AVK ALTERNATOR PROTECTION LIST (RLPCL)
VAMP 210 RELAY
1. AC Inverse Time Overcurrent
ANSI (American National Standards Institute) Code=51
In (585A) *1.2=703A/Time Delay=0.2s
2.Instantaneous Overcurrent
ANSI Code=50
In (585A) *2.5=1464A/Time Delay=0.6s
3.Reverse-phase/Phase-Balance Current Relay/Unbalance Load
ANSI Code=46
In (585A) *0.08=47A/Time Delay=20s
4.Directional Earth Fault relay/ Directional Residual Current
ANSI Code=67N
CT Primary Current (50) *0.04=2A/Time Delay=0.3s
5.Ac Inverse Time Earth Overcurrent Relay (Residual Method)/ Residual Current
ANSI Code=51N
CT Primary Current (50) *0.04=2A/Time Delay=1s
Residual Current Stage >> 51N
CT Primary Current (50) *0.15=7.5A /Time Delay=0.3s
6.Neutral Voltage Displacement /Earth Fault
ANSI Code= 59N
Uon (6350V) *0.1(10%)=635V /Time Delay=2s
Earth Fault Stage U0>> 59N
Uon (6350V) *0.2(20%)=1270V /Time Delay=1s
7.Overvoltage
ANSI Code= 59
Overvoltage Stage U> 59
Un(11000V) *1.12(112%)=12320V /Time Delay=4s
Overvoltage Stage U>> 59
Un(11000V) *1.4(140%)=15400V/ Time Delay=0.5s
8.Undervoltage
ANSI Code= 27
Un(11000V) *0.8(80%)=8800V/ Time Delay=20s
9.Loss of Excitation / Under Excitation
ANSI Code= 40
Sn (11155kVA) *0.3(-30%)=-3347kVAr /Time Delay=2s
10.Reverse Power
ANSI Code= 32
Pn (8924kW) *0.04(-4%)=357kW /Time Delay=2s
11.Overfrequency
ANSI Code= 81O
Fn (50Hz) *1.15(15%)=57.5Hz /Time Delay=3s
12.Underfrequency
ANSI Code= 81U
Fn (50Hz) *0.95(5%)=47.5Hz /Time Delay=4s
13.VT Supervision
        The voltage transformer supervision (VTS) feature is used to detect failure of the ac voltage inputs to the
        relay. This may be caused by internal voltage transformer faults, overloading, or faults on the interconnecting
        wiring to relays. This usually results in one or more VT fuses blowing. Following a failure of the ac voltage
        input there would be a misrepresentation of the phase voltages on the power as measured by the relay, which
        may result in maloperation.
ANSI Code= 60
Un(11000V) *0.7(70%)=>7700V
In(585A) *0.1(10%)=<59A
Time Delay=0.2s
14.CT Supervision (Ctsup)
        The current transformer supervision feature is used to detect failure of one or more of the ac phase current
        inputs to the relay. Failure of a phase CT or an open circuit of the interconnecting wiring can result in
        incorrect operation of any current operated element. Additionally, interruption in the ac current circuits risks
        dangerous CT secondary voltages being generated.
ANSI Code= 60
In(585A) *0.2(20%)= 117A (Imax)/In(585A) *0.1(10%)= 59A (Imin)/Time Delay=2s
       VAMP 265 RELAY
Differential Current Relay
        Protection for generator stator windings-(Phase to Ground, Phase to Phase, Turn to Turn Fault).
ANSI Code= 87
Stage I> 87
I> pick-up (Ibias < 0.5Ign)
In(585A) *0.25(25%)=146A
Slope 1=25%
Ibias for start of slope 2
In(585A) *3=1756A
Slope 2=100%
Stage I>> 87
In(585A) *5=2927A
                PLC
1.Alternator Winding Temperature
Alarm -140C
Trip -150C
2. DE & NDE Bearing Temperature
Alarm -105C
Trip -110C
                                                                       Md. Ruhul Amin
                                                                                               EE, RLPCL