Blower Door Manual Ingles
Blower Door Manual Ingles
Operation Manual
             for
 Model 3 and Model 4 Systems
         Minneapolis Blower Door
                            Operation Manual
                                                 for
           Model 3 and Model 4 Systems
Minneapolis Blower Door, TECTITE, Duct Mask and Automated Performance Testing (APT) System are
trademarks of The Energy Conservatory, Inc. Minneapolis Duct Blaster and TrueFlow Air Handler Flow Meter
are registered trademarks of The Energy Conservatory, Inc.
Seller warrants that this product, under normal use and service as described in the operators manual, shall be free from defects in
workmanship and material for a period of 24 months, or such shorter length of time as may be specified in the operators manual, from the
date of shipment to the Customer.
This limited warranty set forth above is subject to the following exclusions:
a)          With respect to any repair services rendered, Seller warrants that the parts repaired or replaced will be free from defects in
       workmanship and material, under normal use, for a period of 90 days from the date of shipment to the Purchaser.
b)          Seller does not provide any warranty on finished goods manufactured by others. Only the original manufacturers warranty applies.
c)          Unless specifically authorized in a separate writing, Seller makes no warranty with respect to, and shall have no liability in
       connection with, any goods which are incorporated into other products or equipment by the Purchaser.
d)          All products returned under warranty shall be at the Purchasers risk of loss. The Purchaser is responsible for all shipping charges
       to return the product to The Energy Conservatory. The Energy Conservatory will be responsible for return standard ground shipping
       charges. The Customer may request and pay for the added cost of expedited return shipping.
The foregoing warranty is in lieu of all other warranties and is subject to the conditions and limitations stated herein. No other express or
implied warranty IS PROVIDED, AND THE SELLER DISCLAIMS ANY IMPLIED WARRANTY OF FITNESS for particular purpose or
merchantability.
The exclusive remedy of the purchaser FOR ANY BREACH OF WARRANTY shall be the return of the product to the factory or designated
location for repair or replacement, or, at the option of The Energy Conservatory, refund of the purchase price.
The Energy Conservatorys maximum liability for any and all losses, injuries or damages (regardless of whether such claims are based on
contract, negligence, strict liability or other tort) shall be the purchase price paid for the products. In no event shall the Seller be liable for any
special, incidental or consequential damages. The Energy Conservatory shall not be responsible for installation, dismantling, reassembly or
reinstallation costs or charges. No action, regardless of form, may be brought against the Seller more than one year after the cause of action
has accrued.
The Customer is deemed to have accepted the terms of this Limitation of Warranty and Liability, which contains the complete and exclusive
limited warranty of the Seller. This Limitation of Warranty and Liability may not be amended or modified, nor may any of its terms be waived
except by a writing signed by an authorized representative of the Seller.
TO ARRANGE A REPAIR: Please call The Energy Conservatory at 612-827-1117 before sending any product back for repair or to inquire
about warranty coverage. All products returned for repair should include a return shipping address, name and phone number of a contact
person concerning this repair, and the purchase date of the equipment.
Table of Contents
SAFETY INFORMATION                                                1
CHAPTER 1       INTRODUCTION                                      2
  1.1 What is a Blower Door?                                       2
  1.2 Air Leakage Basics                                           3
     1.2.a Stack Effect:                                           4
     1.2.b Wind Pressure:                                          4
     1.2.c Point Source Exhaust or Supply Devices:                 4
     1.2.d Duct Leakage to the Outside:                            4
     1.2.e Door Closure Coupled with Forced Air Duct Systems:      4
  1.3 Common Air Leakage Sites                                     4
APPENDIX G REFERENCES 85
Safety Information
             The Blower Door fan should only be connected to a properly installed and tested power supply. In
             case of emergencies, disconnect the power cord from the AC power mains outlet. During
             installation, use the nearest readily accessible power outlet and keep all objects away from
             interfering with access to the outlet.
   Disconnect the power plug from the Blower Door fan receptacle before examining or making any
    adjustments to the fan motor, blades or electrical components.
   The Blower Door Fan is a very powerful and potentially dangerous piece of equipment if not used and
    maintained properly. Carefully examine the fan before each use. If the fan housing, fan guards, blade,
    controller or cords become damaged, do not operate the fan until repairs have been made. Repairs should
    only be made by qualified repair personnel.
   If you notice any unusual noises or vibrations, stop and unplug the fan. If you cant find the source of the
    problem, contact the manufacturer/distributor.
   Keep people, animals and objects away from the Blower Door fan when it is operating.
   Press the power plug firmly into the power receptacle on the Blower Door fan, and the AC power mains
    outlet. Failure to do so can cause overheating of the power cord and possible damage.
   Do not use ungrounded outlets or adapter plugs. Never remove or modify the grounding prong. Use only
    approved and inspected electrical wiring and connections.
   Do not operate the Blower Door fan if the motor, controller or any of the electrical connections are wet.
   For long-term operation, such as maintaining building pressure while air-sealing, use a flow ring whenever
    possible to ensure proper cooling of the BlowerDoor fan motor. This will minimize the heating of the fan
    and is important in warmer weather.
   Do not reverse the Blower Door fan (if the fan has a flow direction switch) while the blades are turning.
   The motor is thermally protected and if you experience a motor shut down, be sure to turn off the fan speed
    controller so that the fan does not restart unexpectantly after the motor cools down.
   The operator should wear hearing protection when in close proximity to the fan operating at high speed.
   Adjust all combustion appliances so they do not turn on during the test. If combustion appliances turn on
    during a depressurization test, it is possible for flames to be sucked out of the combustion air inlet (flame
    rollout). This is a fire hazard and can possibly result in high CO levels.
   If there are attached spaces (e.g. townhouses) that could contain a vented combustion appliance, either
    adjust those appliances to prevent them from turning on during the test, or be sure that the attached spaces
    are not depressurized or pressurized when the Blower Door is operating.
   Be sure that fires in fireplaces and woodstoves are completely out before conducting a test. Take
    precautions to prevent ashes from being sucked into the building during the test. In most cases it will be
    necessary to either tape doors shut, clean out the ashes, and/or cover the ashes with newspaper.
   Be sure you have returned the building to its original condition before leaving. This includes turning the
    thermostat and water heater temperature controls to their original setting. Always check to see that furnace,
    water heater and gas fireplace pilot lights have not been blown out during the Blower Door test - re-light
    them if necessary. Remove any temporary seals from fireplaces or other openings sealed during the test.
   If combustion safety problems are found, tenants and building owners should be notified immediately and
    steps taken to correct the problem including notifying a professional heating contractor if basic remedial
    actions are not available. Remember, the presence of elevated levels of carbon monoxide in ambient
    building air or in combustion products is a potentially life threatening situation. Air sealing work should not
    be undertaken until existing combustion safety problems are resolved, or unless air sealing is itself being
    used as a remedial action.
                                                        1
                                                                                        Chapter 1      Introduction
Chapter 1 Introduction
The Blower Door consists of a powerful, calibrated fan that is temporarily sealed into an exterior doorway. The
fan blows air into or out of the building to create a slight pressure difference between inside and outside. This
pressure difference forces air through all holes and penetrations in the exterior envelope. By simultaneously
measuring the air flow through the fan and its effect on the air pressure in the building, the Blower Door system
measures the airtightness of the entire building envelope. The tighter the building (e.g. fewer holes), the less air
you need from the Blower Door fan to create a change in building pressure.
                                                         2
                                                                                           Chapter 1   Introduction
 A typical Blower Door test will include a series of fan flow measurements at a variety of building pressures
 ranging from 60 Pascals to 15 Pascals (one Pascal (Pa) equals approximately 0.004 inches of water column).
 Tests are conducted at these relatively high pressures to mitigate the effects of wind and stack effect pressures
 on the test results. Sometimes a simple one-point test is conducted where the building is tested at a single
 pressure (typically 50 Pascals). This is done when a quick assessment of airtightness is needed, and there is no
 need to calculate leakage areas (i.e. estimate the cumulative size of the hole in the building envelope).
 It takes about 20 minutes to set-up a Blower Door, conduct a test, and document the airtightness of a building. In
 addition to assessing the overall airtightness level of the building envelope, the Blower Door can be used to
 estimate the amount of leakage between the conditioned space of the building and attached structural
 components such as garages, attics and crawlspaces. It can also be used to estimate the amount of outside
 leakage in forced air duct systems. And because the Blower Door forces air through all holes and penetrations
 that are connected to outside, these problem spots are easier to find using chemical smoke, an infrared camera or
 simply feeling with your hand. The airtightness measurement can also help you assess the potential for
 backdrafting of natural draft combustion appliances by exhaust fans and other mechanical devices, and help
 determine the need for mechanical ventilation in the house.
                                                                   3
                                                                                         Chapter 1      Introduction
                                                          4
                                                                                         Chapter 1      Introduction
The next most important location of leaks is in the lowest part of the building. The bottom of the building is
subject to the largest negative pressures, which induces cold air infiltration. Importantly, if spillage prone natural
draft combustion appliances are present, do not seal lower level building leaks unless you have first addressed
leaks in the attic or top part of the building. Sealing only lower level leakage areas while leaving large high level
leaks could create large enough negative pressures to cause combustion appliance backdrafting.
In addition to these common leakage sites, there can also be large leakage paths associated with hidden
construction details such as attached porches, cantilevered floors and overhangs. Figures 4 - 6 show a number
of potentially important leakage paths which are often overlooked by crews using traditional weatherization
techniques. Use of densely blown cellulose insulation or other barrier-type air sealing techniques at these key
junctures often result in dramatic air leakage reductions.
                                                          5
                                                                                    Chapter 1      Introduction
Forced air system ductwork can also be a major air leakage site. Even small leaks in ductwork can result in
significant air leakage due to the high pressures found in ducts whenever the heating or cooling system is
operating. More information on duct leakage can be found in Chapter 9.
                                                       6
                                                                              Chapter 2      System Components
This Manual includes operating instructions for the following models of Minneapolis Blower Door:
While the Blower Door fan motor, flow sensor and speed controller vary slightly between the three different
Minneapolis Blower Door systems, the other system components are identical.
PC based test analysis software (TECTITE) is also available to help you document and analyze Blower Door
test results.
The Blower Door fan can accurately measure airflow over a wide range of flow rates using a series of calibrated
Flow Rings which are attached to the inlet of the fan. The standard Minneapolis Blower Door system comes
with 2 Flow Rings (A and B) capable of measuring flows as low as 300 Cubic Feet per Minute (cfm). Optional
Rings C, D and E are available which allows flow measurements as low as 85, 30 and 11 cfm respectively.
                                                         7
                                                                             Chapter 2    System Components
The main distinguishing feature between the Model 3 and Model 4 fans is the shape of the flow sensor attached
to the fan motor. Model 3 fans (both 110V and 230V) use a round white plastic flow sensor, while the Model 4
fan uses a flow sensor manufactured out of stainless steel tubing.
Model 3 Fan and Flow Sensor Model 4 Fan and Flow Sensor
              Fan Configuration               Flow Range (cfm) for           Flow Range (cfm) for
                                                  Model 3 Fan                    Model 4 Fan
              Open (no Flow Ring)                 6,100 - 2,435                  4,850 - 2,090
              Ring A                              2,800 - 915                    2,500 - 790
              Ring B                              1,100 - 300                      900 - 215
              Ring C                                330 -    85                    260 -    45
              Ring D                                115 -    30                    125 -    30
              Ring E                                 45 -    11                     50 -    11
To install Flow Ring A, place Ring A onto the inlet side of the fan
housing and rotate the 8 fastener clips attached to the housing flange so
that they rotate over the edge of Ring A and secure it in place.
                                                        8
                                                                           Chapter 2      System Components
The DG-700 can also be used to automate control of the Blower Door fan using the following two features:
       The-DG-700 can be used along with TECTITE software and a user supplied laptop computer to
    conduct a fully automated Blower Door test. When conducting automated tests, the speed of the Blower
    Door fan is computer controlled while the TECTITE program simultaneously monitors the building
    pressure and fan flow using the DG-700s two pressure channels. Test results are recorded, displayed on the
    screen, and can be saved to a file. Note: Automated testing requires the TECTITE software and special
    cabling.
      Newer DG-700 gauges have a built-in Cruise Control feature which allow the user to control the
    Blower Door fan to maintain a constant building pressure, without using the TECTITE software or a laptop
    computer.
                                                         9
                                                                            Chapter 2       System Components
If the APT system contains more than 2 installed pressure channels, the additional
channels can be used to monitor and record pressures in attached zones (e.g. attic or
crawlspace) during the automated Blower Door test.
       One Data Acquisition Box (DAB) with 2 to 8 on-board pressure channels and
    phone jacks for 8 voltage input channels.
       One 6 serial cable (w/ 9 pin connectors) to connect the DAB with your
    computer.
       One 12V power supply for the DAB.
       One CD containing the TECTITE software.
The Data Acquisition Box (DAB) comes fastened to a black plastic mounting board. The mounting board may
also contain two electrical outlets which can be used to power the Blower Door fan, DAB or a lap-top computer.
Note: When using an APT system, only automated Blower Door testing can be conducted because the APTs
DAB does not have a built-in display. Manual testing must be done with a DG-700 or DG-3 gauge.
                                                       10
                                                                            Chapter 2     System Components
The Model 4 fan speed controller will either be attached to a mounting board (system with DG-700 gauge), or
simply have an attachment clamp connected directly on the back of the speed controller box (system with APT
system).
To assemble the frame, remove one long and one short frame piece from the
case. Disengage the cam levers on each piece by flipping the cam lever to
the relaxed position. Be sure the adjustment knobs have been tightened so
                                       that the frame piece does not extend
                                       as you put the frame together. Snap
                                       the two pieces together by sliding one end of the short piece over one
                                       corner block on the long frame piece. You will need to push in the round
                                       bullet on the corner block as you slide the pieces together. The round
                                       bullet will snap into the hole located on the short frame piece. Assemble
                                       all four sides of the frame together in this manner. Be sure that the cam
                                       levers and adjustment knobs are all on the same side of the frame as you
                                       assemble the pieces.
