Directional Overcurrent Relay Guide
Directional Overcurrent Relay Guide
      Abstract  Directional overcurrent relaying (67) refers to     lagging current conditions rather then 1.0 power factor
relaying that can use the phase relationship of voltage and          conditions. One approach, seen in Fig. 1, is to phase shift the
current to determine direction to a fault. There are a variety of    voltage signal so that the relays internal voltage signal
concepts by which this task is done. This paper will review the      (VPolarity, abbreviated as VPol) is in phase with current when
mainstream methods by which 67 type directional decisions are
made by protective relays. The paper focuses on how a numeric
                                                                     current lags the 1.0 power factor condition by some setting,
directional relay uses the phase relationship of sequence            typically between 300 and 900. The angle setting is commonly
components such as positive sequence (V1 vs. I1), negative           referred to as the maximum torque angle, MTA. In some
sequence (V2 vs. I2), and zero sequence (V0 vs. I0) to sense fault   designs of this concept, the current signal is skewed rather
direction, but other concepts such as using quadrature voltage       than the voltage signal. In some designs, other phase voltages
(e.g., VAB vs IC) are included.                                      are used. For instance, IA could be compared to VAB, VCA,
                                                                     VBN, or VCN, and the detection algorithm would work, though
    Index Terms: directional relaying, sequence component,           the quadrature voltage VBC gives the most independence of the
negative sequence, zero sequence, 67, 32, quadrature voltage.        voltage signal from the effects of an A-N, A-B, or A-C fault.
                       I. INTRODUCTION
In some medium voltage distribution lines and almost all high
voltage transmission lines, a fault can be in two different
directions from a relay, and it can be highly desirable for a
relay to respond differently for faults in the forward or reverse
direction. The IEEE device number used to signify a
directional element is either a 21 (impedance element, based
on Z=V/I, and having a distance to fault capability) or a 67
(directional overcurrent, generally based on the phase
relationship of V and I, with no distance to fault capability).
Some applications also might use a 32 (power element, based
on P=Re[VxI*]) for directional control, though in some
circumstances a 32 element may not be a good indication of
direction to fault. This paper will review some of the various
implementations      of    67     elements      as   found     in
electromechanical, solid state, and numeric (i.e., multifunction
programmable logic microprocessor based) relays.
                                                                       2
In the typical power system, we can usually assume that, at the                                                                 V0, Relay
remote system, voltage has very low V0 and V2, and V1 is 1.0,                                                    Z 0,Relay =                 = -Z 0, Sys                                         (6)
                                                                                                                                I 0, Relay
or at least very close to 1.0. At the other end, the fault
location, every type of fault will have differing values of V0,                                                                 V2, Relay
V1, and V2 and will need to be calculated via means that will                                                    Z 2, Relay =                = -Z 2, Sys .                                       (7)
                                                                                                                                I 2, Relay
not be covered here (see [1]), but we know that some value
exists. Hence, (2) reduces to
                                                                                                            Note that in (6) and (7) the equations for Z0,Relay and Z2,Relay,
                                                                                                            the impedance seen by the relay will be dependent solely upon
       0  V0, Fault   Z 0                    0        0   I0                                        the source impedance. (The dependency on source impedance
      V                        
                                                           0   I1  .
       1, System  - V1, Fault  =  0          Z1                                              (3)       might be counter-intuitive to engineers accustomed to setting
       0  V2, Fault   0                 0        Z 2   I 2                                  impedance relays in terms of line impedances.) The angle of
                                                                                                            Z0,Relay and Z2,Relay is the source of determining the direction to
                                                                                                            a fault. For instance, in Fig. 1, a CT polarity orientation can
If Z0, Z1, and Z2 are divided into two impedances as seen from                                              cause the apparent Z0 and Z2 at the relay to either match the
the relay location (line impedance and source impedance), the                                               source impedance angle or to be inverted by 1800. The current
net system and associated voltage drop has the appearance of                                                polarity would be the signature of a fault that is either forward
Fig. 4.                                                                                                     or reverse from the relays location.
