Table 3 Main mechanical parameters of the circuit breaker and actuator                                       XGN66A-12 AC Fixed Type Metal-clad Switchgear
With Spring operation mechanism
                                                                                                                                                   Summary
                                         Item                               Unit                            Data
      Rated power of storage motor                                           W                                  110                           XGN66A-12 a pplies to 3.6~12kV three phase AC 50Hz system to receive and
      Rated voltage of storage motor                                         V                      110 220          85~110%                  distribute power energy, suitable for sites with frequent operation and used to
      Power storage time                                                     S                                   12                           improve switchgear with oil switch. It can be arranged for single bus system
      Rated voltage of opening/closing coil                                  V         110           220                   110          220   and single bus sectionalizing system. The pa nel accords with IEC62271-200 AC
      Rated current of opening/closing coil                                  A         3.6           2.6                   2.3          1.4   Metal-enclosed Switchgear and Control Equipment above 1kV an d below
      Rated voltage of auxilary switch                                       A                10( 220V) 2(=220V T 20ms)
                                                                                                                                              52kV AC, GB3906 3~3.5kV AC Metal-enclosed Switchgear. It is novel in
      Distance of open contact                                              mm                               10~12
                                                                                                                                              appearance and small in volume, and also has pr eventi on function of
      Super travel of contact                                               mm                               3.5~5
                                                                                                                                              mal-operation. The main switch inside the panel is VHY1-12, VS1-12 /ZN73-12
      Tripping time of closing time                                         ms                                   2
                                                                                                                                              model VCB produced by Huayi Group, GN30-12, GN19-12 model disconnect
      Interval of three pole on-off                                         ms                                   2
                                                                                                                                              switch and JN15-12 model earthing switch are used in panel.
      Average closing speed                                                 m/s                             1.0 0.2
      Average opening speed                                                 m/s                             0.6 0.2
                                                                                                                                                   Ambient condition
      Main loop resistance                                                                                  60/35/25*
      Pressure on closing contact                                            N               3000   100/5000 200/6000 400**                   1. Ambient temperature: -10 ~+40 ;
      Distance between the center pole                                      mm                              270        2                      2. Altitude:    1000m;
     Permanent magnetic                                                                                                                       3. Relative humidity: daily average          95     , monthly average      90   ;
                                         Item                               Unit                            Data                              4. Earthquake intensity:      8 degree;
      External control voltage                                               V                 110(1 20%)                220(1   20%)         5. Applicable occasions should be free from inflammable, explosives and severe vibration.
      External control current                                               A                                     2
      Control signal voltage
                                                                                                                                                   Model
                                                                             V                             220(1         20%)
      Control signal current                                                 A                                   0.1
                                                                                                                                                    X G N 66A 12 (Z)
     *Corresponding to rated current 1600/3150/4000A
     **Corresponding to breaking current 31.5/40/50kA                                                                                                                                              Vacuum circuit breaker
                                                                                                                                                                                                   Rated voltage(kV)
                                      Table 4 Main technical parameters of GN58-12D Isolation switch
                                                                                                                                                                                                   Design serial No.
                                         Item                               Unit                            Data                                                                                   Indoor
      Rated voltage                                                          kV                                 12                                                                                 Fixed
      P.F. withstand voltage (Phase to phase, phase to earth)                kV                                 42                                                                                 Metal-clad
      P.F. withstand voltage (Across open contacts)                          kV                                 49
      Lightning impulse withstand voltage(Phase to phase, phase to earth)    kV                                 75                                 Technical specification
      Lightning impulse withstand voltage(Across open contacts)              kV                                 85
      Rated frequency                                                        Hz                                 50
                                                                                                                                                         No.                           Item                            Unit               Data
      Rated current                                                          A     630 1250 1600 2000 2500 3150 4000 5000(Air-cooled)                           Rated voltage                                           kV
                                                                                                                                                         1                                                                                3.6~12
      Rated short-time withstand voltage                                     kA                      25     31.5 40         50                                  Rated current                                           A
                                                                                                                                                         2                                                                              630,1250
      Rated peak withstand voltage                                           kA                        82    104         130                                    Rated short circuit breaking current                    kA
                                                                                                                                                         3                                                                             20, 25, 31.5
      Rated short circuit duration (50kA)                                    s                              4    2                                              Rated short circuit making current(peak)                kA
                                                                                                                                                         4                                                                             50, 63, 80
      Rated short-circuit making current of earthing switch Peak             kA                                 80
                                                                                                                                                         5      Rated short time withstand current(4s virtual value)    kA             20,25,31.5
                                                                                                                                                         6      Rated peak withstand current(peak)                      kA              50,63,80
                                                 Table 5 Main technical parameter of CT
                                                                                                                                                         7      1min. PF Withstand voltage                              kV                42/48
                                         Item                               Unit                            Data
                                                                                                                                                         8      Lightning impulse withstand voltage                     kV                75/85
      Rated voltage                                                          kV                                 12
                                                                                                                                                         9      Auxiliary loop 1min. PF withstand voltage               kV                    2
      Rated single current                                                   A                              5~5000
                                                                                                                                                        10      Protection degree                                                            IP3X
      Rated secondary current                                                A                               1       5
                                                                                                                                                         11     Outline dimension(cable outgoing, W D H)               mm         900(840)    1200    2400
      Accuracy Class                                                                            0.2s/0.5/10P10(0.2s/10P15
      Minimum rated output capacity                                         VA                        10/10/15(15/15)
25                                                                                                                                                                                                                                                           26
                                                                                                                                           XGN36-12 (DXG-12) AC Fixed Type Metal-clad Switchgear
                            Main technical parameters for VHY1-12/VS1-12/ZN73-12 type VCB                                                       Summary
            No.                              Item                           Unit                        Data                               XGN36-12( DXG-12) s witchgear is a new miniaturization power network
              1      Rated voltage                                           kV                          12                                equipment which introduced advanced technology and combine with our
              2      Rated current                                           A                        630, 1250                            company real condition. With excellence of high grade, complete parameter,
              3      Rated short circuit breaking current                    kA                      20, 25, 31.5                          low price, few maintenance. It applies to 3.6~12kV three phase AC 50/60Hz
              4      Rated short circuit making current(peak)                kA                       50, 63, 80                           single busbar or busbar sectional system for receiving and distribution power
              5      Rated short time withstand current(4s virtual value)    kA                      20, 25, 31.5                          energy. It can widely used for electric power, metallurgy, petrifaction and urban
              6      Rated peak withstand current(peak)                                               50, 63, 80                           construction.
