S1DX
COMPACT SIZE
HIGH PRECISION TIMERS
VARIOUS OUTPUT &
OPERATION MODE TYPES
(one)
S1DX Timers
UL File No.: E122222
CSA File No.: LR39291
Features
3 operation modes added for
fuller lineup
Output contact relay construction
Available contact relay output types: 2C and 4C
Now, operation modes include not only
On Delay, but Flicker, One Shot, and
One Cycle modes as well.
Panels can be installed
Operation can be
checked easily
In addition to conventional DIN rail
installation, panels can be installed using
an mounting frame.
The compact timer size means that larger
panels can be used.
Power supply: Green
Operation: Orange LED display
Output terminal
A plug-in terminal and printed
circuit terminal are provided.
Compliant with UL,
CSA and CE.
Easier than ever to
read and use
Large-sized transparent dial
makes setting time easy!
High precision
Repeatability error: 1%
RoHS Directive compatibility information
http://www.nais-e.com/
Product types
Plug-in terminal
Power ON-delay
AC operating type
Time range
Time-out
2 Form C
type
Time-out
4 Form C
type
0.05 to 0.5 s
0.1 to 1 s
0.1 to 3 s
0.2 to 5 s
0.5 to 10 s
1 to 30 s
3 to 60 s
0.1 to 3 min
0.5 to 10 min
1 to 30 min
3 to 60 min
0.1 to 3 h
0.05 to 0.5 s
0.1 to 1 s
0.1 to 3 s
0.2 to 5 s
0.5 to 10 s
1 to 30 s
3 to 60 s
0.1 to 3 min
0.5 to 10 min
1 to 30 min
3 to 60 min
0.1 to 3 h
24V AC
Part number
S1DX-A2C0.5S-AC24V
S1DX-A2C1S-AC24V
S1DX-A2C3S-AC24V
S1DX-A2C5S-AC24V
S1DX-A2C10S-AC24V
S1DX-A2C30S-AC24V
S1DX-A2C60S-AC24V
S1DX-A2C3M-AC24V
S1DX-A2C10M-AC24V
S1DX-A2C30M-AC24V
S1DX-A2C60M-AC24V
S1DX-A2C3H-AC24V
S1DX-A4C0.5S-AC24V
S1DX-A4C1S-AC24V
S1DX-A4C3S-AC24V
S1DX-A4C5S-AC24V
S1DX-A4C10S-AC24V
S1DX-A4C30S-AC24V
S1DX-A4C60S-AC24V
S1DX-A4C3M-AC24V
S1DX-A4C10M-AC24V
S1DX-A4C30M-AC24V
S1DX-A4C60M-AC24V
S1DX-A4C3H-AC24V
100 to 120V AC
Part number
S1DX-A2C0.5S-AC120V
S1DX-A2C1S-AC120V
S1DX-A2C3S-AC120V
S1DX-A2C5S-AC120V
S1DX-A2C10S-AC120V
S1DX-A2C30S-AC120V
S1DX-A2C60S-AC120V
S1DX-A2C3M-AC120V
S1DX-A2C10M-AC120V
S1DX-A2C30M-AC120V
S1DX-A2C60M-AC120V
S1DX-A2C3H-AC120V
S1DX-A4C0.5S-AC120V
S1DX-A4C1S-AC120V
S1DX-A4C3S-AC120V
S1DX-A4C5S-AC120V
S1DX-A4C10S-AC120V
S1DX-A4C30S-AC120V
S1DX-A4C60S-AC120V
S1DX-A4C3M-AC120V
S1DX-A4C10M-AC120V
S1DX-A4C30M-AC120V
S1DX-A4C60M-AC120V
S1DX-A4C3H-AC120V
200 to 220V AC
Part number
S1DX-A2C0.5S-AC220V
S1DX-A2C1S-AC220V
S1DX-A2C3S-AC220V
S1DX-A2C5S-AC220V
S1DX-A2C10S-AC220V
S1DX-A2C30S-AC220V
S1DX-A2C60S-AC220V
S1DX-A2C3M-AC220V
S1DX-A2C10M-AC220V
S1DX-A2C30M-AC220V
S1DX-A2C60M-AC220V
S1DX-A2C3H-AC220V
S1DX-A4C0.5S-AC220V
S1DX-A4C1S-AC220V
S1DX-A4C3S-AC220V
S1DX-A4C5S-AC220V
S1DX-A4C10S-AC220V
S1DX-A4C30S-AC220V
S1DX-A4C60S-AC220V
S1DX-A4C3M-AC220V
S1DX-A4C10M-AC220V
S1DX-A4C30M-AC220V
S1DX-A4C60M-AC220V
S1DX-A4C3H-AC220V
* Wire springs (ADX18005) are included.
