Protection Systems: Fenwal 732 Conventional Fire Alarm-Suppression Control Unit
Protection Systems: Fenwal 732 Conventional Fire Alarm-Suppression Control Unit
Protection Systems
  A UTC Fire & Security Company
Fenwal 732
Conventional Fire
Alarm-Suppression Control
Unit
                                     ICE OF
                              O FF
                                      P/N 06-236717-001
                                            August 2007
                                              FOREWORD                                                                                               TERMS AND ABBREVIATIONS
Note: This Manual, P/N 06-236717-001, is to be used by qualified and factory-trained personnel, knowledgeable
      of NFPA standards and any other applicable standards in effect.
This Manual is intended to provide guidance to qualified technical professionals for the installation, operation and      C          Centigrade                                       LCD:        Liquid Crystal Display
maintenance of the Fenwal 732 Conventional Fire Alarm-Suppression Control Unit.                                          F          Farenheit                                        LED:        Light Emitting Diode
Only qualified persons experienced and trained in the installation of this type of equipment should install and
                                                                                                                          A:          Ampere                                            MEA:        Materials and Equipment Acceptance
configure the Fenwal 732. They must be familiar and experienced with the wiring diagrams and components,
                                                                                                                                                                                                    Division of the City of New York
electrical installation, and familiar not only with NEC, relevant NFPA and local codes but also trained and qualified
by Kidde-Fenwal, Inc. Kidde-Fenwal, Inc. is a manufacturer of the components that make up the Fenwal 732                  AC:         Alternating Current                               NAC:        Notification Appliance Circuit
system, and may not have the opportunity to visit the sites where the product is installed or intended to be
                                                                                                                          ADA:        Americans with Disabilities Act                   N.C.:       Normally Closed
installed. It is the responsibility of the professional installer (described above) to properly install and configure
the systems. Under no circumstances will Kidde-Fenwal be liable for improper installation or configuration of the         AH:         Ampere Hour                                       NEC:        National Electrical Code
systems.
                                                                                                                          AHJ:        Authority Having Jurisdiction                     NFPA:       National Fire Protection Association
The technical data contained herein is provided for informational purposes only, and should not be used as a
substitute for professional judgment. Although, Kidde-Fenwal believes this information to be true and correct, it         ARC:        Automatic Release Circuit                         N.O.:       Normally Open
is published and presented without any guarantee or warranty whatsoever. Kidde-Fenwal disclaims any liability             AWG:        American Wire Gauge                               NYC:        New York City
for any use of the data other than as set out in this manual, foreword included.
                                                                                                                          CSFM:       California State Fire Marshal                     PCB:        Printed Circuit Board
Any questions concerning the information presented in this manual should be addressed to:
Kidde-Fenwal, Inc.                                                                                                        DACT:       Digital Alarm Comm. Transmitter                   pF:         Pico-farads
400 Main Street                                                                                                           DC:         Direct Current                                    P/N:        Part Number
Ashland, MA 01721
Phone: (508) 881-2000                                                                                                     DET:        Detector                                          PSU:        Power Supply Unit
Toll Free: (800) 872-6527                                                                                                 EOLD:       End of Line Device                                RAM:        Random Access Memory
Technical Support: (866) 287-2531
Fax: (508) 881-8920                                                                                                       EOLR:       End of Line Resistor                              SLC:        Signaling Line Circuit
                                                                                                                          FM:         Factory Mutual                                    TB:         Terminal Block
                                                                                                                          ft.:        Feet                                              UL/ULI:     Underwriters Laboratories, Inc.
                                                                                                                          HSSD:       High Sensitivity Smoke Detector                   V:          Volts
                                                                                                                          Hz:         Hertz (Frequency)                                 Vac:        Volts AC
                                                                                                                          in.:        Inch                                              Vdc:        Volts DC
                                                                                                                          IRI:        Industrial Risk Insurers                          VRMS:       Volts Root Mean Square
                                                                                                                        CAUTION              A caution identifies a procedure, practice, or statement, which, if not strictly followed, could
                                                                                                                                             result in programming errors, impairment of equipment operation, or equipment damage.
                    System Re-acceptance Test after Re-Programming: To ensure proper system operation, this                 Auxiliary Equipment used in the system may not be technically compatible with the control unit. It is essential to
                    system must be retested in accordance with NFPA 72 Chapter 10 after any programming                     use only equipment listed for service with your control unit.
                    change. Re-acceptance testing is also required after any addition or deletion of system                 Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of
CAUTION             components, and after any modification, repair or adjustment to system hardware or wiring.              service or temporarily disabled.
                    All components, circuits and system operations known to be affected by a change must be                 The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system
                    100% tested. In addition, to ensure that other operations are not inadvertently affected, at least      wiring should be tested and maintained by professional fire alarm installers following written procedures supplied
                    10% of initiating devices that are not directly affected by the change, up to a maximum of 50           with each device. System inspection and testing should be scheduled monthly or as required by national and/or
                    devices, must also be tested and proper system operation verified.                                      local fire codes. Adequate written records of all inspections should be kept.
This system meets FM and ANSI/UL 864 requirements for operation at 32 to 120F (0 to 49C) and at a relative
                                                                                                                            GENERAL SAFETY NOTICES                          The following must be observed to maintain personnel safety.
humidity of 93% (non-condensing) @ 90F (32.2C). However, the useful life of the systems standby batteries and            The following general safety notices supplement specific warnings and cautions appearing in the manual. The
the electronic components may be adversely effected by continuous operation at these environmental limits.                  safety precautions in this section must be understood and applied during operation and maintenance. This
Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal             manual is to be used by trained distributors/technicians. The entire manual should be read and fully understood
room temperature of 60-80F.                                                                                                prior to installation.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to
lightning induced transients. Although no system is completely immune from lightning transients and interference,           FIRST AID
proper grounding will reduce susceptibility. The use of overhead or outside aerial wiring is not                            Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention
recommended due to the increased susceptibility to nearby lightning strikes. Consult with the Technical                     immediately.
Support Department if any problems are anticipated or encountered.
Do not install electronic assemblies prior to mounting and attaching conduit for field wiring to the enclosure.             GENERAL PRECAUTIONS
Before making modifications, verify that they will not interfere with battery and printed circuit board locations. Do       The following general safety precautions are to be observed at all times:
not overtighten screw terminals. Overtightening may damage threads, resulting in reduced terminal contact
                                                                                                                            1.    All electrical components associated with equipment shall be installed and grounded in accordance with
pressure and difficulty with screw terminal removal.
                                                                                                                                  NEC and local regulatory requirements.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before
                                                                                                                            2.    Special precautionary measures are essential to prevent applying power to equipment at any time mainte-
handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect
                                                                                                                                  nance work is in progress.
electronic assemblies removed from the control unit.
                                                                                                                            3.    Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
Follow the instructions in this manual. These instructions must be followed to avoid damage to the control unit
and associated equipment. System operation and reliability depend upon proper installation.                                 4.    When working near electricity, do not use metal rulers, flashlights, metallic pencils, or any other
                                                                                                                                  objects having exposed conductive material.
Fire Alarm System Limitations                  While installing a fire alarm system may make lower insurance
                                               rates possible, it is not a substitute for fire insurance!                   5.    When connecting a meter to terminals for measurement, use a voltage range higher than expected voltage to
                                                                                                                                  be measured.
An automatic fire alarm system  typically made up of smoke detectors, heat detectors, manual pull stations, notification
appliances, and a fire alarm control unit with remote-notification capability  can provide early warning of a developing
fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, on
roofs, or on the other side of closed doors. Smoke detectors on one level also may not sense a fire on another level
or floor of a building. A second floor detector, for example, may not sense a first floor or basement fire.
CHAPTER 2           INSTALLATION
  2-1               Installation Materials ....................................................................................................... 2-1
  2-2               Installation Guidelines ..................................................................................................... 2-2
  2-3               Installation Procedure...................................................................................................... 2-4
  2-4               Terminations And Wiring Diagrams................................................................................. 2-14
  2-5               Installing the Bezel, P/N 06-220115-001 .......................................................................... 2-21
  2-6               Installing Optional Dead-Front Panel, P/N 06-220175-001 .............................................. 2-21
  2-7               Installing the Enclosure Door (Standard Door)................................................................ 2-21
  2-8               Installing the Enclosure Door (Door with Switches)......................................................... 2-21
  2-9               Completing the Installation .............................................................................................. 2-23
CHAPTER 3           CONFIGURATION
  3-1               Entering Site - Specific Configuration .............................................................................. 3-1
  3-2               Configuration Settings ..................................................................................................... 3-2
CHAPTER 4           OPERATION
  4-1               Introduction..................................................................................................................... 4-1
  4-2               Control Switch Functionality ........................................................................................... 4-2
CHAPTER 6           TROUBLESHOOTING
  6-1               Purpose ........................................................................................................................... 6-1
  6-2               Trouble Diagnostics ......................................................................................................... 6-1
  6-3               Trouble Codes and Corrective Action............................................................................... 6-1
P/N 06-236717-001                                                           vii                                                                    August 2007   August 2007                               viii                          P/N 06-236717-001
                                                   LIST OF FIGURES                                                                                                                                                LIST OF TABLES
Figure      Name                                                                                                                    Page Number                Table       Name                                                                                                                          Page Number
1-1         Control Unit Components and Dimensions .............................................................................. 1-3                          1-1         Agency Listing/Approval by System Classification ..................................................................... 1-1
1-2         Printed Circuit Board (PCB) ..................................................................................................... 1-5              1-2         Listed/Approved Suppression Systems ..................................................................................... 1-2
                                                                                                                                                               1-3         LED Indicator and Display Color.............................................................................................. 1-6
2-1         Installation Height Above Floor................................................................................................. 2-4               2-1         Fenwal 732 Control Unit Contents............................................................................................ 2-1
2-2         Control Unit and Surface Mounting Dimensions....................................................................... 2-5                            2-2         Hardware Kit Contents (P/N 06-220147-001) ........................................................................... 2-1
2-3         Semi-Flush Mounting Dimensions ............................................................................................ 2-6                    2-3         Wiring Gauge Recommendation, Resistance, and Maximum Lengths........................................ 2-3
2-4         Trim Ring Dimensions.............................................................................................................. 2-6             3-1         Configuration Settings .............................................................................................................. 3-2
2-5         Trim Ring Installed................................................................................................................... 2-7         4-1         Acknowledge............................................................................................................................. 4-2
2-6         Power Supply Unit Wiring......................................................................................................... 2-8              5-1         Testing Frequency .................................................................................................................... 5-1
2-7         Power Supply Unit Installation ................................................................................................. 2-9               A-1         Duration Time for Standby and Alarm ..................................................................................... A-1
2-8         PCB Installation........................................................................................................................ 2-10      A-2         Power Consumptions for System Components ......................................................................... A-1
2-9         PCB-to-Cabinet Grounding Diagram ......................................................................................... 2-11                    A-3         Standby and Alarm Calculation Guide...................................................................................... A-2
2-10        Primary Power Connections...................................................................................................... 2-12               A-4         Battery Capacity Calculations ................................................................................................... A-3
2-11        Backup Battery Connections..................................................................................................... 2-13               B-1         Detectors and Bases .................................................................................................................B-1
2-12        Printed Circuit Board ............................................................................................................... 2-14         B-2         Releasing Solenoid....................................................................................................................B-2
2-13        Initiating Device Circuit Wiring ................................................................................................. 2-16            B-3         Initiator-Based Releasing Devices .............................................................................................B-2
2-14        Notification Appliance Circuit Wiring ........................................................................................ 2-17                B-4         Miscellaneous Devices ..............................................................................................................B-2
2-15        Agent Release Circuit Wiring..................................................................................................... 2-20
2-16        Dead-Front Panel Installation ................................................................................................... 2-21
2-17        Installation of Manual Release and Abort Switches ................................................................... 2-22
2-18        Installing Switch Harness Assembly ......................................................................................... 2-23
                                                                                                                                          The Fenwal 732 is listed/approved for the control and activation of suppression systems listed in
                                                                                                                                          Table 1-2 which the designer/installer should be familiar with.
1-1            INTRODUCTION
               The Fenwal 732 is a versatile, flexible, microprocessor-based conventional fire alarm/suppression                                              Table 1-2. Listed/Approved Suppression Systems
               control system which can be used in a wide range of fire alarm and release applications.
                                                                                                                                                                  Application                          Applicable NFPA Standard
P/N 06-236717-001                                              1-1                                            August 2007   August 2007                                              1-2                                       P/N 06-236717-001
                                                                                                    General Information             General Information
              The Fenwal 732 consists of the following: Enclosure with Door, Power Supply Unit, Printed Circuit                                   The power supply unit mounts behind the circuit board and operates from either 120 Vac 50/60 Hz
              Board (PCB), and Secondary Standby Batteries (ordered separately).                                                                  or 240 Vac 50/60 Hz. It powers the system and also charges a standby battery set which provides
                                                                                                                                                  backup in case of loss of power from the AC source.
                                                                                            5 in.
                                                                                         (127 mm)                                                 The battery charger is capable of charging sealed lead-acid 24 Vdc batteries of capacity up to 68 AH.