                                                                             kA
              7      Mechanical endurance                                   Times                       10000
                                                                                                                                                Ambient condition
              8      Rated short circuit breaking current breaking time     Times                        50
              9      Rated operation sequence                                                     O-0.3s-CO-180s-CO                        1. Ambient temperature: -10 ~+40 ;
                                                                                                                                           2. Altitude:    1000m;
                                                                                                                                           3. Relative humidity: daily average         95%, monthly average       90%;
          Product structure
                                                                                                                                           4. Earthquake intensity:     8 degree;
     The panel is case fixed type, whose body is made of aluminium-zinc plated steel sheet after multi-bending. Its rear-upper par t       5. Applicable occasions should be free from inflammable, explosives and severe vibration.
     is main bus compartment, and a pressure releasing device locates on the top. The front-upper part is low voltage compartment,
                                                                                                                                                Model
     secondary bus can be connected by cables from the bottom, or a bronze tube or stick can be installed on the top. Busbar
     compartment can keep electric connection with the middle/lower part of the cubicle through G N 30 model rotating disconnect                X G N 36 - 12
     switch. The VCB is in stalled in the middle of cubicle, earthing switch and disconnect switch of the outgoing cable side are
     installed in the lower part of panel. CT, PT and lightning arrester can be installed in the rear of panel, primary cable can go out                                                  Rated voltage(kV)
     from the back-lower part of panel. Earthing busbar installed on the bottom of panel are through all cubicles. D isconnect switch                                                     Design serial No.
                                                                                                                                                                                          Indoor
     and earthing switch will be operated on the front-right part of panel.
                                                                                                                                                                                          Fixed
                                                                                                                                                                                          Metal-clad
          Outline dimension
                                                                                                                                                Structure feature
                                    100
                                          HEAG       XGN66A-12
                                                                                                                                           1. The panel is novel and complete function, not only with fixed panel isolate live busbar feature, but also convenient for
                                                                                                                                             maintenance, easily to exchange circuit breaker, thereby assure of maintaining safely and conveniently, meanwhile, choose
                                                                                                                                             primary plug in contact.
                                                                                                                                           2. Main switch is miniaturization vacuum circuit breaker(introduce advanced technology). Choose large creeping distance porcelain
                                                                                                                                             enclosure vacuum arc extinction chamber, adopt air insulation. It suitable for rural net work reconstruction and industrial
                                                                                                                                             enterprise specially, equipped with miniaturization disconnect switch, double functions for main knife switch and earthing switch,
                                                                                                                                             gear drive type.
                                                                                                                                           3. Panel is combination type, without welding, withou t deformation, miniaturization volume. With reliable "five prot ection" in terlock
                                                                                                                                             function, compulsive mechanical interlock on rear and front door.
                             2500
                                                                                                                                                Technical specification
                                                                                                                                                   No.                        Item                        Unit                           Parameter
                                                                                                                                                    1      Rated voltage                                      kV                                12
                                                                                                                                                    2      Rated current                                      A             400    630   1250      1600      2000    3150
                                                                                                                                                    3      Rated peak withstand current                       kA                  31.5   40   50       63   80     100
                                                                                                                                                    4      Rated short time withstand current(4s)             kA                  12.5   16   20       25   31.5    40
                                                                                                                                                    5      Rated short time current breaking time        Times                                  50
                                                                                                                                                    6      Mechanical life                               Times                                20000
                                                                                           1200
                                                                                                                                                    7      Rated short time duration                          s                                    4
                                                         Drawing 1 Schematic Drawing                                                                8      Rated breaking current                             kA                  12.5   16   20       25   31.5    40
27                                                                                                                                                                                                                                                                                    28