                                                       11
                                                                              Chapter 2   System Components
Now remove the cross bar from the frame case. The hooks at each end of
the middle bar will fit into one set of slots which are found on the inside
edges of the vertical frame pieces. To insert the middle frame bar, first
loosen the adjustment knobs on the cross bar and the top and bottom
frame pieces. With the frame adjusted to its smallest size and the cam
levers and knobs facing you, insert one hook into the 2nd slot from the top
on one side of the frame. Extend the middle bar and insert the second
hook on the other side of the frame. Push the middle bar down so that the
hooks are fully set into the slots.
                                          Assembled Aluminum Frame
Note: If you receive the TECTITE software, the program CD contains a separate software operation manual. A
fully functional copy of TECTITE is available to download from The Energy Conservatory's website at
www.energyconservatory.com.
                                                       12
                                       Chapter 3     Installing the Blower Door for Depressurization Testing
One of the primary reasons depressurization testing is the most commonly used test method is that back-draft
dampers in exhaust fans and dryers will be pulled closed during the test. Because back-draft dampers are
typically shut most of the time, leakage from these devices should generally not be included in the results of a
Blower Door test.
Information on how and why to conduct Blower Door pressurization tests (i.e. blowing air into the building) is
discussed in Chapter 7.
        It is always best to install the Blower Door system in an exterior doorway of a large open room.
        Try to avoid installing the fan in a doorway where there are stairways or major obstructions to air flow
    very close (1-5 feet) to the fan inlet. See Appendix A for additional information on obstructions to air flow.
        If the doorway leads to a porch or garage, make sure this space is open to the outside by opening doors
    and/or windows.
        The door frame is almost always installed from the inside of the building and may be installed in place
    of the prime door, the storm door, or anywhere in between.
        Always open the inside door and outside storm door as much as possible during the test to prevent
    restrictions to airflow.
                                                       13
                                       Chapter 3      Installing the Blower Door for Depressurization Testing
Remove the frame from the door opening and set it up against a wall. Take the nylon panel
out of the accessory case and drape the top of the panel over the top of the frame. Use the
long Velcro strip at the top of the panel to hold the panel over the top frame piece.
                                     You are now ready to fit the frame and panel into
                                     the door opening and secure it in place. Lift the
                                     frame and panel assembly and insert it into the
                                     doorway and up against the door stop. Once the
                                     frame is firmly pushed up against the door stop,
release the top Velcro strip and 4 side Velcro tabs. If necessary, re-adjust the frame so
it fits snugly in the door opening, being sure to re-tighten the 5 adjustment knobs.
                                                        14
                                       Chapter 3      Installing the Blower Door for Depressurization Testing
                                                         15
                                      Chapter 3      Installing the Blower Door for Depressurization Testing
                                                       16
                                       Chapter 3      Installing the Blower Door for Depressurization Testing
Note: See the TECTITE manual for information on measuring zone pressures with installed pressure channels
P3 through P8.
Note: Model 4 fans and newer Model 3 fans are not reversible.
          In case of emergencies, disconnect the power cord from the AC power mains outlet. During
          installation, use the nearest readily accessible power outlet and keep all objects away from interfering
          with access to the outlet.
                                                       17
                                      Chapter 3       Installing the Blower Door for Depressurization Testing
                                 If your Model 4 fan has 2 pressure taps located on the electrical box, connect this second
                                 pressure tap (located by the receptacle) to the Channel B/P2 Reference tap using an
                                 additional piece of Clear tubing provided with your system.
                                 Note: Use of this second pressure tap is not required, provided that the Channel B/P2
                                 Reference tap is sensing the air pressure upstream of the fan (i.e. the air being pulled into
                                 the fan).
                                                         18
                                                              Chapter 4      Setting Up the Building for Testing
After installing the Blower Door system, you will need to set up the building for the airtightness test. This
typically includes closing adjustable openings and preparing combustion appliances and exhaust fans. The
following preparations are appropriate when using the Blower Door to determine retrofit airsealing potential,
weatherization effectiveness or estimating natural infiltration rates. If the purpose of the Blower Door test is to
document construction airtightness quality for new houses, additional preparation may be needed (see Testing
For New Construction below). If you are using the Blower Door to estimate duct leakage, see Chapter 9 for set
up procedures. Your program guidelines may require you to prepare the building differently than described
below.
Note: The building set-up and test procedures contained within this manual are recommended specifically by
The Energy Conservatory. These procedures generally conform to the Canadian General Standards Board
(CGSB) standard CGSB-149.10-M86 "Determination of the Airtightness of Building Envelopes by the Fan
Depressurization Method", and American Society for Testing and Materials (ASTM) standard E779-10
"Standard Test Method for Determining the Air Leakage Rate by Fan Pressurization". However, our procedures
include options and recommendations that are not contained within the CGSB and ASTM standards. If you need
to perform a Blower Door airtightness test that exactly meets the CGSB, ASTM or some other test procedure
(e.g. RESNET), you should obtain a copy of the applicable standard and follow the specific set-up directions
contained in the standard.
                                                        19
                                                                 Chapter 4     Setting Up the Building for Testing
   Exterior windows and doors, fireplace and stove doors should be closed, but not sealed, beyond the
    intended weatherstripping or other infiltration control measures.
   Dampers including exhaust, intake, makeup air, backdraft and flue dampers shall be closed, but not sealed
    beyond intended infiltration control measures.
   Interior doors, if installed at the time of the test, shall be open.
   Exterior doors for continuous ventilation systems and heat recovery ventilators shall be closed and sealed.
   Heating and cooling systems, if installed at the time of the test, shall be turned off.
   Supply and return registers, if installed at the time of the test, shall be fully open.
                                                          20
                                             Chapter 5      Conducting a Blower Door Depressurization Test
The following instructions assume you are conducting a depressurization test and have set up the Blower Door
system and building as outlined in Chapters 3 and 4 above. These instructions cover manual test operation using
the DG-700 and DG-3 Digital Pressure Gauges. If you are using the DG-700 or APT System to conduct a fully
automated Blower Door test with the TECTITE Software, follow the test instructions contained in the TECTITE
Software Users Guide (available from the TECTITE Help menu). Information on how and why to conduct
Blower Door pressurization tests (i.e. blowing air into the building) is discussed in Chapter 7.
The Multi-Point Test procedure involves testing the building over a range of pressures (typically 60 Pascals
down to 15 Pascals) and analyzing the data using a Blower Door test analysis computer program (e.g.
TECTITE). When conducting a Multi-Point Test, we generally recommend that the building be tested at 8
different target pressures between 60 Pa and 15 Pa. For example, a common set of target building pressures
includes 60 Pa, 50 Pa, 40 Pa, 35 Pa, 30 Pa, 25 Pa, 20 Pa and 15 Pa. Other target pressures may be used as long
as they cover a variety of building pressures between 60 Pa and 15 Pa. Making multiple measurements allows
some of the errors introduced by fluctuating pressures and operator error to be averaged out over several
measurements, thus increasing test accuracy. In addition, a Multi-Point Test allows the operator to estimate the
leakage area of the building (i.e. estimate the cumulative size of the hole in the building envelope). Leakage area
values are used in detailed infiltration models and can be a useful way to express the results of the Blower Door
test.
                                                       21
                                             Chapter 5      Conducting a Blower Door Depressurization Test
b) Measure the baseline building pressure (same for both One-Point and Multi-Point Tests).
When conducting a Blower Door test, we want to measure the change in building pressure caused by air flowing
through the Blower Door fan. In order to measure this change accurately, we need to account for any existing
pressures on the building caused by stack, wind and other driving forces. This existing building pressure is
called the "baseline building pressure".
The DG-700 has a built-in baseline measurement procedure which allows the user to quickly measure and record
the baseline pressure on Channel A, and then display the baseline adjusted pressure. This feature makes it
possible to zero out the baseline building pressure on Channel A, and display the actual change in building
pressure caused by the Blower Door fan.
With the fan sealed off, begin a baseline building pressure reading from Channel A by pressing the BASELINE
button. The word BASELINE will begin to flash in the Channel A display indicating that the baseline feature
has been initiated. Press START to start the baseline measurement. During a baseline measurement, Channel A
will display a long-term average baseline pressure reading while Channel B is used as a timer in seconds to
show the elapsed measurement time. When you are satisfied with the baseline measurement, press the ENTER
button to accept and enter the baseline reading into the gauge. The Channel A display will now show an ADJ
icon to indicate that it is displaying a baseline adjusted building pressure value. Note: Once a baseline
measurement has been taken and entered into the gauge (i.e. ADJ appears below the Channel A reading), a new
baseline measurement procedure can be initiated by pressing the BASELINE button.
c)   Choose a Flow Ring for the Blower Door fan (same for both One-Point and Multi-Point Tests).
Remove the No-Flow Plate from the Blower Door fan and                   Fan Configuration     Flow Range (cfm) for
install the Flow Ring which you think best matches the needed                                     Model 3 Fan
fan flow. Installation of Flow Rings will depend on the tightness       Open (no Flow Ring)        6,300 - 2,425
level of the building stock being tested. For example, for              Ring A                     2,800 - 915
                                                                        Ring B                     1,100 - 300
relatively leaky buildings (greater than 3,000 CFM50), you will         Ring C                       330 -    85
want to start the test using the Open Fan configuration (i.e. no
Flow Rings installed). As you test tighter buildings, you will need to install Flow Rings A or B. Refer to the
Table to the right for approximate flow ranges of the fan using the various Flow Rings configurations. Don't
worry if you guess wrong and start the test with the incorrect Flow Ring - you can change the Fan Configuration
during the test procedure.
d) Enter the selected Flow Ring into the Gauge (same for both One-Point and Multi-Point Tests).
In order for the DG-700 to properly display fan flow, you need to input the Blower Door fan model and selected
Flow Ring into the gauge. Check (and adjust if necessary) the selected test Device (i.e. fan) and Configuration
(i.e. Flow Ring) shown in the upper part of the gauge display to match the fan and Flow Ring used in the test.
Press the DEVICE button to change the selected Blower Door fan.
         Device Icon
         BD 3                       Model 3 110V fan
         BD 3 220                   Model 3 220V fan
         BD 4                       Model 4 220V fan
Once the fan is selected, the configuration of the fan can be selected by pressing the CONFIG button. The
currently selected Flow Ring configuration is shown in the Config section of the gauge display.
         Config Icon                                            Config Icon
         OPEN              No Flow Ring                         C3                Ring C
         A1                Ring A                               D                 Ring D
         B2                Ring B                               E                 Ring E
                                                       22
                                             Chapter 5      Conducting a Blower Door Depressurization Test
Also be sure that Channel B is showing the proper air flow units for your test (this should typically be set to
CFM). Units can be changed by pressing the UNITS button.
e)   Turn on the fan for an initial inspection (same for both One-Point and Multi-Point Tests).
Turn on the Blower Door fan by slowly turning the fan controller clockwise. As the fan speed increases, the
building depressurization displayed on Channel A should also increase. As you increase the fan speed, you will
be increasing the pressure difference between the building and outside resulting in increased pressure exerted on
the aluminum door frame installed in the door opening. If you did not properly install the door frame, the frame
may pop out of the doorway at higher building pressures (over 30 Pascals). If this happens, simply reinstall the
frame more securely. When installed properly, the frame will easily stay in place during the entire test
procedure. Before making measurements, you may want to quickly walk around the building with the fan
producing about 30 Pascals of building pressure to check for any problems such as windows or doors blown
open or blowing ashes from a fire place or wood stove.
Channel B will now display the One-Point CFM50 leakage estimate. If the leakage estimate is fluctuating more
than desired, try changing the Time Averaging setting on the gauge by pressing the TIME AVG button and
choosing the 5 or 10 second or Long-term averaging period. Record the CFM50 test reading on a Test Form
(see Appendix D).
Turn off the fan. If you are using Cruise Control, this is done by pressing the Stop Fan (Clear) button.
         Whenever ----- or LO appears on Channel B in the PR/ FL @ 50 mode, the DG-700 can not
         calculate a reliable leakage estimate. The messages ----- and LO appear on Channel B under the
         following three conditions:
         -        ----- is continuously displayed when the building test pressure from Channel A is below a
              minimum value of 10 Pascals. Estimating leakage results when the test pressure is below this value
              may result in unacceptably large errors. If possible, install a larger Flow Ring or remove the Flow
              Rings to generate more fan flow.
         -        LO is continuously displayed when there is negligible air flow through the test device.
                                                       23
                                             Chapter 5       Conducting a Blower Door Depressurization Test
         -         LO alternates with a flow reading when the air flow reading through the device is unreliable
             (i.e. you are trying to measure a flow outside of the calibrated range of the test device in its current
             configuration). If possible, you should change the test device configuration to match the flow rate
             being measured (e.g. install a Flow Ring or a smaller Flow Ring).
         Note: If you change the Flow Ring on the fan, be sure to change the Configuration setting on the gauge
         (using the CONFIG button) to match the installed Ring. If you are using the Cruise Control feature,
         you will need to exit Cruise (by pressing the CLEAR button) before using the CONFIG button to
         change the selected Flow Ring.
Enter the test readings into the TECTITE software to generate you final test results. Note: Enter a baseline
pressure value of 0 into the TECTITE Manual Data Entry Screen because you zeroed out the baseline
pressure using the DG-700s built-in baseline feature.
         Whenever LO appears on Channel B in the PR/ FL Mode, the DG-700 can not display a reliable
         fan flow reading. The message LO appears on Channel B under the following two conditions:
         -        LO is continuously displayed when there is negligible air flow through the test device.
         -         LO alternates with a flow reading when the air flow reading through the device is unreliable
             (i.e. you are trying to measure a flow outside of the calibrated range of the test device in its current
             configuration). If possible, you should change the test device configuration to match the flow rate
             being measured (e.g. install a Flow Ring or a smaller Flow Ring).
         Note: If you change the Flow Ring on the fan, be sure to change the Configuration setting on the gauge
         (using the CONFIG button) to match the installed Ring.
a) Turn on the DG-3 and put it into the proper Mode (same for both One-Point and Multi-Point Tests).
Turn the CHANNEL knob to A, turn the MODE switch to Pressure, and put the RANGE switch in the Low
Range position (200.0 Pa).
b) Measure the baseline building pressure (same for both One-Point and Multi-Point Tests).
