Configuración Inicial PCC 1301

This document outlines the configuration menu for a PCC 1301 genset service menu, including settings for voltage, frequency, phase, charging alternator, governor control, customer I/O, meter calibration, annunciator faults, genset setup, voltage protection, current protection, engine protection, and overspeed threshold. It provides the parameter names and factory default values for configuring and monitoring the genset control system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views2 pages

Configuración Inicial PCC 1301

This document outlines the configuration menu for a PCC 1301 genset service menu, including settings for voltage, frequency, phase, charging alternator, governor control, customer I/O, meter calibration, annunciator faults, genset setup, voltage protection, current protection, engine protection, and overspeed threshold. It provides the parameter names and factory default values for configuring and monitoring the genset control system.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CONFIGURACIN INICIAL PCC 1301

SERVICE MENU
1 Setup Menu 1 Genset Service 1 Genset Volt Ac: 220 Gov Crank Fuel
Hertz: 60 Initial Dc: 25.0%
N of Phase: 3 Initial Time: 2s
Phase: Wye Ramp Rate: 25.0
Glow Plug: No Max Dc: 100.0%
Charging Alt. Enable: Yes Elect Governor
Star/Stop Delay Gain: 100 %
Start: 0 sec Int: 100 %
Stop: 0 sec D: 100 %
Cycle Crank Elect Governor
Attemp: 3 Crank Exit
Crank: 10 sec Fuel Dc: 25.0%
Rest: 30 sec Diter Factor: 15
Battle Short Ramp Time: 0.25
Battle Short: Inactive Elect Governor
AVR Setup Enable Speed: 700 rpm
AVR Enable: Yes Min Gov Dc: 20 %
V/Hz Setup Max Gov Dc: 95 %
V/Hz Slope: 4.0 Genset Number
V/Hz Knee: 0.5 Model N: C40 D6 4
Regulator Serial: A06T001694
Gain: 100 % Display Setup
Int: 100 % Conection: Local
D: 100 % Acces Code: No
Elect Governor Symbols: Yes
Gov Enable: Yes
2 Customer I/O Customer Input 1 Text Customer Output 1 Map
Type: Shutdown Fault Number: 156
Low Coolant Level Common Warning
Customer Input 2 Text Customer Output 2 Map
Type: Warning Fault Number: 157
Low Fuel Common Shutdown
3 Meter Calib Meter Calib Metering Voltage Adjust
Reg Volt Adj: 102.6% L1-N: 0 VAC
Voltage: 0.0 L2-N: 0 VAC
L3-N: 0 VAC
Freq Adjust Metering Current Adjust
Freq Adj: + 0.1 Hz L1: 0 Amp
Frequency: 0.0 Hz L2: 0 Amp
L3: 0 Amp
4 Annunciator Annunciator Fault 1 Text Annunciator Output 2 Map
Type: Warning Number: 0
Annunciator Fault 1 N Fault:
Annunciator Fault 2 Text Annunciator Output 3 Map
Type: Warning Number: 0
Annunciator Fault 2 N Fault:
Annunciator Fault 3 Text Annunciator Output 4 Map
Type: Warning Number: 0
Annunciator Fault 3 N Fault:
Annunciator Output 1 Map
Number: 0
N Fault:
2 Genset Setup 1 Genset Genset Battery Select
Ct Ratio: 146:5 Nominal Battery Voltage: 12 V
Mpu Enable: Yes Batt Thresholds 12 V
Fly Teeth: 159 Low Batt: 12.00 V
Rpm/Hz Ratio: 30 High Batt: 16.00 V
Application Rating Select Weak Batt: 8.00 V
Application Rating: Stand By Batt Delay Setup
KVA Stand By L. Batt TD: 60.0 s
1 Ph/60Hz: 25.0 H. Batt TD: 60.0 s
3 Ph/60Hz: 50.0 Wk. Batt TD: 2.0 s
1 Ph/50Hz: 25.0 Oil Press Setup
3 Ph/50Hz: 25.0 Sensor Type: Sender
KVA Prime Oil Press Setup
1 Ph/60Hz: 25.0 Sender Type: 3 Wire
3 Ph/60Hz: 25.0
1 Ph/50Hz: 25.0
3 Ph/50Hz: 25.0
2 Volt Protect Volt Protection Volt Protection
High AC Voltage Threshold: 110 V Overfrequency Threshold: 6.0 Hz
High AC Voltage Time Delay: 10.0 s Overfrequency Time Delay: 1100
Volt Protection Volt Protection
Low AC Voltage Threshold: 85 V Underfrequency Threshold: 6.0 Hz
Low AC Voltage Time Delay: 10.0 s Underfrequency Time Delay: 1100
3 Curr Protect Curr Protection Curr Protection
H Curr Warning Threshold: 110% H Curr Shuthdown Threshold: 150%
H Curr Warning Time Delay: 60 Sec H Curr Shutdown Time Delay: 10 Sec
4 Engine Protect Overspeed Threshold (50 Hz) Low Setup
20: 1150 rpm Lop Shutdown Threshold: 30 psi
30: 1725 rpm Lop Shutdown Time Delay: 8 sec
60: 3450 rpm Hct Setup
Overspeed Threshold (60 Hz) Hct Warning Threshold: 215 F
20: 1400 rpm Hct Warning Time Delay: 2 sec
30: 2075 rpm HCT Setup
60: 4150 rpm HCT Shutdown Threshold: 223 F
Eng Protection HCT Shutdown Time Delay: 2 sec
Speed/Freq Fault Threshold: 2.0 Hz Eng Protection
Speed/Freq Fault Time Delay: 1.5 s LCT Warning Threshold: 70 F
Low Setup Charger Failed H. Threshold: 18.00 V
Lop Warning Threshold: 35 psi Eng Protection
Lop Warning Time Delay: 5 sec Charger Failed L. Threshold: 5.00 V
Charger Failed Time Delay: 120.0
2 History / About History About Control
Starts: 28 P/N:
Hours: 1.4 S/N: 3025756B03
Control Hours: 5 SW P/N: 3266612
About Genset SW Version: 5.07
Model Number: C40 D6 4 About Display
Control: SW P/N: 3266217
About Genset SW Version: 2.00
KVA (Stand By) Rating: 50 KVA Scrn P/N: 3266219
Scrn Ver: 3.01
3 Screen Adjust Contraste:
Brightnees:
Unit: F, Psi
4 Fault History Fault History Fault History (Es Secuencial)
At: 3.5 Hrs At:
Fault Number: 13 Fault Number:
Low AC Voltage Low AC Voltage
5 Status Status
AVR Dc: 0.0 %
Gov Dc: 00.00 %
6 Lamp Test Verifica los leeds

7 Netwoks Status Netwoks Status Netwoks Status


AMF Modules: 0 Control: 0
Annunciators: 0 I/O Modules: 0
Bar Graph: 0 O/P Panels: 0
Batt Graph: 0