All Rights Reserved COPYRIGHT Matsushita Electric Works, Ltd.
220 to 240V AC
Part number
S1DX-A2C0.5S-AC240V
S1DX-A2C1S-AC240V
S1DX-A2C3S-AC240V
S1DX-A2C5S-AC240V
S1DX-A2C10S-AC240V
S1DX-A2C30S-AC240V
S1DX-A2C60S-AC240V
S1DX-A2C3M-AC240V
S1DX-A2C10M-AC240V
S1DX-A2C30M-AC240V
S1DX-A2C60M-AC240V
S1DX-A2C3H-AC240V
S1DX-A4C0.5S-AC240V
S1DX-A4C1S-AC240V
S1DX-A4C3S-AC240V
S1DX-A4C5S-AC240V
S1DX-A4C10S-AC240V
S1DX-A4C30S-AC240V
S1DX-A4C60S-AC240V
S1DX-A4C3M-AC240V
S1DX-A4C10M-AC240V
S1DX-A4C30M-AC240V
S1DX-A4C60M-AC240V
S1DX-A4C3H-AC240V
S1DX
DC operating type
Time range
Time-out
2 Form C
type
Time-out
4 Form C
type
0.05 to 0.5 s
0.1 to 1 s
0.1 to 3 s
0.2 to 5 s
0.5 to 10 s
1 to 30 s
3 to 60 s
0.1 to 3 min
0.5 to 10 min
1 to 30 min
3 to 60 min
0.1 to 3 h
0.05 to 0.5 s
0.1 to 1 s
0.1 to 3 s
0.2 to 5 s
0.5 to 10 s
1 to 30 s
3 to 60 s
0.1 to 3 min
0.5 to 10 min
1 to 30 min
3 to 60 min
0.1 to 3 h
12V DC
Part number
S1DX-A2C0.5S-DC12V
S1DX-A2C1S-DC12V
S1DX-A2C3S-DC12V
S1DX-A2C5S-DC12V
S1DX-A2C10S-DC12V
S1DX-A2C30S-DC12V
S1DX-A2C60S-DC12V
S1DX-A2C3M-DC12V
S1DX-A2C10M-DC12V
S1DX-A2C30M-DC12V
S1DX-A2C60M-DC12V
S1DX-A2C3H-DC12V
S1DX-A4C0.5S-DC12V
S1DX-A4C1S-DC12V
S1DX-A4C3S-DC12V
S1DX-A4C5S-DC12V
S1DX-A4C10S-DC12V
S1DX-A4C30S-DC12V
S1DX-A4C60S-DC12V
S1DX-A4C3M-DC12V
S1DX-A4C10M-DC12V
S1DX-A4C30M-DC12V
S1DX-A4C60M-DC12V
S1DX-A4C3H-DC12V
24V DC
Part number
S1DX-A2C0.5S-DC24V
S1DX-A2C1S-DC24V
S1DX-A2C3S-DC24V
S1DX-A2C5S-DC24V
S1DX-A2C10S-DC24V
S1DX-A2C30S-DC24V
S1DX-A2C60S-DC24V
S1DX-A2C3M-DC24V
S1DX-A2C10M-DC24V
S1DX-A2C30M-DC24V
S1DX-A2C60M-DC24V
S1DX-A2C3H-DC24V
S1DX-A4C0.5S-DC24V
S1DX-A4C1S-DC24V
S1DX-A4C3S-DC24V
S1DX-A4C5S-DC24V
S1DX-A4C10S-DC24V
S1DX-A4C30S-DC24V
S1DX-A4C60S-DC24V
S1DX-A4C3M-DC24V
S1DX-A4C10M-DC24V
S1DX-A4C30M-DC24V
S1DX-A4C60M-DC24V
S1DX-A4C3H-DC24V
* Wire springs (ADX18005) are included.
Please select power flicker, power one-shot or power one-cycle specifications based on the ordering information listed below.