When conducting a Blower Door test, we want to measure the change in building pressure caused by air flowing
through the Blower Door fan. In order to measure this change accurately, we need to account for any existing
pressures on the building caused by stack, wind and other driving forces. This existing building pressure is
called the "baseline building pressure".
                                                        24
                                             Chapter 5       Conducting a Blower Door Depressurization Test
When using the DG-3 gauge, we need to measure and record the actual baseline building pressure (see
Appendix D for a sample test recording form). Baseline building pressure is read from Channel A of the gauge.
With the fan sealed off, record the baseline building pressure on a Test Form, including the sign of the reading
(i.e. negative or positive reading). If the pressure is fluctuating too much to determine the reading, try changing
the Time Averaging setting on the gauge by turning the Mode Switch to Time Select, choosing the 5 or 10
second or Long-term average, and then return the Mode Switch to the Pressure setting.
Note: If you will be using the TECTITE software, the measured baseline building pressure will need to be
entered into the program's Data Table.
c)     Choose a Flow Ring for the Blower Door fan (same for both One-Point and Multi-Point Tests).
Remove the No-Flow Plate and install the Flow Ring which you               Fan Configuration      Flow Range (cfm) for
think best matches the needed fan flow. Installation of Flow Rings                                    Model 3 Fan
                                                                           Open (no Flow Ring)         6,300 - 2,430
will depend on the tightness level of the building stock being tested.     Ring A                      2,800 - 915
For example, for relatively leaky buildings (greater than 3,000            Ring B                      1,100 - 300
CFM50), you will want to start the test using the Open Fan                 Ring C                        330 -    85
configuration (i.e. no Flow Rings installed). As you test tighter
buildings, you will need to install Flow Rings A or B. Refer to the Table to the right for approximate flow
ranges of the fan using the various Flow Rings configurations. Don't worry if you guess wrong and start the test
with the incorrect Flow Ring - you can change the Fan Configuration during the test procedure.
d) Enter the selected Flow Ring into the Gauge (same for both One-Point and Multi-Point Tests).
In order for the DG-3 to properly display fan flow, you need to input the Blower Door fan model and selected
Flow Ring into the gauge. To select the fan type and fan configuration being used in your test, first turn the
MODE knob to the Fan Select position. The gauge display will show "-SEL" to indicate that a fan type and fan
configuration have not yet been selected. The fan type can be selected by toggling the SELECT Switch up. The
fan configuration can be selected by toggling the SELECT switch down.
If the
Display
Shows              Description
-SEL Begin fan type selection by toggling the SELECT switch up once.
 3-0               This indicates that you have chosen the Model 3 Minneapolis Blower Door fan, and that the
                   fan is in the "Open" inlet configuration (i.e. no Flow Rings installed).
                   To change the fan inlet configuration for the Model 3 Blower Door fan, toggle the SELECT
                   switch down.
 3-1               Model 3 Blower Door fan with Ring A installed.
 3-2               Model 3 Blower Door fan with Ring B installed.
 3-3               Model 3 Blower Door fan with Ring C installed.
 3-4               Model 3 Blower Door fan with Ring D installed.
 3-5               Model 3 Blower Door fan with Ring E installed.
To change the fan type to the Model 4 Blower Door fan, toggle the SELECT switch up twice (DG-3E gauge
only).
 4-0               This indicates that you have chosen the Model 4 Minneapolis Blower Door fan, and that the
                   fan is in the "Open" inlet configuration (i.e. no Flow Rings installed).
                   To change the fan inlet configuration for the Model 4 Blower Door fan, toggle the SELECT
                   switch down.
                                                        25
                                              Chapter 5      Conducting a Blower Door Depressurization Test
Once you have input the fan configuration, turn the MODE knob back to Pressure, and then flip the RANGE
switch to the 2000 setting (High Range).
e)    Turn on the fan for an initial inspection (same for both One-Point and Multi-Point Tests).
With the CHANNEL knob set to Channel A, turn on the Blower Door fan by slowly turning the fan controller
clockwise. As the fan speed increases, building pressure indicated on Channel A should also increase. As you
increase the fan speed, you will be increasing the pressure difference between the building and outside resulting
in increased pressure exerted on the aluminum door frame installed in the door opening. If you did not properly
install the door frame, the frame may pop out of the doorway at higher building pressures (over 30 Pascals). If
this happens, simply reinstall the frame more securely. When installed properly, the frame will easily stay in
place during the entire test procedure. Before making measurements, you may want to quickly walk around the
building with the fan producing about 30 Pascals of building pressure to check for any problems such as
windows or doors blown open or blowing ashes from a fire place or wood stove.
                                                        26
                                             Chapter 5      Conducting a Blower Door Depressurization Test
Increase the fan speed until you achieve the highest target building pressure (e.g. -60 Pascals) on Channel A.
Now determine the air flow through the fan needed to create this building pressure by first turning the
CHANNEL switch to Channel B, and then turning the MODE knob to the Flow position. The gauge will now
display the flow through the fan. Record the test readings (building pressure and fan flow) on a Test Form (see
Appendix D).
Turn the CHANNEL switch back to Channel A and then turn the MODE knob back to the Pressure setting.
Now reduce the fan speed until the building pressure equals the next target pressure (e.g. -50 Pa). Once again
determine the air flow from Channel B and record the test readings on a Test Form. Continue this procedure for
each of the remaining target pressures. Turn off the fan when the final set of readings are completed.
Enter the test readings into the TECTITE software to generate your final test results.
                                                       27
                                            Chapter 5       Conducting a Blower Door Depressurization Test
    Example: With the fan running full speed, you are able to achieve a building pressure of 28 Pascals with a
    measured fan flow of 5,600 cfm. The corresponding CRF Factor for a building pressure of 28 Pascals is
    1.46. The estimated flow needed to achieve the target pressure of 50 Pascals is 5,600 x 1.46 = 8,176 cfm.
                                                                                     0.65
                                                                  50
                   Cant Reach Fifty         =
                        Factor                        Current Test Pressure (Pa)
                                                           (Channel A)
Note: The TECTITE program automatically applies the CRF Factors to One-Point Test data.
5.4.a Potential Errors In One-Point CFM50 Estimate from Using the CRF Factors:
Table 3 below show the potential errors in the One-Point CFM50 leakage estimates from using the CRF factors.
There are two main sources of error:
        -    The actual test pressure (Channel A) not being equal to the target pressure of 50 Pascals.
        -    The actual exponent of the leaks being measured differing from the assumed exponent of 0.65.
                                             Actual exponent n
                                      0.5      0.55        0.6       0.65      0.7      0.75
       Test                 10     21.4%     14.9%       7.7%       0.0%    -8.4%    -17.5%
       Pressure in Pa       15     16.5%     11.3%       5.8%       0.0%    -6.2%    -12.8%
       (Channel A)          20     12.8%      8.8%       4.5%       0.0%    -4.7%     -9.6%
                            25      9.9%      6.7%       3.4%       0.0%    -3.5%     -7.2%
                            30      7.4%      5.0%       2.5%       0.0%    -2.6%     -5.2%
                            35      5.2%      3.5%       1.8%       0.0%    -1.8%     -3.6%
                            40      3.3%      2.2%       1.1%       0.0%    -1.1%     -2.3%
                            45      1.6%      1.0%       0.5%       0.0%    -0.5%     -1.1%
                            50      0.0%      0.0%       0.0%       0.0%     0.0%      0.0%
                            55     -1.4%     -1.0%      -0.5%       0.0%     0.5%      0.9%
                            60     -2.8%     -1.8%      -0.9%       0.0%     0.9%      1.8%
                            65     -4.0%     -2.7%      -1.3%       0.0%     1.3%      2.6%
                                                       28
                                             Chapter 5      Conducting a Blower Door Depressurization Test
For example, Table 3 shows that for a One-Point 50 Pa Blower Door building airtightness test, a 2.5% error
would be introduced if the leakage estimate was determined at an actual test pressure of 30 Pa (Channel A), and
the actual exponent of the leaks was 0.60 rather than the assumed value of 0.65.
While conducting a multi-point Blower Door test over a wide range of building pressures will tend to even out
some of the error introduced from moderate wind fluctuations, significant wind related error can still exist.
Under very windy conditions, it is sometimes impossible to manually collect accurate and repeatable test data.
Under these conditions, conducting a fully automated test using a DG-700 or APT system may be the only way
to collect accurate and repeatable test results. During an automated test hundreds of simultaneous measurements
of building pressure and fan flow are quickly collected greatly reducing the variability of tests results due to
wind.
Be sure you have returned the building to its original condition before leaving. This includes turning the
thermostat and water heater temperature controls to their original setting. Always check to see that furnace,
water heater and gas fireplace pilot lights have not been blown out during the Blower Door test - re-light them if
necessary. Remove any temporary seals from fireplaces, woodstoves or other openings sealed during the test. In
addition, combustion safety tests (see Chapter 10) should usually be performed before leaving the house.
                                                       29
                                                                                 Chapter 6     Basic Test Results
Basic test results from a One-Point Test can be manually calculated to provide a quick assessment of the
airtightness of the building. For more complicated calculation procedures including analysis of Multi-Point Test
data, calculated physical leakage areas, estimated natural infiltration rates (including design infiltration rates),
estimated cost of air leakage and ventilation guidelines, we recommend that you use the TECTITE program.
   CFM50:
CFM50 is the airflow (in cubic feet per minute) from the Blower Door fan needed to create a change in building
pressure of 50 Pascals (0.2 inches of water column). A 50 Pascal pressure is roughly equivalent to the pressure
generated by a 20 mph wind blowing on the building from all directions. CFM50 is the most commonly used
measure of building airtightness and gives a quick indication of the total air leakage in the building envelope.
When conducting a One-Point Test at 50 Pascals of building pressure, you are directly measuring CFM50.
Note: Air Leakage at 50 Pa can also be presented in units of liters per second (l/s), or cubic meters per second
(m3/s).
As a point of reference, an old uninsulated two-story Victorian style wood framed house in Minneapolis would
likely produce a CFM50 test result in the range of 4,000 to 8,000 - quite leaky. A new modern house built to a
strict airtightness standard would likely produce a test result in the 600 to 1,000 CFM50 range - quite airtight -
in fact tight enough that a mechanical ventilation system would be needed to maintain good indoor air quality.
The airtightness of existing homes can vary dramatically based on the construction style, age and region. Below
are airtightness test results from a few field tests of new and existing homes around the United States.
                                                                                     Average CFM50
             64 New Houses in Minnesota (1984)                                            1390
             22 New Houses in Arizona (1994)                                              1959
             18 New Houses North Carolina (1990)                                          1987
             19 Existing Houses in Arkansas (low-income weatherization)                   3071
             6,711 Existing Houses in Ohio (low-income weatherization)                    4451
                                                         30
                                                                                  Chapter 6      Basic Test Results
Note: If you included the basement of a house in the Blower Door test, (i.e. opened the door between the
basement and house during the test) we recommend that you include the basement in your volume calculation.
                                                  CFM50 x 60
                            ACH50 =             ------------------------
                                            Building Volume (cubic feet)
Many airtightness test standards for new houses have specified a maximum allowable ACH50 leakage rate.
Some examples are listed below.
                                                                                         ACH50
                    Canadian R-2000 *                                                     1.5
                    Alaska Craftsman Home *                                               1.5
                    Sweden *                                                              3.0
The airtightness of existing homes can vary dramatically based on the construction style, age and region. Below
are results expressed in ACH50 from a few field tests of new and existing homes around the country.
                                                                               Average ACH50 Pa
                 64 New Houses in Minnesota (1984)                                      3.7
                 129 New Electric Homes in Pacific NW (1987-88)                         5.6
                 134 New Electric Homes in Pacific NW (1980-87)                         9.3
                 98 Existing Homes in Florida                                          12.7
                                                         31
                                                                                  Chapter 6       Basic Test Results
                                                                             CFM50
                  CFM50 per Square Foot of Floor Area          =       ------------------------
                                                                   Square Feet of Floor Area
   Air Leakage at 50 Pascals per Unit of Above Grade Surface Area (Minneapolis Leakage Ratio):
Also known as the Minneapolis Leakage Ratio (MLR), this is the measured Air Leakage at 50 Pascals (e.g.
CFM50) divided by the above grade surface area of the building. MLR is a useful method of adjusting the
leakage rate by the amount of envelope surface through which air leakage can occur. The MLR has been
particularly useful for weatherization crews working on wood frame buildings. Experience to date has shown
that for uninsulated wood frame houses with a MLR above 1.0, very large cost-effective reductions in house
leakage can often be achieved by using dense-pack cellulose insulation techniques and airsealing other large
hidden construction openings. In houses with a calculated MLR in the 0.5 to 1.0 range, it is often more difficult
to achieve economical improvements in airtightness.
                                                                           CFM50
                  Minneapolis Leakage Ratio =                    ------------------------
                                                          Square Feet of Above Grade Surface Area
Note: When calculating Above Grade Surface Area, we recommend including all surfaces separating the
conditioned space of the building from unconditioned spaces (e.g. exterior walls, floors over unheated and
vented crawlspaces, surfaces separating the building and the attic).
Note: If you are using the TECTITE program, corrections for air density are made automatically.
                                                        32
                                                                                Chapter 6      Basic Test Results
Typically, two separate leakage area estimates are calculated based on differing assumptions about the physical
shape and behavior of the leaks. These two leakage areas are compatible with the two most commonly used
infiltration models.
   Equivalent Leakage Area (EqLA): EqLA is defined by Canadian researchers at the Canadian National
    Research Council as the area of a sharp edged orifice (a sharp round hole cut in a thin plate) that would leak
    the same amount of air as the building does at a pressure of 10 Pascals. The EqLA is used in the AIM
    infiltration model (which is used in the HOT2000 simulation program).
   Effective Leakage Area (ELA): ELA was developed by Lawrence Berkeley Laboratory (LBL) and is
    used in their infiltration model. The Effective Leakage Area is defined as the area of a special nozzle shaped
    hole (similar to the inlet of your Blower Door fan) that would leak the same amount of air as the building
    does at a pressure of 4 Pascals.
