Manual TCH-240 PDF
Manual TCH-240 PDF
5 - 20 TR 50 Hz, 12.5 - 25 TR 60 Hz
Main features :
Single circuit unit : sizes 063 and 073,
Dual circuit unit : sizes 100 to 200,
3 D-Scroll compressor for sizes 125 to 250,
Self-contained rooftop unit
Internal protection of winding for fans
and compressor(s),
Crankcase heater on size 063 to 100, VOYAGER I and II range
Frost protection control system, TCD: Downflow discharge and intake
Direct drive outdoor axial fan : TCH: Horizontal discharge and intake
- 1 fan : TCD/H 063 to 125,
- 2 fans : TCD/H 150 to 250,
Variable pulley-belt drive indoor centrifugal fan,
Galvanised steel water-tight casing,
Disposable filters supplied as standard.
Factory mounted options :
Economizer for fresh air intake
and free-cooling (comparative
enthalpy control),
Motorized hood 0-50% for fresh air intake,
NEW : CO2 sensor (operates with
the economizer),
Smoke detector,
Electric heater,
Disconnect switch (Pre-wired),
Clogged filter sensor,
Oversized drive kit (ton increase available
static pressure),
Field installed accessories :
0-25% manual hood for fresh air intake,
NEW : Remote potentiometer (for remote
control of the motorized hood 0-50%),
Fire thermostat,
Roofcurbs (TCD only),
Control :
Control of the unit by microprocessor,
Non-programmable electronic
thermostat BAYSENS 010,
Programmable electronic thermostat
BAYSENS 019 (accessory).
Interface for communication with Tracer-
Tracker and supervisor Varitrac,
CTI board to adapt to thermostats other BAYSENS 010 BAYSENS 019
than zone sensors.
Operating limits :
Cooling mode
Outdoor air temperature - 18C to + 46C
Min. intake temperature on the indoor coil + 18C
Model TC* 063 073 89 100 125 155 175 200 250 150 180 210 240 300
ARI Gross Cooling Capacity (MBH)1 65.2 80.8 91 106.7 124.9 152.5 176.3 208.2 225.3 150 182 210 242 290
System Power (kW) 6.4 8.2 9.7 10.4 12.2 14.7 18 20 21.3 14.49 17.57 20.0 23.91 28.05
Optional Electric Heater (kW) 26.9 26.9 26.9 26.9 26.9 40.3 53.8 53.8 53.8 54 54 72 72 72
Compressor No./Type 1/Recip. 1/Recip. 1/Recip. 2/Recip. 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Sound Rating (BELS)2 8.6 8.6 8.8 8.8 9.0 9.0 9.2 9.2 9.4 9.2 9.2 9.4 9.4 9.4
Drain Connection Number. 1 1 1 1 1 1 1 2 2 1 1 1 1 1
3
Drain Connection Size in. /4 PVC 3/4 PVC 3/4 PVC 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 21 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT
Outdoor Fan No. Motors/HP 1/0.5 1/0.5 1/0.5 1/0.75 1/0.75 2/0.33 2/0.75 2/0.75 2/0.75 2/0.5 2/0.5 2/1.0 2/1.0 2/1.0
Indoor Fan HP 1.0 1.0 2.0 1.5 2.0 2.0 3.0 3.0 5.0 3.0 3.0 5.0 5.0 7.5
Refrigerant Charge (lbs of R22) 8.5 10 5.7 8.0 8.4 10.8 13.1 12.9 15.9 9.3 17.5 21 18.9 17
per circuit3 9.2 6.8 8.7 9.4 9.5 14.3 21
(1) Cooling mode with inlet air temperature of 27C DB/19C WB and outdoor temperature of 35C. (2) Sound Ratings shown are tested in accordance with ARI standard 270 or 370.
(3) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
Dimensions : see page 56
70
UN-PRC001-EN
YCD-YCH
5 - 20 TR, 12.5 - 25 TR 60 Hz
Main features :
Single circuit unit : sizes 063 to 089,
Dual circuit unit : sizes 100 to 200,
Gas-fired self-contained rooftop unit 3 D-Scroll compressor for sizes 125 to 250,
Internal protection of windings for fans and
VOYAGER I and II range compressor(s),
Crankcase heater on size 063 to 100,
YCD: downflow discharge and intake
Frost protection control system,
YCH : horizontal discharge and intake Direct drive axial outdoor fan :
- 1 fan for sizes 063 to 125.