  V0, Relay   0   Z 0, Sys           0         0   I 0, Relay                                       If a relay uses Z1,Relay for sensing direction to fault, the Z1,Relay
                                                                     
  V1,Relay  = V1, Sys  -  0        Z1, Sys     0   I1, Relay  .                           (5)       measurement will see balanced load flow as an indication of
  V2, Relay   0   0                0       Z 2, Sys   I 2,Relay                                the direction to fault and, hence, to turn on overcurrent
                           
                                                                                                            elements (67/51) that are set to look in the direction of present
                                                                                                            load flow. The Z1 that is sensed during balanced load flow
If we solve (5) for the impedances, since V2,Sys = 0 and V0,Sys =                                           conditions is a minor modification of (9):
0, then
                                                                                                                 Z1, Relay = Z1, Line + Z1, Load .                                              (12)
                                                                                                        3
                                                                                       would fall into either the forward or reverse zone, depending
The angle of Z1 can be a poor indicator of fault location. For                         on relay setup and CT connections. Note that in an impedance
instance, when a customers DG (distributed generator) exists                          plot, MTA is counterclockwise from the reference R axis, as
to peak shave, it has the ability to control the power factor at                       compared to the classical approach of showing I relative to V
the PCC (point of common coupling). Power swings that                                  where MTA is clockwise from the reference VA axis.
occur in post fault conditions give transient VA flow at almost
any angle. On a more steady state basis, a DG that runs to
keep power at the PCC near zero could cause net power factor,
and hence the angle of Z1, to be almost any value.
In (13), Z#,Line refers to the entire line impedance. The 11800                                   Fig. 6. Forward and Reverse Impedance Angles
factor in (13) accounts for the effective change in CT polarity                        As previously mentioned, the various relay manufacturers
for faults in the reverse direction. The positive sequence                             have differing ways of sensing angular relationships. The most
impedance does not lend itself to simple equations such as                             obvious process is to measure the impedance angle and
(13), but for 3 phase faults and unfaulted load flow conditions                        compare it to a window of the MTA +/-900 as forward or
                                                                                       reverse. There are alternate processes in use. For instance, as
      Z1,Re lay , Forward , Faulted = Z1, Line, Flt                                    seen in Fig. 7, one manufacturer configures its Z2,Relay and
     Z1,Re lay ,Re veverse , Faulted = Z1, Sys , A,to Fault                            Z0,Relay directional elements to subtract the MTA from the
                                                                   .        (14)       calculated impedance, and then find the real portion of this
     Z1,Re lay , Forward ,Unfaulted = Z1, Line + Z1, Load , B                          resultant impedance, ZReal, which can be a positive or negative
     Z1,Re lay ,Re verse ,Unfaulted = Z1, Sys , A + Z1, Load , A                       value. Then, ZReal is compared to user settings for the decision
                                                                                       points for forward and reverse. For the great majority of cases
                                                                                       this gives the same result as the phase angle window.
A graphical representation of the forward and reverse zones of
protection can be seen in Fig. 6. The MTA is a user setting
that effectively defines forward and reverse phase angles.
Sensed impedance angles that are +/- 900 from the MTA
                                                                                   4
                                                                            and 67/51Q (negative sequence) elements and similar 67/50
                                                                            elements, and that each has a forward or reverse looking mode
                                                                            with different settings for each direction. There are three
                                                                            directional elements called the 67POS (positive sequence),
                                                                            67NEG (negative sequence), and 67ZERO (zero sequence) that
                                                                            control the 67/51 and 67/50 elements. The protective elements
                                                                            and their directional controls are:
                                                                        5
C. Superimposed Components                                               phase element. Assume for simplicity of the figure that the
When heavy load flow occurs at the same time as a low level              fault is at a point such that half the system impedance is
fault, it can confuse a directional element. This situation will         between the facility and the fault location.
be seen in the application discussed in section VIII. Some
manufacturers have implemented a scheme that tries to
separate out load flow currents from fault currents, using
schemes referred to as superimposed components. It is similar
in application to memory polarization but involves both
current and voltage from the past into the present, rather than
just the voltage. Assume steady state load flow conditions.