Note: The calculated EqLA will typically be about 2 times as large as the ELA. When using leakage area
calculations to demonstrate physical changes in building airtightness, we recommend using the EqLA
measurement. Typically, EqLA more closely approximates physical changes in building airtightness. For
example, if you performed a Blower Door test, and then opened a window to create a 50 square inch hole and
repeated the test, the estimated EqLA for the building will have increased by approximately 50 square inches
from the initial test results.
In essence, a Blower Door test measures the cumulative hole size, or leakage area, in the building's air barrier
(see Leakage Areas above). From this measurement of leakage area, estimates of natural infiltration rates can be
made using mathematical infiltration models. The TECTITE software uses the calculation procedure contained
in the American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE) Standard 136 to
estimate the average annual natural infiltration rate for purposes of evaluating indoor air quality and the need for
mechanical ventilation.
                                                        33
                                                                                Chapter 6      Basic Test Results
   Daily and seasonal naturally occurring air change rates will vary dramatically from the estimated annual
    average rate due to changes in weather conditions (i.e. wind and outside temperature).
   The physical location of the holes in the building air barrier compared to the assumptions used in the
    infiltration model will cause actual annual average infiltration rates to vary from the estimated values.
    Research done in the Pacific Northwest on a large sample of houses suggests that estimated infiltration rates
    for an individual house (based on a Blower Door test) may vary by as much as a factor of two when
    compared to tracer gas tests - one of the most accurate methods of measuring actual infiltration rates.
   The annual average infiltration estimates from ASHRAE Standard 136 should be used only for evaluating
    detached single-family dwellings, and are not appropriate for use in estimating peak pollutant levels or
    energy loss due to infiltration. If any of the building leakage is located in the forced air distribution system,
    actual air leakage rates may be much greater than the estimates provided here. Duct leaks result in much
    greater air leakage because they are subjected to much higher pressures than typical building leaks. The
    ASHRAE 136 standard assumes that 1/4 of the building leakage is in the ceiling, 1/4 is in the floor, 1/2 is in
    the walls, and that leaks are uniformly distributed.
         Recommended Whole Building Mechanical Ventilation Rate: This value is the recommended whole
         building ventilation rate to be supplied on a continuous basis using a mechanical ventilation system.
         The recommended mechanical ventilation rate is based on 7.5 CFM per person (or number of
         bedrooms plus one  whichever is greater), plus 1 CFM per 100 square feet of floor area. This
         guideline assumes that in addition to the mechanical ventilation, natural infiltration is providing 2 CFM
         per 100 square feet of floor area..
         For buildings where the estimated annual natural infiltration rate (based on the Blower Door test) is
         greater than 2 CFM per 100 square feet of floor area, the recommended mechanical ventilation rate is
         reduced to provide ventilation credit for excess infiltration. In these cases, the recommended
         mechanical ventilation rate is reduced by the following amount:
0.5 x (estimated annual natural infiltration rate (CFM) 0.02 CFM x sq. ft. of floor area )
   ASHRAE Standard 62.2-10 also contains requirements for local kitchen and bathroom mechanical exhaust
    systems. These local exhaust systems may be incorporated into a whole building ventilation strategy.
    Consult Standard 62.2-10 for more information on ventilation strategies and specific requirements and
    exceptions contained in the Standard.
                                                        34
                                                                              Chapter 6      Basic Test Results
   Compliance with the ventilation guideline does not guarantee that a moisture or indoor air quality (IAQ)
    problem will not develop. Many factors contribute to indoor air quality including ventilation rates, sources
    and locations of pollutants, and occupant behavior. Additional testing (including combustion safety testing)
    is needed to fully evaluate air quality in buildings. In many cases, a combination of pollutant source control
    and mechanical ventilation will be required in order to ensure adequate indoor air quality.
        - HDD is the annual base 65 F heating degree days for the building location.
        - The Fuel Price is the cost of fuel in dollars per Btu.
        - N is the Energy Climate Factor from the Climate Information Screen (adjusted for wind
          shielding and building height). See Appendix E for more information.
        - Seasonal Efficiency is the AFUE rating of the heating system.
        - CDD is the base 70 F cooling degree days for the building location.
        - The Fuel Price is the cost of electricity in dollars per kwh.
        - N is the Energy Climate Factor from the Climate Screen (adjusted for wind shielding and
          building height). See Appendix E for more information.
        - SEER is the SEER rating for the air conditioner.
        Note: Cooling Cost procedure is based on sensible loads only. In hot humid climates, latent loads due
        to air leakage can be greater than the sensible loads which are estimated by this procedure.
                                                           35
                                                                         Chapter 7        Pressurization Testing
Blower Door airtightness measurements are typically performed with the building depressurized relative to the
outdoors (i.e. the Blower Door fan exhausting air out of the building). However, under certain conditions it is
necessary to conduct a Blower Door test by pressurizing the building. For example, if a Blower Door test is
being conducted where there is a fire in a fireplace or woodstove, pressurization testing should be performed to
prevent smoke from being drawn into the building through the fireplace. Pressurization testing may also be used
to avoid the possibility of pulling known pollutants into the building during the test procedure (e.g. mold from
walls or crawlspaces). In addition, some testing procedures (ASTM E779, EN 13829) recommend that both
depressurization and pressurization tests be performed, and then averaged to determine building airtightness.
Connect one end of the Red tubing to the Channel B Input tap.
The remaining end of the Green tubing should be                           Connect one end of the extra 30 foot
run to the outside (see Chapter 3 instructions for                        Clear tubing (stored in the accessory
installing the Outside Building Pressure Tubing).                         case) to the Channel B Reference tap.
                                                              36
                                                                       Chapter 7      Pressurization Testing
Connect one end of the Red tubing to the Channel P2 Input tap.
Connect one end of the Red tubing to the Channel P2 Input tap. APT 3-8
  Connect the Green tubing to the Channel P1Reference tap.                 Connect one end of the extra 30 foot
                                                                           Clear tubing (stored in the accessory
  The remaining end of the Green tubing should be                          case) to the Channel P2 Reference tap.
  run to the outside (see Chapter 3 instructions for
  installing the Outside Building Pressure Tubing).                        The remaining end of the Clear tubing
                                                                           should be run to the outside, through the
                                                                           open patch at the bottom of the nylon
                                                                           panel. The end of this tubing should be
                                                                           placed next to the side of the fan, but not
                                                                           in the fan's airstream. *
* Note: Newer Model 4 fans have 2 pressure taps located on the fan
electrical box. If your Model 4 fan has 2 pressure taps, connect the
remaining end of the Clear tubing to the second pressure tap
(located by the receptacle), rather than running it to the outside.
                                                           37
                                                                           Chapter 7      Pressurization Testing
The fan is held in place and stabilized by the Velcro strap attached to
                                      aluminum frame cross bar. Slip the
                                      Velcro strap through the fan handle
                                      and loop it up and back around the
                                      cross bar. Pull the strap tight so that it
                                      is holding the bottom of the fan flange off the floor (approximately 2 inches
                                      off the floor if possible.)
                                     You are now ready to make your pressurization measurements using the
                                     same testing procedures described in Chapter 5.
Note: If you are using the TECTITE software, corrections for air density are made automatically
                                                        38
                                                                                 Chapter 8     Finding Air Leaks
There are many techniques that are used to find air leaks with the Blower Door. Air leaks between the interior
and exterior of the building often follow long and complicated leakage paths. Typically, the air sealing goal is to
find where the leaks cross the "exterior envelope" of the building and to concentrate sealing activities on those
areas.
                                      Note: Smoke from the chemical puffer is very corrosive. Do not store the
                                      puffer in a closed container with other items, especially tools or gauges.
Note: Pressurizing the building and inspecting from the outside can also be useful.
                                                       39
                                                                               Chapter 8      Finding Air Leaks
Soffit Cabinets
Diagnostic procedures have been developed over the past decade to analyze series leakage. These procedures,
called zone pressure diagnostics (ZPD), are widely used by weatherization professionals to prioritize airsealing
efforts in houses by estimating the amount of air leakage from attached zones (e.g. attics, crawlspaces, garages
and basements). ZPD techniques typically combine Blower Door airtightness test results with zone pressure
measurements made both before and after an opening or hole has been added to one surface of the zone being
tested.
In 2000, the Energy Center of Wisconsin commissioned a study of ZPD techniques and procedures in order to
improve the accuracy and reliability of zone leakage estimates. The results of that study, published in 2002,
include numerous improvements to both the methodology used to collect ZPD measurements and the calculation
procedures used to estimate the magnitude of air leakage from tested zones.
To assist our customers in using ZPD calculation methods, we have developed a simple software program which
can be used to quickly perform ZPD calculations using many of the improvements recommended in the Energy
Centers study. The ZPD Calculation Utility is comprised of 7 Steps (or screens) which are used to input test
information and display test results. The ZPD Calculation Utility program and operation manual are available at
no cost from our website (www.energyconservatory.com). The ZPD Calculation Utility assumes that the Blower
Door test results and zone pressure measurements are being collected using either an Energy Conservatory
digital pressure gauge, or as part of an automated Blower Door test using an APT system.
                                                       40
                                          Chapter 9      Testing for Duct Leakage and Pressure Imbalances
Here are just a few of the problems resulting from duct leakage:
   Leaks in the supply ductwork cause expensive conditioned air to be dumped directly outside or into the attic
    or crawlspace rather than delivered to the building.
   Leaks in the return ductwork pull unconditioned air directly into the HVAC system reducing both efficiency
    and capacity. For example, if 10 percent of the return air for an air conditioning system is pulled from a hot
    attic (120 F), system efficiency and capacity could be reduced by as much as 30 percent. In humid climates,
    moist air being drawn into return leaks can overwhelm the dehumidification capacity of air conditioning
    systems causing buildings to feel clammy even when the air conditioner is running.
   Duct leakage has been found to greatly increase the use of electric strip heaters in heat pumps during the
    heating season.
   Infiltration rates can increase by 2 or 3 times whenever the air handler is operating.
   Leaks in return ductwork draw air into the building from crawlspaces, garages and attics bringing with it
    dust, mold spores, insulation fibers and other contaminants.
   Building depressurization from duct leaks and imbalanced duct systems can cause spillage of combustion
    products (from furnaces, water heaters and fireplaces).
Duct leaks can be caused by a variety of installation and equipment failures including:
The impact on a particular building will depend on the size of the duct leak, the location of the duct leak and
whether or not the leak is connected to the outside.
                                                        41
                                          Chapter 9     Testing for Duct Leakage and Pressure Imbalances
9.1.c How Much Can Energy Bills Be Reduced By Sealing Duct Leaks?
Numerous studies conducted by nationally recognized research organizations has shown that testing and sealing
leaky distribution systems is one of the most cost-effective energy improvements available in many houses.
   Air conditioner use was decreased by an average of 17.2% in a sample of 46 houses where comprehensive
    duct leakage diagnostics and sealing were performed.
   These houses saved an average of $110 per year on cooling bills at a cost of approximately $200 for repairs.
   Duct leaks also waste energy in heating climates. A study of 18 houses showed that a duct leakage repair
    service saved 21.8% on heating bills by eliminating three-quarters of the duct leakage in the study houses.
In addition to the energy savings, duct leakage repair improved homeowner comfort and reduced callbacks by
allowing the HVAC system to work as designed.
                                                       42
                                             Chapter 9       Testing for Duct Leakage and Pressure Imbalances
However, the Minnesota study did find that leaky return systems can cause the basement (where the furnace and
water heater are located) to depressurize to the point where combustion products from the water heater or
furnace would spill into the house. Negative pressures from return leaks can also contribute to increased
moisture and radon entry into houses. In addition, many comfort problems were experienced in the summer due
to leaks in the supply duct system dumping much of the cool conditioned air into the basement. These problems
all suggest that controlling duct leakage to the inside may be just as important as leakage to the outside.
                                                           43
                                         Chapter 9      Testing for Duct Leakage and Pressure Imbalances
                                                       44
                                          Chapter 9     Testing for Duct Leakage and Pressure Imbalances
-   Using the pressure measured in Step 3, look up the appropriate correction factor in Table 4 below. This
    correction is needed to account for any underestimation of duct leakage due to connections between the
    duct system and the building.
-   Calculate Duct Leakage to Outside =
(Whole House CFM50 - Envelope Only CFM50) x Subtraction Correction Factor (SCF)
Table 4:
Because Blower Door Subtraction involves subtraction of two separate Blower Door test results (using the same
Blower Door), the accuracy of the duct leakage estimate using this technique is a function of the repeatability of
the Blower Door measurements. The example below shows how repeatability errors can affect the accuracy of
Blower Door subtraction test results.
                                                       45
                                         Chapter 9      Testing for Duct Leakage and Pressure Imbalances
Assume you conducted a Blower Door subtraction test with the following results:
The estimated duct leakage would be (3,000 - 2,750) * 1.29 = 322 cfm
On a day with only slight wind, our experience is that the repeatability of manual Blower Door test is about
+/- 3% of the unsealed whole house CFM50 value when using the same gauges for both tests. For the example
above, a repeatability error of 3% means we have an error of approximately +/- 90 CFM50 (0.03 x ,3,000
CFM50) in our leakage estimate. We must also apply the correction factor calculated above to the 90 CFM50
error which increases the error to +/- 116 CFM50 (90 x 1.29). Thus our final duct leakage estimate is 322
CFM50 (+/- 116 CFM50). This means the actual leakage in the duct system is somewhere between 206 CFM50
and 438 CFM50, a fairly wide variation in test results.
In very windy weather, repeatability error for a manual Blower Door test will increase to much larger than the
3% shown here. However, if you are using an APT system to conduct your Blower Door test, repeatability errors
will typically be reduced below the 3% quoted above, and the APT system will provide you with a estimate of
the measurement uncertainty.
9.3.b Flow Hood Method: (Requires use of calibrated flow capture hood)
-   Set up the building for a standard Blower Door pressurization test (see Chapter 7).
-   Turn the air handler fan off, open all registers and remove all HVAC filters including remote filters.
-   Temporarily seal all exterior combustion air intakes and ventilation system air intakes that are connected to
    the forced air duct system.
-   Tape off all supply and return registers, except the largest and closest return to the air handler, with Duct
    Mask temporary register sealing film (available from The Energy Conservatory) or use paper and high
    quality painters masking tape. Include all ventilation system registers connected to the forced air duct
    system.
