Relion 605 series

Feeder protection and control


REF601
Product Guide

Relion 605 series


Relion 605 series

Feeder Protection
REF601
Product version: 2.0

1MDB07207-YN

Contents
1. Description......................................................................3

13. Inputs and outputs...........................................................6

2. Relay functions................................................................3

14. Communication................................................................6

3. Protection functions........................................................4

15. Application warning.........................................................6

4. Application.......................................................................4

16. Technical data..................................................................7

5. Sensor technology..........................................................4

17. Protection functions.......................................................13

6. Control............................................................................5

18. Dimension and mounting...............................................16

7. Measurement..................................................................5

19. Selection and ordering data...........................................17

8. Event log.........................................................................5

20. Accessories and ordering data.......................................18

9. Recorded data.................................................................5

21. Terminal diagram...........................................................19

10. Self-supervision and test function....................................5

22. References....................................................................20

11. Trip-circuit supervision.....................................................6

23. Document revision history..............................................20

12 Access control................................................................6

Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any
errors that may appear in this document.
Copyright 2012 ABB Ltd.
All rights reserved.
Trademarks
ABB and Relion are registered trademark of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered
trademarks of their respective holders.

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Issued: 2012-03-27
Revision: E

1. Description
REF601 is a dedicated feeder protection relay,
intended for the protection and control of utility
substations and industrial power systems, in primary
and secondary distribution networks. REF601 is a
member of ABBs Relion product family and part of
its 605 series.
The relay uses the Rogowski coil sensors for current measurement. The new feeder protection relay
is designed to unleash the advantages of current
sensors for protection and control in medium voltage
applications.

2. Relay functions
REF601 offers pre-configured functionality which facilitates easy and fast commissioning of switchgear.
To emphasize the relays simplicity of usage, only application specific parameters needs to set within the
relays intended area of application.
The settings can be changed by LHMI (local humanmachin interface) or through optional communication
interface MODBUS master with setting capability.
The relay offers protection, control, measurement
and condition monitoring functionality.

Table 1. Supported functions of REF601


Functionality

IEC

ANSI

Non-directional overcurrent protection, low-set stage

3I>

51

Non-directional overcurrent protection, high-set stage

3I>>

50-1

Non-directional overcurrent protection, very high-set stage

3I>>>

50-2

Earth-fault protection, low-set stage

Io>

51N

Earth-fault protection, high-set stage

Io>>

50N

Three phase transformer inrush detector

3I2f>

68

I <-> O CB

I <-> O CB

TCS

TCM

Three-phase current measurement

3I

3I

Residual current measurement

Io

In

Protection

Control
Circuit-breaker control

Condition monitoring
Trip circuit supervision
Measurement

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

3. Protection functions
REF601 offers three-stage phase segregated
overcurrent and two-stage earth-fault protection
functions. The transformer inrush detector function
is incorporated to prevent unwanted trippings due
to energizing of transformers.
The low-set stages for overcurrent and earth-fault

protection are equipped with selectable characteristics - Definite time (DT) and Inverse definite
minimum time (IDMT) . The relay features standard IDMT characteristics Normal Inverse (NI),
Very Inverse (VI), Extremely Inverse (EI), Long-time
Inverse (LI) and a special characteristic RI inverse
(RI) for better co-ordination with rest of the network
protection.

50-1

50-1

50-2

50-2

50N

Lockout
relay

86

REF601

Lockout
relay

86

REF601

Figure 1. Protection function overview of REF601



with earth current measurement by internal

calculation

Figure 2. Protection function overview of REF601


with earth current measurement by exter
nal core-balance current transformer

4. Application
The REF601 is a protection relay aimed at protection and control of incoming and outgoing feeders
in MV distribution substations. The relay can be
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
applied for the short-circuit over current and earthfault protection of overhead lines and cable feeders
of distribution and sub-distribution network.

5. Sensor technology
Sensors based on Rogowski coil principle have
been introduced in order to get benefit of improved
performance like saturation of conventional current
transformer and equipment size reduction. ABB is
offering two types of sensors - KECA and KEVCR
which employees the Rogowski coil principle for
measurement of current. Albeit this principle is far
from new, now it is possible to exploit the advantages of sensor with the advent of numerical relays
like REF601.

