Afhx 220 PDF
Afhx 220 PDF
INSTALLATION,  SCREW
 OPERATION & COMPRESSOR
MAINTENANCE     AIR
   MANUAL     COOLED
                                             FLOODED
                                             CHILLERS
    MODEL:
   AFHX Series                                R134a
                60Hz
TABLE OF CONTENTS
To use this manual effectively, you must first identify your unit model
from the unit nameplate.
It is assumed the user of this manual and those who install, operate and
maintain this equipment are experienced and qualified air conditioning
equipment personnel.
A F HX 210 T - 5 S R HR
 Flooded Evaporator
                                                         Blank = R22
                                                         R     = R134a
 Horizontal Screw Compressor
                                                         C      = Compact
 Nominal Tons                                            H      = High Ambient
                                                         S      = Standard
                                                         Q      = Special
 T    = Optional Two
         Compressors                                     5      = 50Hz
 Blank = Standard                                        6      = 60Hz
COMPRESSOR
MIN. % UNIT CAPACITY REDUCTION 25% 12.5% 12.5% 12.5% 12.5% 12.5%
EVAPORATOR
MODEL (QTY) L1R (1) D2R (2) J1R (2) J1R (2) K1R (2) K2R (2)
NOM. WATER FLOW / PD GPM / FT IN WG 499/ 14.67 529/ 7.2 565/ 9.63 618/ 11.16 673/ 11.25 743/ 11.53
MIN/ MAX WATER FLOW GPM 159/ 787 235/ 1174 236/ 1174 236/ 1174 257/ 1281 283/ 1409
MIN/ MAX WATER PD FT IN WG. 1.89/ 33.28 1.65/ 30.52 1.96/ 35.56 1.96/ 35.56 1.99/ 36.06 2.02/ 36.77
CONDENSER
COIL ROWS DEEP/ TOTAL FA (SQ.FT) 4/ 282.3 4/ 282.3 4/ 282.3 4/ 141.2, 3/ 188.2 3/ 376.4 4/ 188.2, 3/ 188.2
NO. OF FAN 12 12 12 14 16 16
ELECTRICAL
GENERAL
OPERATING CHARGE R134a LBS[KG] 567[257] 600[272] 642[291] 703[319] 794[360] 877[398]
COMPRESSOR
MIN. % UNIT CAPACITY REDUCTION 12.5% 12.5% 12.5% 8.33% 8.33% 8.33%
EVAPORATOR
MODEL (QTY) L2R (2) L3R (2) M1R (2) L2R (1), M2R (1) L3R (1), M2R (1) L3R (1), M3R (1)
NOM. WATER FLOW / PD GPM / FT IN WG 852/ 9.02 966/ 10.03 1042/ 9.17 1104/ 11.89 1231/ 14.45 1337/ 14.95
MIN/ MAX WATER FLOW GPM 365/ 1810 390/ 1948 436/ 2173 411/ 2040 423/ 2109 439/ 2184
MIN/ MAX WATER PD FT IN WG. 1.96/ 35.14 1.96/ 35.59 1.93/ 34.47 1.95/ 34.81 1.94/ 35.04 1.97/ 35.22
CONDENSER
COIL ROWS DEEP/ TOTAL FA (SQ.FT) 4/ 188.2, 3/ 235.3 4/ 235.3, 3/ 235.3 4/ 470.6 3/ 256.7, 4/ 385 4/ 641.7 4/ 641.7
NO. OF FAN 18 20 20 20 20 20
ELECTRICAL
GENERAL
OPERATING CHARGE R134a LBS[KG] 1005[456] 1140[517] 1228[557] 1303[591] 1453[659] 1576[715]
2.1 GENERAL                                                   1.) Check all crates and cartons received against
                                                                  the Bill of Lading/ Shipping Papers to be sure
Packaged chillers are designed to cool water or
                                                                  they agree.
other non-corrosive liquids. The liquid to be
cooled is to be circulated through the tubes of a             2.) Check the model number and the electrical
refrigerant evaporator where the temperature is                   characteristics on the nameplate to determine
reduced to the desired level. The heat absorbed by                if they are correct.
the refrigerant in the evaporator is rejected via the         3.) Check for freight damage, shortages or other
condenser where it raises the temperature of                      discrepancies and note them on the delivery
another liquid stream (usually water) being                       receipt before signing.
circulated through the tubes. This heat is usually            In the event that any damage is found, a damage
rejected by a cooling tower or closed circuit                 claim should immediately be filed by the
cooled.                                                       purchaser against the delivering carrier as all
Care should be taken to see that the equipment is             shipments are F.O.B. Factory.
properly installed and adjusted. An installer or
operator should first become familiar with the
information contained in this manual.
                                                              2.3 RIGGING
2.1.1 APPLICATION PRECAUTIONS                                 2.3.1 GENERAL
       The following instructions are intended to                    Each unit has been carefully tested and
       help assure proper and successful                             crafted at the factory where every
       application of your water chilling machine.                   precaution is taken to assure that the unit
                                                                     reaches you in perfect condition. It is very
2.1.2 CHILLED WATER FLOW                                             important that the riggers and movers
       The Dunham-Bush AFHX Packaged                                 should use the same care and precaution in
       Water Chiller is designed for a constant                      moving the equipment into place. Make
       chilled water flow rate, even when the                        sure that chains, cables. or other moving
       cooling load is varying. The machine will                     equipment are placed so as to avoid
       generally perform satisfactorily with                         damage to the unit or piping. The
       steady flow rates deviating from design by                    refrigerant piping must not be used as a
       as much as 10%. However, varying water                       ladder or as a handhold. Do not attach a
       flow rates can cause control instability                      chain hoist sling to the piping or
       which will result in undesirable system                       equipment. Move the unit in an upright
       effects, particularly poor control of leaving                 position and let it down gently from trucks
       chilled water temperature. If two-way                         or rollers.
       valves are used to control flow through
       cooling coils, some means such as an                   2.3.2 RIGGING AND MOVING
       automatic modulating valve should be                          Any unit mounted on skids may be moved
       provided in the system to maintain steady
                                                                     with a forklift, but care must be taken not
       flow through the evaporator.
                                                                     to damage the unit with forks. The skids
       If the chilled water system is arranged for                   should not be removed until the unit is at
       the dual purpose of cooling and heating,                      its final location.
       the evaporator must incorporate valves to
       prevent the flow of hot water through it.                     The AFHX model is to be rigged through
       This can be done with either manual or                        the holes in the base side rails. In all cases,
       automatic shutoff valves, but the method                      spreader bars must be used between
       of control must be that water temperature                     rigging lines to prevent coil or fan deck
       entering the evaporator never exceeds                         damage. The unit must be lifted using All
       90F[32.2C].                                                 Rigging Points. Refer to Rigging
                                                                     Instructions on Figure 2.3.2.
