Kata Log
Kata Log
www.esitas.com
Company Profile Page 2
Insulators Page 93
Mission Statement
As Esitas Group, we aim to be the main supplier of the market leaders in the world transformer
industry and to be a permanent player in the developing countries; by keeping our leader position
in domestic market in instrument transformers and increasing awareness of our products in the
global market, together with continuously improving our existent quality and introducing innovati-
ons in order to increase efficiency for ourselves and our customers.
Group Companies:
Esitas Brand has been in the transformer industry more than 25 years. Esitas Group Companies
have been producing and serving the electrical products and contacting businesses with two
factories specializing in their markets.
ESITAS ELEKTRIK is the parent company of the group located in Istanbul, Turkey produces
and sells Low and Medium Voltage Instrument Transformers (both Current - Voltage and Indoor-
Outdoor Types), Low and Medium Voltage Insulators and LPCTs.
ESITAS ELEKTRIK is in the preferred suppliers list of Turkish Electric Authority, has been selling to
many foreign electricity authorities and to various branches of multinational market leaders in the
industry like ABB, Schneider, Siemens and others.
2
www.esitas.com
PT ESITAS PACIFIC is the Groups production plant located in Jakarta Indonesia produces and sells
Low and Medium Voltage Instrument Transformers (both Current-Voltage and Indoor-Outdoor Types),
Low and Medium Voltage Insulators. Indonesia founded to serve the customers more conveniently
in Asia Pacific zone and to further furnish its existence in the world market.
With its mission of ... continuously improving our existent quality and introducing innovations
in order to increase efficiency for ourselves and our customers, Esitas is your partner in the world
transformer market.
3
CURRENT TRANSFORMERS
General Definitions
General definitions have been given according to International Standarts IEC 6OO44
6OO44.
Instrument Transformer
A transformer intended to supply measuring instruments meters, protection relays and other similiar apparatus.
Applicable Standards
Our transformers comply with applicable national and international standards.
Current Transformers
An instrument transformer in which the secondary current, in normal conditions of useuse, is substantially proportional to the primary
current and differs in phase from it by angle which is approximately zero for an appropriate direction of the connections.
It isolates the instrument and protection circuit from the primary side and protect the devices against overload according to the
overcurrent characteristics of the transformer. Current transformers can have several secondary windings with cores of identical of
different characteristics completely isolated from each other.
Primary Winding
The winding through which flows the current to be transformed.
Secondary Winding
The winding, which supplies the current circuits of measuring instruments, meters, relays or similiar devices.
Secondary Circuit
The external circuit supplied by the secondary winding of a transformer.
Where
Kn is the rated transformation ratio;
Ip is the actual primary current
Is is the actual secondary current when Ip is flowing under the conditions of measurements.
6
www.esitas.com
Accuracy Class
A designation assigned to a current transformer errors of which remain within specified limits under prescribed conditions of use.
Burden
The impedance of the secondary circuit in ohms and power-factor. The burden is usually expressed as the apparent power in
voltamperes absorbed at a specified power-factor and at the rated secondary current.
Rated Burden
The value of the burden on which the accuracy requirements are based on.
Rated Output
The value of the apparent power (in voltamperes at a specified power-factor) which the transformer is intended to supply to the
secondary circuit at the rated secondary current and with rated burden connected to it.
Rated Frequency
This is the frequency for which the transformer is designed and given in Hz on the rating plate.
7
CURRENT TRANSFORMERS
CONNECTION DIAGRAMS
P1 P2 P1 P2
P1 C1 C2 P2
Primary Reconnection
Changeover will be done at the primary
side by using joint bars.
Can be used only for primary currents up to 2 x 6OOA
S1 S2
Secondary Tapping
Changeover will be done at the secondary side. P1 P2
S1 S2 S3
8
www.esitas.com
- When the secondary terminals are connected to the measuring or protection devices P1 P2
one of the terminals should be earthed for safety as seen in Diagram-1.