The relay is well-matched for mounting on the ABB


circuit breakers VD4 & HD4. Along with sensors, it
will be a part of ABBs offering of integrated apparatus. The relay has small mounting depth and does
not have any loose mounting accessories while the
press-fit mounting arrangement makes it suitable
for quick and easy installation on switchgear panels
too.

50N

Rogowski coil is a toroidal coil without an iron core,


placed around the primary conductor in the same
way as the secondary winding in a current transformer. However, the output signal from Rogowski

ABB

Feeder Protection
REF601
Product version: 2.0

coil is not current, but a voltage. Due to absence


of ferromagnetic core, the sensor is linear up to the
highest currents.
The wide measurement range of sensors with high
accuracy eliminates the need for high variants of
conventional instrument transformers, resulting in
simplified engineering, logistics and reduced inventory. The low level voltage signals and integrated
secondary cables contribute to easy and fast installation with enhanced safety.

6. Control
The relay offers control of one circuit breaker with
dedicated push-buttons and guidance on local HMI
for opening and closing. It includes two dedicated
outputs for breaker control. The breaker control is
also possible through optional MODBUS communication.

7. Measurement
The relay continuously measures phase currents
and earth current. Earth current can be measured
using external core balance current transformer or
can be calculated internally.
During service, the default view of display shows
the most loaded phase current in primary terms
(Amps) and the earth current in terms of nominal
value of CT. The values measured can be accessed
locally via the user interface on the relay or remotely
via the communication interface of the relay.
To maintain the measurement accuracy of the
overall protection system, the sensor calibration
constants available on the rating plate of sensors
can be programmed to the relay.

8. Event log
To collect sequence-of-events (SoE) information,
the relay incorporates a non-volatile memory with a
capacity of storing 100 events with associated time
stamps with resolution of 1 milli second. Event log
includes trip circuit supervision status, protection

ABB

1MDB07207-YN

operation status, binary I/O status and relay fault


code. The event logs are stored sequentially, the
most recent being first and so on. The non-volatile
memory retains its data also in case the relay temporarily loses its auxiliary supply.
The event log facilitates detailed post-fault analysis
of feeder faults and disturbances. The SoE information can be accessed locally via the user interface
on the relay front panel or remotely via the communication interface of the relay.

9. Recorded data
The relay stores fault records of analog values for
two trip events in non-volatile memory. The fault
recording is triggered by the trip signal of protection
function. A sample of analog value is recorded for
every power frequency cycle. Fifteen such samples
are recorded, five before the trip and ten after the
trip event. These records enable the user to analyze
the two most recent power system events. Each
record includes the current values for three phases
and earth current.
The relay records the number of phase and earth
fault trip events into dedicated trip counters. These
trip counters can not be reset by the user and are
stored in non-volatile memory.
The recorded information can be accessed locally
via user interface on the relay front panel and can
be uploaded for subsequent fault analysis.

10. Self-supervision and test function


The relays built-in self-supervision system continuously monitors the state of the relay hardware
and the operation of the relay software. Any fault
or malfunction detected will be used for alerting
the operator. A permanent relay fault will block the
protection functions of the relay to prevent incorrect
relay operation.
The relay supports a built-in test mode which enables user to test the relay HMI and trip outputs.

Feeder Protection
REF601
Product version: 2.0

1MDB07207-YN

11. Trip-circuit supervision


The trip-circuit supervision continuously monitors
the availability and operability of the trip circuit. It
provides open-circuit monitoring both when the circuit breaker is in its closed and in its open position.
It also detects loss of circuit-breaker control voltage.

14. Communication
The relay is available with optional communication feature with Modbus RTU protocol on RS-485
bus with two wire connection. This allows relay to
connect to control and monitoring system through
serial communication for remote monitoring.

12. Access control


To protect the relay from unauthorized access and
to maintain the integrity of information, the relay
is armed with a three level, role-based user authentication system with individual password for
the operator, engineer and administrator level. The
password is a combination of different navigation
keys.

