2 Kg/4.
5 Kg CO2 extinguisher
a) Description :
2 Kg/4.5 Kg CO2 extinguishers use CO2 which is stored in pressure containers for
extinguishing fires.
b) Operation :
1. Open Valve in anti-clock wise direction
2. Aim nozzle at the source of fire
3. Keep on moving nozzle briskly until carbon di-oxide continues
4. Close valve
a) Periodic checking/maintenance :
Sl Part Inspection Items to be checked
No. frequency
1 cylinder once a a) visual check cylinder body externally
month for any Dents/ deformations or
corrosion reject if severe.
b) visual check for corrosion on the
surface below clamping rings for
reject if severe.
once in 3 visually check external painting of shell for
months damage/ deterioration.
Check and record weight of cylinder and
send for refilling if loss in weight is more than
10%.
once in 3 Check coating thickness or carry out
years repainting.
before every Hydrostatic test of the cylinder shell along
refilling or with cap and hose assembly at 30kg/sq.cm .
once in 5 Measure Ultrasonic thickness of the shell
years and record readings.
Check coating thickness or carry out
repainting.
2 thread joint once a Check for damage/wear/ deterioration
between cap month
and neck
.
3 Nozzle & once in 3 inspect visually that the orifices are clear and
Discharge months unobstructed . Also check that valves are not
Fittings jammed.
4 Hose once in 3 check hose condition visually for
months ageing/cracks..
5 Safety Valve during Overhaul & reset
refilling or
once in 5
years
whichever is
earlier.