                                                                     All models can be pushed or pulled (with
2.2 INSPECTION                                                       chains) from the control box end only.
When the equipment is delivered, it is important                     Truck forks must be kept level and not
that the following inspection be completed in the                    tilted back. Do not raise the end of the unit
presence of the carrier's representative.                            more than 2"[51mm] off the floor.
The unit should be located so that air may circulate freely and not be recirculated. For proper airflow
and access all sides of the unit must be a minimum of eight feet [2438mm] away from any wall or
obstruction. It is preferred that this distance be increased whenever possible. Care should be taken to
see that ample room is left for maintenance work through access doors and panels. Overhead
obstructions are not permitted. When the unit is in an area where it is enclosed by three walls the unit
must be installed as indicated for units in a pit.
Multi Pit
                                    Notes:
                                    1.) All dimensions are minimal, unless
                                        otherwise noted.
 Corner Wall
                                    2.) Pit installations are not re-
                                        commended. Re-circulation of hot
                                        condenser air in combination with
                                        surface air turbulence cannot be
                                        predicted. Hot air re-circulation will
                                        severely affect unit efficiency (EER)
                                        and can cause high pressure or fan
                                        motor temperature trips. Dunham-
                                        Bush will not be responsible for
                                        ducting fans to a higher level to
                                        alleviate the above mentioned
                                        conditions.
AFHX 210-6SR
AFHX 260-6SR
AFHX 280-6SR
AFHX 310-6SR
AFHX 355-6SR
 210-6SR      2414 [1095]    2652 [1203]   2890 [1311]   3067 [1391]    3195 [1449]   3323 [1507]        -                -       17542 [7957]
 220-6SR      3092 [1403]    3179 [1442]   3265 [1481]   3258 [1478]    3190 [1447]   3123 [1417]        -                -       19107 [8667]
 235-6SR      3272 [1484]    3330 [1511]   3389 [1537]   3428 [1555]    3370 [1529]   3311 [1502]        -                -       20099 [9117]
 260-6SR      3733 [1694]    3667 [1663]   3600 [1633]   3506 [1591]    3610 [1638]   3714 [1685]        -                -       21831 [9903]
 280-6SR      3272 [1484]    3098 [1405]   2924 [1326]   2749 [1247]    2779 [1261]   2953 [1340]   3128 [1419]   3302 [1498]    24205 [10979]
 310-6SR      3412 [1548]    3275 [1486]   3137 [1423]   3000 [1361]    3030 [1374]   3167 [1437]   3304 [1499]   3442 [1561]    25768 [11688]
355-6SR 86 [2184] 40.75 [1035] 68.25 [1734] 68.25 [1734] 68.5 [1740] 68.25 [1734] 68.25 [1734] 40.75 [1035]
405-6SR 86 [2184] 40.75 [1035] 76.5 [1944] 76.5 [1943] 77.5 [1969] 76.5 [1943] 76.5 [1943] 40.75 [1035]
435-6SR 86 [2184] 40.75 [1035] 76.5 [1944] 76.5 [1943] 77.5 [1969] 76.5 [1943] 76.5 [1943] 40.75 [1035]
460-6SR 86 [2184] 40.75 [1035] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 40.75 [1035]
515-6SR 86 [2184] 40.75 [1035] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 40.75 [1035]
555-6SR 86 [2184] 40.75 [1035] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 40.75 [1035]
              2437        2393       2350         2307       2264     2220     2234       2326         2417       2509     2600      2692         28749
 355-6SR
             [1105]      [1086]     [1066]       [1046]     [1027]   [1007]   [1013]     [1055]       [1096]     [1138]   [1179]    [1221]       [13040]
              2810        2781       2752         2723       2694     2665     2705       2734         2763       2792     2821      2850         33091
 405-6SR
             [1275]      [1262]     [1249]       [1235]     [1222]   [1209]   [1227]     [1240]       [1253]     [1266]   [1280]    [1293]       [15010]
              2974        2926       2878         2831       2783     2735     2745       2823         2870       2918     2966      3013         34492
 435-6SR
             [1349]      [1327]     [1306]       [1284]     [1262]   [1241]   [1259]     [1280]       [1302]     [1324]   [1345]    [1367]       [15646]
              2937        2938       2939         2940       2941     2942     2999       2996         2992       2989     2986      2983         35582
 460-6SR
             [1332]      [1333]     [1333]       [1334]     [1334]   [1335]   [1360]     [1359]       [1357]     [1356]   [1354]    [1353]       [16140]
              2984        3035       3086         3137       3188     3240     3296       3243         3190       3136     3083      3030         37648
 515-6SR
             [1354]      [1377]     [1400]       [1423]     [1446]   [1470]   [1495]     [1471]       [1447]     [1423]   [1398]    [1374]       [17077]
              3368        3308       3247         3187       3126     3066     3122       3181         3239       3297     3356      3414         38912
 555-6SR
             [1528]      [1500]     [1473]       [1446]     [1418]   [1391]   [1416]     [1443]       [1469]     [1496]   [1522]    [1549]       [17651]
3.1 GENERAL                                            pump contacts to start & stop this unit. These are
                                                       safety controls, not operational controls.
The unit should be started up only by a
refrigeration technician who is familiar with
                                                       3.4.1 AIR COOLED PACKAGE
accepted operation practices for refrigeration
systems.                                                     CHILLER START-UP
Use small screw unit start-up report to record all            The unit is ready for start-up when the
temperature, pressure, electrical readings and                following       procedures    have     been
control settings. A copy must be forwarded to                 completed.
Dunham-Bush, Inc., before the warranty will be                1. Water piping for the evaporator is
honored.                                                          installed and tested.
                                                              2. Electrical connections are made and
                                                                  properly fused.
3.2 UNIT PIPING                                               3. Unit has been leak tested. Leaks
Each unit has a separate refrigerant circuit for                  corrected, and charge completed.
each compressor. See Figure 3.2 for typical unit              4. Compressor crankcase heater(s) has
piping schematic.                                                 been energized for a minimum of 24
                                                                  hours.