Diagram-1
S1 S2
A
- The secondary circuit of a current transformer must not be operated with an open - circuit. P1 P2
- The secondary winding of a current transformer which will not be used must
be short - circuited and earthed as seen in Diagram-2
Diagram-2
S1 S2
P1 P2
- For the transformer with reconnectable and - or tapped secondaries
unused terminals must be left open as seen in Diagram-3.
Diagram-3
S1 S2
S3 open
A
- The current transformers which have capacitive divider tap (Ck) must be connected to the indicator if the tap will
not be used then it must be earthed.
a b
9
CURRENT TRANSFORMERS
- Up to 3 cores
cores*
- On request with capacitive layer.
- On request with barrier.
Technical Data
- Up to 3 cores
cores*
- On request with capacitive layer.
- On request with barrier.
Technical Data
8Omm will be
7Omm at
ATB1O-BS
Technical Data
INDOOR SUPPORT TYPE CAST RESIN INSULATED C.T.S C.T. S TECHNICAL DRAWING
(Um=3,6kV .............. 12kV NARROW BLOCK TYPES)
- Up to 3 cores.
cores.*
- On request with capacitive layer.
- On request with barrier.
Technical Data
TYPES ATB 2O-B ATB 2O-B2 ATB 2O-B4 ATB 2O-3 ATB 2O-3B ATB 2O-3K
- Up to 3 cores.
cores.*
- On request with capacitive layer.
- On request with barrier.
Technical Data
Technical Data
- Up to 3 cores.
cores.*
- On request with capacitive layer.
- On request with barrier.
Technical Data
TYPES ATB 3O-S ATB 3O-S1 ATB 3O-1 ATB 3O-2 ATB 3O-3
TYPES A B C D E F G H I J
ATB 3O-S 385 17O 36O 255 25O 125 21O 225 3OO 2O
ATB 3O-S1 385 17O 36O 255 27O 135 22O 225 3OO 2O TIGHTENING TORQUE (Nm) min. max.
ATB 3O-1 385 17O 36O 255 27O 135 22O 225 3OO 2O M5 (Secondary Terminal) 2.5 3.5
ATB 3O-2 385 17O 36O 255 31O 155 24O 225 3OO 2O M8 (Ground Terminal) 15 2O
ATB 3O-3 455 21O 36O 255 389 195 249 225 375 2O M12 (Primary Terminal) 6O 7O
Technical Data
INDOOR SUPPORT TYPE CAST RESIN INSULATED NARROW TYPE CURRENT TRANSFORMERS
(Um=7,2kV .......... 24kV BLOCK TYPES)
Types: ATU 24
- Up to 2 cores.
Technical Data
TYPES ATU 24
Operating voltage, Um (kV) 7,2 12 17,5 24
Rated power-frequency withstand voltage (1 minute) (kV) 2O 28 38 5O
6O 75 95 125
Rated frequency (Hz) 5O-6O
Primary rated current (A) 1O - up to 8OO
Primary reconnection (A) 2x1O - 2x4OO
Secondary rated current (A) 1-5
Metering classes O,2 - O,2S - O,5 - O,5S - 1 - 3 - 5 Acc. to IEC 6OO44-1
Protection classes 5P- 1OP Acc. to IEC 6OO44-1
Rated short-time thermal current (lth) (1s) (kA) 1OO x In*
In
Rated dynamic current (ldyn) (kA) 2,5 x lth
Short-time load (mechanical) (N) 5OOO
Insulation class E
Ambient temperature (C) -25............+4O**
-25............+4O **
Altitude (m) 1OOO
Standard According to the customer requirements
Weight (approx.) (kg) 24
- Up to 2 cores.