                                                                                                        14-1/4 in.                                The charge voltage is 27.4 Vdc nominal.
                                                                                                        (362 mm)
                                                        ENCLOSURE                                                                                 The actual battery capacity used for an application is a function of the control units components,
                                                                                                                                                  devices and configuration. Refer to Appendix A for battery capacity calculations.
                                                                                                                                                  The power supply monitoring circuit provides a trouble signal if any of the following occur:
                                                       PRINTED CIRCUIT BOARD
                                                                                                                                                     Loss of AC input or if AC power falls below 85% of nominal. This causes an immediate change-
                                                                                                                                                      over to battery operation and a trouble signal after 30 seconds.
                                                        POWER SUPPLY UNIT
                                                                                                                                                     Detection of a ground fault.
                                                                                                                           19 in.
                                                        (BEHIND PRINTED CIRCUIT BOARD)                                   (483 mm)
                                                                                                                                                     Low charging current.
                                                                                                                                                     High output voltage
                                                                                                                                                  The battery monitoring circuit provides a trouble signal if any of the following occur:
            ENCLOSURE                  SECONDARY
            DOOR                       STANDBY
                                       BATTERIES
                                                                                                                                                     The battery is installed backwards.
                                                                                                                                                     The battery is disconnected.
                                                                                                                                                     Battery voltage falls below 19.5 V (this condition causes the battery to disconnect and can only
                                                                                                                                                      be cleared when primary AC main power is restored).
                              Figure 1-1. Control Unit Components and Dimensions
                                                                                                                                    1-4.3         Printed Circuit Board
1-4.1         Enclosure with Door
                                                                                                                                                  The printed circuit board provides an interface or terminals for the following:
              The enclosure meets the requirements for NEMA Type 1 and is intended to be used indoors in a                                           Power Supply Unit
              relatively dust-free environment. The enclosure has a hinged door that swings open 180 for
                                                                                                                                                     Battery
              accessibility. The enclosure can be surface or recessed mounted. A trim ring is available for recessed
              mounting. The enclosure is constructed of 18 gauge sheet steel. A steel door is held closed by a key                                   Initiating Device Circuits (System Inputs)
              lock. All operator interface switches and indicators are located behind the locked cover. The                                          System Outputs
              enclosure is large enough to house two 12 Vdc, 12 AH batteries required for standby operation.                                         Operator Interface
              The enclosure and door has two color options  blue for most UL/cUL applications and red for                                           Auxiliary Power Output
              MEA/NYC applications. Refer to Table 1-1 for current listings/approvals.
              The standard enclosure door allows the operator to view the operator interface display mounted on
              the PCB behind a Plexiglas window. The Fenwal 732 is also available with an alternate door that
              allows an abort and manual release switch to be mounted. The manual release switch incorporates
              a lift type guard and the abort switch incorporates a safety guard to prevent inadvertent activation.
              The control unit is also suitable for mounting a dead-front panel (P/N 06-220175-001) that is
              mandatory for use in Canada. The dead-front is intended to protect the user from inadvertent access
              to any exposed potentially hazardous/high voltage components.
P/N 06-236717-001                                        1-3                                                         August 2007    August 2007                                              1-4                                        P/N 06-236717-001
                                                                                                  General Information     General Information
                                                                                                                                        There are four Control Switches on the Operator Interface. They are:
     AC IN                             TB14        TB15          TB16           TB17     TB18             NAC 2
                                                                                                                                           Acknowledge  Silences the buzzer which sounds when a new supervisory, alarm, or trouble is
                                                                                                                                            detected. Holding this control switch for five seconds, activates the control unit Lamp Test. This
                  TB13                                                                                                                      control switch is also used in conjunction with the System Reset control switch to enter the
                                                                                                                                            configuration mode.
                                      RELEASE 1   RELEASE 2       AUX           NAC 3
                                        ARC 1       ARC 2        24 VDC                                                                 Note: Microprocessor and PCB troubles are latching and cannot be silenced or reset. Refer to
                                                                                                                                              Chapter 6, Troubleshooting.
                                         Figure 1-2. Printed Circuit Board (PCB)
                                                                                                                                           Signal Silence  Silences the NAC circuits.
                                                                                                                                           System Reset  Disconnects power from all input and output circuits and the auxiliary output
1-4.3.1       OPERATOR INTERFACE                                                                                                            for a period of five (5) seconds. This control switch is also used in conjunction with the
                                                                                                                                            Acknowledge control switch to enter the configuration mode.
              All alarms, troubles and supervisory signals are received at the control unit and displayed for the                          Output Disable  Disables the release of agent, and as selected in the system configuration, the
              operator. The Operator Interface consists of four main components and are visible and/or audible                              activation of NAC outputs and/or Programmable Relays. This is used when performing
              through a transparent window:                                                                                                 maintenance on the system.
                   LED Indicators
                   Control Switches                                                                                      1-4.3.1.3     Digital Display
                   Digital Display                                                                                                     The three digit display is used for the following:
                   Buzzer                                                                                                                 View and enter field configuration settings
                                                                                                                                           Display troubleshooting/diagnostic codes
                                                                                                                                           Display battery voltage and charging current
                                                                                                                                           Count-down timer for agent release
P/N 06-236717-001                                          1-5                                              August 2007   August 2007                                               1-6                                      P/N 06-236717-001
                                                                                              General Information       General Information
1-4.3.1.4     Buzzer                                                                                                                  Abort Mode 4 (New York City)  When the abort is activated, the timer is stopped and reset to 120
                                                                                                                                      seconds. The timer will not start as long as the Abort switch is held. The timeout restarts when the
              The buzzer will sound when an alarm, trouble or supervisory condition is present.                                       Abort switch is released. Successive Abort switch operations resets the timer back to the full 120
                                                                                                                                      second delay. Selection of this mode does not have an over-ruling effect on any programmed manual
1-4.3.2       INITIATING DEVICE CIRCUITS (SYSTEM INPUTS)                                                                              or auto-release delays, regardless of whether an abort has actually occurred. In this mode, the delay
                                                                                                                                      from a manual release is forced to zero (0), and the auto-release delay is restricted to a maximum of
              The Fenwal 732 has the following system inputs:                                                                         30 seconds. NYC Mode does not comply with ANSI/UL 864.
                   Three (3) Detection Inputs
                   One (1) Manual Release                                                                                                  The setting of non-compliant delays with New York City Abort is not error-trapped or over-
                   One (1) Abort                                                                                       WARNING             ruled by the control unit.
                   Two (2) Supervisory Inputs
              Each detector circuit is suitable for Class A or Class B wiring and is capable of operating with up to    1-4.4         System Outputs
              25 smoke/electronic heat detectors and a quantity of contact-closure type devices (up to the limitation
              imposed by wiring resistance). For a list of compatible devices, refer to Appendix B.                                   The Fenwal 732 has the following system outputs:
                                                                                                                                         Three (3) Notification Appliance Circuits (NACs)
1-4.3.2.2     Manual Release                                                                                                             Two (2) Agent Release Circuits (ARC)
              Operation of a manual release pull station activates the NACs and initiates the release sequence. The                      Three (3) Programmable Relays
              configured time delay and agent release output is activated after the site configured time delay.                          One (1) Dedicated Trouble Relay
              Manual release overrides any other time delay. The circuit is suitable for either Class A or Class B
                                                                                                                                         One (1) Auxiliary Power Output
              wiring and any quantity of contact closure type manual release stations subject to the limitations
              imposed by the wiring resistance. The manual release will also override any activated abort switch.
                                                                                                                        1-4.4.1       NOTIFICATION APPLIANCE CIRCUITS (NACs)
1-4.3.2.3     Abort                                                                                                                   The Fenwal 732 has three dedicated notification appliance circuits (NAC). Any NAC can be configured
                                                                                                                                      in system configuration to operate on one or more of First Alarm, Pre-Release, and Releasing
              Activation of the abort station temporarily delays the impending agent release. Operation of the abort
                                                                                                                                      conditions. In the case that the control unit is being used in a non-suppression application, the three
              switch during non-alarm conditions will cause a trouble signal. However, if the Abort switch is
                                                                                                                                      NACs may be configured to operate on Alarm from DET 1, DET 2, and DET 3. Each circuit is driven
              pressed and held during either a non-alarm condition or during a first alarm condition, and remains
                                                                                                                                      independently and is user configurable for either Class A (Style Z) or Class B (Style Y) operation with
              held until an alarm pre-release condition exists occurs, the Abort function will execute as normal, per
                                                                                                                                      the following coded patterns:
              the configuration setting. The following abort modes are configurable.
                                                                                                                                         60 beats per minute (BPM)
              Abort Mode 1 (ANSI/UL 864) - When the abort input is received, the release timeout continues and                           120 beats per minute (BPM)
              stops at ten (10) seconds. If the timeout was less than ten (10) seconds when the abort signal is
                                                                                                                                         Temporal
              received, timeout is reset to ten (10) seconds. When the abort is released, the timeout resumes.
              Successive aborts are permitted.                                                                                           Continuous
              Abort Mode 2 (Reset) - When abort is activated, the timer is stopped and the full delay is loaded into                  The three circuits are supervised, power-limited, and are compatible with conventional UL listed, 24
              it. The timeout begins when the Abort control switch is released. Successive aborts are permitted. If                   Vdc notification appliances. They can also be used with the following synchronizable horns and
              Mode 2 is selected with a zero (0) abort delay, the abort is disabled. Mode 2 does not comply with                      strobes:
              ANSI/UL 864.                                                                                                               MT series multi-tone horns and horn/strobes
                                                                                                                                         NS series horn/strobes
              Abort Mode 3 (IRI) - This mode is only valid for cross-zoned release when both initiating inputs are
              needed to cause the agent release activation (if selected for single zone, the abort will be disabled).                    NH series horns
              This mode is similar to Mode 1 with the exception that the abort will function only if held after the                      RSS(P) series strobes
              receipt of the first alarm, but prior to the receipt of the second alarm. Abort activation at any other
              time is ignored.
P/N 06-236717-001                                        1-7                                              August 2007   August 2007                                              1-8                                        P/N 06-236717-001
                                                                                              General Information       General Information
              The MT and NS series network appliances provide the option to use silencable horns and non-               1-4.4.3.2     Trouble Relay
              silenceable strobes on the same NAC.
                                                                                                                                      The trouble relay is "normally energized with AC Power ON and will de-energize upon receipt of a
              Multiple NAC circuits (connected to audible devices only) programmed with the same master code                          trouble condition. This change is non-latching and the relay will revert to its normal state upon
              pattern are synchronized, regardless of any differing starting times that preceded their concurrent                     removal of the trouble state. For Central Station operation, especially with an intermittent AC power
              operation.                                                                                                              supply, it may be desirable to delay the change of state of the trouble relay in case of AC power failure.
                                                                                                                                      See Chapter 3, Configuration to enable this configuration.
              The control unit is designed for user selection of an intelligent synchronization feature. This feature
              allows the silenceable horn to be shut off while the strobe continues to flash in synchronized fashion.
                                                                                                                        1-4.4.4       Auxiliary Power Output
              Each NAC is rated 1.5A at 24 Vdc and is suitable for polarized 24 Vdc appliances only.
                                                                                                                                      The Fenwal 732 provides one auxiliary power output rated 1 Amp at 24 Vdc (Nominal) and is
              The maximum number of synchronized devices is 35.
                                                                                                                                      intended to be used with 4-wire devices such as Flame Detectors, Smoke Detectors, etc. All applicable
                                                                                                                                      compatible devices contained in this manual may be used. For FM Approved installations, use FM
1-4.4.2       AGENT RELEASE CIRCUITS (ARC)                                                                                            Approved Flame Detectors.
              The Fenwal 732 has two (2) dedicated, independently controlled Class B ARCs compatable with                             Note: Operation of the System Reset control switch will interrupt the Auxiliary Power Output for a
              devices listed in Appendix B.                                                                                                 period of time not exceeding five (5) seconds.
              The release circuit may be programmed for an ON time of 90 seconds for Control Heads and either
              10 minutes, 15 minutes or On-until-reset for Deluge/Pre-Action Solenoids. When programmed for
              initiators, the ARC remains ON for 200 milliseconds.
              The ARCs can be configured to activate on a variety of conditions based on inputs from manual
              release, detection circuits and supervisory circuits. Activation of the ARCs can be delayed from 0 to
              60 seconds (in 10 second increments) in automatic release mode. Manual Release can be delayed
              from 0 to 30 seconds (in 10 second increments).
              The ARCs are suitable to operate different release device types on both circuits. In other words, ARC1
              may activate solenoids and ARC2 may activate an initiator. See Chapter 2, Installation.
              ARCs are not inherently power-limited. For the circuits to be power-limited, the ARC should be field
              terminated with an in-line supervisory device P/N 06-220023-001. ARCs activating initiators cannot be
              made power-limited.
              The Fenwal 732 has three independently programmable relays and one dedicated Trouble relay. The
              relays are Form-C type with contacts rated 3A @ 30 Vdc (resistive).