-   Pressurize the building to 50 Pa WRT outside with the Blower Door.
-   Place the flow capture hood over the open return register and record the flow going into the return register.
    This measured flow is an estimate of the CFM50 duct leakage to the outside.
Note: This procedure can also be conducted by depressurizing the building and measuring the air flow coming
out of the open return register.
                                                      46
                                           Chapter 9      Testing for Duct Leakage and Pressure Imbalances
You can measure the degree of connection between an unconditioned space and the outside by measuring the
pressure difference between the building and the space during the Blower Door test. If the pressure between the
building and the unconditioned space is less than 45 Pa (assuming the building to outside pressure difference is
50 Pa with the Blower Door running), then the duct leakage measurement will be underestimated. The lower the
pressure, the greater the underestimation.
9.5 Testing for Pressure Imbalances Caused By Forced Air System Flows
Air handler fans commonly move 500 to 2000 cubic feet of air per minute (CFM). Pressure imbalances within
the building can be caused by air hander fan operation if supply and return air flows to each part of the building
are not in balance. Pressure imbalances within the building can significantly increase infiltration rates, contribute
to radon and moisture entry, create durability problems, and cause potential combustion appliance spillage and
backdrafting. Research on combustion appliances has found that very small negative pressures (as low as 3 to 5
Pascals) can cause spillage and backdrafting in natural draft appliances.
Building pressure imbalances can also be caused by duct leakage to the outside. If either the supply or return air
ductwork has leaks to the outside, air will be forced through these leaks when the air handler fan is operating. If
the leaks are in the supply ducts, building air will be exhausted to the outside through the leaks and this will tend
to depressurize the building. If the leaks are in the return system, outside air will be sucked into the leaks and the
building will tend to be pressurized. If there are equal amounts of leakage in both the supply and return, no
change in building pressure will occur, even though large energy losses may result.
Below are a set of test procedures used to help identify pressure imbalances caused by leaks between the duct
system and the outside, and by imbalanced supply and return air flows throughout a building. These tests are
very sensitive to wind effects, and on windy days it can be very difficult to get accurate results.
-   Turn off the Blower Door and close off the Blower Door fan opening with the "No-Flow" plate.
-   Be sure all exterior doors and windows in the building are closed. Replace all HVAC filters (be sure they
    are clean). Open all interior doors and check that all exhaust fans and the air handler fan are off.
-   Set up a digital gauge to measure the building pressure With Respect To (WRT) outside. The outside
    pressure hose should be connected to the bottom (Reference) pressure tap on Channel A (top tap should be
    open). Set the gauge Mode to measure pressures.
-   Turn on the air handler fan and record the change in building pressure indicated on the gauge.
-   Repeat this test several times by turning the air handler on and off for better certainty.
   Greater leakage on the return side of the duct system will typically cause the building to become pressurized
    since the return ductwork is drawing outside air into the ductwork. In this case, there will be a positive
    reading on pressure gauge. The size of the pressure change will depend on both the amount of imbalanced
    duct leakage and the tightness of the building being tested (see Figure 10 in Chapter 10).
                                                         47
                                          Chapter 9      Testing for Duct Leakage and Pressure Imbalances
   Greater leakage on the supply side of the system will typically cause the building to become depressurized
    since the supply ductwork is exhausting building air to the outside, just like an exhaust fan. In this case,
    there will be a negative reading on the pressure gauge. The size of the pressure change will depend on both
    the amount of imbalanced duct leakage and the tightness of the building being tested (see Figure 10 in
    Chapter 10).
In cold climates, pressurizing a building to even 1 Pascal could lead to moisture problems caused by forcing
warm, moist air into the walls and attic where it can condense on cold surfaces. In warm humid climates,
depressurization by 1 Pa can also cause severe moisture problems from warm moist outside air being drawn into
the walls where it can condense on the backside of cooled gypsum board. If there are natural draft combustion
appliances, or if radon is a problem, depressurizing a building by 1 Pascal may also be a problem.
If there is no change in building pressure, this means that there is either equal supply and return leakage to the
outside, no leaks to the outside, or the building itself is too leaky for the duct leakage to create a measurable
pressure change.
Note: For APT users, a prototype software program called ONOFF is available to help precisely measure small
changes in building or room pressures. The program uses a signal averaging technique which significantly
reduces noise, particularly in windy weather, allowing for precise measurement of small pressure changes.
Contact The Energy Conservatory for more information.
-   Keep the gauge set up to measure the pressure between the main body of the building WRT outside.
-   With air handler still running, close the master suite door.
-   Record the total pressure difference from the main body of the building WRT outside. (Large impacts from
    Master Suite Door Closure are most common in single and double return houses.)
-   Consider pressure relief if the Master Suite door is frequently closed and causes the pressure in the main
    body of the building to change by 1 Pascal or more in either direction.
-   Keep the gauge set up to measure the pressure between the main body of the building WRT outside.
-   With the air handler still running, close all interior doors.
-   Record the total pressure difference from the main body of the building WRT outside.
-   Consider pressure relief if closing all the doors causes the pressure in the main body of the building to
    change by 2 Pascals or more in either direction.
                                                        48
                                          Chapter 9     Testing for Duct Leakage and Pressure Imbalances
-   Close all interior doors and walk around the building with a digital pressure gauge.
-   Connect tubing to the Channel A Input tap and leave the bottom Reference tap open. Set the gauge Mode
    to measure pressures.
-   While standing in the main body of the building, place the hose from the gauge under each door (including
    the combustion appliance room and/or basement).
-   Record the pressure difference from each room WRT the main body.
-   Consider pressure relief for any rooms pressurized or depressurized by 3 Pa or more with respect to the
    main body of the building.
Note: If there are combustion appliances in a depressurized area (i.e. fireplaces, furnace or water heater), their
ability to draft properly may be affected. Try to eliminate all depressurization in combustion appliance zones by
finding and sealing leaks in the return ducts, plenum, filter access door and air handler cabinet, or by providing
pressure relief. See Chapter 10 for more information on Combustion Safety Testing Procedures.
Note: Research has shown that in most cases, the temperature rise method and fan curve method are much less
accurate than either the Duct Blaster or TrueFlow methods.
                                                       49
                                                          Chapter 10      Combustion Safety Test Procedure
10.1 Overview
Buildings with natural draft combustion appliances should be routinely tested to ensure that the spillage of
combustion products into the building is unlikely. Combustion safety testing is critical because of the potential
for severe health effects from improperly venting appliances, including carbon monoxide poisoning. Because the
goal of Blower Door guided air sealing activities is to reduce the infiltration rate (and subsequent ventilation
rate) of the building, contractors need to check that they are not leaving a building with a potential problem.
Spillage of combustion products into the building can be caused by a variety of conditions including:
Many cases of improperly venting combustion appliances have been related to depressurization (or negative
pressures) in the room that contains the combustion appliance. Depressurization can be caused by exhaust fans,
dryers, imbalanced forced air distribution systems, and forced air system duct leakage. As buildings (or
combustion appliance rooms) are made tighter, these problems can be made worse, although very leaky
buildings can also have venting problems related to depressurization. Figure 10 below estimates the amount of
depressurization that can be caused by various exhaust fan flows. For example, from Figure 10 we can see that a
400 cfm exhaust fan will depressurize a 2,500 CFM50 building (or room) to approximately 3 Pascals. That same
400 cfm fan would produce over 10 Pascals of depressurization in a 1,000 CFM50 building.
The presence of code approved combustion air intakes does not ensure that venting problems will not occur.
Significant combustion room depressurization is frequently found even after code approved combustion air
intakes have been installed. Passive combustion room air intakes typically do not provide sufficient airflow to
relieve negative pressures caused by distribution imbalances, duct leakage, or large exhaust appliances. For
example, a typical 6" passive inlet can at best supply only about 50 cfm at a 5 Pa negative building pressure.
And because passive air intakes are often poorly installed (i.e. many sharp bends, long runs), they typically
provide much lower flows than designed. Building codes typically give little or no guidance on how one would
design a combustion air opening when competing exhaust appliances are present (the 2000 Minnesota Energy
Code is the only code we are aware of to give such guidance).
The only way to be reasonably sure that venting problems will not occur in a building is to perform combustion
safety tests. Described below are commonly used test procedures to locate existing or potential combustion
safety problems in buildings. These procedures are offered only as an example of what other organizations
in North America typically recommend for testing. The Energy Conservatory assumes no liability for
their use, and contractors should have a working knowledge of local codes and practices before
attempting to use the procedures outlined below.
If combustion safety problems are found, tenants and building owners should be notified immediately and steps
taken to correct the problem including notifying a professional heating contractor if basic remedial actions are
not available. Remember, the presence of elevated levels of carbon monoxide in ambient building air or in
combustion products is a potentially life threatening situation. Air sealing work should not be undertaken
until existing combustion safety problems are resolved, or unless air sealing is itself being used as a
remedial action.
                                                      50
                                                           Chapter 10      Combustion Safety Test Procedure
Figure 10:
                                                       51
                                                           Chapter 10      Combustion Safety Test Procedure
Gas or fuel leaks are a very serious safety problem requiring immediate remedial action.
Initial Preparation
Close all exterior windows and doors and be sure furnace, water heater and other vented combustion appliances
are off. Close all interior doors. Set up a digital gauge to measure the pressure difference of the combustion
appliance zone (CAZ) with reference to (WRT) outside on Channel A. If using a DG-3 gauge, record the
baseline CAZ to outside pressure. If using a DG-700, use the built-in baseline feature to measure and record
the baseline CAZ to outside pressure on Channel A. Once the baseline feature has been used with the DG-
700, Channel A will display the baseline adjusted pressure.
                                                       52
                                                            Chapter 10       Combustion Safety Test Procedure
Turn on all exhaust fans found in the survey above (for dryer, clean out lint filter before turning on). Now
determine the worst case position of interior doors with the smoke test below:
         Smoke Test: While standing in the main body of the building, squirt smoke under each door
         containing an exhaust fan (except the CAZ currently being tested). If the smoke goes into the room,
         open the door. If the smoke comes back into the main body of the building, keep the door closed.
         Now squirt smoke under the CAZ door (while continuing to stand in the main body). If smoke goes
         into the CAZ, leave the CAZ door shut. If smoke comes back into the main body of the building, open
         the door.
Measure the depressurization of the CAZ WRT outside caused by turning on the exhaust fans. Depressurization
should not exceed the appropriate House Depressurization Limits (HDL) listed below. If it is windy, it is often
necessary to turn fans off and on several times to obtain good pressure readings.
         Fireplace Zones: For Fireplace Zones, repeat the same procedure and measure and record
         depressurization of fireplace zone WRT outside from exhaust fan operation. Depressurization should
         not exceed the appropriate HDL listed below.
With exhaust fans continuing to run, turn on the air handler fan (note: air handler fan only, do not turn on
burner) and close any supply registers in combustion appliance room. For both CAZ and Fireplace Zone tests,
re-determine worst case position of all interior doors with the smoke test described above. If cooling is
available, be sure air handler fan is running at high speed. Repeat worst case depressurization measurements.
 Turn off all exhaust fans and leave air handler operating (if cooling is available, be sure air handler is running at
high speed). For both CAZ and Fireplace Zone tests, re-determine worst case position of all interior doors with
the smoke test described above. Repeat worst case depressurization measurements.
         If the HDL are exceeded for any of the worst case depressurization tests above, pressure relief is
         needed. Pressure relief could include duct system repair, undercutting of doors, installation of transfer
         grills, eliminating or reducing exhaust fan capacity, or instructing homeowner on safe exhaust fan
         operation. If negative pressures in the combustion appliance zone (or basement) are a function of
         return leaks in that area, check for leaks in the return ductwork, plenum, filter access door and air
         handler cabinet. Pay particular attention to panned under floor joists (used as returns) as they typically
         have many leaks.
Note: For APT users, a prototype software program called ONOFF is available to help precisely measure small
changes in building or room pressures. The program uses a signal averaging technique which significantly
reduces noise, particularly in windy weather, allowing for precise measurement of small pressure changes.
Contact The Energy Conservatory for more information.
                                                         53
                                                           Chapter 10       Combustion Safety Test Procedure
-   With building set up in worst case depressurization mode (as specified above), fire up each combustion
    appliance.
-   If appliances are common vented, conduct test on smallest input appliance first, then test with both
    appliances running.
-   When burner lights, check for flame rollout (stand away from burner).
-   Check for spillage (using chemical smoke) at the end of the spillage test period (see Table 6 below). For
    natural draft appliances, spillage is tested at the draft divertor. When an induced draft heating system is
    vented in common with a natural draft water heater, spillage is checked at the water heater draft divertor.
    For a single induced draft appliance, spillage is checked at the base of the chimney liner or flue, typically
    using the drip tee at the bottom of the liner.
                                          Table 6: Spillage Test Period
                              Appliance Type               Spillage Test Period (minutes)
                       Water heater, gravity furnace                 3.0 minutes
                       and boiler
                       Space heater                                   2.0 minutes
                       Furnace                                        1.0 minutes
Source: CEE Appliance Safety Test Methods, MAC Part 150 Residential Sound Insulation Program, Mpls,
MN.
-   If spillage continues beyond the spillage test period, remove the negative pressure in combustion room by
    turning off fans and/or opening an exterior window or door.
-   Re-check for spillage. If spillage stops, there is a pressure induced spillage problem. If spillage continues,
    check flue and chimney for obstructions, and check compatibility of appliance BTU input with chimney
    size.
         Spillage of combustion products beyond the spillage test period is a health and safety concern. If the
         problem is a blocked flue or chimney, or inadequately sized flue or chimney, consult a professional
         heating contractor. If the problem is pressure induced, provide pressure relief. Re-check for spillage
         following attempt to provide pressure relief. If spillage continues, contact a professional heating
         contractor to investigate the problem.
                                                        54
                                                           Chapter 10         Combustion Safety Test Procedure
-   After 5 minutes of appliance operation, measure the CO level in the flue products of all combustion
    appliances.
-   CO should be measured before appliance draft diverter, or barometric damper.
-   CO levels should be below 100 ppm in all flues.