15. Application warning


In case the relay REF601 is supplied with UPS stepwave or square-wave, an interposing transformer is
needed to keep the supply voltage (peak voltage)
below the upper limit of the relay.
These are the recommended transformer characteristics:
Nominal Power: 20 VA
Secondary voltage: in the range 30...150 V AC

13. Inputs and outputs


The relay is equipped with three Rogowski sensor
inputs. The relay has an additional earth-current
input suitable for a 1A which can be connected to
core-balanced current transformer /split core current transformer.
Relay binary input/output overview:
Two binary inputs one for remote-trip and one for
remote-reset
One normally open trip output, with trip circuit
supervision functionality
One normally-closed trip output
Two signalling outputs one for phased overcurrent fault and one for earth fault
One breaker close output
Unit ready / IRF output
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN
LED indication for Ready/IRF, Protection start,
protection trip, Phase fault and Earth fault trip,
Trip circuit fault

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

16. Technical data


Table 2. Dimensions
Description

Value

Width

frame

130.0 mm

case

121.5 mm

Height

frame

160.0 mm

case

151.5 mm

Depth

case

102.0 mm (92 + 10 mm)

Weight

relay

1.2 kg

Table 3. Power supply


Description

Value

Uaux nominal

24...240 V AC, 50 and 60 Hz

24...240 V DC

Uaux variation

85...110% of Uaux (20.4...264 V AC)

70...120% of Uaux (16.8...288 V DC)

Burden of auxiliary voltage supply under < 12.0 VA


quiescent (Pq)/operating condition
Ripple in the DC auxiliary voltage

Max 12% of the DC value (at frequency of 100 Hz)

Maximum interruption time in auxiliary

50 ms at Uaux rated

DC voltage without resetting the relay

Table 4. Energizing inputs


Description

Value

Rated frequency

50/60 Hz

Phase sensor
inputs

5 Hz

Input type:

Rogowski coil sensor

Rated transformation ratio, Kra

250A / 0.15V at 50Hz


250A / 0.18V at 60Hz

Earth current
input

Linear current measurement

4A - 25 kA

Input type

Current transformer

Rated current, In

1A

Linear current measurement

0.5- 12.5 x In

Thermal withstand capability:


Continuously

4A

For 1 sec

100 A

Dynamic current withstand:

ABB

Half-wave value

250 A

Input impedance

< 100 m
7

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 5. Binary input


Value

Description
Rated voltage

24...240 V AC / DC

Operating range

85...110% of Uaux for AC and 70...120% of Uaux for DC

Current drain

2...20 mA

Power consumption / input

< 0.5 W

Input sensing time

100 ms

Table 6. Double-pole power output relay with TCS function (Trip 2 output - Normally open, pulsed contact)
Value

Description
Rated voltage

240 V AC / DC

Continuous contact carry


Make and carry for 3.0 s

8A

15 A

Make and carry for 0.5 s

30 A

Breaking capacity when the control-circuit time

5A/3A/1A

constant L/R<40 ms, at 48/110/220 V DC


(two contacts connected in series)
Minimum contact load

100 mA at 24 V AC / DC

Trip-circuit supervision (TCS):


Control voltage range
Current drain through the supervision circuit

48...250 V AC / DC
~ 1.5 mA

Minimum voltage over the TCS contact

20V AC / DC (15...20 V)

Table 7. Single-pole power output relay (Trip 1 output - Normally closed, pulsed contact)
Value

Description
Rated voltage

240 V AC / DC

Continuous contact carry

8A

GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

Make and carry for 3.0 s

15 A

Make and carry for 0.5 s

30 A

Breaking capacity when the control-circuit time

5A / 0.2 A

constant L/R<40 ms, at 35/220 V DC


Minimum contact load

Pulse duration of contact operation

100 mA at 24 V AC / DC
200 msec

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 8. Single-pole signal and IRF output relay (O/C and E/F Trip, Unit ready, Breaker close)
Value

Description
Rated voltage

240 V AC / DC

Continuous contact carry

6A

Make and carry for 3.0 s

8A

Make and carry for 0.5 s

10 A

Breaking capacity when the control-circuit time

4A / 0.15 A

constant L/R<40 ms, at 35/220 V DC


Minimum contact load

100 mA at 24 V AC / DC

Table 9. Degree of protection of relay


Value

Description
Front side

Side with terminal connector

IP 43
IP 20

Table 10. Environmental conditions


Value

Description
Operating temperature range

-25...+70C (<16 h)