Technical Data
- Up to 2 cores.
cores.*
Technical Data
INDOOR POST BUSBAR TYPE CAST RESIN INSULATED C.T.S TECHNICAL DRAWING
(Um=3,6kV ..............24kV)
- Up to 3 cores.
cores.*
Technical Data
INDOOR POST BUSBAR TYPE CAST RESIN INSULATED C.T.S TECHNICAL DRAWING
(Um=3,6kV............24kV)
- ATH 2O up to 1 core.*
core.
cores.
- ATH 21 up to 2 cores.* For the connection
cores.
- ATH 22 up to 3 cores.* of aluminium conductors
steel reinforced
Technical Data
TYPES A B C D E F G H
max. max.
ATH 2O 245 1O5 35O 22O 225 178 175 2O TIGHTENING TORQUE (Nm) min. max.
max. max.
ATH 21 35O 165 37O 3OO 34O 27O 2OO 65 M6 (Secondary Terminal) 3 5
max. max.
ATH 22 4OO 195 38O 37O 415 34O 25O 7O M12 (Primary & Ground Terminal) 6O 7O
Types: ATH 3O
ATH 32
- ATH 3O up to 2 cores.*
cores.
cores.
- ATH 32 up to 3 cores.*
For the connection
of aluminium conductors
steel reinforced
Technical Data
Types: ATH 52
- Up to 2 cores.
cores.*
TYPES ATH 52
Operating voltage, Um (kV) 52
Rated power-frequency withstand voltage (1 minute) (kV) 95
25O
Rated frequency (Hz) 5O-6O
Primary rated current (A) 5-25OO
Primary reconnection (A) 2x5 - 2x6OO
Secondary rated current (A) 1-5
Metering classes O,2 - O,2S - O,5 - O,5S - 1 - 3 - 5 Acc. to IEC 6OO44-1
Protection classes 5P- 1OP; CI:PX Acc. to IEC 6OO44-1
Rated short-time thermal current (lth) (1s) (kA) max. 1OOO x In
Rated dynamic current (ldyn) (kA) 2,5 x lth
Short-time load (mechanical) (N) 25OO
Insulation class E
Min. creepage distance (mm) 16OO
Altitude (m) According to the customer requirements
Standard According to the customer requirements
Weight (approx.) (kg) 14O
Technical Data
TYPES KAP
Operating voltage, Um (kV) O,72
Rated power-frequency withstand voltage (1 minute) (kV) 3
-
Rated frequency (Hz) 5O-6O
Primary rated current (A) 4O ........... 3OOO
Secondary rated current (A) 1-5
Metering classes O,2 - O,2S - O,5 - O,5S - 1 - 3 - 5 Acc. to IEC 6OO44-1
Protection classes 5P- 1OP; Acc. to IEC 6OO44-1
Rated short-time thermal current (lth) (1s) (kA) max. 1OO
Rated dynamic current (ldyn) (kA) Practically unlimited
Insulation class E
Ambient temperature (C) -25............+4O**
-25............+4O **
Altitude (m) 1OOO
Standard According to the customer requirements
INDOOR KAP TYPE (CABLE TYPE) CAST RESIN INSULATED AND ENCLOSED BY PLASTIC COVER
C.T.S TECHNICAL DRAWING (Um=O,72kV)
INDOOR KAP TYPE (CABLE TYPE) CAST RESIN INSULATED AND ENCLOSED BY PLASTIC COVER
C.T.S TECHNICAL DRAWING (Um=O,72kV)
Technical Data
TYPES A-KAP
Operating voltage, Um (kV) O,72
Rated power-frequency withstand voltage (1 minute) (kV) 3
-
Rated frequency (Hz) 5O-6O
Primary rated current (A) 5O ........... 2OOO
Secondary rated current (A) 1-5
Metering classes O,2 - O,2S - O,5 - O,5S - 1 - 3 - 5 Acc. to IEC 6OO44-1
Protection classes 5P- 1OP; Acc. to IEC 6OO44-1
Rated short-time thermal current (lth) (1s) (kA) max. 1OO
Rated dynamic current (ldyn) (kA) Practically unlimited
Insulation class E
Ambient temperature (C) -25............+4O*
-25............+4O
Altitude (m) 1OOO
Standard According to the customer requirements
* It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility. 47
CURRENT TRANSFORMERS
INDOOR A-KAP TYPE (SPLIT TYPE) CAST RESIN INSULATED AND ENCLOSED BY PLASTIC COVER
C.T.S TECHNICAL DRAWING (Um=O,72kV)
NO A
TIGHTENING TORQUE (Nm) min. max.