-   For gas stoves, measure CO from oven exhaust port and 3 feet above burners with all burners running. CO
    level should be below 50 ppm.
-   If CO found in gas stove, re-measure ambient kitchen CO after 10 minutes of stove operation.
         The presence of CO and spillage requires immediate remedial action.
-   Drill a small hole in the vent pipe approx. 2 feet downstream of the draft divertor or barometric damper.
    Insert a static pressure probe.
-   Measure draft pressure (vent WRT combustion room) with digital pressure gauge after 5 minutes of
    operation.
-   Compare measured draft with minimum draft pressures below:
                                      Table 7: Minimum Draft Pressures
If measured draft is below the minimum draft pressure above, check for flue or chimney obstructions,
disconnected vents, open chimney cleanout doors etc.. Also remove sources depressurization (e.g. turn off
exhaust fans) and test again to determine if CAZ depressurization is contributing to poor draft.
                                                        55
                                                          Chapter 10      Combustion Safety Test Procedure
component of the spillage test. Another method for conducting a flame distortion test is to slowly extend a match
up and down into each combustion chamber with the burner off and the air handler fan on, and watch for
movement of the flame head.
With the furnace off, block the flue ports leading from the combustion chamber to the draft diverter or
barometric damper. Squirt smoke into the combustion chamber. Turn on the furnace fan and watch to see if the
smoke is disturbed when the fan comes on. Smoke movement indicates a hole or crack in the heat exchanger.
A number of testing procedures exist for injecting a tracer gas into the combustion chamber (usually with the
furnace fan off) and then measuring or detecting the tracer gas on the warm air side of the heat exchanger.
         If any of the above heat exchanger tests provides a positive indication for a cracked heat exchanger,
         immediate action should be taken to notify the residents of the potential danger, and a professional
         heating contractor should be contacted to investigate the problem.
Turn off fans and return appliance controls to their original settings once the test
procedures have been completed.
Special thanks to Advanced Energy, Sun Power and the Center for Energy and Environment (CEE) for their
work in developing and refining the combustion safety test procedures above.
                                                      56
                                                                     Appendix A       Calibration and Maintenance
Note: All fan flows indicated on Energy Conservatory gauges or flow tables are corrected to a standard air
density of 0.075 lbs/cubic foot, and are not the actual volumetric flow going through the fan. The indicated
flows are corrected to standard air density according to the CGSB Standard CAN/CG-SB-149.10-M86. The
correction is done in such a way that, for particular types of leaks (where the viscosity of air is negligible and the
flow exponent "n" equals 0.5), the indicated flow is independent of barometric pressure. For this type of leak,
the indicated flow is the flow that would have been going through the fan if the building had been tested at
standard barometric pressure, and indoor and outdoor temperatures were unchanged.
If the actual volumetric flow rate going through the fan is desired, multiply the indicated flow by:
                                  0.075
                            actual air density*                (where air density is in lb/ft3)
or
                                  1.204
                            actual air density*                (where air density is in Kg/m3)
                                                          57
                                                                     Appendix A       Calibration and Maintenance
Model 3 fans (both 110V and 230V) use a round white plastic flow sensor, while the Model 4 fan uses a flow
sensor manufactured out of thin stainless steel tubing. The flow sensors are permanently attached to the end of
the fan motor opposite the fan blades.
First visually confirm that the sensor is not broken or deformed due to impact. Check that the sensor is firmly
attached to the motor. Next, perform a test for leaks in the sensor or the tubing connecting the sensor to the fan
pressure tap (this test is easier if you first place the fan in an elevated position such as on a bench top or table.)
Attach a piece of tubing to the pressure tap on the Blower Door fan electrical box. Leave the other end of the
tubing open. Find the 4 intentional pin holes in the flow sensor. For the Model 3 flow sensor they are evenly
spaced around the outside rim of the sensor - for the Model 4 flow sensor they are evenly spaced on the back
side of the sensor. Temporarily seal the 4 holes by covering them with masking tape. Next, create a vacuum in
the fan pressure tubing by sucking on the open end. A vacuum in the tubing assures that the flow sensor does not
leak. There is a vacuum, if by placing your tongue over the end of the tubing, the tubing sticks to your tongue.
Make sure that the vacuum persists for at least 5 seconds. If a vacuum can not be created, contact The Energy
Conservatory to further diagnose the sensor leakage problem.
If a fan has been dropped, the motor may have shifted from its proper position in the motor mount. This can
degrade the fan calibration. To test the motor position, lay the fan on its side with the flow sensor facing up and
all Flow Rings removed. Place a straightedge (such as a heavy yardstick on edge) across the inlet of the fan. Use
a ruler to measure the following distance and compare this measurement to the appropriate specification.
                                                          58
                                                                                                 Appendix A         Calibration and Maintenance
                         Model 3 Fan: Measure the distance from the bottom of the straightedge to the face of the flow sensor.
                         This distance should be in the range of 3/16th to 5/16th of an inch. If the motor is not in the proper
                         position, call The Energy Conservatory for further instructions.
                         Model 4 Fan: Measure the distance from the bottom of the straightedge to the face of the motor
                         bearing cover. This distance should be in the range of 3/8th to 5/8th of an inch. If the motor is not in the
                         proper position, call The Energy Conservatory for further instructions.
MODEL 3 120/240 Vac BLOWER DOOR MODEL 4 240 Vac BLOWER DOOR
motor motor
                                                                                    59
                                                                   Appendix A       Calibration and Maintenance
   It is always best to install the fan in a doorway leading to a large open room. Try to avoid installing the fan
    in a doorway where there are stairways or major obstructions to air flow very close (1-5 feet) to the fan
    inlet.
   If the fan must be installed next to a stairway or major obstruction, it is best to take measurements using one
    of the Flow Rings and not open fan.
   Always open the inside door and outside storm door as much as possible during the Blower Door test to
    prevent restrictions to air flow.
The term "backpressure" is used to describe the pressure that the Blower Door fan is working against when it is
running. Backpressure is determined by measuring the static pressure difference between the air directly
upstream of the fan, and the air directly exiting the fan.
Under typical testing applications, the backpressure seen by the fan is simply the test pressure at which the
building airtightness measurement is being measured made (e.g. 50 Pascals). However, there are applications
where the Blower Door fan could see backpressures that are greater than the test pressure. For example, if the
Blower Door fan is exhausting air into a confined area (such as an attached porch), it is possible that the porch
area could become pressurized relative to outside creating a backpressure condition that is greater than the test
pressure. Although the Blower Door 's flow sensor was designed to be affected as little as possible by variations
in backpressure, under certain high backpressure operating conditions (described below) the calibration of the
fan can degrade.
Model 3 and Model 4 Blower Door fans can be used in testing applications with backpressures up to 80 Pascals
with no significant effect on calibration accuracy. This is true for all fan flow configurations (Open through Ring
E), provided that the fan is operated within the accepted flow range for each configuration. Backpressures above
80 Pa can diminish the accuracy of the fan calibration and should be avoided.
                                                        60
                                                                 Appendix A       Calibration and Maintenance
   Examine the motor cooling holes for excessive dust build-up. Use a vacuum with a brush attachment to
    remove dust, or blow out the dust with compressed air.
   Inspect housing, blades and guards. Especially note clearance of blade tips relative to the fan housing.
    There should be about 1/4 inch of clearance.
   Inspect electrical wiring and electrical connections on the fan and the fan speed controller.
   Do not reverse the fan (if the fan has a flow direction switch) while the blades are turning. Turn off the fan
    and wait for it to come to a complete stop before reversing the flow direction.
   For long-term operation, such as maintaining house pressure while air-sealing, use a Flow Ring whenever
    possible to ensure good airflow over the fan. This will minimize heating of the fan and is important in
    warmer weather.
   Do not run the fan for long periods of time in reverse.
   The motor is thermally protected and if you experience a motor shut down, be sure to turn off the fan speed
    controller so that the fan does not restart unexpectedly after the motor cools down.
   Make sure to press the power plug firmly into power receptacle on fan. Failure to do so can cause
    overheating of the power cord and possible damage.
   Do not use ungrounded outlets or adapter plugs.
   Do not operate if the motor, controller or any of the electrical connections are wet.
The Blower Door Fan is a very powerful and potentially dangerous piece of equipment if not used and
maintained properly. Carefully examine the fan before each use. If the fan housing, fan guards, blade,
controller or cords become damaged, do not operate the fan until repairs have been made. Keep people and pets
away from the fan when it is operating. Contact The Energy Conservatory if there are any unusual noises or
vibrations while the fan is running.
If the Model 4 Bower Door fan stops running or fails to respond to speed commands:
                                                       61
                                                                 Appendix A       Calibration and Maintenance
Replacement Fuse Specification 5 Amp, 250VAC, 5 X 20 mm, FAST acting, approved by VDE/UL
   Verify the power cord is not plugged into an AC mains power and that the controller power switch is OFF.
   Remove the four screws attaching the bottom enclosure cover to the two endplates
   Carefully separate the bottom cover from the rest of the enclosure. Do not disconnect the green and yellow
    ground wire which connects the top and bottom halves of the enclosure.
   Locate the terminal block fuse holder next to the printed circuit board and power line filter. See photo
    below for details.
   Firmly grasp the black handle of the fuse holder and pull out the old fuse.
   Carefully slip the old fuse out of the black handle. Insert the new fuse into the black handle.
   Align the rib on the black handle with the notch in the terminal block fuse holder.
   Press the black handle and new fuse back into the terminal block fuse holder.
   Position the bottom enclosure cover in place between the two end plates.
   CAUTION  verify that no wires are being pinched as the enclosure is closed.
   Replace the four screws. With each screw, align the screw in its hole perpendicular to the end plate. Rotate
    the screw counterclockwise about one full turn until the threads drop into place.
   Tighten each screw and verify that each screw is tight.
Verify Operation:
                                                       62
                                                                  Appendix A      Calibration and Maintenance
This technique is used to compare the readings of two digital gauges when they are both connected to the same
pressure source. When two gauges are being compared, you should expect them to agree within their
specifications:
   2 digital gauges
   one Magnehelic gauge
   2 T fittings
   one syringe
   five 1 foot sections of tubing
Comparison Procedure
Using the two T fittings and short sections of hose, hook up the gauges and syringe as shown in Figure 12
below. Turn on the digital gauges, (if DG-3s, set on High Range). They should both be reading 0 Pa. Pull out
on the syringe slowly until the desired test pressure on the digital gauges is achieved. Record your results and
compare with the specifications above.
                                                       63
                                                                 Appendix A         Calibration and Maintenance
Digital Gauge
Digital Gauge
                                   Magnehelic
                                   Gauge
-   Before starting, inspect both ends of the tubing to make sure they are not stretched out to the point where
    they will not make a good seal when attached to a gauge.
-   Seal off one end of the tubing by doubling it over on itself near the end.
-   Create a vacuum in the tubing by sucking on the open end (make sure the hose is clean first!). Let the end of
    the tubing stick to your tongue due to the vacuum.
-   The tubing should stick to your tongue indefinitely if there are no leaks. Waiting for 5 seconds or so is a
    good enough test.
-   If the tubing has a leak, it should be replaced immediately.
-   The ends of the tubing will sometimes get stretched out or torn after many uses. Periodically trim 1/4" off
    the ends of the tubing to remove the damaged end.
