This document contains 30 multiple choice questions related to BS7671, the UK wiring regulations. The questions cover a range of topics within BS7671 including protective measures, earthing requirements, installation methods and protection against electric shock. The answers provided indicate the relevant section within BS7671 that specifies the correct response for each question.

Uploaded by

jackwpso
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
156 views5 pages

17thedition Mock Exam1

This document contains 30 multiple choice questions related to BS7671, the UK wiring regulations. The questions cover a range of topics within BS7671 including protective measures, earthing requirements, installation methods and protection against electric shock. The answers provided indicate the relevant section within BS7671 that specifies the correct response for each question.

Uploaded by

jackwpso
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

2382-15 TEST QUESTIONS PAPER 1

1. BS7671 applies to:


a) aircraft
b) photovoltaic supplies
c) distributors equipment
d) electrical equipment of machines

2. BS 7671 does not apply to:


a) railway traction equipment
b) photovoltaic systems
c) marinas
d) fairgrounds

3. Protection against electric shock under single fault conditions is:


a) basic protection
b) fault protection
c) additional protection
d) supplementary protection

4. Which of the following would not be defined as a live part?


a) neutral conductor
b) line conductor
c) neutral bar
d) PEN conductor

5. Every installation should be divided into circuits as necessary to avoid:


a) fuse discrimination problems
b) hazards to minimise inconvenience in the event of a fault
c) unauthorised interference with safety supplies
d) wiring impracticability

6. The protective measure automatic disconnection of supply:


a) is only permitted if the installation is under effective supervision
b) is a method of reducing thermal effects
c) is a combination of basic and fault protection
d) is a combination of under and over voltage protection

7. The maximum disconnection time for a 16A final circuit having Uo


230V ac on a TN system is:
a) 5 s
b) 0.2 s
c) 0.4 s
d) 0.1 s

8. Where there is a danger of fire due to the nature of stored materials a


motor with star delta starting must be protected against excessive
temperature:
a) in star
b) in delta
c) in both star and delta
d) only if 10 kw or more

9. In the event of failure of the provision for basic protection, additional


protection may be provided by:
a) supplementary bonding
b) use of a time delay 100mA RCD
c) use of a RCD with ln not exceeding 30mA
d) electrical separation

10. Which of the following is not a method of fault protection:


a) placing out of reach
b) use of class II equipment
c) earthing and bonding
d) electrical separation

11. For a TT system where disconnection in the case of earth fault is


achieved by RCD, the maximum disconnection time for a general
socket in a domestic kitchen is:
a) 0.1 s
b) 0.2 s
c) 0.4 s
d) 5 s

12. In the event of an earth fault on the HV side of a substation, the LV


installation may be affected by:
a) power frequency fault currents
b) power frequency stress voltages
c) power current stresses
d) power plus current stresses

13. Connection of extraneous conductive parts to the MET of an


installation forms part of the requirements for:
a) SELV
b) enclosures
c) basic protection
d) fault protection

14. Thermoplastic PVC T&E buried less than 50mm must be protected by:
a) MCB
b) cpc the same size as the P & N
c) 30mA RCD
d) disconnection time of 0.4 s

15. RCD installed for protection against fire must have a rating not
exceeding:
a) 30 mA
b) 100 mA
c) 300 mA
d) 500 mA
16. Which of the following may not be used as an earth electrode:
a) underground structural steel work
b) welded metal reinforcement
c) water utility supply pipes
d) earth plates

17. Socket outlets with a rating not exceeding 20A for general use by
ordinary persons should be:
a) connected as a ring circuit
b) connected as a radial circuit
c) protected by a 30mA RCD
d) protected by a 20A CB

18. Lighting installations in bus shelters must be protected by:


a) CCTV
b) double pole circuit breakers
c) graffiti proof covers
d) 30mA RCD

19. Busbar trunking systems must comply with:


a) BSEN 60439-2
b) BSEN 61534-1
c) BSEN 60898-7
d) BSEN 60309-2

20. The minimum acceptable value for insulation resistance in 230v supply
is:
a) 0.25 MF
b) 0.5 MF
c) 1.0 MF
d) 5.0 MF

21. Insulation resistance measured between line and neutral of a 230v


domestic installation should not be less than:
a) 0.25 MF
b) 0.5 MF
c) 0.75 MF
d) 1.0 MF

22. A PV generator and array junction box must have a warning label
indicating that:
a) high voltage is present
b) parts inside may still be live following isolation
c) PV array must be cleaned regularly
d) PV arrays are fragile

23. All circuits in a bathroom must have:


a) protection by a 30mA RCD
b) disconnection time of 5 s
c) supplementary bonding
d) protected by a CB

24. Electrical cables in Zone 1 of a fountain shall be protected against


mechanical impact to:
a) AG1
b) AG2
c) AH2
d) AH3

25. On agricultural premises an RCD may be used for protection against


fire providing that the rating of the RCD does not exceed:
a) 30 mA
b) 150 mA
c) 300 mA
d) 500 mA

26. Any luminaries of lighting chains used at a circus must be firmly fixed
when at a height less than:
a) 1 m
b) 1.5 m
c) 2 m
d) 2.5 m

27. In a bathroom the protective measure of obstacles is:


a) allowed in all zones
b) allowed in zones 1 & 2
c) allowed in zone 2 only
d) not allowed

28. Where a TN system of earthing is used in a marina the final circuits for
the supply of a pleasure craft must not include:
a) any earth conductors
b) a PEN conductor
c) any RCDs
d) protective devices

29. For a 100 mA non-delay RCD to BSEN 61008 the residual test currents
and maximum permitted disconnection times are:
a) 100 mA 300ms 500 mA 40ms
b) 100 mA 130ms 1500 mA 150ms
c) 100 mA 0ms 100 mA 40ms
d) 100 mA 400ms 500 mA 50ms

30. Flat T & E cable clipped direct to a ceiling joist where thermal insulation
exceeds 100mm thickness is installation method:
a) 101
b) 100
c) 3
d) 20
Answers:

1 B 110.1 (xii)
2 A 110.2 (ii)
3 B Definitions
4 D Definitions
5 B 314.1 (i)
6 C 411.1 (i) (ii)
7 C Table 41
8 C 422.3.7
9 C 415.1.1
10 A 417.1
11 B Table 41.1
12 B 422.2 (ii)
13 D 411.3.1.2
14 C 522.6.7
15 C 532.1 (i)
16 C 542.2.1
17 C 411.3.3 (i) & 415.1
18 D 559.10.3.2 & 415.1
19 A 521.4
20 C Table 61
21 D Table 61
22 B 712.537.2.2.5.1
23 A 701.411.3.3
24 B 702.55.3
25 C 705.411.1 (iii)
26 D 740.55.1.1
27 D 701.410.3.5
28 B 709.411.4
29 A Table 3A Page 243
30 A Table 4A2 Page 265