                                                              5. Calibrated refrigerant gages have been
3.3 SYSTEM               WATER           FLOW                     connected to the suction and discharge.
    RATE                                                      6. Turn on the chilled water pump, check
The quantity of chilled water being circulated can                direction of rotation and adjust the
be measured quite accurately (5%) by                             water flow through the evaporator to
determining the water pressure drop through the                   the specified flow rate. Bleed off all
evaporator and reading GPM [m/hr] from the                       entrained air.
evaporator pressure drop curve, Figure 3.3.                   7. Manually energize the fan starters and
Connect reliable pressure gauges to valves                        check the fan rotation. Fans should pull
installed in evaporator entering and leaving water                air through the condenser coil and
vent connections and read pressure difference                     discharge vertically upwards.
with chilled water pump in operation. An                      8. Check all refrigerant valves to be sure
alternative method of determining GPM [m/hr] is                  they are open.
to measure pressure difference from pump inlet to             9. Proceed to System Start-up.
outlet and read GPM [m/hr] from pump curve.                  Compressor #1 will start in about 15
However due to the quality of water at the jobsite,           minutes & proceed to load up if leaving
the accuracy of the curve might vary. Conditions              water temperature is above setpoint.
such as water hardness, organic material,                     Compressor #2 will follow as the demand
suspended solids and water velocity may                       dictates.
contribute to a greater fouling. The quality of the
water could be maintained by chemical treatment
and periodical cleaning. The curve plotted is          3.5 SYSTEM START UP
based on a clean water system.                         1. Before starting the compressor(s), check all
                                                          three phases of supply voltage, of all legs of
                                                          the motor. They must be within 10% of the
3.4 UNIT OPERATION                                        nameplate voltage. Check to be sure
    INCLUDING OVERNIGHT                                   compressor is not running backwards.
    SHUT-DOWN AND                                      2. Start compressor(s), check the gages and note
    MORNING RESTART                                       if the pressures are within the prescribed
Caution: These units may equipped with                    limits.
manifold installed manual discharge valve that         3. Stage unit down until all compressors are off
must be opened before attempting to start.                and check the compressor crankcase sight
Important: Do not use chilled water pump                  glass for oil level. It should be 1/2 to 3/4 of the
operation via the flow switch or Aux chilled water        compressor sight glass.
              AFHX 210-6SR
              AFHX 220-6SR
              AFHX 235-6SR
              AFHX 260-6SR
              AFHX 280-6SR
              AFHX 310-6SR
              AFHX 355-6SR
              AFHX 405-6SR
                                      AFHX 435-6SR
              AFHX 460-6SR            AFHX 555-6SR
              AFHX 515-6SR
4. The electrical control settings should be               operating season or every 6 months if the unit
   checked and if necessary, reset to those                is used year round
   settings indicated on the wiring diagram.               The power supply to the unit may be de-
   Safety controls are factory set and must be             energized to conserve energy. Just remember
   maintained at settings indicated on the wiring          that all heaters will now be inactive, and the
   diagram.                                                evaporator could freeze-up if not properly
5. The temperatures of the chilled water both in           drained.
   and out, should be checked to insure the unit is
   operating within the desired temperatures.
                                                       3.8 SEASONAL                        START-UP
                                                           PROCEDURE
3.6 SHUT-DOWN (OVERNIGHT                               l. Check fan drives for wear, rust, propeller
      OR WEEKEND)                                         clearance, etc. and make necessary repairs &
                                                          adjustments. Grease main fan shaft bearings
To shut down in the unit with compressors on or
                                                          with a good grade of EP ball bearing grease.
off, turn each individual compressor switch. Do
not close any valve. The chilled water pump shall      2. Check & clean condenser fin surface if
then be turned off. Finally, do not open the main         necessary. Use a warm water soap solution,
unit disconnect. Main power is required to keep           being careful not to bend fins. Comb out bent
the sump heaters.                                         fin areas.
                                                       3. Check all power supply connections at all
Important: Discontinue chilled water                      points, and all control terminal screws for
pump operation when unit is not                           tightness.
operational.
                                                       4. Energize main power to unit & leave on for at
Note: For chillers operating in low                       least 24 hours in order for compressors to
ambient, if it is possible that the overnight             thoroughly warm up.
ambient will drop below 45F [7C], it is              5. Start chilled water pump and verify correct
preferable to leave the chilled water pump                flow-rate glycol % if required. Bleed-off
on.                                                       system air if necessary.
                                                       6. Open main discharge valve in discharge
                                                          header.
3.7 SEASONAL SHUT-DOWN                                 7. Open liquid valve on sealpot.
    PROCEDURE                                          8. Turn control circuit power switch on, and all
                                                          individual compressor circuit switches. Press
Standard Ambient Units                                    computer keyboard reset key (RST).
1. Follow standard overnight shutdown procedure           Compressors should start after start-up clock
2. Turn off chilled water pump                            times out and will come on in sequence to
3. Close manual discharge valve                           satisfy the existing load.
4. Close liquid valve on sealpot
5. If ambient temperature during the extended          3.9 SAFETY RELIEF VALVES
   shut-down period will not get below freezing,       Each pressure vessel is protected by a safety relief
   the chilled water system may be left filled, If     valve as required by ASME Code. Each
   the ambient temperature will be below               compressor is protected by a relief valve which is
   freezing, drain all water thoroughly, removing      vented to atmosphere. Never install any kind of
   all vent & drain plugs from both heads of the       shut-off valve in a safety relief vent line.
   evaporator, and blow out tubes will
   compressed air to avoid serious stagnant water
   corrosion.                                          3.10 REFRIGERATION CYCLE
6. Finally, it is recommended that an oil sample               -MULTIPLE COMPRESSOR
   be taken from each compressor & submitted                    AFHX
   for lab analysis. Dunham-Bush offers this           Following is the normal sequence of operation for
   service in its "Oil Kare" program. This             a unit installed in a typical air conditioning
   analysis should be done at the end of each          system. Refer to Figure 3.2, the typical piping
                                                                              AFHX Standard R134a 60Hz  IOM Manual
                                                  - 22 -
3.0 OPERATION
schematic for multiple compressor AFHX unit.             system designed to feed refrigerant liquid into the
Each horizontal screw compressor discharges hot,         compressor to provide additional motor cooling as
high pressure gas into a hot gas manifold through        required. The liquid injection control the
an oil separator and is then split and routed into       compressor discharge gas temperature below
the left-hand and right-hand side condenser where        158F[70C], the maximum discharge operating
it condenses, rejecting heat to the outdoor air          temperature of these compressors.
drawn through the coil by fans. The liquid
refrigerant from the condenser is drain out from
bottom of the condenser coil through liquid stop
                                                         3.13 HYDRAULIC CAPACITY
valve into the economizer feed line.