ORDERING INFORMATION
Ex. S1DX-
Operation mode
Control output
arrangement
F: Power Flicker
S: Power One-shot
C: Power One-cycle
2C: Timed-out 2 Form C
4C: Timed-out 4 Form C
2C
5S
AC120V
Time range *
0.5S: 0.05 to 0.5 s
1S: 0.1 to 1 s
3S: 0.1 to 3 s
5S: 0.2 to 5 s
10S: 0.5 to 10 s
30S: 1 to 30 s
60S: 3 to 60 s
3M: 0.1 to 3 min
10M: 0.5 to 10 min
30M: 1 to 30 min
60M: 3 to 60 min
3H: 0.1 to 3 h
Operating voltage *
AC24V: 24V AC
AC120V: 100 to 120V AC
AC220V: 200 to 220V AC
AC240V: 220 to 240V AC
DC12V: 12V DC
DC24V: 24V DC
*For other time range types and operating voltage types, please consult us.
PC board terminal
Power ON-delay
Time range
Time-out
2 Form C
type
Time-out
4 Form C
type
0.05 to 0.5 s
0.1 to 1 s
0.1 to 3 s
0.2 to 5 s
0.5 to 10 s
1 to 30 s
3 to 60 s
0.05 to 0.5 s
0.1 to 1 s
0.1 to 3 s
0.2 to 5 s
0.5 to 10 s
1 to 30 s
60 s
100 to 120V AC
Part number
S1DX-A2C0.5S-AC120VP
S1DX-A2C1S-AC120VP
S1DX-A2C3S-AC120VP
S1DX-A2C5S-AC120VP
S1DX-A2C10S-AC120VP
S1DX-A2C30S-AC120VP
S1DX-A2C60S-AC120VP
S1DX-A4C0.5S-AC120VP
S1DX-A4C1S-AC120VP
S1DX-A4C3S-AC120VP
S1DX-A4C5S-AC120VP
S1DX-A4C10S-AC120VP
S1DX-A4C30S-AC120VP
S1DX-A4C60S-AC120VP
200 to 220V AC
Part number
S1DX-A2C0.5S-AC220VP
S1DX-A2C1S-AC220VP
S1DX-A2C3S-AC220VP
S1DX-A2C5S-AC220VP
S1DX-A2C10S-AC220VP
S1DX-A2C30S-AC220VP
S1DX-A2C60S-AC220VP
S1DX-A4C0.5S-AC220VP
S1DX-A4C1S-AC220VP
S1DX-A4C3S-AC220VP
S1DX-A4C5S-AC220VP
S1DX-A4C10S-AC220VP
S1DX-A4C30S-AC220VP
S1DX-A4C60S-AC220VP
* Wire springs (ADX18005) are included.
All Rights Reserved COPYRIGHT Matsushita Electric Works, Ltd.
24V DC
Part number
S1DX-A2C0.5S-DC24VP
S1DX-A2C1S-DC24VP
S1DX-A2C3S-DC24VP
S1DX-A2C5S-DC24VP
S1DX-A2C10S-DC24VP
S1DX-A2C30S-DC24VP
S1DX-A2C60S-DC24VP
S1DX-A4C0.5S-DC24VP
S1DX-A4C1S-DC24VP
S1DX-A4C3S-DC24VP
S1DX-A4C5S-DC24VP
S1DX-A4C10S-DC24VP
S1DX-A4C30S-DC24VP
S1DX-A4C60S-DC24VP
S1DX
Specifications
Type
Rated operating voltage
Allowable operating voltage range
Rated frequency
Power supply ripple
Rated power consumption
Rated control capacity
UL/CSA rating
AC operating type
DC operating type
12V, 24V
24V, 100 to 120V, 200 to 220V, 220 to 240V
80 to 110% of rated operating voltage
50/60Hz common
Full-wave rectified (Approx. 48%)
Max. 2W
Max. 3VA
[Timed -out 2 Form C]: 7A 250V AC
[Timed -out 4 Form C]: 5A 250V AC (resistive load)
[Timed -out 2 Form C]: 7A 125 AC, 6A 250V AC, 1/6HP 125, 250V AC, PILOT DUTY C300
[Timed -out 4 Form C]: 5A 250V AC, 1/10HP 125, 250V AC, PILOT DUTY C300
Timed-out 2 Form C, Timed-out 4 Form C
[Except 0.5s & 1s types] 1%
[0.5s type]: (2%+10ms)
[1s type]:
(1%+10ms)
(power off time change at the range of 0.1 s to 1 h)
Output arrangement
Operating time
fluctuation & Power off
time change error
Time
accuracy
(max.)
