                           XMT *908 series intellective temperature adjustment
                                       instrument Instruction manual
      Main technical specification
          z Measurement deviation: 0.5%FS1
          z Cold end compensating deviation: 2.0
          z Sampling cycle: 0.5S
          z Control cycle: relay output 2120S , other is 2S.
          z Relay output contact capacity: AC250V/7A (resistance load) or AC250V/0.3A (perceptual load)
          z Driving controllable pulse output: 3V scope, 40us widths over zero or trigger contact pulse
          z Driving solid relay signal output: driving electric current15mA, voltage9V.
          z Continuous PID          : 010mA (load 500200), 420mA (load 250100),
                                     or 05V (load100k) , 15V (load100k)
          z Exterior and hole size:4848110             4444
          z Power supply: AC110V242V, 50/60Hz
          z Working condition: temperature 050.0, relative humidity85%RH, without corrode and strong
              electric radiation.
      Code setting mode
Series     Code               Name             Setting range                 Manual                       Remarks
                                               Determined by
  0         SP          Appointed data                                                                      50.0
                                                P-SL P-SH
                                               Determined by
                                                 P-SL,P-SH
                                              when the upper
                                              and lower limit
  1        AL-1             Alarm 1             range,it is0          Alarm 1 setting value                 10
                                               50.0 when the
                                              upper and lower
                                               limit deviation
                                                    alarm
                                              Determined by
                                                P-SL,P-SH
  2        AL-2             Alarm 2                                    Alarm 1 setting value                 10
                                              when the upper
                                              and lower limit
                                                            1
      Yuyao changjiang temperature meter factory
                                       range,it is0
                                      50.0 when the
                                     upper and lower
                                      limit deviation
                                           alarm
                                                          When the P,the the proportion
3     P     Proportion modulus           0100                       function                       8
                                                        When P=0,the meter is ON/OFF control
4     I         Calculus time           02000S                                                     240
5     d       differential time         0200S                                                      30
                                     ON:open setting
                                      inself function
6     At        Setting itself          OFF:close                Select of setting itself           OFF
                                       setting itself
                                         function
               SSR proportion                             the movements cycle ON/OFF of
7     t                                 1120S                                                      20
               Control period                           Setting relays control is no meaning
              Main control by                           Only have meaning when main control
8     Hy                                0.150.0                                                    1.0
               drop in level                                   output is ON/OFF(P=0)
                  Alarm 1                               It has use drop in level setting of alarm
9    Hy-1                               0.150.0                                                    1.0
                drop in level                                        contact output
                  Alarm 2                                It has use dropin level setting of alarm
10   Hy-2                               0.150.0                                                    1.0
                drop in level                                         contact output
                Sensor error                            The sensor have deviation can use item
11    Pb                                 20.0                                                           0
                amendment                                             to revisal
                                                          Is the software filter constants of
                                                        measurement sampling.The constant
                                                         ,the Measurements antijamming
12   FILT       Filt modulus             050                                                            20
                                                        capabilityMeasurements   antijamming
                                                        capability,but the measurement and
                                                        system time 
                                                          0: have radix point,1: have no radix
13    dp       Show accuracy              01                                                        
                                                                         point
                                                         Can set the high limit displaying input
14   P-SH   Display the high limit    P-SL9999                                                      400
                                                                         signal
                                                         Can set the low limit displaying input
15   P-SL   Display the low limit     -1999P-SH                                                         0
                                                                         signal
            Allow exports min                                 It will no role when lowest
16   OUTL                             0.0OUTH                                                       0.0
                   value                                   outputlimit,,manual and position.
            Allow exports max                                It will no role when highest
17   OUTH                             OUTL200                                                      200.0
                   value                                   outputlimit,,manual and position.
            Alarm1 and output                                  o:indicate no alarm
18   ALP1                                 04                                                            
                 definition                                   1:upper limit touch alarm
                          Yuyao gongyi meter CO.,LTD
                                                                    2:lower limit touch alarm
                 Alarm2 and output
19    ALP2                                      04                  3:upper windage alarm                      
                      definition
                                                                     4:lower windage alarm
                   System function                                      0:reverse control
20    COOL                                      01                                                               0
                        choice                                          1:positive control
                                                              Soft start functionthat meters coefficient
21    OPPO        Open power output           0100                                                               0
                                                                 after first export of electric power
                                                                0- all the parameter can be revised
22    LOCK            Code lock                050                                                               0
                                                                  1- only the sp can be revised
                                                             0-CU50 (-50.0  150.0  ) ;1-PT1
                                                             (-200.0  200.0  ) ;2-PT2 (-200.0 
                                                             600.0) ;3-K (01300) ;4-E (0
23      Sn            Input type                07
                                                             700.0  ) ;5-J (0  900.0  ) ;6-T
                                                             (-200400.0) ;7-S (01600) ;
                                                                    1- RLP SSR output mode
                                                                     2- SSR solid state relay
                                                                3- Zero controllable silicon contact
                                                                   signal when it exceed zero output
                                                                                 mode
                                                              4- Mut controllable silicon phase trigger
24    OP-A           Output type                14
                                                                       contact output mode
                                                               5- 0~10MA linearity control electric
                                                                           current output
                                                              6- 4~20MA linearity control electric
                                                                           current output
 Technical indexes
     1 The first setting area
         Press the SET key 3S enter into the first setting area, the meter will display the parameter code 124in
        the window at the upper row and display the parameter data at the low row. In this time press the 
        or W key to adjust the parameter, then press the SET key to preserve. Press the SET key long
        time will withdraw or press the SETe key will directly withdraw. If within 10 seconds do not press
        every key then it will automatically to preserve the data and withdraw the setting.
     2The second setting area
         When the meter is set up with the electricity, press the SET key enter into the second setting area, you can
         according the 1 to set the SP.
     3 Manual regulation
         When the meter is set up with the electricity, press the W key about 3S enter into the manual regulation, it
         will display H at the lower row, in this time can set the output power; press the W key about 3S again it
                                                         3
       Yuyao changjiang temperature meter factory
       will withdraw the manual regulation.
Setting itself
    The meter use in the first time or the surroundings have changer, finding it control not good, in this time you
    need use the setting itself. For example:
    The first set the AT=ON,A-M light flickered, the meter enter into setting itself, press the SET key enter into
    parameter setting. Set the Hy is 0.51, if the output is relay set the t=2S, the meter have three times
    vibrate, automatic preserved P, I, D parameter and the AT light off, the setting itself finish.
connection scheme(consult)