The refrigerant flows through the economizer                  CONTROL SYSTEM
feed ball valve, dropping its pressure, causing it to    Each compressor has a hydraulic control system
flash. It then flows into the flash economizer tank      to supply the proper force necessary to actuate the
which is at an intermediate pressure between             slide valve, thereby regulating compressor
condenser and evaporator Liquid is centrifugally         loading for maximum unit capacity. It is
separated from the flash gas and the liquid drains       composed of a normally closed solenoid valve
to the bottom of the tank, exits via the economizer      (SV1), a normally closed solenoid valve (SV2), a
drain line, and passes through the economizer            slide valve, rod, cylinder and piston. The slide
drain ball valve. Both economizer ball valves are        valve and the piston are connected by the rod.
actuated by a Modutrol motor that adjusts flow to        During start up, valve SV1 is energized while
maintain an appropriate refrigerant level in the         valve SV2 is not energized. There will not be a
evaporator, determined by a liquid level float           sufficient oil pressure in the cylinder to overcome
switch.                                                  the opposing spring force. This starting position
From the drain line, liquid refrigerant flows into       of the side valve allows the maximum amount of
the flooded evaporator, where it boils, cooling the      refrigerant to bypass the compression chamber i.e
water flowing inside evaporator tubes. Vapor             25% of full load. This minimum load will require
from the boiling refrigerant flows up the suction        low starting current which is important in
pipes through a shut-off valve (optional), suction       protecting the compressor motor. When loading,
check valve and suction filter (inside compressor)       valve SV1 is not energized while valve SV2 is
into the compressor where it is compressed and           energized. Oil will flow into the cylinder, building
starts the cycle again.                                  sufficient pressure to overcome the opposing
Vapor flows from the top of flash economizer into        spring force causing the slide valve moving to the
the compressor at the vapor injection port, which        right. This will increase the effective compression
feeds it into the compressor part way through the        volume in the compression chamber and hence
compression process. Check valve prevents                the refrigeration flow rate. As a result,
backflow at shutdown in multi-compressor units.          refrigeration capacity increases. When the
All compressors operate in parallel on a common          compressor is given a hold command, valve SV1
evaporator and condenser.                                and SV2 are not energized. This will prevent oil
                                                         flow into or out of the cylinder causing the piston
                                                         to halt. During unloading, valve SV1 is energized
                                                         while valve SV2 is not energized. The spring
3.11 FAN CYCLING                                         force will cause oil to bleed from the cylinder and
On start-up, all fan will remain off (some units         push the slide valve towards its original position.
may have base fans which run together with
compressor). As the head pressure builds up, next
fan stage will start. Subsequently fan stage will                              SOLENOID
                                                                                VALVE 1
                                                                                                     SOLENOID
                                                                                                      VALVE 2
start if the head pressure continues to rise. Refer
wiring circuit diagram for number of fan stage.                 Start           Energize             Not Energize
Each compressor is fitted with a liquid injection Stable Not Energize Not Energize
4.2 WIRING DIAGRAM                                             - power has been on the controller for 15 minutes
                                                               - all safety conditions satisfied
Figure 4.2 are wiring diagrams for 2-compressor
                                                               - leaving chilled water temperature 2F [1.1C]
unit control by Vision 2020i controller. This may
                                                                 or more above setpoint
not be an accurate representation of your unit. It is
best to use the wiring diagram mounted in the                  A compressor is started by first energizing 1MC
package control panel. A copy of that diagram is               followed by 1DC and 1SC. Anti-recycle time of
furnished with the unit owners manual.                        15 minutes is initiated within the computer at
                                                               start.
                                                               When the compressor starts, the controller
4.3 TYPICAL OPERATION                                          monitors amperage by means of 1CT, voltage
In order to start a compressor, the following                  using 3T, leaving water temperature using TS,
conditions must be met:                                        and condensing pressure. These inputs are used to
- system voltage above phase control relay (PCR)               control the loading and staging of the compressor.
  setting                                                      The compressor's loading is controlled by pulsing
- chilled water pump running                                   signals to the load and unload solenoids.
- chilled water flow switch made                               To shut down the unit automatically, the customer
- compressor circuit breakers on                               control contacts must be opened. To shut down
- customer unit control contact closed                         the unit manually, simply shut off the compressor
- control switch and compressor switches on                    switches. This will cause a no-run alarm that must
- reset pressed on controller keypad                           be reset to restart the compressor.
         The three buttons at the bottom left are                              Scroll the various screens when the
         to access different level of setting                                  cursor is in the top left of the display.
                                                                               If the cursor is inside a numeric field,
         changes.                                              UP              the button increases or decreases
                                                                               the corresponding value. If the field is
         These are 'User', 'Technician'        and                             a selection, pressing the button
                                                                               displays the available options.
         'Factory' levels, from left.
                                                               DOWN            See the UP arrow
         It can only be access depend on the
         password level. The higher password can
                                                                               To move the cursor around the
         access the lower password level's setting             ENTER           screens and to save the values of the
                                                                               set parameters
         and not vice versa.
                                                                    ALARM HISTORY
       Press down arrow key or press
       setpoint key to go to next screen:                    001-C1 Starter
                                                             19:03    05/12/05
                                                            TR: 030.2 LWT: 64.3 [17.9]
                                                            DP: 191 [13.6]
                                                            SP: 076 [5.4]
       Repeat the same steps to go to other
       setpoints screen and perform setpoint               Press down arrow key or press alarm
       modification.                                       key to go to next screen for other alarm
                                                           history:
4.4.2.5 Clock key:
       To read the current day, time and date,
       unit scheduling and ice-cel mode
       scheduling (optional), press the clock              To clear alarm history, press input key
       key                                                 and authorization key together and then
                                                           press the alarm key again. Now the
                                                           display should be showing No alarm
4.4.3 Authorization
                                                           Press down arrow key or user key to go
4.4.3.1 Authorization key                                  to next screen for other setpoint:
        To get authorization level, press
        authorization key:
        Press enter key and use the up-down         4.4.5 TECHNICIAN KEY and MENU
        arrow key to change the password
        settings and press enter key to confirm.
                                                    4.4.5.1 Technician status key
                                                           This key is use to view and change the
                                                           compressor FLA setpoint, sensors
        Now the authorization status change to             calibration, manually control digital
        different access level.                            inputs and outputs, manually control
                                                           compressor. In order to gain access to
4.4.4   Advanced user key and                              this button, you must be authorized and
                                                           log in at least as user level. See the
        menu
                                                           authorization section about this
                                                           procedure.
4.4.4.1 User Key
        User key is use to view and change the      4.4.5.2 Technician status key main
        pressure, ampere safety limits and                  menu
        liquid injection temperature setpoints,             Press technician key to go to
        unit of measurements. In order to gain              technician setpoints main menu:
        access to this button, you must be
        authorized and log in at least as user
        level.
                                                           The display is showing the data as
                                                           follows:
        Press the user key and display is
        showing the data as follows:                               Technician Setpoints
                                                                        Main Menu
                 USER SETPOINT 1                            Comp FLA Calibration
                                                            Sensor Calibration
                High Pressure Safety                        Manual Control
                      Limits                                Compressor Control
         Hold=          246PSI [17.0BAR]                    Sensors Override
         Unload=        256PSI [17.7BAR]
         Cutout=        270PSI [18.6BAR]                   Press enter key to move the cursor
                                                           to the sub-menu.