5% (at 20C ambient temp. at the range of 10 to +50C +14 to +122F)
[Except 0.5s & 1s types] 1%
[0.5s type]: (2%+10ms)
[1s type]:
(1%+10ms)
(at the operating voltage changes between 20 to +10%)
10% (Full-scale value)
100ms
Temperature error
Voltage error
Setting error
Min. power off time
Contact resistance (Initial value)
Mechanical (constant)
Life
Electrical (constant)
Max. 100m (at 1A, 6V DC)
107
5
210 (at rated control capacity)
Min. 100M Between live and dead metal parts/input and output
Min. 100M Between contact sets
(At 500V DC)
Min. 100M Between contacts
1500Vrms for 1min Between live and dead metal parts/input and output
1500Vrms for 1min Between contact sets
1000Vrms for 1min Between contacts
10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Min. 98m/s2 (4 times on 3 axes)
Min. 980m/s2 (5 times on 3 axes)
70C 158F
10 to 50C + 14 to 122F
30 to 85% RH (non-condensing)
Insulation resistance (Initial value)
Breakdown voltage (Initial value)
Vibration resistance
Shock resistance
Functional
Destructive
Functional
Destructive
Max. temperature rise
Ambient temperature
Ambient humidity
*Power one-shot type of 1 s type: +(2% + 10 ms)
mm inch
Dimensions
Plug-in terminal
22.1
.870
57.9
2.280
52.7
2.075
Timed-out
2 Form C type
Timed-out
4 Form C type
13.35
.526
13.35
.526
4.45
.175
6.4
.252
5
.197
5
.197
UP
ON
28.5
1.122
4.1
.161
6.3
.248
6.4
.252
21.5
.846
4.1
.161
6.3
.248
6.4
.252
Terminal layouts and
Wiring diagram
Timed-out
2 Form C type
Timed-out
4 Form C type
4
8
9
13
12
14
9
13
11
12
14
S1DX
10
Operating
voltage
Timed-out
2 Form C type
Printed circuit board terminal
1.5
.059
57.9
2.280
22.1
.870
52.7
2.075
ON
5
.197
1.5
.059
5
.197
13.35
.526
4.45
.175
UP
21.5
.846
28.5
1.122
13.35
.526
3.5
.138
0.5
.020
Timed-out
4 Form C type
4.1
.161
6.3
.248
6.4
.252
4.1
.161
6.3
.248
6.4
.252
Operating
voltage
(For the DC operating type, terminal 14 is +, and terminal 13 is .)
PC board pattern
Timed-out
2 Form C type
Timed-out
4 Form C type
4.1
.161
4.1
.161
S1DX
10.4
.409 16.8
.661
Tolerance: 0.5 .020
13.35
.526
8- 2 hole
8- .079 hole
10.4
.409 16.8
.661
4.45
.175
8.9
.350
14- 2 hole
14- .079 hole
13.35
.526
General tolerance: 0.1 .004
All Rights Reserved COPYRIGHT Matsushita Electric Works, Ltd.
S1DX
Applicable standard
Safety standard
Pollution Degree 2/Overvoltage Category II (2 Form C type)
Pollution Degree 2/Overvoltage Category II (4 Form C type)
EN61812-1
(EMI)EN61000-6-4
Radiation interference electric field strength
Noise terminal voltage
(EMS)EN61000-6-2
Static discharge immunity
EN55011 Group1 ClassA
EN55011 Group1 ClassA
EN61000-4-2
4 kV contact
8 kV air
EN61000-4-3 10 V/m AM modulation (80 MHz to 1 GHz)
10 V/m pulse modulation (895 MHz to 905 MHz)
EN61000-4-4 2 kV (power supply line)
1 kV (signal line)
EN61000-4-5 1 kV (power line)
EN61000-4-6 10 V/m AM modulation (0.15 MHz to 80 MHz)
EN61000-4-8 30 A/m (50 Hz)
EN61000-4-11 10 ms, 30% (rated voltage)
100 ms, 60% (rated voltage)
1,000 ms, 60% (rated voltage)
5,000 ms, 95% (rated voltage)
RF electromagnetic field immunity
EMC
EFT/B immunity
Surge immunity
Conductivity noise immunity
Power frequency magnetic field immunity
Voltage dip/Instantaneous stop/Voltage fluctuation immunity
Data
1. Load control capacity and life
Switching capacity
Life curve
No. of operations, 104
Load current, A
10
7
5
2 Form C 4 Form C
type
type
1,000
No load life
No load life: Min. 107 ope.
