Worldwide Contacts
www.tyco-fire.com
Worldwide
Contacts
www.tyco-fire.com
Resilient-Seated Gate Valves
Outside Screw and Yoke
General
Description
TYCO Resilient-Seated Gate Valves
are used in Fire Protection Systems
for on/off operation. End connection
configurations including Flange by
Flange, Flange by Groove, and Groove
by Groove are available.
The ductile Iron body weighs approximately 50% less than conventional
cast iron valves, which allows easier
handling on site and reduced shipping
costs.
The fully encapsulated EPDM ductile iron Wedge ensures bubble-tight
sealing.
Valve components are either inherently corrosion-resistant or protected
with fusion-bonded epoxy resin coating for a long, dependable service life
and enhanced UV protection in exposed installations.
This valve is one of the lightest, most
durable gate valves on the market today. Its design features and material
selection criteria fulfill the need for a
dependable, long life and easy to operate gate valve.
NOTICE
Never remove any piping component
nor correct or modify any piping deficiencies without first de-pressurizing
and draining the system. Failure to do
so may result in serious personal injury, property damage, and/or impaired
device performance.
It is the designers responsibility to select products suitable for the intended
service and to ensure that pressure
ratings and performance data are not
exceeded. Material and gasket selection should be verified for compatibility with the specific application. Always
read and understand the installation
instructions.
TYCO Gate Valves described herein must be installed and maintained
in compliance with this document, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may result in serious personal injury or impair the performance of
these devices.
The owner is responsible for maintaining their mechanical system and devices in proper operating condition.
The installing contractor or device
manufacturer should be contacted
with any questions.
Technical
Data
Sizes
2 (DN50), 2-1/2 (DN65), 3 (DN80),
4 (DN100), 6 (DN150), 8 (DN200),
10 (DN250), and 12 (DN300)
Approvals
UL Listed
FM Approved
Maximum Working Pressure
UL - 300 psi (20,87 bar)
FM - 232 psi (16 bar)
Flanges
ASME B16.1/ASME B16.42
EN 1092-2/ISO 7005-2
Drilled to ANSI 125/150 or PN10/PN16
or AS 2129 (Table E).
Materials of Construction
See valve parts list, Figure 1.
Page 1 of 6
DECEMBER 2013
TFP1540
TFP1540
Page 2 of 6
15
14
16
17
12
10
22
11
17
13
13
19
20
18
6
4
21
18
14
3
2
1
NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DESCRIPTION
QTY.
Wedge . . . . . . . . . . . . . 1
Wedge Nut . . . . . . . . . . 1
Stem Pin . . . . . . . . . . . 1
Sealing Gasket . . . . . . 1
Sealing O-Ring . . . . . . 3
Stem Guide . . . . . . . . . 1
Stem O-Ring . . . . . . . . 2
Compression Washer . . 1
Top Gland . . . . . . . . . . 1
Washers . . . . . . . . . . . 2
Top Nut . . . . . . . . . . . . 2
Handwheel . . . . . . . . . . 1
Yoke . . . . . . . . . . . . . . 1
Stem . . . . . . . . . . . . . . 1
Gland Stud . . . . . . . . . . 2
Gland Hex Nut . . . . . . . 2
Flat Washer . . . . . . . . . 4
Bonnet . . . . . . . . . . . . . 1
Screw Grouting . . . . . . 1
Bonnet Screw . . . . . . . 4
Body . . . . . . . . . . . . . . . 1
Yoke Hex Nut . . . . . . . . 2
MATERIAL
EPDM Coated Ductile Iron
Bronze
Stainless Steel
EPDM
NBR
Bronze
NBR
Stainless Steel
FBE Coated Ductile Iron
Bronze
Bronze
FBE Coated Ductile Iron
FBE Coated Ductile Iron
Stainless Steel
Zinc Coated Carbon Steel
Zinc Coated Carbon Steel
Zinc Coated Carbon Steel
FBE Coated Ductile Iron
Activated Resin
Black Oxide Carbon Steel
FBE Coated Ductile Iron
Zinc Coated Carbon Steel
FIGURE 1
OUTSIDE SCREW AND YOKE GATE VALVE
ASSEMBLY
Installation
In piping systems, TYCO ResilientSeated Gate Valves should be located where operation, inspection, and
maintenance are readily accessible.
Care and
Maintenance
The TYCO Resilient-Seated Gate
Valves must be maintained and serviced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection system from the proper authorities and
notify all personnel who may be affected by this decision.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for monitoring proprietary and/or central station alarms.