              The three programmable relays are normally in the de-energized condition and will energize upon
              receipt of one of the following listed conditions. These relays will latch on change of state and shall
              remain latched until manually reset by the System Reset control switch.
                   1st Alarm: DET 1, DET 2, DET 3/WF, or Manual Release
              Note: DET 3/WF will only be active if its part of the activation condition.
                   1st Alarm: DET 1, DET 2, DET 3/WF, SUPV 1, or Manual Release
              Note: SUPV 1 will only be active if its part of the activation condition.
                   Agent Pre-Release Condition
                   Agent Release Condition
                   Manual Release Input
                   Waterflow Input
                   Abort Input
                   Supervisory Input
                   Any Alarm: DET 1, DET 2, DET 3/WF, or Manual Release
P/N 06-236717-001                                        1-9                                              August 2007   August 2007                                               1-10                                         P/N 06-236717-001
                                                                                                           Installation   Installation
              Check and ensure that the received shipment of the Fenwal 732 control unit consists of:                                   Take special care when installing the system and follow the guidelines given in the following
                                                                                                                                         paragraphs.
                                                                                                                                         Install electrical conduit and wiring in accordance with applicable National Electrical Code, NFPA
                                     Table 2-1. Fenwal 732 Control Unit Contents
                                                                                                                                         Standard and state and local building code requirements.
                                    Description                          Part Number            Quantity
                                                                                                                                         The incoming AC voltage must be stable and within the permissible voltage range. This is especially
           Blue Enclosure Assembly (with door) (UL/cUL), or              06-220133-001              1                                    important in new construction where incoming power may be high or unstable, and temporary
           Red Enclosure Assembly (with door) (MEA/NYC)                  06-220135-001                                                   connections may cause large inductive voltage spikes.
           Power Supply Unit                                             06-118394-001              1                                    Most supervised circuits use voltage or current sensing circuits that are sensitive to induced voltages
           Printed Circuit Board (PCB)                                   06-220113-001              1                                    on the sensor wiring.
              The Hardware Kit contains the following:                                                                                       The system should never be connected to a conduit or green wire circuit that is also used to
                                                                                                                                             power resistance heating, motors, fans, air-conditioning equipment or fluorescent lighting
                                                                                                                                             circuits. Leakage currents from these types of circuits into the ground return could damage
                                Table 2-2. Hardware Kit Contents (P/N 06-220147-001)                                                         sensitive system components.
                                               Description                               Quantity                                            A separate earth ground or cold water pipe with properly bypassed water meter should be
                                                                                                                                             used. All external devices such as horns or alarm bells should have their housings grounded.
               Ground Wire Assembly (Power Supply Unit Enclosure)                           1                                                All low-level signal cables should have foil shielding and a drain wire to be installed in their
               Power Supply Unit Wiring Harness                                             1                                                own grounded metallic conduit.
               Battery Harness (2 long jumpers, 1 in-line fuse holder)                      1                                                Ground only one end of the drain wire or shield, since a ground on both ends will provide a
                                                                                                                                             current path and thus subject the circuit to induced RF currents and noise. A minimum
               AC Safety Cover/Warning Label                                                1                                                alternative would be to use shielded #16 AWG twisted pair wire.
               3/4-inch Nylon Spacer                                                        1                             CAUTION Adequate lightning protection must be provided for the incoming power at the building entry.
               Nylon Pan Head Screw (8-32 x 1-1/4)                                          1                                                Arrestor circuitry and earth grounding should be in accordance with article 250 of the
                                                                                                                                             National Electric Code.
               Threaded Aluminum Standoff (8-32 x 2-3/8)                                    8
                                                                                                                                             There is no known protective device available that is capable of protecting equipment from
               INT Sems Screw (8-32 x 5/16)                                                 8                                                damage caused by a direct lightning hit due to the extremely high energy released (10 million
               Power Supply Unit Retention Screw (M3 x 5)                                   1                                                to 100 million volts at 10,000 to 30,000 or more amperes). However, line surges from indirect
                                                                                                                                             strikes and voltage spikes induced through power line load switching can be minimized by
               End of Line Resistor Assembly (5.1K)                                        10
                                                                                                                                             the addition of transient suppressors.
               1/4-inch x 1-1/4-inch 10A Time Delay Fuse Cooper Bussman MDA-10-R            1                                                Although the Fenwal 732 circuits have transient protection devices, additional protection is
                                                                                                                                             required in areas subject to above average lightning activity or induced voltage spikes and
2-1.2         Materials Required                                                                                                             fluctuations due to power line load switching.
              The materials listed below are not supplied with the system, but are required for installation.
                   No. 10 or 3/16-inch mounting hardware
P/N 06-236717-001                                            2-1                                            August 2007   August 2007                                                2-2                                       P/N 06-236717-001
                                                                                                       Installation    Installation
              For all subassemblies, strip 1/2-inch (13 mm) and leave straight for insertion beneath head of screw
                                                                                                                       2-3.1          Mounting the Enclosure Assembly, P/N 06-220133-001
              on one side only (do not loop conductor around screw). If using stranded conductor, twist and tin or
              use terminal lug.                                                                                                       The control unit is designed to be surface or semi-flush mounted. Use screws or bolts no smaller than
                                                                                                                                      No. 10 (3/16-inch or 5 mm) in diameter to secure the enclosure to wall studs or masonry walls. Never
2-2.4         Maximum Wiring Length                                                                                                   mount the enclosure to drywall or plaster walls without securing to studs.
              Table 2-3 lists wiring gauge recommendations, resistance, and maximum length.                                           Locate the middle of the enclosure approximately 66-inches (1676 mm) above the floor so the control
                                                                                                                                      unit display is positioned at a convenient height for the operator. Refer to Figure 2-1. Figure 2-2
              Refer to Appendix C for maximum allowable wire resistance for alarm signaling and initiating                            shows the control unit enclosure dimensions.
              circuits.
              Operating power for all initiating and indicating circuits is provided by the power supply. 4-wire
              24 Vdc smoke detectors and other listed, compatible external 24 Vdc loads may be powered from the                                                                                      66 in.
              power auxiliary output. DC load calculations must be performed to determine if the power supply is                                                                                  (1676 mm)
                                                                                                                                                                                                     MAX.
              capable of providing the total system current demand. The calculations will also determine the
              minimum standby battery capacity in accordance with applicable NFPA codes. Refer to Appendix A
              for Battery Capacity Calculations.
              Care should be taken in planning the enclosure location. The enclosure is intended only for indoor
              use in a location free from rain, condensation, excessive dust, moisture or other airborne                                                                       FLOOR
              contamination. The enclosure must not be exposed to ambient conditions outside those specified in
              Appendix C.                                                                                                                                    Figure 2-1. Installation Height Above Floor
P/N 06-236717-001                                        2-3                                             August 2007   August 2007                                               2-4                                        P/N 06-236717-001
                                                                                                                                                                  Installation    Installation
                                                                                  TOP VIEW
                 1/2 in.
                (13 mm)
                                                                                                                                                                                                                                                18-13/16 in.
          TYP 2 PLACES                                                                     1 in.                                                                                                                              WALL CUTOUT        (978 mm)                    19-1/8 in.
                                                                                         (25 mm)                                       2-1/2 in.
                                                                                                                                       (64 mm)                                                                                                                               (486 mm)
                                                        12-1/4 in.
                                                        (311 mm)
                    1 in.
                  (25 mm)                                                                                                                            2 in.
                                                                                                                                                   (57 mm)
                                                                                                                                                                                                                                 14-3/8 in.
                                                                                                                                                                                                                                 (365 mm)                            5 in.
                                                                                                                                                       5 in.
                                                                                                                                                    (127 mm)                                                                                                      (127 mm)
                                                                                                     18-13/16 in.
                             17 in.
                           (432 mm)
                                                                                                      (978 mm)
                                                                                                                                                                                                 2.   Position and plumb the back box in the opening made in Step 1. Ensure that the front edge of
                                                                                                                                                                                                      the back box is at least 3/4-inch (19 mm) from the surface of the wall. Secure the back box to the
                                                                                                                                                                    19 in.                            wall with appropriate mounting bolts (up to 1/4-20).
                                                                                                                                                                  (483 mm)
                                                                                                                                                                                                 3.   Attach wiring conduit to the enclosure through the enclosure knockouts, and pull the required
                                                                                                                                                                                                      number of wires through the conduit to the enclosure. Leave approximately 2 to 3 feet (600 to
                                                                                                                                                                                                      900 mm) of wire length in the enclosure for future internal connections.
P/N 06-236717-001                                                                       2-5                                                                         August 2007   August 2007                                                       2-6                                   P/N 06-236717-001
                                                                                                             Installation    Installation
                                      1-3/4 in.
                                      (44 mm)
                                        MIN.
                                                                                                                                                                                NEUTRAL
                                                  COVER                                                                                              TO PSU J2
                                                                                                                                                                                          + 24 V
                                                                                                                                                                                          - 24 V
                                                                                                                                                                                LINE
                                                                                                                                                                                GND
                                                                                                                                                 CONNECTOR ON
                                                                                                                                                          PCB
                                                                                                                                                                         WHT/BLK
                                                                                                                                                                          WHT
                                                                                                                                                                          BLK
                                                                                                                                                                          RED
GRN
OR
                                                                                                                                                                                NEUTRAL
                      Use a ground strap to prevent static discharge that could damage the power supply.                                            TO PSU J2
CAUTION
                                                                                                                                                                                GND
                                                                                                                                                                                LINE
                                                                                                                                                                                - V
                                                                                                                                                                                - V
                                                                                                                                                                                +V
                                                                                                                                                                                +V
                                                                                                                                                CONNECTOR ON
                                                                                                                                                         PCB
                                                                                                                                                                         WHT/BLK
1. Make sure the control unit location is dry and that the enclosure is free of construction dust and WHT
                                                                                                                                                                          BLK
                    metal shavings prior to installing the power supply.                                                                                                  RED
2. Remove the power supply unit from its shipping carton. GRN
              3.    The Fenwal 732 control unit is supplied with one of two equivalent power supplies. Compare the
                    terminal block wiring legend on the provided power supply with the diagrams in Figure 2-6 and                                                GROUND WIRE FROM INSTALLATION KIT
                    connect the wiring harness as shown.                                                                                                      CONNECT TO LOWER EARTH-GROUND STUD
                                                                                                                                                              ON LEFT-HAND SIDE OF ENCLOSURE
              4.    Connect the Power Supply Wiring Harness (P/N 06-220025-001) to the power supply unit. Next
                    connect the fork end of the green ground wire (P/N 06-129928-002) to the earth-ground terminal
                    of the power supply unit. Refer to Figure 2-6 and Figure 2-7 for wire harness and earth-ground
                    connections.                                                                                                                                      ATTENTION!
                                                                                                                                               THE CONTROL UNIT IS SUPPLIED WITH ONE OF TWO EQUIVALENT
                                                                                                                                              POWER SUPPLIES. COMPARE THE TERMINAL BLOCK WIRING LEGEND
                                                                                                                                                 ON THE PROVIDED POWER SUPPLY WITH THE DIAGRAMS AND
                                                                                                                                            CONNECT THE WIRING HARNESS AS SHOWN IN THE APPLICABLE DIAGRAM.
P/N 06-236717-001                                             2-7                                              August 2007   August 2007                                 2-8                                 P/N 06-236717-001
                                                                                                             Installation    Installation
                                         FASTENING TAB
                                         FOR SCREW
         230 V
 115 V
                                      RETENTION
                                         TABS
                                        TYP (2)
P/N 06-236717-001                                            2-9                                               August 2007   August 2007                                                2-10                                     P/N 06-236717-001
                                                                                                                                   Installation   Installation
                                                                                                                                                                                                                                    PROTECTIVE COVER
                                                                                                                                                                                                                                    FOR AC POWER INPUT
                                                                                                                                                                                      ENCLOSURE WALL
                                                                            TB7     TB6               TB5    TB4      TB3   TB2
                                                                     TB8
                                                                                                                             TB1
                                                                     TB9
TB10
TB11
                                                                     TB12
                                                                                                                                                       POWER CONNECTIONS
                                                                                                                                                       FROM AC SUPPLY
Figure 2-9. PCB-to-Cabinet Grounding Diagram Figure 2-10. Primary Power Connections
                                                                                                                                                                 4.   To install the Protective Cover for AC Power input, fold along scored lines as shown in
2-3.4        AC Input and Battery Backup Connections                                                                                                                  Figure 2-10.
                                                                                                                                                                 5.   Insert spacer and align thru holes and spacer with PCB standoff in lower left corner.
            The control unit uses AC power (by others) as the primary power source, together with a 24 Vdc                                                       6.   Attach to PCB with nylon screw.
            standby battery.
                     Use caution when connecting AC power to the control unit. High-voltage and AC-powered
                     circuits are present in the control unit. Be sure to take suitable precautions and to
WARNING              adequately ground the control unit to reduce the risk of electrical shock.
              AC power must be provided to the control unit using a 3-conductor 14 AWG cable. The AC power
              cable shall be run through a one-inch conduit from a dedicated, 15-ampere circuit breaker. The
              conduit must be attached to the left side of the enclosure through one of the upper left corner
              knockouts.