Short-time service temperature range


Relative humidity

Atmospheric pressure
Altitude

-25...+55C

< 93%, non-condensing


86...106 kPa

Transport and storage temperature range

up to 2000 m
-40...+85C

Table 11. Environmental tests


Description

Type test value

Dry heat test (humidity < 50% )

Reference
IEC 60068-2-2
IEC 60068-2-48

Working
Storing

96 h at +70C
96 h at +85C

Dry cold test


Working
Storing

IEC 60068-2-1
IEC 60068-2-48
96 h at -25C
96 h at -40C

Damp heat test, cyclic

IEC 60068-2-30
2 cycles at +25C+55C
humidity > 93%

Damp heat test, steady state

IEC 60068-2-78
96 h at +40C, humidity
> 93%

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 12. Electromagnetic compatibility tests


Description

Type test value

Reference
IEC 61000-4-12

1 MHz burst disturbance test:

IEC 60255-22-1, class III


Common mode
Differential mode

2.5 kV, 1MHz, 400 pulses/sec


1.0 kV, 1MHz, 400 pulses/sec
IEC 60255-22-2, class III
IEC 61000-4-2

Electrostatic discharge test:


Contact discharge
Air discharge

6 kV, 150 pF/330


8 kV, 150 pF/330
IEC 60255-22-3, class III
IEC 61000-4-3

Radio frequency, electro-magnetic


field immunity test:
10 V/m
f=80-1000 MHz
10 V/m
f=80, 160, 450, 900 MHz

IEC 60255-22-4, class A


IEC 61000-4-4

Fast transient disturbance tests:

All ports

4 kV, 5.0 kHz


IEC 60255-22-5

Surge immunity test:

IEC 61000-4-5
Common mode
Differential mode

1.0 kV, 1.2/50 s


0.5 kV, 1.2/50 s
IEC 61000-4-8

Immunity to conducted disturbance


induced by RF:
Continuous
Short duration ( 1 sec )

GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

100 A/m
1000 A/m
IEC 60255-22-6, class III

Conducted radio frequency


interferene tests:

IEC 61000-4-6
10 V
f=150 KHz...80 Mhz
IEC 61000-4-9

Pulse magnetic field immunity tests:


1000 A/m, 6.4/16 s

10

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 13. Electromagnetic compatibility tests, continued


Description

Type test value

Reference
IEC 60255-25

Emission tests:

EN 55011-CISPR II
Conducted
150 kHz-0.5 MHz
0.5 MHz-30 MHz

< 66 dB ( V/m)
< 60 dB ( V/m)

Radiated
30-230 MHz
230-1000 MHz

< 40 dB ( V/m)
< 47 dB ( V/m)

Table 14. Insulation tests


Description

Type test value

Dielectric test
Test voltage

IEC 60255-5
IEC 60255-27
2 kV, 50 Hz, 1 min

Impulse voltage test


Test voltage

IEC 60255-5
IEC 60255-27
5 kV, 1.2/50 s, 0.5 J

Insulation resistance test


Isolation resistance

Reference

IEC 60255-5
IEC 60255-27
> 100 M at 500 V DC

Table 15. Mechanical tests


Description

Type test value

Vibration tests

Reference
IEC 60255-21-1, class II

Response

10...150 Hz, 0.035 mm / 1.0 g,


1 sweep / axis

Endurance / Withstand

10...150 Hz, 2.0 g,


20 sweeps / axis

Shock tests

IEC 60255-21-2, class II

Response

10 g, 3 pulses in each direction

Endurance / Withstand

30 g, 3 pulses in each direction

Bump tests

IEC 60255-21-2, class II


20 g, 1000 bumps in each direction

ABB

11

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 16. Product safety


Description

Type test value

LV directive

2006/95/IEC

Standard

EN 60255-27 (2005)
EN 60255-1 (2009)

Table 17. EMC compliance


Description

Type test value

EMC directive

2004/108/IEC

Standard

EN 50263 (2000)
EN 60255-26 (2007)