- 2 fans for sizes 150 to 250.
Variable pulley-belt drive centrifugal indoor
fan,
Galvanised steel water-tight casing,
Disposable filters supplied as standard.
Characteristics of the GAS heating
module :
Burner with forced combustion blower,
High efficiency (> 86%),.
Gases used : natural gas. Option L.P. gas.
Factory mounted options :
Economizer for fresh air intake and free-
cooling (comparative enthalpy control),
Motorized hood 0-50% for fresh air intake,
NEW : CO2 sensor (operates with
the economizer),
Smoke detector,
YCD Propane gas conversion,
Disconnect switch (Pre-wired),
Clogged filter sensor,
Oversized drive kit (ton increase available
static pressure),
Field installed accessories :
0-25% manual hood for fresh air intake,
NEW : Remote potentiometer (for remote
BAYSENS 010 BAYSENS 019 control of the motorized hood 0-50%),
Fire thermostat,
Roofcurbs (YCD only),
Controls :
Operating limits : Control of unit by 24 V microprocessor,
Non-programmable electronic
Cooling mode Heating mode thermostat BAYSENS 010,
Outside air temperature - 18C to + 46C - Programmable electronic thermostat
Min. inlet temperature on indoor coil + 18C - BAYSENS 019.
on the burner - + 5C TC3 interface for communication with
Tracer-Tracker and supervisor Varitrac
CTI board to adapt to thermostats other
than BAYSENS 010 or BAYSENS 019
Model YC* 063 073 89 100 125 155 175 200 250 150 180 210 240 300
ARI Gross Cooling Capacity (MBH)1 65.2 80.8 91 104.3 124.9 152.5 176.3 208.2 225.3 150 182 210 242 290
System Power (kW) 6.4 8.2 9.7 10.9 12.2 14.7 18 20 21.3 14.8 17.94 20.41 24.42 28.05
Heating Output (MBH)2 137.9 137.9 137.9 118.1 118.1 233.1 233.1 268.9 268.9 203 203 284 324 324
First Stage (MBH) 100 100 100 118.1 118.1 166.9 166.9 202 202 142 142 203 243 243
Steady State Efficiency (%) 81 81 81 81 81 81 81 81 81 81 81 81 81 81
1 1 1 1 1 1 1 1 1 1 3 3 3 3
Gas Connection Pipe (in.) /2 /2 /2 /2 /2 /2 /2 /2 /2 /2 /4 /4 /4 /4
Compressor No./Type 1/Recip. 1/Recip. 1/Recip. 2/Recip. 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Sound Rating (BELS)3 8.6 8.6 8.8 8.8 9.0 9.0 9.2 9.2 9.4 9.2 9.2 9.4 9.4 9.4
Drain Connection Number. 1 1 1 1 1 1 1 2 2 1 1 1 1 1
3
Drain Connection Size in. /4 PVC 3/4 PVC 3/4 PVC 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT 1 NPT
Outdoor Fan No. Motors/HP 1/0.5 1/0.5 1/0.5 1/0.75 1/0.75 2/0.33 2/0.75 2/0.75 2/0.75 2/0.5 2/0.5 2/1.0 2/1.0 2/1.0
Indoor Fan HP 1.0 1.0 2.0 1.5 2.0 2.0 3.0 3.0 5.0 3.0 3.0 5.0 5.0 7.5
Refrigerant Charge (lbs of R22) 8.5 10 5.7 8.0 8.4 10.8 13.1 12.9 15.9 9.3 17.5 21 18.9 17
per circuit4 9.2 6.8 8.7 9.4 9.5 14.3 21
(1) Cooling mode with inlet air temperature of 27C DB/19C WB and outdoor
temperature of 35C. (2) High output capacity. (3) Sound Ratings shown are tested in
accordance with ARI standard 270 or 370. (4) Refrigerant charge is an approximate
value. For a more precise value, see unit nameplate and service instructions.
Dimensions : see page 58
LIGHT COMMERCIAL RANGE
71
UN-PRC001-EN
WCD-WCH
5 - 20 TR
Main features :
Single circuit unit : sizes 063 and 073,
Dual circuit unit : sizes 100 to 200,
Internal protection of winding for fans Self-contained rooftop unit
and compressor(s),
Crankcase heater on size 063 to 100,
4-way reversing valve, VOYAGER I and II range
Frost protection control system,
Direct drive outdoor axial fan : WCD: Downflow discharge and intake
- 1 fan : WCD-WCH 063 to 125 WCH: Horizontal discharge and intake
- 2 fans : WCD-WCH 150 to 250,
Variable pulley-belt drive indoor
centrifugal fan,
Galvanised steel water-tight casing,
Disposable filters supplied as standard.