                                                      64
                                                                          Appendix B      Flow Conversion Tables
                                                         65
                                                                      Appendix B     Flow Conversion Tables
                                                      66
                                                                        Appendix B      Flow Conversion Tables
Model 3 (230V)
                       Flow (cfm)                                               Flow (cfm)
    Fan         Open                                        Fan          Open
Pressure (Pa)   Fan      Ring A     Ring B    Ring C    Pressure (Pa)    Fan      Ring A     Ring B    Ring C
                                                                  122      5297      1991        653       246
                                                                  124      5340      2007        659       248
                                                                  126      5382      2022        664       250
                                                                  128      5424      2038        669       252
                                                                  130      5466      2053        674       255
                                                                  132      5507      2069        679       257
                                                                  134      5548      2084        684       259
                                                                  136      5588      2099        689       261
                                                                  138      5628      2114        694       263
                                                                  140      5668      2129        699       264
                                                                  142      5708      2144        704       266
                                                                  144      5747      2159        709       268
           26    2477        935        304       111             146      5787      2173        714       270
           28    2569        969        315       115             148      5825      2188        719       272
           30    2657       1003        326       119             150      5864      2202        724       274
           32    2743       1035        336       123             152      5902      2217        729       276
           34    2826       1066        347       127             154      5940      2231        733       278
           36    2907       1096        357       131             156      5978      2245        738       280
           38    2985       1125        366       135             158      6016      2259        743       282
           40    3061       1154        376       138             160      6053      2273        747       283
           42    3136       1182        385       142             162      6090      2287        752       285
           44    3208       1209        394       145             164      6127      2300        756       287
           46    3279       1236        403       149             166      6164      2314        761       289
           48    3348       1262        411       152             168      6200      2328        766       291
           50    3416       1287        420       155             170      6236      2341        770       292
           52    3483       1312        428       158             172      6272      2355        775       294
           54    3548       1336        436       161             174      6308      2368        779       296
           56    3612       1360        444       165             176      6344      2381        783       298
           58    3675       1384        452       168             178      6379      2394        788       299
           60    3737       1407        459       171             180      6414      2408        792       301
           62    3797       1430        467       173             182      6449      2421        797       303
           64    3857       1452        474       176             184      6484      2434        801       305
           66    3916       1474        482       179             186      6518      2447        805       306
           68    3974       1496        489       182             188      6553      2459        809       308
           70    4031       1517        496       185             190                2472        814       310
           72    4087       1538        503       187             192                2485        818       311
           74    4143       1559        510       190             194                2497        822       313
           76    4197       1579        517       193             196                2510        826       315
           78    4251       1600        523       195             198                2522        831       316
           80    4305       1620        530       198             200                2535        835       318
           82    4357       1639        536       200             202                2547        839       320
           84    4409       1659        543       203             204                2560        843       321
           86    4460       1678        549       205             206                2572        847       323
           88    4511       1697        556       208             208                2584        851       325
           90    4561       1716        562       210             210                2596        855       326
           92    4611       1734        568       213             212                2608        859       328
           94    4660       1752        574       215             214                2620        863       329
           96    4708       1771        580       218             216                2632        867       331
           98    4756       1789        586       220             218                2644        871       333
          100    4804       1806        592       222             220                2656        875       334
          102    4851       1824        598       224             222                2668        879       336
          104    4897       1841        604       227             224                2679        883       337
          106    4944       1858        609       229             226                2691        887       339
          108    4989       1876        615       231             228                2703        891       340
          110    5034       1892        621       233             230                2714        895       342
          112    5079       1909        626       236             232                2726        898       344
          114    5124       1926        632       238             234                2737        902       345
          116    5168       1942        637       240             236                2749        906       347
          118    5211       1959        643       242             238                2760        910       348
          120    5255       1975        648       244             240                2771        914       350
                                                        67
                                                                        Appendix B        Flow Conversion Tables
                                                        68
                                                                    Appendix B        Flow Conversion Tables
Model 4 (230V)
                     Flow (cfm)                                            Flow (cfm)
    Fan       Open                                      Fan         Open
Pressure (Pa) Fan     Ring A    Ring B    Ring C    Pressure (Pa)   Fan      Ring A     Ring B    Ring C
                                                              122     4504      1736        523       135
                                                              124     4540      1750        527       136
                                                              126     4575      1764        531       138
                                                              128     4610      1777        536       139
                                                              130     4645      1791        540       140
                                                              132     4680      1805        544       141
                                                              134     4714      1818        548       142
         16                                    47             136     4748      1832        552       143
         18                                    50             138     4782      1845        556       144
         20                         213        53             140     4815      1858        560       145
         22                         223        56             142     4848      1871        564       146
         24                         233        58             144     4881      1884        568       147
         26    2129       807       243        61             146     4914      1897        572       148
         28    2207       837       252        63             148     4947      1910        576       149
         30    2282       866       261        66             150     4979      1923        580       150
         32    2354       895       269        68             152     5011      1935        583       152
         34    2425       922       277        70             154     5043      1948        587       153
         36    2493       948       285        72             156     5075      1960        591       154
         38    2559       974       293        74             158     5106      1973        595       155
         40    2623       999       301        76             160     5137      1985        598       156
         42    2686      1024       308        78             162     5168      1997        602       157
         44    2747      1047       315        80             164     5199      2009        606       158
         46    2807      1071       322        82             166     5230      2022        609       159
         48    2866      1094       329        84             168     5260      2034        613       160
         50    2923      1116       336        85             170     5290      2046        617       161
         52    2979      1138       342        87             172     5320      2057        620       161
         54    3034      1159       349        89             174     5350      2069        624       162
         56    3088      1180       355        91             176     5380      2081        627       163
         58    3141      1201       361        92             178     5410      2093        631       164
         60    3193      1221       368        94             180     5439      2104        634       165
         62    3244      1241       374        95             182     5468      2116        638       166
         64    3295      1261       380        97             184     5497      2127        641       167
         66    3344      1280       385        99             186     5526      2139        645       168
         68    3393      1299       391       100             188     5555      2150        648       169
         70    3441      1318       397       102             190               2161        652       170
         72    3488      1337       402       103             192               2173        655       171
         74    3535      1355       408       105             194               2184        659       172
         76    3581      1373       413       106             196               2195        662       173
         78    3626      1391       419       107             198               2206        665       174
         80    3671      1408       424       109             200               2217        669       175
         82    3715      1426       429       110             202               2228        672       175
         84    3759      1443       434       112             204               2239        675       176
         86    3802      1460       440       113             206               2250        678       177
         88    3845      1476       445       114             208               2260        682       178
         90    3887      1493       450       116             210               2271        685       179
         92    3928      1509       455       117             212               2282        688       180
         94    3970      1525       459       118             214               2292        691       181
         96    4010      1541       464       120             216               2303        695       182
         98    4051      1557       469       121             218               2314        698       182
        100    4090      1573       474       122             220               2324        701       183
        102    4130      1588       478       123             222               2335        704       184
        104    4169      1604       483       125             224               2345        707       185
        106    4208      1619       488       126             226               2355        710       186
        108    4246      1634       492       127             228               2366        714       187
        110    4284      1649       497       128             230               2376        717       188
        112    4321      1664       501       129             232               2386        720       188
        114    4359      1678       506       131             234               2396        723       189
        116    4396      1693       510       132             236               2406        726       190
        118    4432      1707       514       133             238               2416        729       191
        120    4468      1721       519       134             240               2426        732       192
                                                    69
                                                                   Appendix B         Flow Conversion Tables
                                                     70
                                                                   Appendix C   Using Flow Rings C, D and E
C.1.a Installation:
To install Ring C, place Ring C in the center of Ring B and rotate
the 6 fastener clips attached to Ring B so that they rotate over the
edge of Ring C and secure it in place.
C.2.a Installation:
Ring D
                                                        71
                                                                 Appendix C      Using Flow Rings C, D and E
Ring E
Ring D:           Model 3 (110V): Flow (CFM) = 7.216 x (Fan Pressure in Pa) .4942
                  Model 3 (230V): Flow (CFM) = 6.870 x (Fan Pressure in Pa) .5022
                  Model 4 (230V): Flow (CFM) = 7.246 x (Fan Pressure in Pa) .5032
Ring E:           Model 3 (110V): Flow (CFM) = 2.726 x (Fan Pressure in Pa) .5267
                  Model 3 (230V): Flow (CFM) = 2.817 x (Fan Pressure in Pa) .5139
                  Model 4 (230V): Flow (CFM) = 2.802 x (Fan Pressure in Pa) .5166
Note: If you are using Rings C, D or E with an older set of Flow Rings that have 3 fastening washers instead of
the 6 rotating fastener clips, you should temporarily tape the following locations to prevent air leakage between
the Rings.
                                                       72
                                                            Appendix C     Using Flow Rings C, D and E
                                                   73
                                 Appendix D   Sample Test Forms
                          74
Example Completed Form            Building Airtightness Test Form
Comments:
 Owner complains of condensation on windows.
 Crawlspace is wet.
 2 smokers in the house.
 Downspouts dump directly at the base of the house.
Pre-test Baseline Pressure: 0 (Pa)        Mag Gauges          Pre-test Baseline Pressure: ______ (Pa)
  Bdlg Press.    Flow Ring        Fan Press     Flow           Bdlg Press.      Flow Ring        Fan Press        Flow
     (Pa)         Installed         (Pa)        (cfm)             (Pa)           Installed         (Pa)           (cfm)
     -55          Open              73          4091
     -50          Open              65          3862
     -44          Open              56          3588
     -38          Open              45          3220
     -30          Open              33          2762
     -26          Open              26          2455
     -15          Ring A            100         1764
Post-test Baseline Pressure: N/A (Pa)                         Post-test Baseline Pressure: ______ (Pa)
Fan Model/SN:           Model 3               S/N 8331        Fan Model/SN: ___________________________________
                                                         75
Example Blank Form              Building Airtightness Test Form
Comments:
Test #1 Depress ______ Press ______ Test #2 Depress ______ Press ______
 Pre-test Baseline Pressure: ______ (Pa)                     Pre-test Baseline Pressure: ______ (Pa)
  Bdlg Press.      Flow Ring     Fan Press      Flow          Bdlg Press.      Flow Ring        Fan Press     Flow
     (Pa)           Installed      (Pa)         (cfm)            (Pa)           Installed         (Pa)        (cfm)
 Post-test Baseline Pressure: ______ (Pa)                    Post-test Baseline Pressure: ______ (Pa)
 Fan Model/SN: ___________________________________           Fan Model/SN: ___________________________________
 Results:                                                    Results:
  CFM50:                                                      CFM50:
  ACH50:                                                      ACH50:
               2
  CFM50/ft :                                                  CFM50/ft2:
  Mpls Leakage Ratio:                                         Mpls Leakage Ratio:
                                                        76
                                                   Appendix E   Home Energy Article
by Alan Meier
Alan Meier is executive editor of Home Energy Magazine.
This Home Energy classic, originally printed in 1986, explains a simple way
to take one air infiltration measurement and determine a home's average air
infiltration rate.
ACH Divided by 20
In the late 1970s, a simple relation between a one-time pressurization test
and an average infiltration rate grew out of experimentation at Princeton
University. For a few years, the correlation remained "Princeton folklore"
because no real research supported the relationship. In 1982, J. Kronvall
and Andrew Persily compared pressurization tests to infiltration rates
measured with tracer-gas for groups of houses in New Jersey and Sweden.
They focused on pressurization tests at 50 Pascals because this pressure
was already used by the Swedes and Canadians in their building standards.
(This measurement is typically called "ACH50.") Other countries and groups
within the United States have also adopted ACH as a measure of house
tightness. Persily (now at the National Institute of Science and
Technology) obtained a reasonably good estimate of average infiltration
rates by dividing the air change rates at 50 Pascals by 20, that is:
In this formula, ACH50 denotes the hourly air change rate at a pressure
difference of 50 Pascals between inside and outside. Thus, for a house with
15 ACH at 50 Pascals (ACH50 = 15), one would predict an average air change
rate of (15/20 = ) 0.75 ACH.
                                              77
                                                  Appendix E   Home Energy Article
   Windiness and wind shielding. Wind is usually the major driving force in
    infiltration, so it is only reasonable to expect higher infiltration
    rates in windy areas. Thus, given two identical buildings, the one
    located in a windy location will have more wind-induced infiltration.
    Nevertheless, a correlation such as ACH50/20 does not include any
    adjustment for windiness at the house's location. Trees, shrubs,
    neighboring houses, and other materials also shield a house from the
    wind's full force. Since a brisk wind can easily develop 10 Pascals on a
    windward wall, the extent of shielding can significantly influence total
    infiltration. A pressurization test does not directly measure the extent
    of shielding (although a house with good shielding may yield more
    accurate measurements since it is less affected by wind).
                                      78
                                                      Appendix E   Home Energy Article
Max Sherman at LBL used this model to derive the theoretical correlation
between pressure tests at 50 Pascals and annual average infiltration
rates.1 His major contribution was to create a climate factor to reflect
the influence of outside temperature (which determines the stack effect)
and windiness. Sherman estimated the climate factor using climate data for
North America and plotted it (see Figure 1). Since the factor reflects both
temperature and seasonal windiness, a cold, calm location could have the
same climate factor as a warm, windy location. The map also reflects summer
infiltration characteristics. Note how Texas and Vermont have the same
climate factors.
Sherman found that the correlation factor in the revised formula could be
expressed as the product of several factors:
where:
Values for each of the factors can be selected by consulting Figure 1 and
Tables 1-3. An estimate of the average annual infiltration rate is thus
given by
An Example
The application of the climate correction is best shown in an example.
Suppose you are pressure testing a new, low-energy house in Rapid City,
South Dakota. It is a two-story house, on an exposed site, with no
surrounding vegetation or nearby houses to protect it from the wind.
                                        79
                                                 Appendix E   Home Energy Article
6. Calculate N:
= 17
                   ACH =    ACH50
                            -----
                             17
                       = 14
                         --
                         17
= 0.82
The difference in this case (between dividing by 20 and 17) is not great--
only 17%--but it demonstrates how the building conditions and location can
affect the interpretation of pressurization tests.
                                     80
                                                 Appendix E   Home Energy Article
Recommendations
There is no simple way to accurately convert a single pressure-test of a
building to an average infiltration rate, because many building and
climate-dependent factors affect true infiltration. Long-term tracer gas
measurements are the only reliable way to obtain average infiltration
rates. However, tracer gas measurements are impractical for retrofitters,
and even most conservation researchers. A simplified rule of thumb to let
the retrofitter quickly translate a pressure-test to an infiltration rate
is clearly attractive.
Now Sherman has created a similar conversion factor that can be modified to
reflect local building and climate conditions. This correlation factor
accounts for windiness, climate, stack effect, and construction quality.
Some judgement is needed to select the appropriate correction factors, but
the blower-door user can now understand the quantitative impact of local
conditions on infiltration. For example, a three-story house will have
significantly more infiltration than a ranch house--even though the
pressure tests are identical--due to a greater stack effect. (Clearly an
infiltration standard should take these factors into account.)
                                     81
                                                 Appendix E   Home Energy Article
                                     82
                                                       Appendix F     Calculating a Design Air Infiltration Rate
The following procedure can be used to calculate a design air infiltration rate for a house from a single or multi-
point blower door airtightness test. Calculated design air infiltration rates can be used in ACCA Manual J load
calculations in lieu of the estimation procedures listed in Manual J. The calculation procedure presented below
is based on the Lawrence Berkeley Laboratory (LBL) infiltration model. More information on this procedure
can be found in the 2009 ASHRAE Fundamentals Handbook, Section 27.21.
Note: This calculation procedure is contained in the TECTITE test analysis software.
   Determine the 4 Pascal Effective Leakage Area (ELA) of the house in square inches from the Blower Door
    test data. This can be done in 2 ways:
    1.   Perform a multi-point Blower Door test of the house and determine the ELA using the TECTITE
         software, or
    2.   Perform a single-point 50 Pa Blower Door test to determine house CFM50. Multiply CFM50 by 0.055
         to estimate the ELA of the house in square inches. This procedure assumes the "House Leakage Curve"
         has a slope (or "N" value) of 0.65. Research has shown that N = 0.65 is a reasonable assumption for a
         large sample of houses.
Determine the Stack Coefficient (A) and the Wind Coefficient (B) for the house from the Tables below:
                                                         83
                                                     Appendix F      Calculating a Design Air Infiltration Rate
Determine the air flow rate due to infiltration from the following equation:
Q = L x ((A x T) + (B x V2))1/2
                  where:
                           Q = airflow rate in cubic feet per minute (CFM).
                           L = Effective Leakage Area (ELA) in square inches.
                           A = Stack Coefficient.
                           T = Design indoor-outdoor temperature difference (F).
                           B = Wind Coefficient.
                           V = Design wind speed (MPH - measured at a local weather station).
                                    Frequency data for mean hourly wind speeds within the United States can be
                                    found in a summarized printed pamphlet from the National Climatic Center
                                    in Asheville, North Carolina, and from the Atmospheric Environment
                                    Service in Downsview, Ontario for Canadian sites.