Table 18. RoHS compliance


Description
Complies with RoHS directive 2002/95/IEC
Table 19. Data communication (Optional)
Description

Type test value

Protocol

MODBUS RTU

Communication port

RS485, 2 wire

GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

12

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

17. Protection functions


Table 20. Low-set phase overcurrent protection, stage I> / 51
Parameter

Value (Range)

Setting range of pick-up current I >

0.2...1.0 x In in steps 0.025, infinite

Operation accuracy

Operate time delay (DMT) t >

0.1...1.6 sec in steps of 0.1 for B=1

5.0% of set value

0.5...8.0 sec in steps of 0.5 for B=5


Operation time accuracy
Operating curve type

5.0% of set value or 30 msec

IEC 60255-3:
Normal inverse, Very inverse, Extremely inverse, Long-time inverse
Special curves:
RI inverse

Time multiplier setting k

0.1...1.6, in steps of 0.1

Operation time accuracy


IEC characteristics

class E(5) or 30 msec

RI characteristics

Reset ratio

IDMT : 0.96 and DT : 0.98

5.0% of set value or 30 msec

Table 21. High-set phase overcurrent protection, stage I>> / 50-1


Parameter

Value (Range)

Setting range of pick-up current I >>

1.0...2.75 x In in steps 0.25, infinite

Operation accuracy

Operation mode

Definite time

Operate time delay (DMT) t >>

0.1...0.45 sec in steps of 0.05

Operation time accuracy

Reset ratio

0.98

5.0% of set value

5.0% of set value or 30 msec

Table 22. Very High-set phase overcurrent protection, stage I>>> / 50-2
Parameter

ABB

Value (Range)

Setting range of pick-up current I >>>

2.0...15.0 x In in steps 1.0, infinite

Operation accuracy

Operation mode

Instantaneous

Operate time t >>>

0.05 sec

Operation time accuracy

Reset ratio

0.98

5.0% of set value

15 msec

13

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 23. Low-set earth-fault protection, stage Io > / 51N


Parameter

Value (Range)

Nominal value of earth current

1A

Measurement range

0.05...5 x In

Setting range of pick-up current Io >

External earth measurement : 0.05...0.1 x In in steps 0.05, infinite


Internal earth measurement : 0.2...1.0 x In in steps 0.05, infinite

Operation accuracy

External earth measurement : 5.0% of set value


Internal earth measurement :

Operate time delay (DMT) to >

15.0% of set value

0.1...1.6 sec in steps of 0.1 for B=1


0.5...8.0 sec in steps of 0.5 for B=5

Operation time accuracy

External earth measurement : 5.0% of set value or 30 msec


Internal earth measurement :

Operating curve type

10.0% of set value or 30 msec

IEC 60255-3:
Normal inverse, Very inverse, Extremely inverse, Long-time inverse
Special curves:
RI inverse

Time multiplier setting k

0.1...1.6, in steps of 0.1

Operation time accuracy


IEC characteristics

External earth measurement : class E(5) or 30 msec

RI characteristics

External earth measurement : class E(7.5) or 30 msec

IEC characteristics

Internal earth measurement :

RI characteristics

Internal earth measurement :

Reset ratio

IDMT : 0.96 and DT : 0.98

5.0% of set value or 30 msec


10.0% of set value or 30 msec

Table 24. High-set earth-fault protection, stage Io >> / 50N


Parameter
GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

Value (Range)

Setting range of pick-up current Io >>

0.5...4.0 x In in steps 0.25, infinite

Operation accuracy

External earth measurement : 5.0% of set value


Internal earth measurement :

15.0% of set value

Operation mode

Definite time

Operate time delay (DMT) to >>

0.00...0.75 sec in steps of 0.05

Operation time accuracy

External earth measurement : 5.0% of set value or 30 msec


Internal earth measurement :

10.0% of set value or 30 msec

For setting 0.00 msec : 45 msec


Reset ratio

14

0.98

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

Table 25. Transformer inrush detector


Parameter

ABB

Value (Range)

Inrush threshold value

0.2...20 x In

Ratio Setting

30%...50%

15

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

18. Dimensions and mounting


The REF601 have been equipped with in-built pressfit mechanism. Without using an additional mounting
accessories, the REF601 can be easily flush mounted on the panel.

