This document provides specifications for two multi-function microprocessor-based circuit breaker relays: the EOCR-3DE and EOCR-3EZ. The EOCR-3DE provides overcurrent, undercurrent, phase loss, phase unbalance, phase reversal, and locked rotor protection. It has adjustable trip time characteristics and load alerting functionality. The EOCR-3EZ provides all the same protections as the EOCR-3DE plus ground fault protection. Both models have digital ammeters, trip cause indicators, and independently adjustable start and trip delay times.

Uploaded by

Mushfiqur Rahman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
389 views1 page

Eocr 3de 3ez

This document provides specifications for two multi-function microprocessor-based circuit breaker relays: the EOCR-3DE and EOCR-3EZ. The EOCR-3DE provides overcurrent, undercurrent, phase loss, phase unbalance, phase reversal, and locked rotor protection. It has adjustable trip time characteristics and load alerting functionality. The EOCR-3EZ provides all the same protections as the EOCR-3DE plus ground fault protection. Both models have digital ammeters, trip cause indicators, and independently adjustable start and trip delay times.

Uploaded by

Mushfiqur Rahman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

EOCR-3DE/3EZ

MCU Based
3 Integral Current Transformers
Over-current, Under-Current, Phase Loss, Phase
Unbalance, Phase Reversal, Locked Rotor Protection
Digital Ammeter & Trip cause indication
Selectable Trip Time-Current Characteristics
Independently Adjustable Starting Trip Delay and
Operating Trip Time
+ Load Alerting Function
EOCR-3DE
+ Ground Fault Protection EOCR-3EZ
EOCR-3DE / 3EZ

Protection

Typical Wiring
EOCR-3DE

Protective Item
Over-current
Under-current
Phase Loss
Phase Unbalance
Phase Reversal
Locked Rotor
-

EOCR-3EZ
Trip Time
O-TIME
0.5~30 sec
3 sec
8 sec
0.1~0.3 sec
D-TIME
-

Protective Item
Over-current
Under-current
Phase Loss
Phase Unbalance
Phase Reversal
Locked Rotor
Ground Fault

Trip Time
O-TIME
0.5~30 sec
3 sec
8 sec
0.1~0.3 sec
D-TIME
0.05~10 sec

Specification
Model
Over Current Setting Range
Ground Fault Current Setting
Alert Setting
Start Delay Time Setting (D-TIME)
Trip Delay Time Setting (O-TIME) INV
DEF
Control Voltage
Contact Rating
OL
AL/GR
Rating
Time Characteristic
In/tcmode
dE/tcmode
Troubleshooting / Trip Indication
Current Sensing
Mounting

EOCR-3DE

EOCR-3EZ
Refer Table #1

50 ~ 100% / OFF

A: 0.02 ~ 3A / B: 0.2~10A
-

1 ~ 200 sec
1 ~ 30
0.2 ~ 30 sec
24VAC/DC, 110VAC 15%, 220VAC 15%
2-SPST
1-SPST
AL Relay
Ground Fault Relay
3A/250VAC Resistive
Inverse (See Curve-1)
Definite (See Curve-2)
LED Display (SSD+LED)
3-CT
35mm Din-rail

EOCR-3DE

Table #1. Current Range


Current Setting Range
(Amps)
0.5 ~ 60A
0.25 ~ 3.0A
0.1 ~ 1.2A
1 ~ 12A
1.5 ~ 18A
2.0 ~ 24A
2.5 ~ 30A
3.0 ~ 36A
4.0 ~ 48A
5 ~ 60A
6 ~ 72A
7.5 ~ 90A
10 ~ 120A
12 ~ 144A
15 ~ 180A
20 ~ 240A
25 ~ 300A
30 ~ 360A
40 ~ 480A
50 ~ 600A
60 ~ 720A
75 ~ 900A
80 ~ 960A

12

Number of Conductors
thru CT windows
1
2
5
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

Extermal CT Ratio

Setting of CT Ratio

Remark

10 : 5
15 : 5
20 : 5
25 : 5
30 : 5
40 : 5
50 : 5
60 : 5
75 : 5
100 : 5
120 : 5
150 : 5
200 : 5
250 : 5
300 : 5
400 : 5
500 : 5
600 : 5
750 : 5
800 : 5

OFF(Mode : --)
2t
5t
10
15
20
25
30
40
50
60
75
100
120
150
200
250
300
400
500
600
750
800

Wide Range

EOCR-3EZ
Tolerance(3DD/ 3DZ / FD / FDZ / PMZ / SSD)
Current

Time

I<1A :
I 1A :

0.05A
5%

0.05s Within 0.05s


t 3s : 0.2S
t>3s : 5%

Caution
The extermal CT should be used in case Inverse curve(toln setting)
is applied over 10Amps.