Diesel Generator set
QST30 series engine
1041kVA - 1110kVA 50Hz
925kW - 1012kW 60Hz
> Specification sheet
  Our energy working for you.
  Description                                                                   Features
                      This generator set is designed in facilities certified    Cummins Heavy-Duty Engine - Rugged 4-cycle industrial
                      to ISO9001 and manufactured in facilities certified to    diesel delivers reliable power, low emissions and fast
                      ISO9001 or ISO9002.                                       response to load changes.
  This Cummins Power Generation commercial generator set is
  a fully integrated power generation system, providing optimum                 Permanent Magnet Generator (PMG) - Offers enhanced motor
  performance, reliability, and versatility for stationary standby,             starting and fault clearing short circuit capability.
  prime power, and continuous duty applications.
  Generator Set Performance                                                     Alternator - Several alternator sizes offer selectable motor
  Voltage Regulation                                                            starting capability with low reactance 2/3 pitch windings; low
  Maintains voltage output to within 1.0%.                                     waveform distortion with non-linear loads, fault clearing short-
  At any power factor between 0.8 and 1.0                                       circuits capability, and class H insulation.
  At any variations from No load to Full load.
  At any variations from Cold to Hot.                                           Control System - Standard PowerCommand electronic
  At speed droop variations up to 4.5%.                                         control provides total system integration including remote
  Frequency Regulation                                                          start/stop, precise frequency and voltage regulation, alarm and
  Isochronous under varying loads from no load to 100% full load                status message display, AmpSentry protection, output
  when electronic governor is fitted.
                                                                                metering, auto-shutdown.
  Random Frequency Variation
  Will not exceed 0.25% of its mean value for constant loads  no
                                                                                Cooling System - Standard integral set-mounted radiator
  load to full load.
                                                                                system, designed and tested for rated ambient temperatures,
  Waveform
                                                                                simplifies facility design requirements for rejected heat.
  Total harmonic distortion open circuit voltage waveform
  in the order of 1.8%. Three-phase balanced load in the order of
  5.0%.                                                                         Enclosures - Optional weather-protective and sound-
  Telephone Influence Factor (TIF)                                              attenuated enclosures are available.
  TIF better than 50.
  THF to BS 4999 Part 40 better than 2%.                                        Warranty and Service - Backed by a comprehensive warranty
  Alternator Temperature Rise                                                   and worldwide distributor network.
  Class H insulation.
  Radio Interference
  In compliance with BS 800 and VDE levels G and N.
                                                  Standby Rating                                                 Prime Rating
        Model                    50Hz kVA (kW)                        60Hz kW (kVA)                 50Hz kVA (kW)             60Hz kW (kVA)
      C1000 D5                      1041.25 (833)                              N/A                     938.75 (751)                  N/A
      C1100 D5                        1110 (888)                               N/A                     1000 (800)                    N/A
       C925 D6                            N/A                           925 (1156.25)                      N/A                  835 (1043.75)
      C1000 D6                            N/A                            1012 (1265)                       N/A                   920 (1150)
 2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered
trademarks of Cummins Inc. PowerCommand is a registered trademark of Cummins Power Generation Inc. "Our energy
working for you." is a trademark of Cummins Power Generation.
APSB-1154-07 (9/07)
Generator Set Specifications
Governor Regulation Class                                            ISO8528
Voltage Regulation, No Load to Full Load                              0.5%
Random Voltage Variation                                              0.5%
Frequency Regulation                                                 Isochronous
Random Frequency Variation                                           0.25%
Radio Frequency Emissions Compliance                                 IEC 801.2 through IEC 801.5; MIL STD 461C, Part 9
Engine Specifications
Design                                                               4 cycle, in line, turbo Charged and after-cooled
Bore                                                                 140.0mm (5.51in.)
Stroke                                                               165.1mm (6.5in.)
Displacement                                                         30.5 liters (1860in.)
Cylinder Block                                                       Cast iron, 50V 12 cylinder
Battery Capacity                                                     254A/hr
Battery Charging Alternator                                          35 amps
Starting Voltage                                                     24-volt, negative ground
Fuel System                                                          Direct injection
Fuel Filter                                                          Spin on fuel filters with water separator
Air Cleaner Type                                                     Dry replaceable element with restriction indicator
Lube Oil Filter Type(s)                                              Four spin-on, full flow; two bypass oil filters
Standard Cooling System                                              122F (50C) ambient radiator
Alternator Specifications
Design                                                               Brushless, 4 pole, drip proof revolving field
Stator                                                               2/3 pitch
Rotor                                                                Direct coupled by flexible disc
Insulation System                                                    Class H
Standard Temperature Rise                                            125C Standby
Exciter Type                                                         PMG (Permanent Magnet Generator)
Phase Rotation                                                       A (U), B (V), C (W)
Alternator Cooling                                                   Direct drive centrifugal blower fan
AC Waveform Total Harmonic Distortion                                No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF)                                     <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF)                                      <3%
Available Voltages
                   50Hz Line  Neutral / Line - Line                                           60Hz Line  Neutral / Line - Line
 240/416                                                         277/480                                                  
 230/400                                                         220/380                                                  
 220/380                                                                                                                  
                                                                                                                          
Generator Set Options
Engine                                                   Alternator                                     Silencer
 Heavy Duty air filter                                   Alternator heater                             Critical silencer
 Water jacket heater 220/240 v                                                                          Residential silencer
Cooling                                                  Control Panel
 Antifreeze 50/50 (Ethylene glycol)                      4 pole Main Circuit Breaker
Enclosure
 Sound attentuated enclosure
Our energy working for you.
www.cumminspower.com
 2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered
trademarks of Cummins Inc. PowerCommand is a registered trademark of Cummins Power Generation Inc. "Our energy
working for you." is a trademark of Cummins Power Generation.