With appropriate mounting accessories the REF601


can be mounted on the circuit breakers type VD4 /
HD4.

The panel cut-out for flush mouting:


Height : 151.5 1 mm
Width : 121.5 1 mm
Thickness of panel : 2.0 - 3.0 mm
102.0

130

4.0

151.5

160

2.5

85.5

3.0 (Max.)
Front

Left

121.5

GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

Top
Figure 3. Dimension of REF601 - Flush mounting

16

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

19. Selection and ordering data


The relay type and serial number label identifies the
protection relay. An order number label is placed on
the side of the relay. The order number consists of
a string of codes generated from the hardware and
software modules of the relay The serial number and
order number label is placed on side of relay.

Use the ordering key information in Fig. 4 to generate the order number when ordering complete
protection relays.

REF601 B A 4 2 6 B A 1 X E
#

Description

Relay type
REF601

REF601
2

Standard
IEC

CEI

3,4

Analog input / output

5,6

Binary input / output

A4

3 sensor and ground CT

26

2 BI + 6 BO

REF601 B A 4 2 6 B A 1 X E
#

Description

Serial communication

with RS485

None

Communication protocol
MODBUS RTU

None

Power supply
1

24...240V AC / DC
10

For future use

11

Version

Undefined

Product version 2.0

Example code: REF601 B A 4 2 6 B A 1 X E

Your ordering code:


Digit (#)

Code

8 9 10 11

Figure 4. Ordering key for complete relay

ABB

17

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

20. Accessories and ordering data


Table 26. Compatible sensors
Item
KEVCR for integrated circuit-breakers type VD4/HD4

Order number
KEVCR24OC2R0101, 630A
KEVCR24AC2R0102, 1250A

KECA for other applications where relay is panel mounted

KECA 250 B1 :

For more information please refer to the catalogue reference

1VL5400052V0101

- no. 1VLC000584.

Figure 5. Outline view of KEVCR sensor

GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

Figure 6. Outline view of KECA sensor

18

ABB

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

21. Terminal diagram

REF601
XK5

DIFF

XK9

IL1
Uaux

XK6
XK7

DIFF

IL2

DIFF

IL3

1
2
3
4

XK2

XK8
1
2

Io (1A)

E/F
Trip

2
3

XK4
1
2

O/C
Trip

BI : Remote Trip

4
5

3
4

Unit
Ready

BI : Remote Reset

6
7

Bkr.
Close
(+)

Trip2 *
TCS

XK3
1
2
3

D+
DG

Communication
on Modbus RTU
Protocol (Optional)

9
10

XK10
1
Trip1 *

SHIELD

* Contact operates for 200 msec and resets

Figure 7. Terminal diagram of REF601

ABB

19

1MDB07207-YN

Feeder Protection
REF601
Product version: 2.0

22. References
The www.abb.com/substationautomation portal
offers you information about the distribution automation product and service range.
You will find the latest relevant information on the
REF601 protection relay on the product page.
The download area on the right hand side of the
Web page contains the latest product

documentation, such as technical reference manual,


installation manual, operator manual, and so on. The
selection tool on the Web page helps you find the
documents by the document category and language.
The Features and Application tabs contain product
related information in a compact format.

23. Document revision history


Document revision/date

Product version

History

A/2009-03-20

1.0

First release

B/2009-08-21

1.0 SP

Content updated to correspond to


the service pack release

C/2010-09-30

1.0 SP2

Content updated to correspond to


the service pack release

D/2011-04-21

1.0 SP2

Content updated

E/2012-04-04

2.0

Content updated to correspond to


the product version

GUID-89A9F7DF-FB82-4E8D-B449-7C0BB51C1DCA V1 EN

20

ABB

www.abb.com/substationautomation

1MDB07207-YN E

ABB Ltd, Distribution Automation


Maneja Works
Vadodara-390013, India
Phone: +91 265 2604386
Fax:
+91 265 2638922

Copyright 2012 ABB. All rights reserved.