1 8O
M5 (Secondary Terminal) 2,5 3,5
2 1OO
3 12O
- Cable type.
- Insulated by cast resin.
- Applicable for measurement and protection purposes.
BUSHING TYPES
Advantages :
-Same transformer is usable for nominal currents of 5A to 125OA.
- Accurracy warranty throughout the range :
Protection : 5A-4OkA ; class 5P
Measuring: 1OOA-125OA; class O,5 (class O,75 for 2OA, class 1,5 for 5A).
Simple Assembly :
- Ready for connection secondary cables.
- Simple connection with insulated cable for all types cubicles.
Safety Operation :
- Openable secondary circuit under load.
cable between 5m - 8m
upon customer request.
Technical Data
50
www.esitas.com
Advantages :
-Same transformer is usable for nominal currents of 5A to 2OOOA.
- Accurracy warranty throughout the range :
Protection : 5A-4OkA ; class 5P
Measuring: 1OOA-2OOOA; class O,5 (class O,75 for 2OA, class 1,5 for 5A).
Simple Assembly :
- Ready for connection secondary cables.
- Simple connection with insulated cable for all types cubicles.
Safety Operation :
- Openable secondary circuit under load. cable between 5m - 8m
upon customer request.
Technical Data
51
VOLTAGE TRANSFORMERS
Voltage Transformers
An instrument transformer in which the secondary voltage, in normal conditions of use, is substantially proportional to the primary
voltage and differs in phase from it by an angle which is approximately zero for an appropriate direction of the connections.
It isolates the primary side rated voltage from the connected instruments and protection circuits and convert the primary
voltage into a measurable secondary voltage, which is true in magnitude and phase.
Primary Winding
The winding to which the voltage to be transformed is applied.
Secondary Winding
The winding, which supplies the voltage circuits of measuring instruments, meters, relays or similar apparatus.
Where
Kn is the rated transformation ratio;
Up is the actual primary voltage;
Us is the actual secondary voltage when Up is applied under the conditions of measurement.
Accuracy Class
A designation assigned to a voltage transformer, the errors of which remain within specified limits under prescribed conditions of use.
Burden
The admittance of the secondary circuit expressed in siemens and power factor (lagging or leading)
Rated Burden
The value of the burden on which the accuracy requirements are based on.
Rated Output
The value of apparent power (in voltamperes at a specified power - factor), which the transformer is intended to supply to the
secondary circuit at the rated secondary voltage and with rated burden, connected to it.
54
www.esitas.com
CONNECTION DIAGRAMS
A N A N A B
a n a n da dn a b
R S T
A B A B
a b
a b
r s t
A B
Diagram-1
a
b
V
55
VOLTAGE TRANSFORMERS
A B
Diagram-2
a b
- For the single phase transformers, the neutral terminal of the primary N must be earthed in the earthed (neutral) systems
as seen in Diagram-3.
A N
Diagram-3
a n
da dn
Diagram-4 dn da
da dn
As the number of cable systems is increasing in the energy distribution systems, the protection of voltage transformers have become
very important for the uninterrupted operation of the system without any failure and
and/or
or down time. For that reason, ESITAS is always
recommending the use of open-delta windings in single phase inductive voltage transformers.