P/N 06-236717-001                                        2-11                                                                       August 2007   August 2007                                               2-12                                       P/N 06-236717-001
                                                                                                          Installation    Installation
TB12
                         12 V           12 V
                       BATTERY        BATTERY                                                                                                                       TB7         TB6                   TB5       TB4      TB3     TB2
                                                                                                                                   TROUBLE RELAY             TB8
                                                                                                                                                                                                                                  TB1            DETECTOR 1
                                                                                                                          PROGRAMMABLE RELAY 3               TB9
                                                                              BATT OUT
                                                                                                                                         BATT OUT            TB12
                         12 V           12 V
                       BATTERY        BATTERY
                                                                              ADDITIONAL BATTERY
                                                                              CABLES TYP (BY INSTALLER)
 BATTERY HARNESS (P/N 06-129925-002)
                                                                 NOTE:
                        12 V           12 V                                                                                                                         AC SUPPLY SELECT SWITCH (S6)
                                                                 LOCATE ALL BATTERIES IN A COMMON BATTERY                                                                                                                                        NAC 1
                      BATTERY        BATTERY                     CABINET, OR IN CLOSE-COUPLED BATTERY CABINETS
                                                                                                                                                                                                                                  TB19
                                      Figure 2-11. Backup Battery Connections                                                                 AC IN                           TB14       TB15        TB16             TB17                       NAC 2
                                                                                                                                                                                                                                  TB18
TB13
P/N 06-236717-001                                         2-13                                              August 2007   August 2007                                                    2-14                                            P/N 06-236717-001
                                                                                                      Installation   Installation
                                                           7        6           7           6
                                                       3                    3
                                                           1        2           1           2
                                                                                                                                                                      EOL RESISTOR
                                                                                                                                      1+ 2+ 2- 1-                         5.1K, 0.5 W
                                                                                                                                                                   P/N 06-129025-002
                                                                  EOL RESISTOR
                            1+ 2+ 2- 1-                               5.1K, 0.5 W
                                                                                                                                    TB1, TB2, TB3, TB4,
                                                               P/N 06-129025-002
                                                                                                                                    TB5, TB6, OR TB7
                                                                7       6               7       6
                                                            3                       3
                                                                1       2               1       2
                                                                                                                                         1+ 2+ 2- 1-
                               1+ 2+ 2- 1-
                                                                                                                                                                        EOL RESISTOR
                                                                                                                                                                        5.1K, 0.5 W
                                                           EOL RESISTOR                                                                 TB1, TB2, TB3, TB4,             P/N 06-129025-002
                              TB1, TB2, TB3                5.1K, 0.5 W                                                                  TB5, TB6, OR TB7
                                                           P/N 06-129025-002
                                                                                                                                            Figure 2-13D. Class A, Style D Wiring for Contact Devices
                          Figure 2-13 B. Class A, Style D Wiring for Smoke/Electronic Heat Detectors
                                                                                                                                            Figure 2-13. Initiating Device Circuit Wiring
P/N 06-236717-001                                       2-15                                           August 2007   August 2007                                2-16                                    P/N 06-236717-001
                                                                                                                       Installation   Installation
2-4.3 Notification Appliance Circuit Wiring (TB17, TB18, TB19) 2-4.4 Agent Releasing Circuit Wiring
TB14 OR TB15
                                                                                          +                    +
                                                                                          -                    -                                                                                                R1+ R2+ R1- R2-
                                                                                             EOL RESISTOR
                                                                                                 5.1K, 0.5 W
                                                                                          P/N 06-129025-002                                                                           RED                 BLK
                                                                                                                                                           SOLENOID
                    1+ 2+ 2- 1-
                                                                                                                                                                                                       P/N 06-220023-001
                                                                                                                                                                                                       IN-LINE RELEASING DEVICE - MUST
                                                                                                                                                                                                       BE INSTALLED CLOSE NIPPLED TO
                    TB17, TB18, TB19
                                                                                                                                                                                                       SOLENOID ENCLOSURES
Figure 2-14 A. Class B , Style Y Notification Appliance Circuit Figure 2-15A. Agent Release Circuit - Single Solenoid, Power-Limited
TB14 OR TB15
                                                                                              +                    +
                                                                                                                                                                                                                    R1+ R2+ R1- R2-
                                                                                              -                    -
                                                                                                                                                                SOLENOID
                                                 EOL RESISTOR
                        1+ 2+ 2- 1-              5.1K, 0.5 W
                                                 P/N 06-129025-002                                                                                                Figure 2-15B. Agent Release Circuit - Single Solenoid, Non-Power-Limited
LEGEND
P/N 06-236717-001                                                  2-17                                                 August 2007   August 2007                                               2-18                                     P/N 06-236717-001
                                                                                               Installation   Installation
                     SOLENOID
                                                                                                                                                                                         BLACK
                                                                                                                                                                                         N.C.
                                                                                                                                                                            WHITE
                                                  BLK            RED                                                                                                                     N.O.
Figure 2-15C. Agent Release Circuit Dual Solenoid, Power-Limited TB14 OR TB15
                                                                       TB14 OR TB15
                                                                                                                                                                                R1+ R2+ R1- R2-
                                                                                                                                  LIMITING RESISTOR
                                                                                                                             Note: 1. Polarities must be observed for solenoids P/N 890181 and 48650001.
                                                                                                                                   2. The inline releasing device P/N 06-220023-001 must be close nippled to Solenoid
                                                                                                                                       enclosures.
                                                                                                                                   3. The ARC is Non-Power-Limited when in-line device is not used.
                      Figure 2-15D. Agent Release Circuit  Dual Solenoid, Non-Power-Limited                                       4. Route Non-Powered-Limited wiring at least 1/4-inch away from all Power-Limited
                                                                                                                                      wiring. See Appendix F. Do not attach Power-Limited wiring to the same terminal block.
                                                                                                                                   5. When using initiators, different types of initiators must NOT be mixed on the same
                                                                                                                                      circuit. The limiting resistor is used to make the total circuit resistance equal to
                                                                                                                                      10 ohms 1 ohm. The limiting resistor must have a rating of 1 watt minimum.
                                                                                                                                   6. Control Head P/N 90-487100-001 when used with the control unit must include
                                                                                                                                      Solenoid P/N 83-100034-001 and Microswitch P/N 87-120039-001.
P/N 06-236717-001                                   2-19                                        August 2007   August 2007                                                2-20                                         P/N 06-236717-001
                                                                                                          Installation    Installation
2-5          INSTALLING THE BEZEL, P/N 06-220115-001                                                                                     Note: Switch guard is keyed and can only be installed one way.
              1.    Align bezel cutouts to the timer and control switches on the PCB.                                                    4.   Install locking nut on the abort switch.
              2.    Gently press the bezel onto PCB so snap-on clips click into the PCB fitted holes.                                    5.   Install abort switch from back of enclosure door. Attach push button switch guard and tighten.
                               MOUNTING SCREWS
                                                                                                                                                                                                            SWITCH
                                                                               DEAD-FRONT                                                                                                MANUAL             GUARD
                                                                               PANEL (SIDE VIEW)                                                                                         RELEASE
                                                                                                                                                                                         SWITCH                                    LOCKING
                                                                                                                                                          MANUAL RELEASE                                                           NUT
                                                                                                                                                                                                          INTERNAL
                                                                                                                                                                                                             TOOTH
                                                                                                                                                                                                       LOCKWASHER
                                                                               THIS SIDE AGAINST                                                                                         ABORT     AND LOCKING RING
                                                                               BEZEL ASSEMBLY                                                                                            SWITCH
                                                                                                                                                                                                                                   LOCKING
                                                                                                                                                               ABORT                                   PUSHBUTTON                  NUT
   DEAD-FRONT                                                                                                                                                                                              SWITCH
        PANEL                                                                                                                                                                                               GUARD
                                                                                                   TAB GOES OVER                                     Figure 2-17. Installation of Manual Release and Abort Switches
                                                                                                   ENCLOSURE BOTTOM
                                                                                                   LIP
                                                                                                                                         6.   Attach black wires from switch wire harness to the right side of the toggle switch as shown in
                                      Figure 2-16. Dead-Front Panel Installation                                                              Figure 2-18.
                                                                                                                                         7.   Route switch wire harness as shown in Figure 2-18.
                                                                                                                                         8.   Install cable clamps and 8-32 kep nuts to secure switch wire harness to enclosure door.
2-7          INSTALLING THE ENCLOSURE DOOR (STANDARD DOOR)
                                                                                                                                         9.   Run the black wires from the Manual Release switch to TB4 on the PCB. Refer to Figure 2-13
              1.    Slide the door to allow the doors hinge pins to align with the mating-hinge sockets in the back
                                                                                                                                              through Figure 2-15 for wiring configurations.
                    box.
                                                                                                                                         10. Run the white wires from the Abort switch to TB5 on the PCB. Refer to Figure 2-13 through
              2.    Connect the ground wire that connects the enclosure door to the back box.
                                                                                                                                             Figure 2-15 for wiring configurations.
P/N 06-236717-001                                          2-21                                             August 2007   August 2007                                               2-22                                     P/N 06-236717-001
                                                                                                        Installation   Installation
                                                                                    - WHITE WIRES
                                                                                      TO TB5
                                                                                    - BLACK WIRES
                                                                                      TO TB4
               BLACK WIRES
               FROM SWITCH
              WIRE HARNESS
                                                                                     CABLE CLAMP
                      MANUAL
                                                                                     AND 8-32 KEP NUT
                     RELEASE
                                                                                     (SUPPLIED)
                      SWITCH
                                                                                     (TYP 3 PLACES)
P/N 06-236717-001                                          2-23                                          August 2007   August 2007                    2-24                  P/N 06-236717-001
                                                                                                  Configuration       Configuration
                                                                                                                                    When at the "Err" display, press the Signal Silence control switch to display a random 3 digit code.
                                                                                                                                    Make a note of the code and call Technical Support. The control unit does not timeout (exit out of the
3-1          ENTERING SITE - SPECIFIC CONFIGURATION                                                                                 configuration mode) when the display reads "Err".
             The Kidde AEGIS is suitable for a wide variety of applications by means of configuring its inputs                     Note: Do not press any buttons while this 3 digit code is being displayed.
             and outputs. Inputs and outputs are configured via the operator interface. The following sections
                                                                                                                                    Technical Support will translate this 3 digit code to a new password that will work only on a control
             details on how to enter or change configuration settings.
                                                                                                                                    unit displaying the original random code for one time only. When given the Temporary Password (the
                                                                                                                                    3 digit code should still be displayed), press the Signal-Silence control switch. The display is now
                                              POSITION                                                                              exactly as it would be to enter a password:
                                                             1         2   3
Figure 3-1. Digital Display Enter the Temporary Password in the same manner as entering a regular Password.
                                                                                                                                    When the password has been accepted (and the first configuration item is being displayed "00x",
3-1.1        Entering the Password                                                                                                  where x is the left most digit of the Temporary Password), you should press the Signal Silence
                                                                                                                                    control switch in order to accept and save the current Password.
             To enter the configuration setting mode, you must enter the factory default password (186) via the
             operator interface. Ensure that no alarms or supervisories are present and perform the following.        3-2           CONFIGURATION SETTINGS
                                                                                                                                    This section describes the configuration settings for the Fenwal 732 unit. Use Table 3-1 to set the
                                                                                                                                    configuration settings.
      Step                                      Description                                         Display
                                                                                                                                       To advance to the next selection for an item, press the Output Disable control switch.
        1     Press and hold the Acknowledge control switch and within five (5) seconds, press
                                                                                                                                       To advance to the next item, press the Acknowledge control switch.
              the System Reset control switch.
                                                                                                                                       To accept a configuration setting change and exit the Configuration menu at any step in the
        2     Press Output Disable to advance (each press advances one digit).                                                          process, press the Signal Silence control switch. Check the configuration by starting the
                                                                                                                                        configuration process again, checking all items, and exiting by pressing System Reset after
                                                                                                                                        inspecting the last item.
        3     When correct, press the Acknowledge control switch. Position 1 is accepted and                                           To exit the configuration menu at any time, press the System Reset control switch. This reverts
              cursor moves to position 2.                                                                                               the control unit to its previous state.
        4     Press Output Disable to advance (each press advances one digit).                                                      Note: The control unit takes about five (5) seconds to boot up after exiting the configuration menu.
                                                                                                                                                                    POSITION
        5     When correct, press the Acknowledge control switch. Position 2 is accepted and
                                                                                                                                                                                   1         2   3
              cursor moves to position 3.
        7     When correct, press the Acknowledge control switch. Position 3 is accepted and if
              the password is is correct, the display shows 00 and the AEGIS enters the
              configuration mode.
