This document provides an air system sizing summary for FF-AHU-03, which includes a heat/humidifier. It will serve one zone covering 544.9 square meters located in Masqat, Oman. Key specs include a total cooling coil load of 131.9 kW occurring in June at 4937 L/s airflow. The central heating coil has a max load of 5.4 kW at 1024 L/s airflow. The supply fan is sized for a max airflow of 5169 L/s requiring 3.85 BHP motor power. Outdoor ventilation air is designed for 1014 L/s at 1.86 L/s per square meter.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views1 page

Air System Sizing Summary For FF-AHU-03 With Heat/humidifier

This document provides an air system sizing summary for FF-AHU-03, which includes a heat/humidifier. It will serve one zone covering 544.9 square meters located in Masqat, Oman. Key specs include a total cooling coil load of 131.9 kW occurring in June at 4937 L/s airflow. The central heating coil has a max load of 5.4 kW at 1024 L/s airflow. The supply fan is sized for a max airflow of 5169 L/s requiring 3.85 BHP motor power. Outdoor ventilation air is designed for 1014 L/s at 1.86 L/s per square meter.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for FF-AHU-03 with heat/humidifier

Project Name: DG Affairs- Office rev. 1 08/27/2011


Prepared by: abc 07:26AM

Air System Information


Air System Name .... FF-AHU-03 with heat/humidifier Number of zones ............................................................. 1
Equipment Class ......................................... SPLT AHU Floor Area ................................................................. 544.9 m
Air System Type ..................................................... VAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s ............................... Peak zone sensible load Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ....................................................... 131.9 kW Load occurs at ................................................... Jun 1600
Sensible coil load ................................................... 96.7 kW OA DB / WB ...................................................... 49.2 / 29.9 C
Coil L/s at Jun 1600 .............................................. 4937 L/s Entering DB / WB ............................................. 28.5 / 19.5 C
Max block L/s at Jun 1600 .................................... 5169 L/s Leaving DB / WB .............................................. 12.2 / 11.5 C
Sum of peak zone L/s ........................................... 5169 L/s Coil ADP ..................................................................... 10.4 C
Sensible heat ratio ............................................... 0.733 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 4.1 Resulting RH ................................................................. 47 %
W/m ..................................................................... 242.0 Design supply temp. ................................................... 12.8 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Central Heating Coil Sizing Data

Max coil load ............................................................ 5.4 kW Load occurs at ..................................................... Des Htg
Coil L/s at Des Htg ................................................ 1024 L/s W/m ............................................................................. 9.9
Max coil L/s ........................................................... 5169 L/s Ent. DB / Lvg DB ................................................ 7.7 / 12.0 C
Water flow @ 11.1 K drop ...................................... N/A

Humidifier Sizing Data

Max steam flow at Des Htg .................................... 0.00 kg/hr Air mass flow .............................................................. 0.00 kg/hr
Airflow Rate ................................................................. 0 L/s Moisture gain .......................................................... .00000 kg/kg

Supply Fan Sizing Data

Actual max L/s at Jun 1600 ................................... 5169 L/s Fan motor BHP ........................................................... 3.85 BHP
Standard L/s .......................................................... 5160 L/s Fan motor kW ............................................................. 2.87 kW
Actual max L/(s-m) ................................................ 9.49 L/(s-m) Fan static ..................................................................... 300 Pa

Outdoor Ventilation Air Data L/s/person ................................................................. 12.83 L/s/person


Design airflow L/s .................................................. 1014 L/s
L/(s-m) ................................................................... 1.86 L/(s-m)

Hourly Analysis Program v.4.3 Page 1 of 1