Assume a sudden change, due to a fault, is seen. The relay can
take the voltage and current from the past several cycles,
before the fault, and project it into the present. This projected
voltage and current is compared to actual faulted voltage and
current. This scheme allows the fault current to be separated
from the overriding load current and, hence, improve the
decision about where the fault is located. The algorithms need
to include intelligence and logic to differentiate normal
switching events from fault events.
D. Minimum Sensitivity
A relay has limits to its sensitivity. There must be sufficient
quantities of current and voltage for a directional decision.
The minimum quantity varies by manufacturer. The response
of the relay to low voltage or current varies, but typically, the
                                                                                               Fig. 8. System One-Line
relay will default to a neither forward nor reverse status if
either currents or voltages are very low. In this case, each
manufacturer and even each relay from a manufacturer may                 The symmetrical component network that describes the
have a different logic on how the relay responds. There may              application, for an A phase to ground fault, is shown in Fig. 9.
be settings to define minimum quantities the relay needs to see          Note that the low negative sequence impedance of the motors
and settings for how the relay responds when values are below            means that the facility can be a negative sequence current
the minimum.                                                             source for the fault. Compare the polarity of forward current at
                                                                         the CT in Fig. 8 to the polarity of current flow at the dot
E. Positive vs. Negative Torque Angles.                                  between Z2T and Z2SYS in Fig. 9. The current flow at the CT in
Each manufacturer has its own way of presenting certain data.            the two cases is opposite. Hence, the 67NEG sees this reverse
For instance, it is counter-intuitive to some users to have              fault and turns on. The heavy current flow into the facility,
negative angles as forward and positive angles as reverse, as            meanwhile, makes the 67/51R time out to a reverse trip, even
seen in (13) and (14), so some manufacturers effectively invert          though power is flowing into the facility on all 3 phases and
the Z2 and Z0 forward impedance angle. Effectively, a -1               the generation is off-line.
factor is entered into the relays impedance angle calculations.
                                                                         In one perspective this is a very good feature. Even in the
                                                                         presence of large forward load flow, the fault still is seen and
VII. APPLICATION NOTE 1: FORWARD POWER SUPERIMPOSED                      cleared. This might be especially good if the generator was
                  ON REVERSE FAULT                                       very small and incapable of feeding significant current into the
                                                                         fault. However, on the other hand, with the generation off line,
To better understand the performance of directional relaying,
                                                                         there was not any benefit in tripping the breaker at the PCC.
let us apply it to a real world situation.
                                                                         One method to stop the trip is to block the 67/51R when the
                                                                         generation is off line, but in some applications the generation
Assume the 67 element in Fig. 8 is an overcurrent relay that
                                                                         might be quite remote from the PCC, making the control
derives its directional characteristics from negative sequence
concepts. The overcurrent element in the reverse direction is            scheme difficult. Another possible resolution that does not
                                                                         need to directly know the generator status will be seen in
set below load current in the forward direction, with the intent
                                                                         Section VIII, where the directional power element, 32,
of being sensitive to remote utility faults. However, assume
the facility generator is off line, so the natural tendency of the       supervises the 67 element, blocking the 67 when power is into
                                                                         the facility on all three phases. However, there could be
operators of the facility is to believe that the 67/51Reverse
elements will not trip for a utility fault. However, assume that         argument against this process: If the generation is in peak
                                                                         shaving mode and power continues to flow into the facility on
the motors are a substantial percentage of the facility loads.