56
www.esitas.com
a a b
57
VOLTAGE TRANSFORMERS
Technical Data
58 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
Technical Data
60 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
Technical Data
62 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
INDOOR PHASE TO PHASE SUPPORT TYPE CAST RESIN INSULATED VOLTAGE TRANSFORMERS
(Um=3,6kV............24kV BLOCK TYPES)
Types: 2VTB 1O
2VTB 2O
Technical Data
64 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
INDOOR PHASE TO PHASE SUPPORT TYPE CAST RESIN INSULATED VOLTAGE TRANSFORMERS
(Um=3,6kV............36kV LARGE TYPES)
Technical Data
66 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
20
Technical Data
68 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
INDOOR SINGLE PHASE CAST RESIN INSULATED BUILT IN FUSE WITHDRAWABLE TYPE
VOLTAGE TRANSFORMERS TECHNICAL DRAWING
(Um=3,6kV............36kV BLOCK TYPES)
TIGHTENING TORQUE (Nm) min. max. NO V.T. Types Rated Currents (A) Rated Voltage (Un) A B (mm)
VTB 1O-KF1 355 155 492 26O 298 29O 335 25 148 148 125 27O 2O 8 3,15 Amper 2O
254
VTB 1O-KF2 355 155 536 26O 298 29O 335 25 148 148 125 27O 2O 9 O,63 Amper
1O VTB 1O-KF1 or KF2 1 Amper 15,5 kV
VTB 2O-KF1 355 155 575 318 363 29O 42O 25 178 178 15O 28O 2O 11
VTB 2O-KF1 or KF2
2 Amper
VTB 2O-KF2 355 155 62O 318 363 29O 42O 25 178 178 15O 28O 2O 12 3,15 Amper
VTB 3O-KF1 395 175 688 364 421,5 32O 513 75 21O 21O 18O 3OO 15 13 O,5 Amper
14 VTB 2O-KF1 or KF2 1 Amper 25,5 kV 34O
VTB 3O-KF2 395 175 733 364 421,5 32O 513 75 21O 21O 18O 3OO 15 15
VTB 3O-KF1 or KF2
2 Amper
Technical Data
70 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
1 O,63 Amper
2 ES 12 VR-F 1 Amper
7,2 kV 19O
3 ES 24 V2-F 2 Amper
4 3,15 Amper
5 O,63 Amper
6 ES 12 VR-F 1 Amper
12 kV TIGHTENING TORQUE (Nm) min. max.
7 ES 24 V2-F 2 Amper
8 3,15 Amper 2O M6 (Secondary Terminal) 3 4
254
9 O,63 Amper
1O ES 12 VR-F 1 Amper
15,5 kV
11 ES 24 V2-F 2 Amper
12 3,15 Amper
13 O,5 Amper
14 ES 24 V2-F 1 Amper 25,5 kV 34O
15 2 Amper
INDOOR SINGLE PHASE CAST RESIN INSULATED BUILT - IN FUSE FIXED TYPE
VOLTAGE TRANSFORMERS
(Um=3,6kV............24kV)
Technical Data
72 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
INDOOR SINGLE PHASE CAST RESIN INSULATED BUILT - IN FUSE WITHDRAWABLE TYPE
VOLTAGE TRANSFORMERS
(Um=36kV)
Technical Data
74 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
INDOOR SINGLE PHASE CAST RESIN INSULATED BUILT - IN FUSE WITHDRAWABLE TYPE
VOLTAGE TRANSFORMERS
TECHNICAL DRAWING
(Um=36kV)
Types: ES 17 V3
Technical Data
TYPES ES 17 V3
Operating voltage, Um (kV) 3,6 7,2 12 17,5
Rated power-frequency withstand voltage (1 minute) (kV) 1O 2O 28 38
4O 6O 75 95
Rated frequency (Hz) 5O-6O
Rated primary voltage (max.) (kV) 3,6/ 3
3,6 7,2/ 3
7,2 12/ 3
12 17/ 3
17
Secondary voltage (V) 1OO/ 3
1OO 11O
11O/ 3 12O
12O/ 3 1OO
1OO/33 11O
11O/33 12O
12O/3
Rated burden (max.) in class O,2 (VA) 3O 2O
Rated burden (max.) in class O,5 (VA) 1OO 6O
Rated burden (max.) in class 1 (VA) 2OO 12O
Rated burden for protection purpose in class 3P (VA) 1OO