P/N 06-236717-001                                                3-1                                   August 2007    August 2007                                                      3-2                                P/N 06-236717-001
                                                                                                       Configuration        Configuration
Configuration                                                                                                               Configuration
                                                                                                                Default                                                                                                               Default
   Number             Configuration Item                   Configuration (Position 3) Selection                                Number         Configuration Item                  Configuration (Position 3) Selection
                                                                                                                 Mode                                                                                                                  Mode
(Position 1, 2)                                                                                                             (Position 1, 2)
       01            2nd Password Character      09                                                               8               07            Input Circuit 3        1  Detector (DET 3)                                            1
       02            3rd Password Character      09                                                               6                                                    2  Waterflow with Non-Silenceable NACs (DET WF)
       03           Application Mode - Release   1  Release Circuit 1 not in use (see note 1)                     6                                                    3  Waterflow with Silenceable NACs (DET WF)
                             Circuit 1
                                                 2  Manual Release or Single Zone input from DET 1                                08         Programmable Relay 1      1  General alarm (DET 1, DET 2, DET 3/WF, or Manual            3
                                                                                                                                                                        Release)
                                                 3  Manual Release or Single Zone input from DET 2
                                                                                                                                                                        2  First Alarm (DET 1, DET 2, DET 3/WF, or Manual Release)
                                                 4  Manual Release or Single Zone input from any one of
                                                                                                                                                                        (see note 2)
                                                 DET 1 or DET 2
                                                                                                                                                                        3  First Alarm (DET 1, DET 2, DET 3/WF, Manual Release, or
                                                 5  Manual Release or Cross Zone input from DET 1 and
                                                                                                                                                                        SUPV 1) (see notes 2 & 3)
                                                 DET 2
                                                                                                                                                                        4  Agent Pre-Release Condition
                                                 6  Manual Release or Cross Zone input from any two of the
                                                 following: DET 1, DET 2 and DET 3/WF                                                                                   5  Agent Release Condition
                                                 7  Manual Release or Cross Zone input from any two of the                                                             6  Manual Release Input
                                                 following: DET 1, DET 2, and SUPV 1
                                                                                                                                                                        7  Waterflow Input
                                                 8  Manual Release or Cross Zone input from any two of the
                                                                                                                                                                        8  Abort Input
                                                 following: DET 1, DET 2, DET 3/WF, and SUPV 1 (except DET
                                                 3/WF and SUPV 1)                                                                                                       9  Supervisory Input
                                                 9  Manual Release or Cross Zone input from SUPV 1 and                             9         Programmable Relay 2      1  General alarm (DET 1, DET 2, DET 3/WF, or Manual            4
                                                 either DET 1 or DET2                                                                                                   Release)
       04           Application Mode - Release   1  Release Circuit 2 not in use (see note 1)                     6                                                    2  First Alarm (DET 1, DET 2, DET 3/WF, or Manual Release)
                             Circuit 2                                                                                                                                  (see note 2)
                                                 2  Manual Release or Single Zone input from DET 1
                                                                                                                                                                        3  First Alarm (DET 1, DET 2, DET 3/WF, Manual Release, or
                                                 3  Manual Release or Single Zone input from DET 2
                                                                                                                                                                        SUPV 1) (see notes 2 & 3)
                                                 4  Manual Release or Single Zone input from any one of
                                                                                                                                                                        4  Agent Pre-Release Condition
                                                 DET 1 or DET 2
                                                                                                                                                                        5  Agent Release Condition
                                                 5  Manual Release or Cross Zone input from DET 1 and
                                                 DET 2                                                                                                                  6  Manual Release Input
                                                 6  Manual Release or Cross Zone input from any two of the                                                             7  Waterflow Input
                                                 following: DET 1, DET 2, and DET 3/WF
                                                                                                                                                                        8  Abort Input
                                                 7  Manual Release or Cross Zone input from any two of the
                                                 following: DET 1, DET 2, and SUPV 1                                                                                    9  Supervisory Input
                                                 8  Manual Release or Cross Zone input from any two of the                        10         Programmable Relay 3      1  General alarm (DET 1, DET 2, DET 3/WF, or Manual            5
                                                 following: DET 1, DET 2, DET 3/WF, and SUPV 1 (except DET                                                              Release)
                                                 3/WF and SUPV 1)                                                                                                       2  First Alarm (DET 1, DET 2, DET 3/WF, or Manual Release)
                                                 9  Manual Release or Cross Zone input from SUPV 1 and                                                                 (see note 2)
                                                 either DET 1 or DET2                                                                                                   3  First Alarm (DET 1, DET 2, DET 3/WF, Manual Release, or
       05             Abort Both or Release      1  Activation aborts ARC 1 and ARC 2                             1                                                    SUPV 1) (see notes 2 & 3)
                            Circuit 1                                                                                                                                   4  Agent Pre-Release Condition
                                                 2  Activation aborts ARC 1 only
       06                     Abort              1  Mode 1 (UL)                                                   1                                                    5  Agent Release Condition
P/N 06-236717-001                                           3-3                                               August 2007   August 2007                                           3-4                                       P/N 06-236717-001
                                                                                                     Configuration     Configuration
Configuration                                                                                                          Configuration
                                                                                                           Default                                                                                                                     Default
   Number              Configuration Item                     Configuration (Position 3) Selection                        Number           Configuration Item                     Configuration (Position 3) Selection
                                                                                                            Mode                                                                                                                        Mode
(Position 1, 2)                                                                                                        (Position 1, 2)
       11                  Trouble Relay           1  AC Failure response - Instantaneous                    4               17          Power Limited - Release      1  Power-Limited (one solenoid)                                   3
                                                   2  AC Failure response - Delayed 1 minute                                              Circuit 1 (see note 4)      2  Power-Limited (two solenoids)
                                                   3  AC Failure response - Delayed 60 minutes                                                                        3  Non-Power-Limited (one solenoid)
                                                   4  AC Failure response - Delayed 90 minutes                                                                        4  Non-Power-Limited (two solenoids)
                                                   5  AC Failure response - Delayed 120 minutes                                                                       5  Initiators
                                                   6  AC Failure response - Delayed 180 minutes                              18         On-Time - Release Circuit 2   1  Agent Control Head 90 seconds                                  1
                                                                                                                                               (see note 4)
       12             Manual Release Station       1  Instantaneous (select for NYC)                         1                                                        2  Deluge Solenoid 10 minutes
                    Time Delay - Release Circuit
                                                   2  10 seconds                                                                                                      3  Deluge Solenoid 15 minutes
                                 1
                                                   3  20 seconds                                                                                                      4  Deluge Solenoid On Until Reset
                                                   4  30 seconds                                                                                                      5  Initiators
       13             Manual Release Station       1  Instantaneous (select for NYC)                         1               19          Power Limited - Release      1  Power-Limited (one solenoid)                                   3
                    Time Delay - Release Circuit                                                                                           Circuit 2 (see note 4)
                                                   2  10 seconds                                                                                                      2  Power-Limited (two solenoids)
                                 2
                                                   3  20 seconds                                                                                                      3  Non-Power-Limited (one solenoid)
                                                   4  30 seconds                                                                                                      4  Non-Power-Limited (two solenoids)
       14             Automatic Time Delay -       1  0 seconds                                              7                                                        5  Initiators
                         Release Circuit 1
                                                   2  10 seconds                                                             20              Trouble Latching         1  Troubles are non-latching                                      1
                                                   3  20 seconds                                                                                                      2  Troubles are latching (required for cUL)
                                                   4  30 seconds (select for NYC)                                            21                Latching for           1  SUPV 1 is non-latching                                         1
                                                                                                                                               Supervisory 1
                                                   5  40 seconds                                                                                                      2  SUPV 1 is latching (forced if part of Cross-Zone)
                                                   6  50 seconds                                                             22                Latching for           1  SUPV 2 is non-latching                                         1
                                                                                                                                               Supervisory 2
                                                   7  60 seconds                                                                                                      2  SUPV 2 is latching
       15             Automatic Time Delay -       1  0 seconds                                              7               23         Outputs Disabled by Isolate   1  Disables ARCs                                                  4
                         Release Circuit 2                                                                                                        Button
                                                   2  10 seconds                                                                                                      2  Disables ARCs and NACs
                                                   3  20 seconds                                                                                                      3  Disables ARCs and Programmable Relays
                                                   4  30 seconds (select for NYC)                                                                                     4  Disables ARCs, NACs, and Programmable Relays
                                                   5  40 seconds                                                             24         NAC 1 relationship to ARCs    1  ARC 1 only                                                     1
                                                   6  50 seconds                                                                                                      2  ARC 2 only
                                                   7  60 seconds                                                                                                      3  Both ARC 1 and ARC 2 (see note 5)
       16           On-Time - Release Circuit 1    1  Agent Control Head 90 seconds                          1                                                        4  Neither ARC 1 nor ARC 2 (see note 6)
                          (see note 4)
                                                   2  Deluge Solenoid 10 minutes                                                                                      5  NAC 1 Not Used (see note 1)
                                                   3  Deluge Solenoid 15 minutes                                             25         NAC 2 relationship to ARCs    1  ARC 1 only                                                     2
                                                   4  Deluge Solenoid On Until Reset                                                                                  2  ARC 2 only
                                                   5  Initiators                                                                                                      3  Both ARC 1 and ARC 2 (see note 5)
                                                                                                                                                                       4  Neither ARC 1 nor ARC 2 (see note 6)
                                                                                                                                                                       5  NAC 2 Not Used (see note 1)
P/N 06-236717-001                                             3-5                                        August 2007   August 2007                                                3-6                                          P/N 06-236717-001
                                                                                                            Configuration      Configuration
Configuration                                                                                                                  Configuration
                                                                                                                   Default                                                                                                                    Default
   Number             Configuration Item                   Configuration (Position 3) Selection                                   Number         Configuration Item                  Configuration (Position 3) Selection
                                                                                                                    Mode                                                                                                                       Mode
(Position 1, 2)                                                                                                                (Position 1, 2)
       26           NAC 3 relationship to ARCs   1  ARC 3 only                                                       3               29           NAC 1 Releasing         0  60 bpm Non-Silenceable                                            5
                                                                                                                                                    (see note 10)
                                                 2  ARC 3 only                                                                                                            1  60 bpm Silenceable
                                                 3  Both ARC 1 and ARC 2 (see note 5)                                                                                     2  120 bpm Non-Silenceable
                                                 4  Neither ARC 1 nor ARC 2 (see note 6)                                                                                  3  120 bpm Silenceable
                                                 5  NAC 3 Not Used (see note 1)                                                                                           4  Steady Non-Silenceable
       27               NAC 1 First Alarm        0  60 bpm Non-Silenceable                                           1                                                    5  Steady Silenceable
                          (see note 8)
                                                 1  60 bpm Silenceable                                                                                                    6  Temporal Non-Silenceable
                                                 2  120 bpm Non-Silenceable                                                                                               7  Temporal Silenceable
                                                 3  120 bpm Silenceable                                                                                                   8  Intelligent Synchronization - Non-Silenceable
                                                 4  Steady Non-Silenceable                                                                                                9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                                 5  Steady Silenceable                                                                                                    A  Intelligent Synchronization - Silenceable (Horn Off)
                                                 6  Temporal Non-Silenceable                                                                                              C  NAC 1 Off (see note 7)
                                                 8  Temporal Silenceable                                                             30          NAC 2 First Alarm        0  60 bpm Non-Silenceable                                            1
                                                                                                                                                    (see note 8)
                                                 8  Intelligent Synchronization - Non-Silenceable                                                                         1  60 bpm Silenceable
                                                 9  Intelligent Synchronization - Silenceable (Horn & Strobe)                                                             2  120 bpm Non-Silenceable
                                                 A  Intelligent Synchronization - Silenceable (Horn Only Off)                                                             3  120 bpm Silenceable
                                                 C  NAC 1 Off (see note 7)                                                                                                4  Steady Non-Silenceable
       28               NAC 1 Pre-Release        0  60 bpm Non-Silenceable                                           3                                                    5  Steady Silenceable
                          (see note 9)
                                                 1  60 bpm Silenceable                                                                                                    6  Temporal Non-Silenceable
                                                 2  120 bpm Non-Silenceable                                                                                               8  Temporal Silenceable
                                                 3  120 bpm Silenceable                                                                                                   8  Intelligent Synchronization - Non-Silenceable
                                                 4  Steady Non-Silenceable                                                                                                9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                                 5  Steady Silenceable                                                                                                    A  Intelligent Synchronization - Silenceable (Horn Only Off)
                                                 6  Temporal Non-Silenceable                                                                                              C  NAC 2 Off (see note 7)
                                                 7  Temporal Silenceable                                                             31          NAC 2 Pre-Release        0  60 bpm Non-Silenceable                                            3