Factory mounted options :
Economizer for fresh air intake and free-
cooling (comparative enthalpy control),
Motorized hood 0-50% for fresh air intake,
NEW : CO2 sensor (operates with
the economizer),
Smoke detector,
Electric heater,
Disconnect switch (Pre-wired),
Washable filters,
Clogged filter sensor,
Oversized drive kit (ton increase available
static pressure),
Field installed accessories :
0-25% manual hood for fresh air intake,
NEW : Remote potentiometer (for remote
control of the motorized hood 0-50%),
Fire thermostat,
Roofcurbs (WCD only),
Duct mounting CO2 sensor kit.
Control :
Control of the unit by microprocessor (24 V),
Non-programmable electronic
thermostat BAYSENS 019,
Programmable electronic thermostat,
Interface for communication with Tracer-
Tracker and supervisor Varitrac,
CTI board to adapt to thermostats other than
BAYSENS 011 or BAYSENS 019. BAYSENS 011 BAYSENS 019
Operating limits :
Cooling mode Heating mode
Outdoor air temperature - 18C to + 46C - 14C to + 18C
Min. intake temperature on the indoor coil + 18C + 10C
Model WC* 063 073 100 125 155 200 150 180 240
ARI Gross Cooling Capacity (MBH)1 65.2 80.8 104.3 124.9 152.5 208.2 152 183.5 233
System Power kW 6.5 8.4 10.5 12.9 15.6 22.3 15.16 18.31 22.2
Heating Output (MBH)2 60.2 73.3 100.2 120.2 130.7 203.3 135 160 208
System Power Heating (kW) 5.4 6.6 9.0 10.5 12.1 18 10.8 15.12 22.2
Compressor No./Type 1/Recip. 1/Recip. 2/Recip. 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll 2/Scroll
Sound Rating (BELS)3 8.6 8.6 8.8 9.0 9.0 9.2 9.2 9.2 9.4
Drain Connection No./Size in. 1/3/4 PVC 1/ 3/4 PVC 1/1 NPT 1/1 NPT 1/1 NPT 2/1 NPT 1/1 NPT 1/1 NPT 1/1 NPT
Outdoor fan No. Motors/HP 1/0.5 1/0.5 1/0.75 2/0.33 2/0.33 2/0.75 2/0.5 2/0.5 2/1.0
Indoor Fan HP 1.0 1.0 1.5 2.0 2.0 3.0 3.0 3.0 5.0
Refrigerant Charge (lbs of R22) 12.5 14.3 11 12 12.3 18 11.1 13.2 22
per circuit4 11.3 11.8 11.4 12.8 21
(1) Cooling mode with inlet air temperature of 27C DB/19C WB and outdoor temperature of 35C. (2) High output capacity. (3) Sound Ratings shown are tested in accordance with
ARI standard 270 or 370. (4) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
Dimensions : see page 57
72
UN-PRC001-EN
TCD-TCH
TED-TEH, YCD-YCH
27.5 - 50 TR
Main features :
3 D-Scroll compressor,
Internal protection of windings for fans
Voyager III and compressor(s),
Frost protection control system,
Direct drive axial outdoor fan :
- 3 fans for sizes 275-300-350 and 330-360-
420,
- 4 fans for sizes 400-500 and 480-600.
Variable pulley-belt drive centrifugal indoor
fan (drive type selected with order).