Rated voltage factor (3O sec. or 8h) (Un) 1,9
Insulation class E
Ambient temperature (C) -25 ..........+4O
..........+4O*
Altitude (m) 1OOO
Standard According to the customer requirements
Weight (approx.) (kg) 22
76 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
Types: ES 24 V2-B
Technical Data
TYPES ES 24 V2-B
Operating voltage, Um (kV) 7,2 12 17,5 24
Rated power-frequency withstand voltage (1 minute) (kV) 2O 28 38 5O
6O 75 95 125
Rated frequency (Hz) 5O-6O
Rated primary voltage (max.) (kV) 7,2/ 3
7,2 12/ 3
12 17,5/ 3
17,5 24/ 3
24
Secondary voltage (V) 1OO/ 3
1OO 11O
11O/ 3 12O
12O/ 3 1OO
1OO/33 11O
11O/33 12O
12O/3
Rated burden (max.) in class O,2 (VA) 3O
Rated burden (max.) in class O,5 (VA) 75
Rated burden (max.) in class 1 (VA) 15O
Rated burden for protection purpose in class 3P (VA) 1OO
Rated voltage factor (3O sec. or 8h) (Un) 1,9
Insulation class E
Ambient temperature (C) -25 ..........+4O
..........+4O*
Altitude (m) 1OOO
Standard According to the customer requirements
Weight (approx.) (kg) 24
78 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
Types: ES 24 V1
Technical Data
TYPES ES 24 V1
Operating voltage, Um (kV) 24
Rated power-frequency withstand voltage (1 minute) (kV) 5O
125
Rated frequency (Hz) 5O-6O
Rated primary voltage (max.) (kV) 24/ 3
24
Secondary voltage (V) 1OO/ 3
1OO 11O
11O/ 3 12O
12O/ 3 1OO
1OO/33 11O
11O/33 12O
12O/3
Rated burden (max.) in class O,2 (VA) 3O
Rated burden (max.) in class O,5 (VA) 1OO
Rated burden (max.) in class 1 (VA) 2OO
Rated burden for protection purpose in class 3P (VA) 1OO
Rated voltage factor (3O sec. or 8h) (Un) 1,9
Insulation class E
Ambient temperature (C) -25 ..........+4O
..........+4O*
Altitude (m) 1OOO
Standard According to the customer requirements
Weight (approx.) (kg) 3O
80 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
Types: VTU-24
Technical Data
TYPES VTU-24
Operating voltage, Um (kV) 7,2 12 17,5 24
Rated power-frequency withstand voltage (1 minute) (kV) 2O 28 38 5O
6O 75 95 125
Rated frequency (Hz) 5O-6O
Rated primary voltage (max.) (kV) 7,2/ 3
7,2 12/ 3
12 17,5/ 3
17,5 24/ 3
24
Secondary voltage (V) 1OO/ 3
1OO 11O/
11O 3 12O/
12O 3 1OO/33
1OO 11O
11O/33 12O/3
12O
Rated burden (max.) in class O,2 (VA) 3O
Rated burden (max.) in class O,5 (VA) 75
Rated burden (max.) in class 1 (VA) 15O
Rated burden for protection purpose in class 3P (VA) 1OO
Rated voltage factor (3Osec. or 8h) (Un) 1,9
Insulation Class E
Ambient Temperature (C) -25.......................+4O*
-25.......................+4O
Altitude (m) 1OOO
Standard According to the customer requirements
Weight (approx.) (kg) 28
82 * It can be produced according to customers specified ambient temperature. Please contact with ESITAS for feasibility.
www.esitas.com
Types: VTH 2O
VTH 3O
84
www.esitas.com
86
www.esitas.com
Types: 2VTH 2O
2VTH 3O
88
www.esitas.com
90
www.esitas.com
Insulators
Insulators are insulating and supporting components of the power transmission lines and busbars (distribution centers ,
switchgears) where they are fixed.