                                                                                                                                                    (see note 9)
                                                 8  Intelligent Synchronization - Non-Silenceable                                                                         1  60 bpm Silenceable
                                                 9  Intelligent Synchronization - Silenceable (Horn & Strobe)                                                             2  120 bpm Non-Silenceable
                                                 A  Intelligent Synchronization - Silenceable (Horn Off)                                                                  3  120 bpm Silenceable
                                                 C  NAC 1 Off (see note 7)                                                                                                4  Steady Non-Silenceable
                                                                                                                                                                           5  Steady Silenceable
                                                                                                                                                                           6  Temporal Non-Silenceable
                                                                                                                                                                           7  Temporal Silenceable
                                                                                                                                                                           8  Intelligent Synchronization - Non-Silenceable
                                                                                                                                                                           9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                                                                                                                                                           A  Intelligent Synchronization - Silenceable (Horn Off)
                                                                                                                                                                           C  NAC 2 Off (see note 7)
P/N 06-236717-001                                           3-7                                                  August 2007   August 2007                                            3-8                                             P/N 06-236717-001
                                                                                                         Configuration      Configuration
Configuration                                                                                                               Configuration
                                                                                                                Default                                                                                                                   Default
   Number           Configuration Item                  Configuration (Position 3) Selection                                   Number         Configuration Item                 Configuration (Position 3) Selection
                                                                                                                 Mode                                                                                                                      Mode
(Position 1, 2)                                                                                                             (Position 1, 2)
       32             NAC 2 Releasing         0  60 bpm Non-Silenceable                                           5               35           NAC 3 Releasing        0  60 bpm Non-Silenceable                                            5
                       (see note 10)                                                                                                             (see note 10)
                                              1  60 bpm Silenceable                                                                                                   1  60 bpm Silenceable
                                              2  120 bpm Non-Silenceable                                                                                              2  120 bpm Non-Silenceable
                                              3  120 bpm Silenceable                                                                                                  3  120 bpm Silenceable
                                              4  Steady Non-Silenceable                                                                                               4  Steady Non-Silenceable
                                              5  Steady Silenceable                                                                                                   5  Steady Silenceable
                                              6  Temporal Non-Silenceable                                                                                             6  Temporal Non-Silenceable
                                              7  Temporal Silenceable                                                                                                 7  Temporal Silenceable
                                              8  Intelligent Synchronization - Non-Silenceable                                                                        8  Intelligent Synchronization - Non-Silenceable
                                              9  Intelligent Synchronization - Silenceable (Horn & Strobe)                                                            9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                              A  Intelligent Synchronization - Silenceable (Horn Off)                                                                 A  Intelligent Synchronization - Silenceable (Horn Off)
                                              C  NAC 2 Off (see note 7)                                                                                               C  NAC 3 Off (see note 7)
       33            NAC 3 First Alarm        0  60 bpm Non-Silenceable                                           1               36            NACs Used for         1  NAC #1                                                            8
                       (see note 8)                                                                                                              General Alarm
                                              1  60 bpm Silenceable                                                                                                   2  NAC #2
                                              2  120 bpm Non-Silenceable                                                                                              3  NAC #1 & NAC #2
                                              3  120 bpm Silenceable                                                                                                  4  NAC #3
                                              4  Steady Non-Silenceable                                                                                               5  NAC #1 and NAC #3
                                              5  Steady Silenceable                                                                                                   6  NAC #2 & NAC #3
                                              6  Temporal Non-Silenceable                                                                                             7  NAC #1 & NAC #2 & NAC #3
                                              8  Temporal Silenceable                                                                                                 8  None (No General Alarm)
                                              8  Intelligent Synchronization - Non-Silenceable                                    37         NAC #1 General Alarm     0  60 bpm Non-Silenceable                                            7
                                              9  Intelligent Synchronization - Silenceable (Horn & Strobe)                                                            1  60 bpm Silenceable
                                              A  Intelligent Synchronization - Silenceable (Horn Only Off)                                                            2  120 bpm Non-Silenceable
                                              C  NAC 3 Off (see note 7)                                                                                               3  120 bpm Silenceable
       34            NAC 3 Pre-Release        0  60 bpm Non-Silenceable                                           3                                                   4  Steady Non-Silenceable
                       (see note 9)
                                              1  60 bpm Silenceable                                                                                                   5  Steady Silenceable
                                              2  120 bpm Non-Silenceable                                                                                              6  Temporal Non-Silenceable
                                              3  120 bpm Silenceable                                                                                                  7  Temporal Silenceable
                                              4  Steady Non-Silenceable                                                                                               8  Intelligent Synchronization - Non-Silenceable
                                              5  Steady Silenceable                                                                                                   9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                              6  Temporal Non-Silenceable                                                                                             A  Intelligent Synchronization - Silenceable (Horn Off)
                                              7  Temporal Silenceable                                                                                                 C  NAC 3 Off (see note 7)
                                              8  Intelligent Synchronization - Non-Silenceable
                                              9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                              A  Intelligent Synchronization - Silenceable (Horn Off)
                                              C  NAC 3 Off (see note 7)
P/N 06-236717-001                                        3-9                                                  August 2007   August 2007                                          3-10                                             P/N 06-236717-001
                                                                                                         Configuration      Configuration
                                         Table 3-1. Configuration Settings                                                        9.      In addition to being selectable for NACx Pre-Release, the various tones are also selectable in the
                                                                                                                                          condition that both ARCs are not used and two of DET 1, DET 2 or DET 3/WF are in alarm.
Configuration
                                                                                                                Default           10. In addition to being selectable for NACx Releasing, the various tones are also selectable in the condition
   Number            Configuration Item                 Configuration (Position 3) Selection
                                                                                                                 Mode                 that both ARCs are not used and all of DET 1, DET 2 and DET 3/WF are in alarm.
(Position 1, 2)
       38           NAC #2 General Alarm      0  60 bpm Non-Silenceable                                           7
                                              1  60 bpm Silenceable
                                              2  120 bpm Non-Silenceable
                                              3  120 bpm Silenceable
                                              4  Steady Non-Silenceable
                                              5  Steady Silenceable
                                              6  Temporal Non-Silenceable
                                              7  Temporal Silenceable
                                              8  Intelligent Synchronization - Non-Silenceable
                                              9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                              A  Intelligent Synchronization - Silenceable (Horn Off)
                                              C  NAC 3 Off (see note 7)
       39           NAC #3 General Alarm      0  60 bpm Non-Silenceable                                           7
                                              1  60 bpm Silenceable
                                              2  120 bpm Non-Silenceable
                                              3  120 bpm Silenceable
                                              4  Steady Non-Silenceable
                                              5  Steady Silenceable
                                              6  Temporal Non-Silenceable
                                              7  Temporal Silenceable
                                              8  Intelligent Synchronization - Non-Silenceable
                                              9  Intelligent Synchronization - Silenceable (Horn & Strobe)
                                              A  Intelligent Synchronization - Silenceable (Horn Off)
                                              C  NAC 3 Off (see note 7)
   NOTES:
      1.    If "circuit not used" is selected, do NOT install an EOL as the control unit needs to see open circuit.
            Using an EOL will cause trouble.
      2.    DET 1, DET 2, and DET 3/WF will activate first alarm ONLY IF it is part of the ARC activation
            condition.
      3.    SUPV 1 will activate first alarm ONLY IF it is part of the ARC activation condition.
      4.    If Initiator is selected for any Release circuit output, the respective Power-Limited switch setting is
            ignored.
      5.    The NAC will be driven by both ARC 1 and ARC 2. However the first ARC to reach each state is given
            precedence. Once its cycle is complete, the other ARC, if active, will gain control.
      6.    The NAC may be related to neither ARC if the control unit is used for non-suppression applications.
            Also see notes 8 to 10.
      7.    An OFF condition is different from NOT USED and will require that an EOL be installed.
      8.    In addition to being selectable for NACx First Alarm, the various tones are also selectable in the
            condition that both ARCs are not used and one of DET 1, DET 2 or DET 3/WF is in alarm.
P/N 06-236717-001                                       3-11                                                  August 2007   August 2007                                            3-12                                       P/N 06-236717-001
                                                                                                          Operation      Operation
              This chapter explains how to read the control unit display, interpret the LEDs, and how to reset the       4-1.4         Trouble Signal State
              unit. The following are the operational modes of the control unit:                                                       In the trouble state, the control unit has detected one or more active troubles such as AC failure, open
                      Normal Mode                                                                                                     circuits, short circuits, ground faults, activation of abort during non-alarm condition, and so on. In
                      Alarm Signal                                                                                                    the trouble mode, the Trouble LED and circuit-specific LED will flash, the internal buzzer will sound,
                                                                                                                                       and the trouble relay will de-energize.
                      Supervisory Signal
                      Trouble Signal State                                                                                            With the exception of microprocessor or PCB troubles, all other troubles may be acknowledged either
                                                                                                                                       automatically (i.e., the trouble event reverts to normal condition) or manually by the operator by
                                                                                                                                       pressing the Acknowledge or System Reset control switches.
4-1.1         Normal Mode
              In the normal mode, the control unit continuously monitors all inputs and outputs for any change of        4-2           CONTROL SWITCH FUNCTIONALITY
              state. In the normal mode the Green AC ON LED is the only illuminated LED. The buzzer and NACs
              are silent, The Programmable Relays are de-energized, and the Trouble relay is energized.                                Illegal button presses, or illegal combinations of button presses, shall result in a momentary display
                                                                                                                                       of "Err".
4-1.2         Alarm Signal State
                                                                                                                         4-2.1         Acknowledge
              In the Alarm state, the control unit has detected one or more active inputs on its input circuits. The
              states of Alarm are:                                                                                                     Pressing the Acknowledge control switch during an active trouble, supervisory, or alarm allows the
              1.       First Alarm  caused when input is received from:                                                               operator to signal the AEGIS that a new event currently being displayed is understood. The AEGIS
                                                                                                                                       control units buzzer will silence and all flashing Alarm, Trouble, or Supervisory LEDs will light
                       DET 1, or                                                                                                      steady.
                       DET 2, or
                       DET 3D
                                                                                                                                                                       Table 4-1. Acknowledge
                       DET 3WF
                       SUPV 1 (if part of ARC activation)                                                                          Event             Circuit Specific LED        System Event LED                      Buzzer
                       Manual Release                                                                                              Alarm                    Steady                     Steady                            Off
              2.       Pre-Release  caused when input is received from:                                                           Trouble                   Steady                     Steady                            Off
                       DET 1 in Single-Zone release mode, or                                                                    Supervisory                 Steady                     Steady                            Off
                       DET 2 in Single-Zone release mode, or
                                                                                                                                 Event Clear                   Off                       Off                              Off
                       DET 1 and DET 2 in Cross-Zone Mode, or
                                                                                                                               Event Recurrence               Flash                     Flash                     On Steady - Alarm
                       DET 1 and DET 3 (Waterflow) in Cross-Zone mode, or                                                                                                                                  On Pulsed - Trouble/Supervisory
                       DET 2 and DET 3 (Waterflow) in Cross-Zone mode, or
                       DET 1 and Supv 1 in Cross-Zone mode, or                                                          4-2.2         Signal Silence
                       DET 2 and Supv 1 in Cross-Zone mode, or
                                                                                                                                       Pressing the Signal Silence control switch at any alarm state will turn on the Signal Silenced LED and
                       Manual Release
                                                                                                                                       silence all NACs unless configured otherwise (non-silenceable).
              3.       Releasing  caused when the pre-release countdown timer has counted down to zero. In this
                       state, the control unit is actively in the process of activating its Agent Release Circuit(s).
                                                                                                                         4-2.3         System Reset
              4.       Post-Release  condition when the control unit has released Agent.
                                                                                                                                       Resets the system including turning off outputs and interrupting power to all input and output
                                                                                                                                       circuits for a period of five (5) seconds.
P/N 06-236717-001                                            4-1                                           August 2007   August 2007                                              4-2                                           P/N 06-236717-001
                                                                                                      Operation     Operation
              When the control switch is engaged, it creates a System Supervisory condition. Pressing the control
              switch momentarily toggles in and out of the disable mode.
P/N 06-236717-001                                      4-3                                            August 2007   August 2007   4-4   P/N 06-236717-001
                                                                                        Testing and Maintenance       Testing and Maintenance
                                                                                                                      5-3           TESTING
                                    CHAPTER 5
                             TESTING AND MAINTENANCE                                                                  5-3.1         Battery Status Check
                                                                                                                                    1.   Disconnect AC power.
                                                                                                                                    2.   Allow control unit to operate on the batteries for about one hour.
5-1           MAINTENANCE REQUIREMENTS                                                                                              3.   Measure the individual battery voltages. If any battery reads 1.5 V or more below its rated voltage,
                                                                                                                                         that battery should be replaced.
              The Fenwal 732 must be inspected, tested and maintained in accordance with the requirements of
              NFPA 72 (latest edition), and/or the local Authority Having Jurisdiction (AHJ).                                       Generally, if one of the batteries is low, the other(s) will soon fail. It is advisable to replace all the
                                                                                                                                    batteries in a set when one requires replacement. Any battery that has been in service for 36 months
                                                                                                                                    or more must be replaced.
                     Two different sources of power can be connected to the control unit. Disconnect both
                     sources of power and critical components such as special extinguishing systems and
                                                                                                                      5-3.2         Battery Test
                     relays controlling facility-power shutoff before servicing the control unit. The control unit
WARNING              and associated equipment may be damaged by connecting or disconnecting wiring while                            The following sequence will display the battery open circuit voltage and charge current:
                     the control unit is energized.