The owner is responsible for the inspection, testing, and maintenance of
their fire protection system and devices in compliance with this document,
as well as with the applicable standards of the National Fire Protection
Association (e.g., NFPA 25), in addition
to the standards of any authority having jurisdiction. The installing contractor or product manufacturer should be
contacted relative to any questions.
Any impairments must be immediately
corrected.
Automatic sprinkler systems are recommended to be inspected, tested,
and maintained by a qualified Inspection Service in accordance with local
requirements and/or national codes.
See Figure 1 for valve components
referenced in this section.
Debris lodged in the sealing area of
the Wedge (1) may cause the valve
to close hard. Backing off the Handwheel (12) and closing it again, several times if necessary, can correct this
problem.
The valve should never be forced to
seat by applying a wrench or extension to the Handwheel (12), as it may
distort the valve components or score
the sealing surfaces. All replacement
parts must be obtained from the manufacturer to assure proper operation
of the valve.
At initial valve installation the Gland
Hex Nuts (16) should be left only finger tight to allow the Gland (9) to remain in a relaxed state during normal valve operation. For applications
where the valve is subject to vibration,
a non-hardening thread sealant may
be applied to the Gland Hex Nuts (16)
to prevent self-loosening and subsequent disengagement of the Gland (9).
If leakage past the Sealing O-Rings (5)
occurs, evenly tighten the Gland Hex
Nuts (16) until the leakage ceases.
TFP1540
Page 3 of 6
OPEN
SHUT
CL1
CL2
FLANGE x FLANGE
FLANGE x GROOVE
GROOVE x GROOVE
Nominal
Valve
Size
Nominal
Pipe Size
Nominal
Handwheel
Turns
to Fully
Operate
(Open or
Shut)
Approx.
Weight
FxF
Lbs.
(kg)
Approx.
Weight
FxG
Lbs.
(kg)
Approx.
Weight
GxG
Lbs.
(kg)
ANSI
Inches
DN
O.D.
Inches
(mm)
CL1
CL2
2
DN50
2.375
(60,3)
7.00
(178)
15.55
(395)
13.07
(332)
13
29.8
(13,5)
27.6
(12,5)
25.4
(11,5)
2-1/2
DN65
2.875
(73,0)
7.50
(190)
16.14
(410)
13.31
(338)
16
35.3
(16)
30.9
(14)
26.5
(12)
DN65
3.000
(76,1)
7.50
(190)
16.14
(410)
13.31
(338)
16
30.9
(14)
26.5
(12)
3
DN80
3.500
(88,9)
8.00
(203)
18.9
(480)
14.96
(380)
20
41.9
(19)
36.4
(16.5)
30.9
(14)
4
DN100
4.500
(114,3)
9.00
(229)
22.56
(573)
17.72
(450)
20
57.3
(26)
50.7
(23)
44.1
(20)
DN150
6.500
(165,1)
10.50
(267)
29.53
(750)
23.31
(592)
25
88.2
(40)
79.4
(36)
6
DN150
6.625
(168,3)
10.50
(267)
29.53
(750)
23.31
(592)
25
97.0
(44)
88.2
(40)
79.4
(36)
8
DN200
8.625
(219,1)
11.50
(292)
37.64
(956)
29.45
(748)
34
154.4
(70)
143.3
(65)
110.3
(50)
10
DN250
10.750
(273,1)
13.00
(330)
46.26
(1175)
34.96
(888)
42
264.6
(120)
242.6
(110)
220.5
(100)
12
DN300
12.750
(323,9)
14.00
(356)
51.89
(1318)
39.57
(1005)
50
330.8
(150)
297.7
(135)
275.6
(125)
Nominal Dimensions
Inches (mm)
FIGURE 2
OUTSIDE SCREW AND YOKE GATE VALVE
NOMINAL DIMENSIONS
TFP1540
Page 4 of 6
Nominal
Valve Size
Nominal Dimensions in Inches (mm)
ANSI
Class 150
ANSI
Inches
DN
ISO 7005-2
PN16
AS 2129
(Table E)
Dim.
A
Dim.
B
Qty.
N
Dim.
A
Dim.
B
Qty.
N
Dim.
A
Dim.
B
Qty.