Rated load life: Min. 2105 ope.
(250V AC cos = 1)
500
400
300
2 Form C
type
0.1
200
100
4 Form C
type
0.01
10
100
1,000
Load current, A
Load voltage, V
2. Time accuracy
80
80
80
100
110
0.1
0.1
0.2
0.2
0.2
Temperature error test II
3 s range, 220V AC operating type 4 pcs.
Temperature
error, %
0.5
20
110
100
Applied voltage,
%V
0.1
Temperature error test I
3 s range, 120V AC operating type 4 pcs.
1
110
100
Applied voltage,
%V
0.5
50
10
Ambient
temperature, C
Temperature error test III
3 s range, 24V DC operating type 3 pcs.
Temperature
error, %
Applied voltage,
%V
10
Ambient
temperature, C
0.1
Voltage error,
%
0.1
0.2
20
0.5
50
0.5
0.5
10
Ambient
temperature, C
All Rights Reserved COPYRIGHT Matsushita Electric Works, Ltd.
Temperature
error, %
0.1
0.2
Voltage error test III
3 s range, 24V DC operating type 3 pcs.
Voltage error,
%
0.2
Voltage error test II
3 s range, 220V AC operating type 3 pcs.
Voltage error,
%
Voltage error test I
3 s range, 120V AC operating type 6 pcs.
20
50
0.5
S1DX
3. Environmental durability
Surge testing
Model
Noise testing
100 to 200 to
12V
120V 220V
DC
AC
AC
24V
DC
48V
DC
100 to
110V
DC
Item
Cold and heat testing
Noise generation
Results
Noise simulator
1,000 V
Power Rise: 1 ns
supply Pulse width: 1 s, 50 ns
Not
weight Repetition cycle: 10 ms
affected
Noise Pulse polarity: Positive, negative
Applied modes: Normal mode
and Common mode
Surge
4,000V 4,000V 1,000V 1,000V 4,000V 4,000V
voltage
Applied voltage: Unipolar full-wave voltage of
(1.2 x 50) s
No. of times applied: 5 times, continuously
Locations at which voltage is applied:
Between power supply terminals (between 13
and 14)
Results: No differences from withstand surge
voltages listed above.
Conditions
Conditions
Operation mode
indicator color
Time chart
Timing operation will
Power supply
start when the power is
supplied, and the control Timed-out contact
(NO)
output turns on after the
Timed-out contact
setting time.
ON
OFF
OFF
ON
Yellow
T
ON
OFF ON
Power One-shot
Power One-cycle
When the power is
supplied, the control
output turns on for one
pulse after the setting
time.
OFF
OFF ON
ON
OFF
ON
OFF
t
ON
OFF
Blue
t<T
ON
When the power is
supplied, control output
turns on for the setting
time.
OFF
Power supply
T
Timed-out contact
(NO)
Timed-out contact
(NC)
ON
OFF
OFF
ON
Green
ON
OFF
Power supply
T
Timed-out contact
(NO)
Timed-out contact
(NC)
Scale intervals
0.5
0.05
(0.02 in a range
of 0.1 to 0.5)
0.05
0.1
0.2
10
0.5
30
60
OFF
ON
Power supply
Timed-out contact
(NO)
Timed-out contact
(NC)
Time type
OFF
ON
(NC)
Power Ficker
Appearance
Operation
Insulation performance
No irregularities
Scale intervals
Description
When the power is
supplied, the control
output turns on after the
setting time and then
turns off after the setting
time. This operation is
repeated sequentially.
Results
Left for 500 hours at
ambient temperature of
40 (C, at relative humidity of 90 to 95%.