                                                                        AFHX Standard R134a 60Hz  IOM Manual
                                               - 32 -
4.0 ELECTRICAL
        The display is showing the data as                 Use up or down arrow key to move the
        follows:                                           cursor to the desired 'Sensor
                                                           Calibration',
                Technician Setpoints
                     Main Menu
         Comp FLA Calibration 
         Sensor Calibration                                The display is showing the data as
         Manual Control                                    follows:
         Compressor Control
         Sensors Override                                        Sensor Offset 1
                                                                 Suction Press
4.4.5.3 Compressor FLA Calibration:                         Current =        076PSI [5.4BAR]
        To calibrate compressor FLA, press                  Average =        187PSI [8.6BAR]
        down arrow key to go the sub-menu                   24Hrs MAX = 200PSI [11.4BAR]
        'Comp FLA Calibration',                             24Hrs MIN = 074PSI [4.6BAR]
                                                            Calibration = 00PSI [0.0BAR]
       The display is showing the data as                  The display is showing the data as
       follows:                                            follows:
       Use up or down arrow key to move the                  Press technician key to go to technician
       cursor to the desired digital input or                setpoints main menu and press enter
       relay output,                                         key four times to move the cursor to the
                                                             manual control sub-menu:
          automatic start after PCR failure.            method of control is enhanced with adaptive, self-
          Compressor will not start for 15              learning, fan control logic. The end result is
          minutes after failure. To select manual       condenser control that offers significantly reduced
          reset, set power loss setpoint to             fan cycling and improved efficiency. The two
          MANUAL. In this case, a power loss            types of air-cooled condenser control logic are
          alarm will be stored by the controller        explained as follows:
          and Reset Alarm must be pressed to
          start.
                                                        1. Adaptive Individual Air-cooled Condenser
                                                           Control
4.4.6.18 Sensor Alarm                                      This type of control is based upon a single
          If the computer measures an analog               compressor per circuit. The individual
          value (temperature, pressure.) that is far       discharge pressure on that circuit will be the
          beyond normal operating values, the              controlling pressure.
          associated compressors are shutdown.
          The computer then stores the alarm            2. Adaptive      Air     Combined      Air-cooled
          code corresponding to the sensor alarm.          Condenser Control
          A sensor alarm indicates a problem in            This type of control is based upon a condenser
          the analog measurement system.                   that is controlled by the highest discharge
                                                           pressure from any one of the compressors
4.4.6.19 No-Stop Alarm                                     sharing that circuit (compressor 1&2 - share;
                                                           compressor 3&4 - share). The highest
          If the controller turns off a compressor,
                                                           discharge pressure between the sharing
          but the compressor digital input does
          not turn off, a No-Stop alarm is                 compressors will be the controlling pressure.
          generated. The computer will turn off
          the control power relay which disables
          all compressor control circuits and will      4.5.1     Air Cooled Condenser
          turn on the alarm light. This alarm                     Control Setpoints
          indicates a wiring or hardware error.
                                                        The air-cooled condenser setpoints are as follows:
Condenser points (i.e. fans) will be turned off    4.5.3.1 Adaptive Control Logic
based upon the value in the setpoint COND ST2               The controller enhances the condenser
OFF (COND Stage 2 turn OFF point). As the                   control logic above with a unique,
discharge pressure is reduced, the condenser                adaptive, self-learning fan control logic.
points will be turned off based upon the COND               These enhancement results in a control
ST2 OFF setpoint, plus the value in the COND                scheme that offers reduced fan cycling
DIFF OFF setpoint for each stage number above               and improved efficiency. Adaptive
stage 2. Stage 2 of condenser staging will be               Control Logic automatically adjusts the
                                                            fan cut-in offset based upon the
turned off based upon the value in the setpoint
                                                            following criteria:
(COND ST2 OFF). See below for an example of
condenser staging.                                          1. If the last fan turned on (including
                                                               FAN 1) is cycled off in 10 minutes
                                                               or less, then a COND ON OFFSET
4.5.2     Increasing Condenser                                 value will be incremented by 5 psig
          Pressure                                             [0.3 BAR]. This increases the fan 1
                                                               turn on value (COND ST1 ON plus
(Example of 4 stage fan cycling)                               COND ON OFFSET) which in turn
COND FAN1 ON when discharge pressure is >                      increases all of the fan turn on
140psig [9.7BAR] (COND Stage 1 ON setpoint)                    settings. This process will continue
                                                               until fan cycling ceases or the
COND FAN2 ON when discharge pressure is >                      adjusted turn on point for the last fan
156psig [10.8BAR] (COND Stage 1 ON plus                        stage is 217 psig [15.0BAR]. This
1xCOND DIFF ON setpoint values)                                will also be a setpoint.
COND FAN3 ON when discharge pressure is >                   2. The cut-in offset (COND ON
172psig [11.9BAR] (COND Stage 1 ON plus                        OFFSET) will be decreased by 5
2xCOND DIFF ON setpoint values)                                psig [0.3 BAR] if the last fan to be
                                                               turned on has not cycled off within 1
COND FAN4 ON when discharge pressure is >                      hour. The offset will continue to
188psig [13.0BAR] (COND Stage 1 ON plus                        decrease by 5 psig [0.3 BAR] every
3xCOND DIFF ON setpoint values)                                10 minutes unless fan cycling begins
                                                               again.
And so on for the number of condenser fans
supplying the circuit.                                      The Adaptive Control Logic will only
                                                            affect the condenser fan turn on logic, it
                                                            will not affect the fan turn off logic.
4.5.3    Decreasing Condenser
         Pressure
(4 fan example "continued")                        4.6 Master/Slave Control
                                                       Sequence
COND FAN4 OFF when discharge pressure is <
124psig [8.5BAR] (COND Stage 2 OFF plus            The optional master/slave control sequence is
2xCOND DIFF OFF setpoint values)                   used to sequence multiple chillers in one
                                                   installation according to the building load
COND FAN3 OFF when discharge pressure is <         demand. It also controls the dedicated chilled
118psig [8.1BAR] (COND Stage 2 OFF plus            water pump or motorized valve.
1xCOND DIFF OFF setpoint values)                   Vision 2020i Controller offers this feature with
COND FAN2 OFF when discharge pressure is <         minimized field wiring cost compare to
112psig [7.7BAR] (COND Stage 2 OFF setpoint        conventional method that involves lots of
value)                                             hardware cost. It is carried out this control
                                                   function    via   the     advanced      DBLAN
COND FAN1 OFF when discharge pressure is <         communication bus to implement the network
105psig [7.2BAR] (COND Stage 1 OFF setpoint        management for multiple chillers lead/lag
value)                                             communication, sequencing and monitoring.