N
2
DN50
4.75
(120,5)
0.75
(19)
4.92
(125,0)
0.75
(19)
4.48
(114,0)
0.71
(18,0)
2-1/2
DN65
5.50
(139,5)
0.75
(19)
5.71
(145,0)
0.75
(19)
5.00
(127,0)
0.71
(18,0)
3
DN80
6.00
(152,5)
0.75
(19)
6.30
(160,0)
0.75
(19)
5.74
(146,0)
0.71
(18,0)
4
DN100
7.50
(190,5)
0.75
(19)
7.09
(180,0)
0.75
(19)
7.00
(178,0)
.071
(18,0)
6
DN150
9.50
(241,5)
0.88
(22)
9.45
(240,0)
0.88
(23)
9.25
(235,0)
0.87
(22,0)
8
DN200
11.75
(298,5)
0.88
(22)
11.61
(295,0)
0.88
(23)
12
111.49
(292,0)
0.87
(22,0)
10
DN250
14.25
(362,0)
1.00
(25)
12
13.98
(355,0)
1.13
(28)
12
14.02
(356,0)
0.87
(22,0)
12
12
DN300
17.00
(432,0)
1.00
(25)
12
16.14
(410,0)
1.13
(28)
12
15.98
(406,0)
1.02
(26,0)
12
Dim. A
Bolt Circle
Diameter
Dim. B
Bolt Hole
Diameter
Qty. N
Number of
Bolt Holes
FIGURE 3
GATE VALVE FLANGE
NOMINAL DIMENSIONS
600
800 1000
20000
30000
0,020
)
300
H(
DN
250
DN
H(
INC
INC
12
)
10
(DN
150
CH
(DN
8 IN
CH
6 IN
200
)
100
4 IN
CH
(DN
80)
(DN
3 IN
CH
H(
INC
/2
0.10
0.09
0.08
0.07
2-1
CH
(DN
DN
50)
65)
0.20
2 IN
NOMINAL PRESSURE DROP
IN POUNDS PER SQUARE INCH (PSI)
0.30
0,006
0,005
0.06
0.05
100
0,010
0,009
0,008
0,007
0,004
200
300
400
600 800 1000
2000
3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
GATE VALVE FRICTION LOSS
6000
10000
NOMINAL PRESSURE DROP IN BAR
(1 PSI = 0.06895 BAR)
400
FLOW RATE IN LITRES PER MINUTE (LPM)
(1 GPM = 3.785 LPM)
2000
3000 4000
6000
10000
TFP1540
Page 5 of 6
Nominal
Valve
Size
Nominal
Pipe
Size
ANSI
Inches
DN
O.D.
Inches
(mm)
Flange x
Flange
ANSI
Class 150
Flange x
Flange
ISO 7005-2
PN16
Flange x
Groove
ANSI
Class 150
Flange x
Groove
ISO 7005-2
PN16
Flange x
Flange
AS 2129
(Table E)
Groove x
Groove
2
DN50
2.375
(60,3)
TMRX-0500003
TMRX-0500001
TMRT-0500603
TMRT-0500601
TMRX-0500005
TMRG-0500604
2-1/2
DN65
2.875
(73,0)
TMRX-0650003
TMRX-0650001
TMRT-0650733
TMRT-0650731
TMRX-0650005
TMRG-0650734
DN65
3.000
(76,1)
TMRT-0650763
TMRT-0650761
TMRG-0650764
3
DN80
3.500
(88,9)
TMRX-0800003
TMRX-0800001
TMRT-0800893
TMRT-0800891
TMRX-0800005
TMRG-0800894
4
DN100
4.500
(114,3)
TMRX-1000003
TMRX-1000001
TMRT-1001143
TMRT-1001141
TMRX-1000005
TMRG-1001144
DN150
6.500
(165,1)
TMRT-1501653
TMRT-1501651
TMRG-1501654
6
DN150
6.625
(168,3)
TMRX-1500003
TMRX-1500001
TMRT-1501683
TMRT-1501681
TMRX-1500005
TMRG-1501684
8
DN200
8.625
(219,1)
TMRX-200-003
TMRX-2000001
TMRT-2002193
TMRT-2002191
TMRX-2000005
TMRG-2002194
10
DN250
10.750
(273,1)
TMRX-2500003
TMRX-2500001
TMRT-2502733
TMRT-2502731
TMRX-2500005
TMRG-2502734
12
DN300
12.750
(323,9)
TMRX-3000003
TMRX-3000001
TMRT-3003243
TMRT-3003241
TMRX-3000005
TMRG-3003244
Part Number
TABLE A
OUTSIDE SCREW AND YOKE GATE VALVE
PART NUMBERS
Ordering
Procedure
Contact your local distributor for availability. When placing an order, indicate the full product name and Part
Number (P/N). Refer to Table A for a
complete list of part numbers.
TFP1540
Page 6 of 6
GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700
Copyright 2013 Tyco Fire Products, LP. All rights reserved.