TECHNICAL SITE SURVEY REPORT
(TSSR)
   SITE ID     :___ MW0622___
   SITE NAME   :___KANDE______
             Jun. 2014
                                              3G SITE SURVEY SHEET
Site Name      KANDE                   No           MW0622              Date          12-08-2014
Location Town         Nkhatabay
Site Type      Airtel
Site Type      Greenfield Rooftop Existing Structure Indoor Outdoor VDM Build Cell C Upgrade
GPS Position Measured During Survey                 Latitude       S11.921706       Longitude          E34.178791
ACCESS INFORMATION
Contact Person                                    Number
Substitute                                      Number
Access Days              12-08-2014                       Access road          Good      Bad        Very bad
Notes
TOWER              N/A      Existing        New                         Tower Height                60 m
Antenna Height (2G)                 57 m
Antenna Azimuth (2G) A Sector                 0     B Sector         120       C Sector           240
Microwave Height               52 m
Tower Type     Monopole        Concrete Mono Pole Lattice               Stub    Enviro Spec          Signboard     Triangle
 Other
Type of Loading Required               Urban      Rural     Environ     Strategic     Rooftop/Stub
Terrain Category                flat                     Tower Category                         .
Aviation Lights      Motivated         Metro      Rural        Paint     Yes        No         Colour          red and white
Notes                There are too many microwaves.
EQUIPMENT SHELTER
N/A      New       Existing
Shelter Type       N/A        Isotherm         Special
Equipment Space           Available         Unavailable
Cable Tray Space          Available         Unavailable
Size                2.4x2.8         2.4x2.4      2.0x2.0       Other
Feeder Entry Plate       Existing       New
Notes
OUTDOOR FOUNDATION
  N/A        New     Existing          Renovate
                                                               1
Concret base                3       m by                3              m
Notes
RF&RRU INSTALLATION
A Sector   Jump cable size            1/2      Jump cable length            2m        Qty        2
B Sector   Jump cable size            1/2      Jump cable length            2m        Qty        2
C Sector   Jump cable size            1/2      Jump cable length            2m        Qty        2
A Sector   RRU mounting height                 55m     Fiber &DC Cable length             66m            Qty   2
B Sector   RRU mounting height                 55m     Fiber &DC Cable length             66m            Qty   2
C Sector   RRU mounting height                 55m     Fiber &DC Cable length             66m            Qty   2
Ant Information
Proposal 3G Antenna Height               52m
Available free space range_______(54-57)m_____________________
Proposal Antenna Azimuth          A Sector         0       B Sector          120        C Sector        240
Existing 2G Antenna type        V-pole       X-pole
H-Frame    New         Existing
Antenna Pole     Yes      No                 Qty        3                        Length              2             m
Transmission Type         Tie Cable      Cable        Microwave            Satelite
Trunking (75x50)          N/A PVC Steel            Length         8m       Paint Yes No         Colour         .
Antenna Mount               Wall Mount       Floor Mount           Pole Mount
Access         Workman Cage          Platform         Scaffolding          Cherry Ricker      Abseiling
Notes
DC INFORMATION
Existing Rec. Model      Existing     Capacity                         _4.8KVA___
Output Voltage     +24V      -48V
Existing circuit Breaker Detail:
Breaker      Available    Unavailable       Capacity                         _32A___
Note:
First to shut down ________63*2+32*3_______________________________
Second to shut down _____________________________________________________________
Battery:
Battery Supplier/Type Existing        Capacity   _(2V,600AH)*24_ Group    1
Notes
                                                              2
SURVEY PHOTOS
The photo for Existing Tower
                                     The position for 3G RRU& ANT.
The photo for site environment
                                 3
    The     photo
    for       Site
    location.
4
    The     photo
    for existing
    room
    location or
    outside
    equipments
    The   photo
    for Existing
    DC.
5
    The     photo
    for the space
    for      New
    Equipment.
    The     photo
    for    access
    road