                                                                         AFHX Standard R134a 60Hz  IOM Manual
                                              - 39 -
4.0 ELECTRICAL
                                                              Graphic
                                                              Display
                                                              (option)
DBLAN
DB3 DBG1 DB3 DBG1 DB3 DBG1 DB3 DBG1 DB3 DBG1 DB3 DBG1
#1 #2 #3 #4 #5 #6
Notes
a) Each chiller has a stand-alone master DB3 board and dedicated graphic display with multiple DB1
   expanders board connected to J23 on DB3
b) Each chiller DB3 will be connected to DBLAN network through J11 connector
c) The chiller lead/lag selection can be determined by
     Manual lead/lag setpoint
     Schedule and holiday setup
     Alarm conditions
d) The lead/lag selection determine the chiller operation sequence as follows,
        Lead chiller              Normal chillers operation sequence                      When DBLAN fails
         selection
e) If the lead/lag selection is changed over to a different chiller, the sequence of operation will be
   rotated
f) Each chiller will use a network address setpoint to determine individual chiller network address
g) Each chiller will require a dedicated chilled water pump or motorized valve digital output, unit
   enable and chilled flow status digital inputs as well as enable next output command.
                                    Vision 2020i
              5 sec
                                                        Turn off DB3 controller.
                                                                                   Terminal config
                                                                                    Press ENTER
                                                                                     To continue
The following mask will appear. Set pLAN
address to 1 (or accordingly) using Up and
Down arrow key. Press Enter key to save and
exit.
            PLAN Address : 1
            Up : Increase                                   Push enter to continue.
            Down : Decrease                                 Then the display appears:
            Enter : Save & Exit
                                                                        P:01     Adr         Priv/Shared
                                                                        Trm1     17          Pr
                                                                        Trm2     32          Sh
                                                                        Trm 3     None       --- OK? NO
Set Trm1, Trm2 and Trm3 to 18 Pr,32 Sh                      Set Trm1, Trm2 and Trm3 to 19 Pr,32 Sh
and None ---, change the 'NO' to 'YES'(to                     and None ---, change the 'NO' to 'YES'(to
confirm and save) and press enter.                              confirm and save) and press enter.
            P:02      Adr        Priv/Shared                                   P:02       Adr         Priv/Shared
            Trm1      18         Pr                                            Trm1       19          Pr
            Trm2      32         Sh                                            Trm2       32          Sh
            Trm 3      None      --- OK? NO                                    Trm 3       None       --- OK? NO
At the third chiller unit Vision 2020i terminal:                With the above settings, terminal with address 17
Press the three keys again, the display will                    will only work with the controller with address 1,
appears:                                                        terminal 18 will only work with the controller
            Display address                                     with address 2, terminal 19 will only work with
            Setting            : 19                          the controller with address 3 and a terminal with
                                                                address 32 will work with both.
            I/o Board address:       03
                       Terminal config
                        Press ENTER
                         To continue                            Red          Yellow        Green
                          Vision 2020i controller is synchronized with all the other DBLAN nodes.
                 ON
                          The node is working correctly.
  GREEN
                OFF       Vision 2020i controller is not network connected or it doesnt receive any signal from the DBLAN
                          Vision 2020i controller software not compatible or variables database not correct, contact Dunham-
                 ON
   RED                    Bush Service Personnel.
PSIG KPA F C PSIG KPA F C PSIG KPA F C PSIG KPA F C PSIG KPA F C
0.00   101.38 -14.70    -25.94   53.00   466.90 56.90   13.83 106.00 832.41   90.90   32.72   159.00 1197.93 115.00    46.11   212.00   1563.45 134.10 56.72
1.00   108.28 -12.00    -24.44   54.00   473.79 57.70   14.28 107.00 839.31   91.50   33.06   160.00 1204.83 115.40    46.33   213.00   1570.34 134.40 56.89
2.00   115.17   -9.50   -23.06   55.00   480.69 58.50   14.72 108.00 846.21   92.00   33.33   161.00 1211.72 115.80    46.56   214.00   1577.24 134.70 57.06
3.00   122.07   -7.10   -21.72   56.00   487.59 59.30   15.17 109.00 853.10   92.50   33.61   162.00 1218.62 116.20    46.78   215.00   1584.14 135.10 57.28
4.00   128.97   -4.80   -20.44   57.00   494.48 60.10   15.61 110.00 860.00   93.00   33.89   163.00 1225.52 116.60    47.00   216.00   1591.03 135.40 57.44
5.00   135.86   -2.60   -19.22   58.00   501.38 60.90   16.06 111.00 866.90   93.50   34.17   164.00 1232.41 117.00    47.22   217.00   1597.93 135.70 57.61
6.00   142.76   -0.50   -18.06   59.00   508.28 61.60   16.44 112.00 873.79   94.00   34.44   165.00 1239.31 117.40    47.44   218.00   1604.83 136.00 57.78
7.00   149.66   1.50    -16.94   60.00   515.17 62.40   16.89 113.00 880.69   94.50   34.72   166.00 1246.21 117.70    47.61   219.00   1611.72 136.40 58.00
8.00   156.55   3.50    -15.83   61.00   522.07 63.10   17.28 114.00 887.59   95.00   35.00   167.00 1253.10 118.10    47.83   220.00   1618.62 136.70 58.17
9.00   163.45   5.30    -14.83   62.00   528.97 63.90   17.72 115.00 894.48   95.50   35.28   168.00 1260.00 118.50    48.06   221.00   1625.52 137.00 58.33
10.00 170.34    7.20    -13.78   63.00   535.86 64.60   18.11 116.00 901.38   96.00   35.56   169.00 1266.90 118.90    48.28   222.00   1632.41 137.30 58.50