                                                                                                                                    1.   Press and hold Acknowledge and Signal Silence control switches simultaneously for five (5)
                                                                                                                                         seconds. As long as both keys are pressed, the battery voltage is displayed for three (3) seconds,
              For inspection, testing and maintenance of the associated extinguishing system, refer to the                               and then the battery current. These alternate every three (3) seconds.
              manufacturers instructions and the standards and codes that apply to that systems.                                    2.   The battery test will exit if either control switch is released, or if a control unit status change
                                                                                                                                         occurs.
              Prior to any testing or maintenance on the Fenwal 732, perform the following:
              1.    Disable ARCs and NACs via the Output Disable control switch.                                      5-3.2.1       BATTERY VOLTAGE DISPLAY
              2.    Physically disconnect the wiring to initiator assemblies (if used) from the release-circuit
                    terminals, short the leads together, and wrap the leads in insulating tape                                      Battery voltage will be as shown in Figure 5-1. The units are in Volts.
              3.    Physically disconnect all control heads (if used) from their associated agent-storage-container
                    discharge valves
              4.    Physically disconnect the wiring to solenoid valves (if used) for pre-action/deluge sprinkler
                    systems
                                                                                                                                                               Figure 5-1. Battery Voltage Display
              5.    Ensure that emergency operations controlled by this system such as facility power shutoff are
                    bypassed
              6.    Notify personnel in the facility and at off-premises monitoring locations that you are
                    working on the system and that you will inform them when system servicing has ended.              5-3.2.2       BATTERY CHARGE CURRENT DISPLAY
5-2 TESTING FREQUENCY Battery charge current will be as shown in Figure 5-2. The units are in Amps.
            The testing frequency shall be per NFPA 72 (latest edition) or the following (whichever is more
            stringent).
                               Lamp test                             Semi-annual                                                    Before replacing batteries, disconnect AC power. Batteries should be replaced at least once every 36
                               System test                           Semi-annual                                                    months, or as directed by the local Authority Having Jurisdiction. Do not install a battery set whose
                                                                                                                                    open circuit voltage is less than 22 volts.
P/N 06-236717-001                                         5-1                                           August 2007   August 2007                                               5-2                                          P/N 06-236717-001
                                                                                           Testing and Maintenance        Testing and Maintenance
Refer to instructions with the Firmware Upgrade Kit when upgrading the control unit.
P/N 06-236717-001                                          5-3                                              August 2007   August 2007                               5-4                   P/N 06-236717-001
                                                                                                              Troubleshooting       Troubleshooting
                                                                                                                                       006        Low Battery                          Check battery voltage, must be greater than 20.5 Vdc in the absence of
                                          TROUBLESHOOTING                                                                                                                              primary power. When voltage drops as low as 19.5 Vdc, the charger will
                                                                                                                                                                                       disconnect and the outputs will be isolated.
                                                                                                                                       007        Reversed Battery                     Verify Battery polarity.
6-1             PURPOSE                                                                                                                008        Detector #1 Open Circuit             Look for discontinuity in detector #1 wiring.
                This chapter provides diagnostic information, probable causes, and the method(s) to return the                                                                         Check for missing/incorrect value 5.1K resistor.
                Fenwal 732 to proper operating conditions.                                                                            009        Detector #2 Open Circuit             Look for discontinuity in Detector #2 wiring.
                                                                                                                                                                                       Check for missing/incorrect value 5.1K resistor.
                Prior to taking corrective action or performing any maintenance functions, you must refer to
                Paragraph 5-1 and follow the instructions specified there.                                                             010        Detector #3/Waterflow Open Circuit   Look for discontinuity in Detector #3/Waterflow wiring.
                                                                                                                                                                                       Check for missing/incorrect value 5.1K resistor.
6-2             TROUBLE DIAGNOSTICS
                                                                                                                                       011        Manual Release Open Circuit          Look for discontinuity in manual release circuit wiring.
                Diagnostics allow the operator to determine the cause of trouble. To access the diagnostic function,                                                                   Check for missing/incorrect value 5.1K resistor.
                the control unit needs to have at least one active trouble condition. Perform the following:                           012        Supervisory #1 Open Circuit          Look for discontinuity in Supervisory #1 wiring.
                                                                                                                                                                                       Check for missing/incorrect value 5.1K resistor.
  Step                            Description                                             Display Examples                             013        Supervisory #2 Open Circuit          Look for discontinuity in Supervisory #2 wiring.
                                                                                                                                                                                       Check for missing/incorrect value 5.1K resistor.
      1     Press and hold the Signal Silence control switch for
            five (5) seconds. A 3-digit Trouble code will be displayed                                                                 014        Invalid Abort                        Abort station activated in non-alarm condition.
            until the Signal Silence control switch is released
                                                                                                                                       015        Abort Open Circuit                   Look for discontinuity in circuit wiring.
            (sample on right).
                                                                                                                                       016        ARC #1 Short Circuit                 Troubleshoot ARC #1 wiring by breaking-up circuit to isolate the short.
      2     If multiple troubles exist, the display will blink one
            second on, one second off, and the trouble codes will                                                                      017        ARC #1 Open Circuit                  Look for discontinuity in ARC #1 wiring.
            sequence to the next code every time the display
                                                                                                                                                                                       Check ARC #1 configuration.
            illuminates. When all codes have been displayed, the
            sequence will repeat until the Signal Silence control                                                                      018        ARC #2 Short Circuit                 Troubleshoot ARC #2 wiring by breaking-up circuit to isolate the short.
            switch is released (sample on right).
                                                                                                                                       019        ARC #2 Open Circuit                  Look for discontinuity in ARC #2 wiring.
                                                                                                                                                                                       Check ARC #2 configuration.
                                                                                                                                       020        NAC #1 Short Circuit                 Troubleshoot NAC #1 wiring by breaking-up circuit to isolate the short.
6-3             TROUBLE CODES AND CORRECTIVE ACTION
                                                                                                                                       021        NAC #1 Open Circuit                  Look for discontinuity in NAC #1 wiring.
                                                                                                                                                                                       Check for missing/incorrect value 5.1K resistor.
   Code                      Trouble                                              Corrective Action                                    022        NAC #2 Short Circuit                 Troubleshoot NAC #1 wiring by breaking-up circuit to isolate the short.
                                                                                                                                       023        NAC #2 Open Circuit                  Look for discontinuity in NAC #1 wiring.
      000     Microprocessor or PCB                   Replace the PCB.
                                                                                                                                                                                       Check for missing/incorrect value 5.1K resistor.
      001     Ground                                  Check for connections to earth ground on field wiring whose removal
                                                      restores proper earth-ground offset voltage of 6.60 Vdc nominal.                 024        NAC #3 Short Circuit                 Troubleshoot NAC #1 wiring by breaking-up circuit to isolate the short.
      002     AC Voltage below 85%                    Check incoming AC power.                                                         025        NAC #3 Open Circuit                  Look for discontinuity in NAC #1 wiring.
      003     Primary PSU Output Voltage              Check power supply connector, from the power supply to main PCB (PSU                                                             Check for missing/incorrect value 5.1K resistor.
                                                      J2).
                                                                                                                                       026        ARC #1 Not Open Circuit              Check configuration to make sure ARC #1 is enabled.
                                                      Replace the power supply assembly.
                                                                                                                                       027        ARC #2 Not Open Circuit              Check configuration to make sure ARC #2 is enabled.
      004     No Secondary Power Connected            Verify battery connections to PCB (TB12). In the presence of primary
                                                                                                                                       028        Serial Cable Connected               Remove serial cable.
                                                      power, no chargeable batteries can be detected. Either they are too
                                                      discharged (<17V), or not connected at all. In either case there will be no
                                                      battery charging.
      005     Battery Charger Fault                   Measure Power Supply voltage (27.6 Vdc) (PSU J2). If correct, replace
                                                      PCB. If not correct, replace power supply.
P/N 06-236717-001                                                6-1                                                  August 2007   August 2007                                                  6-2                                              P/N 06-236717-001
                                                                           Parts List    Parts List
                                                CHAPTER 7
                                                PARTS LIST
P/N 06-236717-001                                   7-1                    August 2007   August 2007                   7-2                   P/N 06-236717-001
                                                                                            Battery Capacity Calculations          Battery Capacity Calculations
 Local or Central Station (Protected Premises) Fire Alarm Systems per NFPA 72                  24 hours         5 minutes
 Clean Agent Suppression Systems per NFPA 12, 12A, 12B, and 2001                               24 hours         5 minutes
                                                                                                                                                                           Table A-3. Standby and Alarm Calculation Guide
 Deluge or Pre-Action Water Spray Systems per Factory Mutual                                   90 hours        10 minutes                                                                       Standby Power (mA)                   Alarm Power (mA)
                                                                                                                                     Number                   Component
                                                                                                                                                                                          Qty            Each      Total       Qty         Each        Total
A-2             POWER CONSUMPTION DATA
                                                                                                                                             1     Fenwal 732 Control Unit                 1            100.00    100.00        1         240.00      240.00
                Table A-2 lists the power consumption of the various system components.                                                      2                                                          1000.00                          1000.00
                                                                                                                                                   Auxiliary Power Output1
                                                                                                                                             3     Programmable Relays2                                  0.00        0.00                 20.00
                                   Table A-2. Power Consumptions for System Components
                                                                                                                                             4     Detection Circuits 1, 2, and 3   3                    0.00        0.00                 70.00
 Number                                 Component                          Standby Power (mA)          Alarm Power (mA)                      5     Ionization Detectors                                  0.07                              0.00
       1      Fenwal 732 Control Unit1                                           100.00                     240.00                          6     Photoelectric Detectors                               0.07                              0.00
2 Auxiliary Power Output2 1000.00 Max. 1000.00 Max. 7 Electronic Heat Detectors 0.07 0.00
3 Programmable Relays 0.00 20.00 8 DH-60 (2W) Duct Detectors 0.07 0.00
4 Ionization/Photoelectric/Electronic Heat Detectors 0.07 70.00 9 Contact Type Heat Detectors 0.00 0.00 0.00
                                                                                                                                           Detection Circuits. However, since only one detector can be in Alarm, the Alarm current should only be considered
      1 The  standby and alarm values for the Fenwal 732 include the Trouble Relay.                                                        for the entire Detection Circuit.
      2 The  Auxiliary Power Output current value stated is the maximum allowed.                                                         4
                                                                                                                                           The value stated for the NACs is the maximum for each. See Note 6 below.
      3 The Standby current stated for Ionization, Photoelectric, Electronic Heat, Duct and Contact Heat Detectors is for                5 For the Alarm current values of Steady Release Solenoids, refer to Appendix B.
        each detector. The Alarm current is for the Detection Circuit.                                                                   6 Since the Power Supply of the Kidde Fenwal 732 unit is rated at 5.4 Amps, the system designer should ensure that
      4
        The current value stated for the Notification Appliance Circuits is the maximum each.                                               the system circuits are loaded so as to keep the calculated alarm current equal to or less than 5.4 Amps.
      5
        For the Alarm current values of Steady Release Solenoids, refer to Appendix B.
      6 Momentary Agent Release Solenoids and Initiators are negligible in their current requirements and do not need to
P/N 06-236717-001                                             A-1                                                    August 2007   August 2007                                                    A-2                                          P/N 06-236717-001
                                                                                    Battery Capacity Calculations    Battery Capacity Calculations
              Based on the Duration for which battery backup is required (refer to Paragraph A-1) and the Total
              Standby Power and Total Alarm Power values (refer to Paragraph A-3), the next step is to calculate
              the battery capacity in Ampere-Hours (AH) using Table A-4.
                                                                         Duration
             Total Power Required (Amps)                 Multiply By                Equals    Ampere-Hour (AH)
                                                                         (Hours)
              Notes: 1. The above battery capacity calculation and subsequent selection assumes that the battery
                     is installed in ambient room temperatures. If installed in below ambient, consult the battery
                     manufacturer for requirement of additional deration factors not considered above.
                      2. 5 minutes = 0.083 hours
                         10 minutes = 0.167 hours
P/N 06-236717-001                                         A-3                                          August 2007   August 2007                                     A-4                   P/N 06-236717-001
                                                                      List of Agency Listed Compatible Devices    List of Agency Listed Compatible Devices
                                                                                                                                             I        Resistance                                                              Max.
                                                                                                                                                                                      12         14        16       18
                                                                                                                           Device          (Min.)       (Max.)         On Time                                              Number          Agency
                                                                                                                                                                                     AWG        AWG       AWG      AWG
B-1         DETECTORS AND BASES                                                                                                            Amps         Ohms                                                               per Circuit
Photoelectric Detector with 135F Sensor PSD-7156 71-560000-001 93-487100-001* 2 12 Momentary 360 240 140 1 or 2 UL, FM
Advanced Photoelectric Smoke Detector PSD-7157 71-570000-001 FM Group A 0.458 52 Steady 1440 760 480 340 1 FM
Advanced Photoelectric Detector Duct Head                          PSD-7157D              71-570000-002              FM Group B, D           0.7            34          Steady           940     500      300       220          1            FM
                                                                                                                     FM Group E, G          0.42            57          Steady       1570        760      525       370          1            FM
Electronic 135F Fixed with 15F ROR Heat Detector                  THD-7052              70-520000-001
                                                                                                                     FM Group F           Skinner 24 Vdc, 22 Watt Solenoid 7312BN4TNLVNOC322C2                                   1            FM
Electronic 135F Fixed Temp Heat Detector                           THD-7053              70-530000-001
                                                                                                                     FM Group I           Victaulic 24 Vdc, 8.7 Watts, 364 mA series 753-E Solenoid                              1            FM
2-Wire Detector Base                                                   2WB                70-501000-001
                                                                                                                     FM Group J           Viking Model No. 11591, 11592, 11595, and 11596, 24 Vdc, 10 Watts               1                FM
2-Wire Detector Base                                                 2WRLT                70-501000-002
                                                                                                                     FM Group K           Viking Model No. 11601, 11602, and 13215, 24 Vdc, 9 Watts                       1                FM
2-Wire Detector Base                                                  2WRB                70-501000-005
2-Wire Relay Module                                                   2WRM                70-500000-004               * Must be used in conjunction with Microswitch P/N 87-120039-001 for momentary operation.