Factory mounted options :
Economizer for fresh air intake and free-
cooling (comparative enthalpy control),
Barometric relief or exhaust fan,
0-25% manual hood for fresh air intake,
NEW : CO2 sensor (operates with
the economizer),
Smoke detector,
Propane gas conversion (YCD/YCH),
Disconnect switch (Pre-wired),
Washable filters,
Clogged filter sensor,
Oversized drive kit (ton increase available
static pressure),
Hinged access doors,
TCD/TED : downflow discharge and intake Coil guard for condenser,
YCD TCH/TEH : horizontal discharge and intake Field installed accessories (NEW) :
TED/TEH : cooling only + electric heater Remote potentiometer (for remote control
YCD/YCH : Gas fired of the motorized hood 0-50%)
BAYSENS 010 BAYSENS 019 Fire thermostat
Roofcurbs (TCD, TED, YCD only)
Operating limits : Control :
Cooling mode Heating mode Control of unit by 24 V microprocessor,
Non-programmable electronic thermostat
Outdoor air temperature - 18C to + 46C -
BAYSENS 010,
Min. inlet temperature on indoor coil + 18C - Programmable electronic thermostat
on burner - + 5C BAYSENS 019 (accessory),
Interface for communication with Tracer-
Tracker and supervisor Varitrac,
CTI board to adapt to thermostats other
than BAYSENS 010 or BAYSENS 019.
60 Hz 50 Hz
General Date Model TC* 330 360 48 450 600 275 305 350 400 500
ARI Gross Cooling Cap. (MBH)1 329 363 417 513 616 279 304 375 409 505
Heating Output (MBH)2 486 486 486 648 648 405 405 405 542.7 542.7
First Stage (MBH)2 344.5 344.5 344.5 486 486 344.3 344.3 344.3 486 486
Steady State Efficiency (%)3 81 81 81 81 81 81 81 81 81 81
No. Burners/No. Stages2 2/2 2/2 2/2 2/2 2/2
Gas Connection Pipe Size (in.)2 1 1 1 1 1 3
/4 3
/4 3
/4 3
/4 3
/4
Electric Heat Range (kW) 27-90 27-90 27-90 41-108 41-108
Compressor No./Type 2/Scroll 2/Scroll 2/Scroll 3/Scroll 3/Scroll 2/Scroll 2/Scroll 2/Scroll 3/Scroll 3/Scroll
Comp. Size (Nominal Tons) 10/15 15 15 15/15/10 14 10/15 15/15 15/15 15/15/10 15/15/15
Comp. Unit Cap. Steps (%) 100/40 100/50 100/50 100/60/40 100/67/33 100/40 100/50 100/50 100/60/40 100/67/33
Outdoor Fan No Motors/HP 3/1.10 3/1.10 3/1.10 4/1.10 4/1.10 3/0.75 3/0.75 3/0.75 4/0.75 4/0.75
Indoor Fan Type/No. Used FC/1 FC/1 FC/1 FC/1 FC/1 FC/1 FC/1 FC/1 FC/1 FC/1
Indoor Fan Diameter (in) 22.4 22.4 22.4 25.0 25.0 22.4 22.4 22.4 25.0 25.0
Indoor Fan Width (in) 22.0 22.0 22.0 25.0 25.0 22.0 22.0 22.0 25.0 25.0
Indoor Fan Motor HP 7.5/10 7.5/10 7.5/10/15 10/15 10/15/20 7.5 7.5 7.5 10.0 10.0
Filters Type Throwaway Throwaway
Filters No. Yes/16 Yes/16 Yes/16 Yes/17 Yes/17 Yes/16 Yes/16 Yes/16 Yes/17 Yes/17
Filters Recommended Size (in) 16x20x2 16x20x2 16x20x2 16x20x2 16x20x2 16x20x2 16x20x2 16x20x2 16x20x2 16x20x2
Refrigerant Charge 46 46.6 51.5 26.0 25.7 46 46 52 24.5 23.9
(lbs of R22) per circuit4 47.1 54.3 42.5 49.4
(1) Minimum Outside Air Temp.
For Mechanical Cooling (F) (2) Cooling mode with inlet air temperature of 27C DB/19C WB
and outdoor temperature of 35C. (3) High output capacity. (4) Steady state efficiency is rated
in accordance with DOE test procedures. (5) Refrigerant charge is an approximate value. For
a more precise value, see unit nameplate and service instructions. LIGHT COMMERCIAL RANGE
Dimensions : see page 58
73
UN-PRC001-EN
Impack (1.5 - 5 TR)
X
Y
Shipping Weights
Size 018 024 030 036 042 048 060
Model TCC 319 327 354 369 389 513 547
Model WCC 337 337 359 383 400 552 547
Model YCC 341 350 398 454 454 576 604
A
C
E
X
B
Y
D
74
UN-PRC001-EN
TCD/TCH - TED/TEH (25 - 50 TR)
A
C
E
X B
Y D
X Y
A
C
E
X
B
D
Y