11.00 177.24    8.90    -12.83   64.00   542.76 65.30   18.50 117.00 908.28   96.50   35.83   170.00 1273.79 119.30    48.50   223.00   1639.31 137.60 58.67
12.00 184.14    10.60   -11.89   65.00   549.66 66.00   18.89 118.00 915.17   97.00   36.11   171.00 1280.69 119.70    48.72   224.00   1646.21 138.00 58.89
13.00 191.03    12.30   -10.94   66.00   556.55 66.80   19.33 119.00 922.07   97.50   36.39   172.00 1287.59 120.00    48.89   225.00   1653.10 138.30 59.06
14.00 197.93    13.90   -10.06   67.00   563.45 67.50   19.72 120.00 928.97   98.00   36.67   173.00 1294.48 120.40    49.11   226.00   1660.00 138.60 59.22
15.00 204.83    15.50   -9.17    68.00   570.34 68.20   20.11 121.00 935.86   98.40   36.89   174.00 1301.38 120.80    49.33   227.00   1666.90 138.90 59.39
16.00 211.72    17.00   -8.33    69.00   577.24 68.90   20.50 122.00 942.76   98.90   37.17   175.00 1308.28 121.20    49.56   228.00   1673.79 139.20 59.56
17.00 218.62    17.50   -8.06    70.00   584.14 69.50   20.83 123.00 949.66   99.40   37.44   176.00 1315.17 121.50    49.72   229.00   1680.69 139.50 59.72
18.00 225.52    20.00   -6.67    71.00   591.03 70.20   21.22 124.00 956.55   99.90   37.72   177.00 1322.07 121.90    49.94   230.00   1687.59 139.80 59.89
19.00 232.41    21.40   -5.89    72.00   597.93 70.90   21.61 125.00 963.45 100.30    37.94   178.00 1328.97 122.30    50.17   231.00   1694.48 140.10 60.06
20.00 239.31    22.80   -5.11    73.00   604.83 71.60   22.00 126.00 970.34 100.80    38.22   179.00 1335.86 122.60    50.33   232.00   1701.38 140.40 60.22
21.00 246.21    24.10   -4.39    74.00   611.72 72.20   22.33 127.00 977.24 101.30    38.50   180.00 1342.76 123.00    50.56   233.00   1708.28 140.80 60.44
22.00 253.10    25.40   -3.67    75.00   618.62 72.90   22.72 128.00 984.14 101.70    38.72   181.00 1349.66 123.40    50.78   234.00   1715.17 141.10 60.61
23.00 260.00    26.70   -2.94    76.00   625.52 73.50   23.06 129.00 991.03 102.20    39.00   182.00 1356.55 123.70    50.94   235.00   1722.07 141.40 60.78
24.00 266.90    28.00   -2.22    77.00   632.41 74.20   23.44 130.00 997.93 102.70    39.28   183.00 1363.45 124.10    51.17   236.00   1728.97 141.70 60.94
25.00 273.79    29.20   -1.56    78.00   639.31 74.80   23.78 131.00 1004.83 103.10   39.50   184.00 1370.34 124.50    51.39   237.00   1735.86 142.00 61.11
26.00 280.69    30.50   -0.83    79.00   646.21 75.50   24.17 132.00 1011.72 103.60   39.78   185.00 1377.24 124.80    51.56   238.00   1742.76 142.30 61.28
27.00 287.59    31.70   -0.17    80.00   653.10 76.10   24.50 133.00 1018.62 104.00   40.00   186.00 1384.14 125.20    51.78   239.00   1749.66 142.60 61.44
28.00 294.48    32.80   0.44     81.00   660.00 76.70   24.83 134.00 1025.52 104.50   40.28   187.00 1391.03 125.50    51.94   240.00   1756.55 142.90 61.61
29.00 301.38    34.00   1.11     82.00   666.90 77.30   25.17 135.00 1032.41 104.90   40.50   188.00 1397.93 125.90    52.17   241.00   1763.45 143.20 61.78
30.00 308.28    35.10   1.72     83.00   673.79 78.00   25.56 136.00 1039.31 105.30   40.72   189.00 1404.83 126.30    52.39   242.00   1770.34 143.50 61.94
31.00 315.17    36.20   2.33     84.00   680.69 78.60   25.89 137.00 1046.21 105.80   41.00   190.00 1411.72 126.60    52.56   243.00   1777.24 143.80 62.11
32.00 322.07    37.30   2.94     85.00   687.59 79.20   26.22 138.00 1053.10 106.20   41.22   191.00 1418.62 127.00    52.78   244.00   1784.14 144.10 62.28
33.00 328.97    38.40   3.56     86.00   694.48 79.80   26.56 139.00 1060.00 106.70   41.50   192.00 1425.52 127.30    52.94   245.00   1791.03 144.40 62.44
34.00 335.86    39.50   4.17     87.00   701.38 80.40   26.89 140.00 1066.90 107.10   41.72   193.00 1432.41 127.70    53.17   246.00   1797.93 144.70 62.61
35.00 342.76    40.50   4.72     88.00   708.28 81.00   27.22 141.00 1073.79 107.50   41.94   194.00 1439.31 128.00    53.33   247.00   1804.83 145.00 62.78
36.00 349.66    41.50   5.28     89.00   715.17 81.50   27.50 142.00 1080.69 108.00   42.22   195.00 1446.21 128.40    53.56   248.00   1811.72 145.30 62.94
37.00 356.55    42.50   5.83     90.00   722.07 82.10   27.83 143.00 1087.59 108.40   42.44   196.00 1453.10 128.70    53.72   249.00   1818.62 145.60 63.11
38.00 363.45    43.50   6.39     91.00   728.97 82.70   28.17 144.00 1094.48 108.80   42.67   197.00 1460.00 129.10    53.94   250.00   1825.52 145.90 63.28
39.00 370.34    44.50   6.94     92.00   735.86 83.30   28.50 145.00 1101.38 109.20   42.89   198.00 1466.90 129.40    54.11   251.00   1832.41 145.20 62.89
40.00 377.24    45.50   7.50     93.00   742.76 83.90   28.83 146.00 1108.28 109.70   43.17   199.00 1473.79 129.70    54.28   252.00   1839.31 146.40 63.56
41.00 384.14    46.40   8.00     94.00   749.66 84.40   29.11 147.00 1115.17 110.10   43.39   200.00 1480.69 130.10    54.50   253.00   1846.21 146.70 63.72
42.00 391.03    47.40   8.56     95.00   756.55 85.00   29.44 148.00 1122.07 110.50   43.61   201.00 1487.59 130.40    54.67   254.00   1853.10 147.00 63.89
43.00 397.93    48.30   9.06     96.00   763.45 85.60   29.78 149.00 1128.97 110.90   43.83   202.00 1494.48 130.80    54.89   255.00   1860.00 147.30 64.06
44.00 404.83    49.20   9.56     97.00   770.34 86.10   30.06 150.00 1135.86 111.30   44.06   203.00 1501.38 131.10    55.06   256.00   1866.90 147.60 64.22
45.00 411.72    50.10   10.06    98.00   777.24 86.70   30.39 151.00 1142.76 111.80   44.33   204.00 1508.28 131.40    55.22   257.00   1873.79 147.90 64.39
46.00 418.62    51.00   10.56    99.00   784.14 87.20   30.67 152.00 1149.66 112.20   44.56   205.00 1515.17 131.80    55.44   258.00   1880.69 148.20 64.56
47.00 425.52    51.90   11.06    100.00 791.03 87.80    31.00 153.00 1156.55 112.60   44.78   206.00 1522.07 132.10    55.61   259.00   1887.59 148.50 64.72
48.00 432.41    52.70   11.50    101.00 797.93 88.30    31.28 154.00 1163.45 113.00   45.00   207.00 1528.97 132.40    55.78   260.00   1894.48 148.70 64.83
49.00 439.31    53.60   12.00    102.00 804.83 88.80    31.56 155.00 1170.34 113.40   45.22   208.00 1535.86 132.80    56.00   261.00   1901.38 149.00 65.00
50.00 446.21    54.40   12.44    103.00 811.72 89.40    31.89 156.00 1177.24 113.80   45.44   209.00 1542.76 133.10    56.17   262.00   1908.28 149.30 65.17
51.00 453.10    55.30   12.94    104.00 818.62 89.90    32.17 157.00 1184.14 114.20   45.67   210.00 1549.66 133.40    56.33   263.00   1915.17 149.60 65.33
52.00 460.00    56.10   13.39    105.00 825.52 90.40    32.44 158.00 1191.03 114.60   45.89   211.00 1556.55 133.80    56.56   264.00   1922.07 149.90 65.50
NOTE : PRESSURE AND TEMPERATURE ARE STATED IN PSIA(KPA) AND F(C) RESPECTIVELY.