Example Calculation
Estimate the winter-time design infiltration rate for a 2 story, 30,000 cubic foot house in Minneapolis with
suburban wind shielding. Use a design wind speed of 20 MPH and a design temperature difference of 82
degrees F. A single-point Blower Door test of the house measured an airtightness rate of 2,350 CFM50.
= 277.4 CFM
                                                        84
                                                                                 Appendix G      References
Appendix G References
1.   ASHRAE, 1989. ASHRAE Standard 62-1989, "Ventilation for Acceptable Indoor Air Quality." American
     Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
2.   ASTM, 1987. ASTM Standard E779-87, "Standard Test Method for Determining Air Leakage Rate by Fan
     Pressurization" American Society for Testing and Materials.
3.   Canadian General Standards Board, 1986. "Determining of the Airtightness of Building Envelopes by the
     Fan Depressurization Method" Standard CAN/CGSB-149.10-M86.
4.   CMHC, 1988. "Chimney Safety Tests Users' Manual: Procedures for Determining the Safety of Residential
     Chimneys." Canada Mortgage and Housing Corporation Information Centre, 700 Montreal Rd., Ottawa,
     Ontario, Canada K1A-0P7 (613) 748-2000.
5.   ASHRAE, 1988. ASHRAE Standard 119-1988, "Air Leakage Performance for Detached Single-Family
     Residential Buildings." American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
6.   ASHRAE, 1993. ASHRAE Standard 136-1993. "A Method of Determining Air Change Rates in Detached
     Dwellings." American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc.
7.   Cummings, James, Tooley, John and Moyer, Neil, 1991. "Investigation of Air Distribution System Leakage
     and It's Impact in Central Florida Homes" Florida Solar Energy Center, January 1991.
8.   Fitzgerald, Jim, Nelson, Gary and Shen, Lester, 1990. "Sidewall Insulation and Air Leakage Control" Home
     Energy, January/February 1990. pp 13-20.
9.   Meier, Alan, 1986. "Infiltration: Just ACH50 Divided By 20?" Energy Auditor and Retrofitter (now Home
     Energy), July/August 1986. pp 16-19.
10. Moffatt, Sebastian, 1990. "Backdrafting Causes and Cures" Journal of Light Construction, 1990. pp. 27-29.
11. Palmiter, Larry, Brown, Ian and Bond, Tammi, 1990. "Infiltration and Ventilation in New Electrically
    Heated Homes in the Pacific Northwest" Proceedings of the ACEEE 1990 Summer Study on Energy
    Efficiency in Buildings, Volume 9. pp 9.241-9.252.
12. Shen, Lester, Nelson, Gary, Dutt, Gautam and Esposito, Bonnie, 1990. "Cost-Effective Weatherization in
    Minnesota: The M200 Enhanced Low-Income Weatherization" Energy Exchange, August 1990. pp 13-18.
13. Tooley, John and Moyer, Neil, 1989. "Air Handler Fan: A Driving Force for Air Infiltration" Home
    Energy, November/December 1989. pp 11-15.
14. Tooley, John and Moyer, Neil, 1989. "MAD-AIR" Residential Energy Forum (now Southern Comfort),
    Summer 1989. pp 2-3, 9.
15. Tooley, John and Moyer, Neil, 1990. "Duct Busting" Southern Comfort, August 1990. pp 2-4, 5, 8.
16. Tooley, John, Moyer, Neil and Cummings, James, 1991. "Pressure Differential "The Measurement of a
    New Decade"" Proceeding of the Ninth Annual International Energy Efficiency Building Conference,
    Indianapolis, IN, March 91. pp A38-A52.
                                                      85
                                                                          Appendix H         Air Density Correction Factors
50 55 60 65 70 75 80 85 90
                          -20      0.929     0.924    0.920       0.915   0.911    0.907       0.903   0.898    0.894
                          -15      0.934     0.930    0.925       0.921   0.916    0.912       0.908   0.904    0.899
                          -10      0.939     0.935    0.930       0.926   0.921    0.917       0.913   0.909    0.904
                           -5      0.945     0.940    0.935       0.931   0.927    0.922       0.918   0.914    0.909
                            0      0.950     0.945    0.941       0.936   0.932    0.927       0.923   0.919    0.914
                            5      0.955     0.950    0.946       0.941   0.937    0.932       0.928   0.924    0.919
                           10      0.960     0.955    0.951       0.946   0.942    0.937       0.933   0.929    0.924
                           15      0.965     0.960    0.956       0.951   0.947    0.942       0.938   0.934    0.929
                           20      0.970     0.965    0.961       0.956   0.952    0.947       0.943   0.938    0.934
                           25      0.975     0.970    0.966       0.961   0.957    0.952       0.948   0.943    0.939
                           30      0.980     0.975    0.971       0.966   0.962    0.957       0.953   0.948    0.944
                           35      0.985     0.980    0.976       0.971   0.966    0.962       0.957   0.953    0.949
OUTSIDE                    40      0.990     0.985    0.981       0.976   0.971    0.967       0.962   0.958    0.953
TEMPERATURE                45      0.995     0.990    0.985       0.981   0.976    0.972       0.967   0.963    0.958
 (F)                       50      1.000     0.995    0.990       0.986   0.981    0.976       0.972   0.967    0.963
                           55      1.005     1.000    0.995       0.990   0.986    0.981       0.977   0.972    0.968
                           60      1.010     1.005    1.000       0.995   0.991    0.986       0.981   0.977    0.972
                           65      1.015     1.010    1.005       1.000   0.995    0.991       0.986   0.981    0.977
                           70      1.019     1.014    1.010       1.005   1.000    0.995       0.991   0.986    0.982
                           75      1.024     1.019    1.014       1.009   1.005    1.000       0.995   0.991    0.986
                           80      1.029     1.024    1.019       1.014   1.009    1.005       1.000   0.995    0.991
                           85      1.034     1.029    1.024       1.019   1.014    1.009       1.005   1.000    0.995
                           90      1.038     1.033    1.028       1.024   1.019    1.014       1.009   1.005    1.000
                           95      1.043     1.038    1.033       1.028   1.023    1.019       1.014   1.009    1.005
                          100      1.048     1.043    1.038       1.033   1.028    1.023       1.018   1.014    1.009
                          105      1.053     1.047    1.042       1.037   1.033    1.028       1.023   1.018    1.014
                          110      1.057     1.052    1.047       1.042   1.037    1.032       1.027   1.023    1.018
          To use the air density correction factor, multiply the measured fan flow by the appropriate correction factor from
          the Table above. For example, if the measured fan flow was 3,200 cfm, and during the test the inside
          temperature was 70 F and the outside temperature was 40 F, the appropriate correction factor would be 0.971.
          The density corrected fan flow is 3,200 x 0.971 = 3,107 cfm
                                                                    86
                                                                       Appendix H         Air Density Correction Factors
50 55 60 65 70 75 80 85 90
                        -20      1.077     1.082    1.087      1.092   1.098     1.103      1.108    1.113   1.118
                        -15      1.071     1.076    1.081      1.086   1.091     1.097      1.102    1.107   1.112
                        -10      1.065     1.070    1.075      1.080   1.085     1.090      1.096    1.101   1.106
                         -5      1.059     1.064    1.069      1.074   1.079     1.084      1.089    1.095   1.100
                          0      1.053     1.058    1.063      1.068   1.073     1.078      1.084    1.089   1.094
                          5      1.047     1.052    1.058      1.063   1.068     1.073      1.078    1.083   1.088
                         10      1.042     1.047    1.052      1.057   1.062     1.067      1.072    1.077   1.082
                         15      1.036     1.041    1.046      1.051   1.056     1.061      1.066    1.071   1.076
                         20      1.031     1.036    1.041      1.046   1.051     1.056      1.061    1.066   1.070
                         25      1.025     1.030    1.035      1.040   1.045     1.050      1.055    1.060   1.065
                         30      1.020     1.025    1.030      1.035   1.040     1.045      1.050    1.055   1.059
                         35      1.015     1.020    1.025      1.030   1.035     1.040      1.044    1.049   1.054
OUTSIDE                  40      1.010     1.015    1.020      1.025   1.030     1.034      1.039    1.044   1.049
TEMPERATURE              45      1.005     1.010    1.015      1.020   1.024     1.029      1.034    1.039   1.044
 (F)                     50      1.000     1.005    1.010      1.015   1.019     1.024      1.029    1.034   1.038
                         55      0.995     1.000    1.005      1.010   1.014     1.019      1.024    1.029   1.033
                         60      0.990     0.995    1.000      1.005   1.010     1.014      1.019    1.024   1.028
                         65      0.986     0.990    0.995      1.000   1.005     1.009      1.014    1.019   1.024
                         70      0.981     0.986    0.991      0.995   1.000     1.005      1.009    1.014   1.019
                         75      0.976     0.981    0.986      0.991   0.995     1.000      1.005    1.009   1.014
                         80      0.972     0.977    0.981      0.986   0.991     0.995      1.000    1.005   1.009
                         85      0.967     0.972    0.977      0.981   0.986     0.991      0.995    1.000   1.005
                         90      0.963     0.968    0.972      0.977   0.982     0.986      0.991    0.995   1.000
                         95      0.959     0.963    0.968      0.973   0.977     0.982      0.986    0.991   0.995
                        100      0.954     0.959    0.964      0.968   0.973     0.977      0.982    0.987   0.991
                        105      0.950     0.955    0.959      0.964   0.969     0.973      0.978    0.982   0.987
                        110      0.946     0.951    0.955      0.960   0.964     0.969      0.973    0.978   0.982
       To use the air density correction factor, multiply the measured fan flow by the appropriate correction factor from
       the Table above. For example, if the measured fan flow was 3,200 cfm, and during the test the inside
       temperature was 70 F and the outside temperature was 40 F, the appropriate correction factor would be 1.030.
       The density corrected fan flow is 3,200 x 1.030 = 3,296 cfm.
                                                                87
                                                       Appendix I      Cruise Control with the DG-700 Gauge
In order to use the Cruise Control feature you will need the following 3 items:
                                      Fan Control
                                      cable with
                                      Blower Door
                                      controller
                                   Fan control
                                   cable with
                                   Duct
                                   Blaster
                                   controller.
                                                        88
                                                        Appendix I     Cruise Control with the DG-700 Gauge
Cruise Overview
Cruise Control uses the DG-700s fan control feature to continuously adjust the (Blower Door) fan to maintain a
constant Cruise target pressure on Channel A of the gauge. Cruise Control can be used in the following gauge
Modes to maintain the listed target pressures:
Before starting Cruise, the Blower Door and DG-700 should be completely set-up (including tubing
connections), the gauge should be in the Mode you wish to use, and the correct Device and Configuration
settings should be entered. If you wish to Cruise with a baseline pressure adjustment applied to Channel A,
simply use the Baseline feature first before beginning Cruise. You will also need to install the fan control cable
and turn the Blower Door speed control knob to the just on position:
    -    Model 3 Blower Door just on - from the off position, turn the controller knob clockwise only until
         you feel the click and no farther - the fan will not be turning.
    -    Duct Blaster just on  turn the controller knob all the way down (counter-clockwise) and flip the
         on/off switch to ON  the fan will not be turning.
Begin Cruise button: When you are ready to begin Cruise, press Begin Cruise to enter Cruise setup. A Cruise
target pressure will appear in the Channel A display and the Cruise icon will flash. The flashing Cruise icon
indicates that the gauge is ready to begin Cruising but is not yet controlling the fan. If you are in the PR/ FL or
PR/ PR modes, you may change the Cruise target pressure at this point by pressing the Cruise Target button.
Note: You can not change the Cruise target pressure when in the PR/ FL @50 and PR/ FL @25 modes.
Start Fan button: Press Start Fan to instruct the DG-700 to begin ramping up the fan to achieve the target
pressure on Channel A. The fan will slowly start increasing speed until the pressure reading on Channel A
matches the Cruise target pressure. The fan will simply run at full speed if the target pressure can not be
achieved. Whenever the DG-700 is calling for full fan speed, the gauge will emit a beeping sound.
Stop Fan button: Press Stop Fan to turn off the fan when you are done Cruising. When the fan is turned off by
pressing Stop Fan, the DG-700 returns to the Cruise setup state (i.e. the Cruise icon is flashing and a Cruise
target pressure is displayed on Channel A). You may re-start Cruise again by pressing Start Fan, or exit the
Cruise feature altogether by pressing the CLEAR button.
The fan will also be stopped while Cruising under the following circumstances:
    -    If Channel A registers a pressure of 100 Pa or more, the fan will automatically be shut down and the
         gauge will revert back to the Cruise setup state.
    -    Pressing the HOLD button will shut down the fan and freeze the display. Pressing Start Fan from a
         display freeze will re-start Cruise. Pressing the HOLD button a second time from a display freeze will
         return the gauge to the Cruise setup state.
    -    The DG-700s auto-off feature will shut down the gauge and turn off the fan after 2 hours of run-time
         (if no buttons are pressed during that time).
Cruising Zero (+0 and -0)
Cruising Zero is designed for specialized testing/research applications and will typically not be used by most
Blower Door technicians. Cruising Zero is useful if you want to control the Blower Door fan to remove an
existing pressure from a building or other enclosure. When using the fan to pressurize a space (that is currently
depressurized) use +0 as your Cruise target pressure. When using the fan to depressurize a space (that is
currently pressurized), use 0 as the Cruise target pressure.
                                                         89
                                                              Appendix J       Blower Door System Specifications
Maximum Flow:         (Model 3 Fan): 6,100 CFM (free air), 5,250 CFM (at 50 Pa).
                      (Model 4 Fan): 4,850 CFM (free air), 4,320 CFM (at 50 Pa).
Minimum Flow: 300 CFM (Ring B), 85 CFM (Ring C), 30 CFM (Ring D), 11 CFM (Ring E).
Flow Accuracy: +/- 3% with DG-500, DG-700 (+/- 4% or 1 CFM for Rings D & E).
Options:
DG-700 Gauge Universal AC Adapter:              100-240V/50-60Hz Input, 12 VDC Output, Center "+", 12mm
                                                Barrel Length, 3W Min. Output (International mains adapters
                                                included).
90