Esitas Insulators are epoxy cast resin insulated with internal metal fittings.
The insulators are particularly suitable to be used as single support or voltage control.
Bushing Insulators
Post Insulators
Capacitive Insulators(voltage divider)
General characteristics
Epoxy resin post insulators, for indoor application, with internal metal fitting.
These insulators are particularly suitable to be used as single supports for conductors, for fuses and for other equip-
equip
ment (as switchgears).
Application
For indoor installation with working condition at T
T max. 85 C.
C.
Service voltage
Up to 36 kV (40,5 kV available on request)
Routine Tests
Visual inspection
Testing of conductive connection of fixing inserts for post insulators
Dry power-frequency withstand voltage
Partial discharge extinction voltage test
Standards
IEC 60273 (CEI 36/12)
36 12) - CENELEC HD 578 S1
IEC 60660
94
www.esitas.com
General characteristics
Epoxy resin post insulators with capacitive divider for the reading of the voltage.
Manufactured with internal metal fitting, they can be equipped with couplings and low voltage light signal box.
These insulators are mainly suitable to be used as insulated supports of equipment, bus bar or fuses.
Application
Max working temperature of 85 C.
C.
Routine Tests
Visual inspection
Testing of conductive connection of fixing inserts for post insulators
Dry power-frequency withstand voltage
Partial discharge extinction voltage test (connected to the voltage indicator)
Service voltage
Up to 36 kV (40,5 available on request)
Standards
IEC 60660
General characteristics
12 - 36 kV epoxy resin bushing insulators. The insulators can be fitted with copper bars
designed from 250 up to 1250 A.
They are equipped with internal metal fittings for installation on the relevant frame and with
brass nuts and washers for fastening of phase connectors.
Application
Indoor/outdoor
Indoor outdoor installation at max working temperature of 85 C.
C.
Service voltage
Up to 36 kV.
Routine Tests
Visual inspection
Dry power-frequency withstand voltage
Measurement of partial discharge quantity
Standards
IEC 60137
95
INSULATORS
Power-frequency Min.
withstand Falling load Weight Dimensions Creepage Number
Um voltage, dry bending app. (mm) Distance of
TYPES (kV) (kV) (N) (kg) a b c d E H t1 t2 t3 t4 (mm) ribs
JO4-75 (1ON5OO) 12 38 4OOO O,6O M16 M12 M6 36 61 13O 25 18 1O 37 17O 5
JO1O-95 (15N1OOO) 17,5 5O 1OOOO 1,45 M2O M16 M1O 46 82 175 27 24 12 42 25O 6
Power-frequency Min.
withstand Falling load Weight Dimensions Creepage Number
Um voltage, dry bending app. (mm) Distance of
TYPES (kV) (kV) (N) (kg) a b c d e E H t1 t2 t3 t4 (mm) ribs
1ON1OOOK 12 38 1OOOO O,97 M2O M16 M1O 46 3O 8O 13O 27 24 12 42 16O 5
Falling load
Um bending In Weight
TYPES (kV) (N) (A) D L (kg)
4OO M16 84O 8,6
Falling load
Um bending In Weight
TYPES (kV) (N) (A) D L (kg)
4OO M16 875 1O,8
98
SPECIAL PRODUCTS
349
320 420
260
16
8
2
12
360
10,5
934
193
181
946
20
30
90
946
193
152 134
101
www.esitas.com
103
www.esitas.com
NOTES
104
www.esitas.com