The unit has four devices designed to protect                    Be careful not to overcharge the machine.
compressor motors and manual motor controllers                   overcharging will result in considerable
from electrical malfunctions: Circuit breakers,                  liquid logging in the condenser, and
starter overload relays, under voltage relay, and                excessive condensing pressure.
motor over temperature protectors (optional).
                                                                 To add refrigerant, connect a refrigerant
If the under voltage relay trips, it is a sign of                vessel to the 1/4" back seating port of the
trouble in incoming power. If it trips again after               suction valve. Purge the air from the tube
resetting, call your electric utility to investigate             with refrigerant gas before connecting.
the problem. If circuit breaker or motor overload                With the unit running, open the refrigerant
relay or motor over temperature protectors trip,                 vessel vapor connection slightly. If the
this is a sign of possible motor trouble. DO NOT                 refrigerant vessel is warmer than the
reset and try to run compressor again. Call                      evaporator, refrigerant will more readily
authorized service representative to check for                   flow from the vessel into the unit.
motor trouble. Resetting these safety devices and
repeated starting could turn a minor motor
problem into a costly major motor burnout.
                                                         5.8 OIL CHARGE
5.9 TROUBLESHOOTING
    SYMPTOM                  POSSIBLE CAUSE                                             REMEDY
1. Unit will not        a.) Power off.                       a.) Check main disconnect switch and main line fuses.
   start.               b.) No control power.                b.) Check control transformer fusing.
                        c.) Compressor circuit               c.) Close circuit breakers. If trip, check compressor.
                            breakers open.
                        d.) Phase control relay open.        d.) Check for power supply problems ( low voltage, phase
                                                                 imbalance). When corrected, press reset button.
                        e.) Flow Switch open.                e.) Start pumps, check flow switch.
                        f.) Compressor switch open.          f.) Turn switch on. Check alarm status. Correct problem.
                        g.) Controller shutdown not          g.) Press reset button.
                            reset.
2. Compressor           a.) Low voltage.                     a.) Check at main entrance and at unit. Consult power
   hums but does                                                 company if voltage is low and increase wire size to the
   not start.                                                    unit if voltage is normal at main and low at unit.
                                                                 Voltage must be within 10% of motor nameplate
                                                                 rating.
                        b.) No power on one phase of         b.) Check fuses and wiring.
                            3 phase unit.
                        c.) Faulty starter or contactor.     c.) Check the contacts and time delay on part wind start.
3. Compressor will      a.) Cooling not required.            a.) Apply load.
   not start when       b.) Computer's time delay            b.) Wait 15 minutes max.
   reset button is          active.
   pushed.              c.) Phase control relay open.        c.) See 1.( d.) above.
                        d.) Flow switch open.                d.) See 1.( e.) above.
Check light:            e.) Compressor switch open.          e.) See 1.( f.) above.
None                    f.) Burned out signal light.         f.) Check signal light bulbs.
                        i.) Wiring problem                   i.) Check wiring against drawing.
4. Compressor           a.) Compressor drawing high          a.) Check motor megohms. Reset overloads; run
   overload.                amps.                                compressor an check amps. Do not exceed RL x 1.25.
                                                                 Call D/B serviceman.
5. High motor           a.) Motor windings failing.          a.) Check megohms. Reset by turning compressor switch
   temperature                                                   off and then on.
6. Low suction          a.) Inadequate feed to               a.) Check to see that main expansion valve superheat.
                            evaporator.
                        b.) Inadequate refrigerant           b.) See information on charging in Section 5.7.
                            charge.
                        c.) Fouling of waterside of          c.) At high load, check evaporator approach (See Section
                            evaporator.                          5.4). If approach is more than 2F [1.1C] above clean
                                                                 valve, fouling is probably the trouble. Clean tube.
                        d.) Inadequate chilled water         d.) Measure pressure drop across vessel and determine
                            flow.                                flowrate from Figure 3.3. If flow rate is low, check
                                                                 chilled water pump, valves and strainers.
                        e.) Too much oil in system.          e.) If all oil level sight glasses are full at all times, remove
                                                                 oil until oil level shows at top of glass on a
                                                                 compressor.
7. High discharge       a.) Inadequate air flow across       a.) Check condenser fan operation and condenser coil for
   pressure.                condenser                            clogging.
8. Oil low in sump.     a.) Low oil level in                 a.) Low oil level in compressor sight glass is acceptable.
                            compressor.
9. Low oil              a.) Low oil in compressor.           a.) See Section 5.8.
   shutdown.
10. Freeze warning.     a.) Operating setpoint too low.      a.) Check leaving water setpoint on controller.
                        b.) Load changing too rapidly.       b.) Load on package must drop at reasonable rate for
                                                                 automatic control to work properly.
11. Improper            a.) Ramp rate incorrect.             a.) See Section 4.4.6.5.
    capacity control.
DATE
TIME
       DISCHARGE SUPERHEAT                             2.
      (DISC. TEMP.-SAT. DISCH.)*                       3.
                                                       4.
                                                       1.
        DISCHARGE SUPERHEAT                            2.
       (DISC. TEMP.-SAT. SUCT.)*                       3.
                                                       4.
1.
           ACTUAL VOLTAGE                              2.
          COMPRESSOR AMPS                              3.
                                                       4.
FAN AMPS
VOLTS
www.dunham-bush.com