
16590
16591

83

Surge arresters

New

PF
PF
Application
The PF self-contained, multiple pole surge arrester range is especially adapted to
TT, TN-S and IT earthing systems. PF surge arresters PF65r and PF30r have a
remote indication function.

15689

Each surge arrester in the range has a specific


use:
Incomer end protection:
The PF65r is recommended for a very high risk
level (highly exposed site),
PF30r/PF30 are recommended for a high risk
level,
The PF15 is recommended for a low risk level.
Secondary protection:
The PF8 ensures the secondary protection of
loads to be protected and is placed in a cascading
configuration with surge arresters at the incomer
end.

Common technical data for PFs

PF30r and PF30

Frequency: 5060Hz.
Max. leakage current < 200mA.
Operation indication by means of an orange
indicator:
Not lit: ok,
Flashing: surge arrester must be immediately
replaced.
Disconnection upon thermal overload built into
the surge arrester.
Disconnection of the short-circuited surge arrester
to be with a circuit breaker.
Permissible internal short circuit current for
PF8 and PF15:
1P+N and 3P+N: 10kA.
Permissible internal short circuit current for PF30
and PF65:
1P+N and 3P+N: 25kA.
Operating temperature: -25C to +60C.
Storage temperature: -40C to +70C.
Protection class:
IP20 at terminals,
IP40 on front panel.
Weight (g):
1P+N: 475,
3P+N: 650.

Standard

84

PF15

NF C 61740/95.

Specific technical data


PF65r

Common mode protection:


Imax (8/20s): 65kA,
In (8/20s): 20kA,
Up: 2kV.
Test button for front panel indicator.
Remote indication contact:
Normally closed,
Connection using tunnel terminals 2 x 2.5mm2.
Connection using tunnel terminals:
Phase and neutral: 25mm2.
Earth: 50mm2.
Flexible or solid cable 10 mm2.

Common mode protection:


Imax (8/20s): 30kA,
In (8/20s): 10kA,
Up: 1.8kV.
Test button for front panel indicator.
The PF30r has a built-in remote indication
contact:
Normally closed,
Connection using tunnel terminals 2 x 2.5mm2,
Connection using tunnel terminals:
Phase and neutral: 25mm2,
Earth: 50mm2.
Flexible or solid cable 10mm2.

Common mode protection:


Imax (8/20s): 15kA,
In (8/20s): 5kA,
Up: 1.8kV.
Differential mode protection:
Imax (8/20s): 8kA,
In (8/20s): 2kA,
Up: 1kV.
Connection using tunnel terminals:
Phase and neutral: 16mm2,
Earth: 25mm2,
Flexible or rigid cable 10mm2 if installation using
lightning conductor.

PF8

Common mode protection:


Imax (8/20s): 8kA,
In (8/20s): 2kA,
Up: 1.5kV.
Differential mode protection:
Imax (8/20s): 8kA,
In (8/20s): 2kA,
Up: 1kV.
Connection using tunnel terminals:
Phase and neutral: 16mm2,
Earth: 25mm2,
Flexible or rigid cable 10mm2 if installation using
lightning conductor.

Surge arresters

New

PF
Type
PF
1P+N

PF
PF
PF
PF
PF

L1
N

Uc
(V)
440
440
440
440
440

In
(kA)
20
10
10
5
2

Width in 18mm
SP ways
7
3
3
2
2

Part No.

65r
30r
30
15
8

Un
(V)
400
400
400
400
400

Uc
(V)
440
440
440
440
440

In
(kA)
20
10
10
5
2

Width in 18mm
SP ways
7
4
4
4
4

Part No.

65r
30r
30
15
8

Un
(V)
400
400
400
400
400

15684
15689
15687
15692
15695

L1

15689

Type
PF
3P+N

PF
PF
PF
PF
PF

L3
L2
L1
N

L1

L2

15685
15690
15688
15693
15696

L3

85

Surge arresters
EM/RM remote indication modules

New

Application
The EM/RM remote indication modules are made up of two optical blocks, a
transmitter and a receiver. They are designed to remotely signal the disconnection
of the surge arrester.

The EM transmitter is mounted to the left and the


RM receiver to the right side of a surge arrester.
The RM receiver has an output contact for the
remote transfer of surge arrester disconnection
information.
The modules can monitor up to 15 surge arrester
modules (18mm) with a limit of 270mm.

Technical data

Voltage rating: 230V AC.


Frequency: 5060Hz.
Surge arrester status indication: by means of
green and red indicators on the front panel
Output contact:
NO/NC (closed between terminals 2 and 4 if fault
on surge arrester),
Min. power: 6V DC and 10mA,
Max. power: 250V AC and 5A,
Insulation between contacts: 1kV AC,
Insulation between the contacts and the coil:
2.5kV AC.
Flexible or solid cable connection:
Up to 2.5mm2.
Operating temperature: -20C, +40C.
Storage temperature: -40C, +70C.
Weight (g): 20.

Type
Remote indication module
EM/RM

L
N

1 3

86

1 3

2 4

Width in 18mm Part No.


SP ways
1+1
16592