2-Wire Duct Housing                                                 DH-60-2W              70-600000-200
2-Wire Duct Housing with CPD-7051D                                 DH-60-2CPD             70-600000-251
                                                                                                                                                            Table B-3. Initiator-Based Releasing Devices
2-Wire Duct Housing with CPD-7054D                                 DH-60-2ACD             70-600000-254
2-Wire Duct Housing with PSD-7155D                                 DH-60-2PSD             70-600000-255
                                                                                                                                                     I (Min.)         Resistance                                   Max. Number per
2-Wire Duct Housing with PSD-7157D                                 DH-60-2APD             70-600000-257                         Device                                                          On Time                                      Agency
                                                                                                                                                      Amps           (Max.) Ohms                                        Circuit
4-Wire Detector Base                                                  4WRB                70-501000-101                  31-199932-004                  *                                     Momentary                  12                 UL, FM
4-Wire Duct Housing less Detector with Integral Exhaust               DH-60               70-600000-000                  31-199932-012                  *                                     Momentary                  8                  UL, FM
Tube & 24/120/240 VAC Transformer
                                                                                                                         93-191001-001                  *                                     Momentary                  6                  UL, FM
4-Wire Duct Housing with Original Ionization Detector              DH-60-CPD              70-600000-051
CPD-7051D
                                                                                                                      * The maximum circuit resistance for this device must be 10 ohms, regardless of the number used. The firing current will be
4-Wire Duct Housing with Advanced Ionization Detector              DH-60-ACD              70-600000-054                  2.5 Amps.
CPD-7054D
4-Wire Duct Housing with Original Photoelectric Detector           DH-60-PSD              70-600000-155
PSD-7155D                                                                                                                                                          Table B-4. Miscellaneous Devices
4-Wire Duct Housing with Advanced Photoelectric Detector           DH-60-APD              70-600000-157
                                                                                                                                                   Device                                          Model Number                      Supplier/Mfg.
PSD-7157D
                                                                                                                  Receiving Units for Central Station                                                  5104B                         Silent Knight
P/N 06-236717-001                                         B-1                                       August 2007   August 2007                                                      B-2                                                  P/N 06-236717-001
                                                                                 Technical Specifications        Technical Specifications
                                       APPENDIX C
                                                                                                                                              Item                                         Description
                                TECHNICAL SPECIFICATIONS                                                         C.2           Manual Release            One (1)
                                                                                                                               Compatible Devices        A quantity of Normally-Open contact-closure devices subject to maximum
                                                                                                                                                         allowable wiring resistance.
                                                                                                                               Circuit Type              - Class A (Style D) or Class B (Style B) supervised
                                 Item                               Description                                                                          - Detects Opens and Ground Faults
 A            NUMBER OF HAZARDS          One (1)                                                                                                         - Power Limited
 B            POWER                                                                                                            Circuit Voltage           Nominal 24 Vdc, 28 Vdc maximum
              AC Main Input              120 Vac/240 Vac 50/60 Hz (90 to 264 Vrms, 47 to 63 Hz)                                Maximum Line Resistance   100 ohms per loop
              Current Consumption                                                                                              Maximum Current           10 mA
                                         3.2 Amps
                    120 Vac:                                                                                                   End-of-Line Resistor      5.1K, 5%, 1/2 W
                                         1.6 Amps
                    240 Vac:                                                                                     C.3           Abort Input               One (1)
              Required Breaker           15 Amps                                                                               Compatible Devices        A quantity of Normally-Open contact-closure devices subject to maximum
                                                                                                                                                         allowable wiring resistance.
              Power Supply Output        5.4 Amps @ 27 Vdc
                                                                                                                               Circuit Type              - Class A (Style D) or Class B (Style B) supervised
              Battery Charger Output     6 Amps @ 27 Vdc
                                                                                                                                                         - Detects Opens and Ground Faults
              Battery Capacity           Up to 68 AH @ 24 Vdc
                                                                                                                                                         - Power Limited
              Battery Cutout Voltage     18.6 Vdc
                                                                                                                               Circuit Voltage           Nominal 24 Vdc, 28 Vdc maximum
              Auxiliary Power Output     1 Amp maximum @ 24 Vdc Nominal
                                                                                                                               Maximum Line Resistance   100 ohms per loop
              Battery Transfer           85% of 120 Vac
                                         85% of 240 Vac                                                                        Maximum Current           10 mA
 C            Input Circuits                                                                                                   End-of-Line Resistor      5.1K, 5%, 1/2 W
 C.1          Detection Circuits         Three (3)                                                               C.4           Supervisory Input         Two (2)
                                         - Two (2) for Suppression Input                                                       Compatible Devices        A quantity of Normally-Open contact-closure devices subject to maximum
                                                                                                                                                         allowable wiring resistance.
                                         - Third configurable as either independent Detection Circuit or for
                                         Waterflow                                                                             Circuit Type              - Class A (Style D) or Class B (Style B) supervised
              Compatible Devices         - 25 conventional electronic Smoke/Heat detectors listed in                                                     - Detects Opens and Ground Faults
                                         Appendix B.
                                                                                                                                                         - Power Limited
                                         - A quantity of Normally-Open contact-closure devices subject to
                                         maximum allowable wiring resistance.                                                  Circuit Voltage           Nominal 24 Vdc, 28 Vdc maximum
Circuit Type - Class A (Style D) or Class B (Style B) supervised Maximum Line Resistance 100 ohms per loop
P/N 06-236717-001                            C-1                                                   August 2007   August 2007                                               C-2                                       P/N 06-236717-001
                                                                                                    Technical Specifications    Technical Specifications
                                                                                                                                                        Item                                               Description
                            Item                                                Description
                                                                                                                                E         ENCLOSURE
D         OUTPUT CIRCUITS                                                                                                                 Degree of Protection               NEMA 1
D.1       Notification Appliance              Three (3)                                                                                   Material of Construction           18 Gauge (0.053 inches or 1.35 mm) sheet steel
                                              - NAC 1: First Alarm Condition                                                              Color                              Blue, except MEA enclosure, which is Red
                                              - NAC 2: Pre-Release Condition
                                              - NAC 3: Release Condition                                                                  Assembled Dimensions
          Compatible Devices                  A quantity of Polarized 24 Vdc Notification Appliances subject to the                       - With Standard Door               14-1/4 in. Width x 5 in. Depth x 19 in. Height (362 mm x 127 mm x 483 mm)
                                              maximum current and maximum allowable voltage drop per circuit.
          Circuit type                        - Class A (Style Y) or Class B (Style Z) supervised                                         - With Switch-Door                 14-1/4 in. Width x 6 in. Depth x 19 in. Height (362 mm x 152 mm x 483 mm)
                                              - Detects Opens and Ground Faults                                                           Approximate Weight (without
                                              - Power Limited                                                                             batteries)
Circuit Voltage Nominal 24 Vdc, 28 Vdc maximum - Standard Assembled 18 lbs. (8 kg)
End-of-Line Resistor 5.1K, 5%, 1/2 W - Assembled with Dead-Front Panel 22 lbs. (10 kg)
D.2 Output Relays Four (4) - Dead Front Panel Shipping 4 lbs. (2 kg)
- Programmable: Three (3), normally de-energized with power on - Switch Panel Assembled 19 lbs. (8 kg)
- Trouble: One (1), normally energized with power on - Switch Panel Shipping 21 lbs. (10 kg)
Contact Rating 3 Amps @ 30 Vdc (resistive) Temperature 32F to 120F (0C to 49C)
P/N 06-236717-001                                             C-3                                                 August 2007   August 2007                                                   C-4                                     P/N 06-236717-001
                                                                         FM Rules for PreAction/Deluge Systems         FM Rules for PreAction/Deluge Systems
                        APPENDIX D
          FM RULES FOR PREACTION/DELUGE SYSTEMS
              Fenwal 732 applications which require Factory Mutual (FM) approved Pre-Action and/or Deluge
              Systems must conform to the following guidelines:
                   Detection Zone 1 (Det1), Detection Zone 2 (Det2) and Waterflow (W'Flow) Initiating Circuits must
                    be configured for Class A, Style D wiring.
                   The Battery backup system must provide for 90 hours of Standby operation followed by 10
                    minutes of Alarm operation. Refer Appendix A for calculations.
                   The Agent Release Output must be configured for Deluge Solenoid activation. The Solenoid
                    Activation Time must be set either for:
                          10 minutes, or
                          15 minutes, or
                          On-until-reset.
              The wiring connection of the Control Unit to the Deluge Solenoids must be as detailed in the
              Installation section of this Manual.
P/N 06-236717-001                                        D-1                                             August 2007   August 2007                                   D-2                   P/N 06-236717-001
                                                                                                                     Central Station Operation    Central Station Operation
                                  APPENDIX E
                           CENTRAL STATION OPERATION
              The Fenwal 732 should be configured for Central Station operation as follows:
                   One of the three (3) Programmable Relays should be configured for any alarm. For example:
                                                                 2,
                                                             1   3, OR   1
                                                                 4
                   The Trouble Relay should be set to delay AC Failure Response by a period acceptable to the local
                    AHJ. For example:
1 15 X
              A Silent Knight DACT Model 5104B must be wired to the control unit, as shown in Figure E-1. Refer
              to the Model 5104B Installation Manual for information regarding connection of the DACT to
              telephone lines for Alarm and Trouble transmission(s).
              Note 1: Wiring must be installed in conduit within 20 feet.
                                                                                                                                                                              THIS PAGE INTENTIONALLY LEFT BLANK.
              Note 2: Central Station is not suitable for use with Canadian applications.
                                               TB 8
                                                  NO NC C
                          TROUBLE
                                                                                         1 2 3 4 5 6 7 8 9 10 1112
RELAY 4.7K
                                       TB 9, TB10, or TB11
                                                   NO NC C
                    PROGRAMMABLE
                                      4.7K
                           RELAYS
SUPERVISORY
                                       TB 9, TB10, or TB11
                                                  NO NC C
                    PROGRAMMABLE
                                      4.7K
                           RELAYS
                                      PROGRAMMED FOR
                                       GENERAL ALARM
P/N 06-236717-001                                                E-1                                                                August 2007   August 2007                                 E-2                   P/N 06-236717-001
                                                                           Routings for Power-Limited and Non-Power-Limited          Routings for Power-Limited and Non-Power-Limited Wiring
                               APPENDIX F
                     ROUTINGS FOR POWER-LIMITED AND
                        NON-POWER-LIMITED WIRING
              This appendix provides guidelines for power-limited and non-power-limited wiring requirements.
              The following wiring requirements shall be observed:
                   Power-limited and non-power-limited wiring must be physically separated within the control-unit
                    enclosure
                   All power-limited wiring must be separated by at least 1/4-inch (6 mm) from any
                    non-power-limited wiring
                   Power-limited and non-power-limited wiring cannot enter and exit the control-unit enclosure
                    through the same knockout or conduit.
Figure F-1 shows typical wiring for power-limited and non-power-limited circuits.
TB10
TB11
TB13
      RELEASE CIRCUITS
 (TB14 AND TB15) CAN BE
WIRED AS POWER-LIMITED
 OR NON-POWER-LIMITED
BATTERY WIRING
P/N 06-236717-001                                                    F-1                                               August 2007   August 2007                                     F-2                 P/N 06-236717-001
Kidde, Fenwal, and HSSD are registered trademarks of Kidde-Fenwal, Inc.
All other trademarks are the property of their respective owners.
                                                                 These instructions do not purport to cover all the details or variations in the equipment de-
                                                                 scribed, nor do they provide for every possible contingency to be met in connection with instal-
             Protection Systems                                  lation, operation and maintenance. All specifications subject to change without notice. Should
                                                                 further information be desired or should particular problems arise which are not covered suf-
                                                                 ficiently for the purchasers purposes, the matter should be referred to KIDDE-FENWAL INC.,
A UTC Fire & Security Company                                    Ashland, Massachusetts
400 Main Street
Ashland, MA 01721                                              P/N 06-236717-001 Rev. AB             2007 Kidde-Fenwal, Inc.                 All Rights Reserved.
Tel.: 508.881.2000                                             Printed in USA
Fax: 508.881.8920
www.fenwalfire.com