Power ON-delay
Appearance
Operation
Insulation performance
No irregularities
Humidity testing
Operation mode and color
Operation type
Results
Left for 1 hour at high
temperature of 80C
176F and low temperature of 25C 13F (25
times)
ON
OFF
OFF
ON
Red
One pulse time: Approx. 1 s
All Rights Reserved COPYRIGHT Matsushita Electric Works, Ltd.
S1DX
Precautions during usage
1. Terminal wiring
Make sure that terminals are wired carefully and correctly, referring to the terminal layout and wiring diagrams.
2. Assembly
1) A dedicated terminal base or socket
should be used for attachment.
2) To assure that characteristics are
maintained, do not remove the case.
3. Rest periods
After unscheduled operations have been
completed, or if the timer operation
power supply has been turned off at any
time during operation, a rest period of at
least 0.1 seconds should be allowed
before resuming operation.
4. External surge protection may be
required if the following values are
exceeded. Otherwise, the internal
circuit will be damaged.
Operation
voltage
100 to 200 to
100 to
12V DC
48V DC 110V
120V 220V
24V DC
AC
AC
DC
Surge
voltage
4,000V 4,000V 1,000V 4,000V 4,000V
Surge voltage (%)
Single-pole, full-wave voltage for surge
waveform [(1.2 50) s]
100
90
6. Soldering and cleaning
1) A flux-tight construction is not used
with this timer, so be careful that flux
does not get inside the case.
2) Terminals should be soldered by hand
(at a soldering iron temperature of 300C
572F, for less than 3 seconds, using a
30 to 60 W soldering iron). Automatic
soldering should be avoided.
3) Cleaning should be avoided as much
as possible. If the timer has to be
cleaned, make sure no cleaning fluid
gets inside the main unit case.
7. Installing the unit
1) The wire spring included in the product packaging is for the HC relay terminal block.
2) The wire spring is not usable with an
HJ relay terminal block, so the stopper
plate spring B (ADX18012: HJ relay terminal block plate spring) (sold separately) for the S1DH should be purchased.
8. Others
1) When connecting the operating power
supply, make sure that no leakage current enters the timer. For example, when
performing contact protection, if set up
like that of fig. A, leaking current will
pass through C and R, enter the unit,
and cause incorrect operation. The fig. B
shows the correct setup.
Crest value
50
30
Leakage current
1.2
50
Time (s)
The typical surge absorption elements
include a varistor, a capacitor, and a
diode. If a surge absorption element is
used, use an oscilloscope to see
whether or not the foreign surge exceeding the specified value appears.
5. Phase synchronization using AC
load
If the turning on of the timer output relay
is synchronized to the AC power supply
phase, there may be times when the service life is shortened because of electrical factors, or when a locking phenomenon (defective relay return) occurs
because of contact point welding or a
shift in the contact relay. Check the operation using the actual timer.
Operating power supply
(Fig. A)
R
Operating power supply
T
C
(Fig. B)
When a contact switch having an operation indicating lamp (lamp equipped limit
switch, etc.) is used to apply power to
the timer, a resistor having a value equal
to or greater than the value below shall
be connected in series with the lamp.
100 to 120V AC operating type:
Min. 33k
200 to 220V AC operating type:
Min. 82k
Resistor Neon lamp
Example of limit switches with lamp.
VL with lamp, Vertical type with lamp, ML with lamp.
2) When setting the time, the dial should
be kept within the range indicated on the
dial face. The 0 marking on the dial
indicatesf the minimum time during
which the control time can be varied (it
does not indicate 0 seconds).
9. Acquisition of CE marking
Please abide by the conditions below
when using in applications that comply
with EN61812-1.
1) Overvoltage category II,
pollution level 2 (2 Form C type)
Overvoltage category II,
pollution level 1 (4 Form C type)
2) The load connected to the output contact should have basic insulation.
This timer is protected with basic insulation and can be double-insulated to meet
EN/IEC requirements by using basic
insulation on the load.
3) Please use a power supply that is protected by an overcurrent protection
device which complies with the EN/IEC
standard (example: 250 V 1 A fuse, etc.).
4) You must use a terminal socket or
socket for the installation. Do not touch
the terminals or other parts of the timer
when it is powered. When installing or
un-installing, make sure that no voltage
is being applied to any of the terminals.
5) Do not use this timer as a safety circuit. For example when using a timer in a
heater circuit, etc., provide a protection
circuit on the machine side.
All Rights Reserved COPYRIGHT Matsushita Electric Works, Ltd.