APSB-1153-07 (9/07)
 Control System - PCC3100                                          P
                                                                   C
                                 The PowerCommand 3100 Control is a microprocessor-based generator set monitoring, and control
                                 system. The control provides an operator interface to the genset, digital voltage regulation, digital
                                 governing and generator set protective functions.
                                 The PowerCommand 3100 generator set control is suitable for use on a wide range of generator sets in
                                 non-paralleling and paralleling applications.
                                 The PowerCommand Control can be configured for any frequency, voltage and power connection
                                 configuration from 120 to13,800 VAC for for 50Hz or 60Hz operation.
                                 Power for the control is derived from the generator set starting batteries. The control functions over a
                                 voltage range from 8VDC to 35VDC.
                                 Major Features
                                  Digital Governing and Voltage Regulation, including digital overcurrent fault regulation.
                                  Digital Voltage Regulation with 3-phase sensing
                                  AmpSentry Protection for true alternator overcurrent protection.
                                  Analog and Digital AC Output Metering.
                                  Battery Monitoring System to sense and warn against a weak battery condition.
                                  Digital Alarm and Status Message Display
                                  Generator set Monitoring: Displays status of all critical engine and alternator generator set functions.
                                  Smart Starting Control System: Integrated fuel ramping to limit black smoke and frequency overshoot,
                                  Advanced Serviceability using InPower, a PC-based software service tool.
                                  PowerCommand Network (optional) Provides LonMark interface to external devices
                                 Control System
                                 Includes all functions to locally or remotely start and stop, and protect the generator set.
                                 Control Switch - RUN/OFF/AUTO
                                       OFF Mode - the generator set is shut down and cannot be started
                                       RUN mode the generator set will execute its start sequence
                                       AUTO mode, the generator set can be started with a start signal from a remote device
                                 LED Indicating Lamps - includes LED indicating lamps for the following functions:
                                       Not-in-auto mode
                                       Common wiring
                                       Shutdown
                                       Phase and scale indication
                                       Fault reset switch. Allows the opperator to reset the control after warning or shutdown
                                       Emergency stop switch - imediately shuts down the generator set operation
                                 Base Engine Protection:
                                      Overspeed shutdown
                                      Low Oil Pressure Warning / Shutdown
                                      High Engine Temperature Warning / Shutdown
                                      Underspeed / Sensor Fail Shutdown
                                      Fail to Start / Fail to Crank
                                      Low / high battery voltage
                                 Options
                                 Integrated PowerCommand Digital Paralleling Controls
                                 Key Type Mode Selector Switch
                                 Exhaust Temperature Monitoring
                                 PowerCommand Network
                                 Refer to the PowerCommand Controls Technical Bulletin for detailed information
                                 (S1025C-Non-Paralleling / S1005c-Paralleling)
Our energy working for you.
www.cumminspower.com
 2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered
trademarks of Cummins Inc. PowerCommand is a registered trademark of Cummins Power Generation Inc. "Our energy
working for you." is a trademark of Cummins Power Generation.
APSB-1153-07 (9/07)
Ratings Definitions
Standby:                                   Limited Time Running:             Prime (Unlimited Running Time):         Base Load (Continuous):
Applicable for supplying power to          Applicable for supplying          Applicable for supplying power to       Applicable for supplying power
varying electrical load for the duration   power to a constant electrical    varying electrical load for unlimited   continuously to a constant
of power interruption of a reliable        load for limited hours. Limited   hours. Prime Power is in accordance     electrical load for unlimited
utility source. Emergency Standby          Time Running Power is in          with ISO 8528.Ten percent overload      hours. Continuous power in
Power (ESP) is in accordance with          accordance with ISO 8528.         capability is available in accordance   accordance with ISO 8528, ISO
ISO 8528. Fuel Stop power in                                                 with ISO 3046, AS 2789, DIN 6271        3046, AS 2789, DIN 6271 and
accordance with ISO 3046, AS 2789,                                           and BS 5514.                            BS 5514.
DIN 6271 and BS 5514.
                         This outline drawing is to provide representative configuration details for Model series only.
                                See respective model data sheet for specific model outline drawing number.
                                                   Do not use for installation design.
                                             Length            Width             Height         Set weight              Set weight
                  Model
                                            (mm)               (mm)              (mm)          dry kg                  wet kg
                C1000 D5                    4230                1756              2248               6890                    7295
                C1100 D5                    4469                1755              2248               7488                    7768
                 C925 D6                    4230                1756              2248               6890                    7295
                C1000 D6                    4469                1755              2248               7488                    7768
Cummins Power Generation
Asia Pacific
10 Toh Guan Road #07-01
TT International Tradepark
Tel: (65) 6417 2388
Fax: (65) 6417 2399
E-Mail: cpg.apmktg@cummins.com
Our energy working for you.
www.cumminspower.com
 2007 Cummins Power Generation Inc. All rights reserved. Cummins Power Generation and Cummins are registered
trademarks of Cummins Inc. PowerCommand is a registered trademark of Cummins Power Generation Inc. "Our energy
working for you." is a trademark of Cummins Power Generation.
APSB-1153-07 (9/07)