                                                                         all three phases during the fault, the utility must trip its
Now, assume a remote system line to ground fault that is slow
to be cleared. Assume the fault is on a lateral and with some            breaker before the relay at the PCC will ever see the fault. A
                                                                         few utilities object to sequential tripping, where one relay will
fault impedance, such that the feeder still carries power to the
                                                                         not see a fault until another breaker trips first.
facility on the faulted phase, above the pickup of the 67/51R
                                                                     6
                                                                         generation may be off during times of high facility loading,
                                                                         the overcurrent relaying at the Point of Common Coupling
                                                                         (PCC) must be able to carry the peak loading of the facility, so
                                                                         its overcurrent setting is, for the purpose of discussion, 1.25
                                                                         per unit, where 1 per unit is the current at peak loading of the
                                                                         facility. Assume a generator is obtained that is 1.0 per unit in
                                                                         capability, though it is common for a DG to be sized much
                                                                         smaller than the local load. The unit size relative to local load
                                                                         means that, during facility light loading times, the generator
                                                                         could easily carry the entire facility and the plant could even
                                                                         export power. However, suppose the generation is designed as
                                                                         a peak shaving no reverse power flow allowed facility;
                                                                         therefore, there has to be a control package for the generator
                                                                         that monitors the voltage, power, and VARs at the facility
                                                                         PCC and takes appropriate action to turn down prime mover
                                                                         power whenever the facility approaches the point of power
                                                                         export. The control system is not a protective relay, so typical
                                                                         engineers and utility personnel will not allow it to be relied
                                                                         upon to prevent an island condition. Compared to facilities
                                                                         where generation is always less than local load, this DG has an
                                                                         increased risk of supporting an island or supporting the fault
                                                                         condition for an extended period.
                                                                      8
We are ignoring load in this figure. To analyze the circuit             reasonable considering a 5% impedance facility transformer
under the presence of load, see reference [2], which analyzes           and a long line to the facility. In any case, the generator
Fig. 14 in detail and also includes facility loads.                     impedance is notably higher than the system impedance and k
                                                                        has a value of about 0.14 in this case. If a generator is used
Let us use VSys as the fixed voltage and rotate the generator           that could support the full facility load, k would have been
voltage phasor around by 3600. The voltage at the PCC will              about 0.25. Per Fig. 7, k=0.25 indicates only a 50% voltage
be:                                                                     dip at the PCC, and at k=0.14, the voltage will drop to about
                                                                        78% of nominal.
                                         VSys  VGen              Let us call the undervoltage element that we want to sense the
   VPCC = VSys  ZSysISys = VSys  ZSys                          out of step condition a 27T-3/3 (T indicates the 27 is a definite
                                         Z +Z                      time delay element, and 3/3 indicates all 3 phases must be low
                                         Sys     Gen        
                                                                    for a trip). Some issues that need consideration when setting
                     (
          = VSys  k VSys  VGen    )                          (15) the 27T-3/3 are:
 where                                                                1. The minimum voltage that will be seen at the PCC
                                                                           during a pole slip needs to be determined. See (15) and
                   ZSys                                                  Ref. [2] as a starting point. The PU setting for 27T-3/3
        k=                                                               element needs to be less than the worst case voltage
             Z +Z             
             Sys         Gen                                             drop that will occur during load inrush at the facility.
                                                                           Load inrush should not cause more than 20% voltage
A k value of 0.5 will indicate the PCC is at the electrical                drop in most facilities, so a setting of 75% of nominal
impedance center. If 0.5<k<1 then the generator impedance is               may be appropriate. Hence, the voltage during a loss of
smaller than the system impedance, and if 0<k<0.5 the                      sync condition might be insufficiently low to reliably
generator impedance is larger than the system impedance.                   differentiate from low voltage due to normal events.
                                                                           This issue may prevent the ability of the 27 to detect
A graphical picture that helps give a feel for the significance            loss of synchronism.
of this equation is seen in Fig. 14. Note in Fig. 14 that if the      2. The low voltage at the PCC for a pole slip will be seen
PCC is near the electrical impedance center, then a very low               on all 3 phases, so to help differentiate the pole slip
voltage will be seen at the PCC for each slip cycle, but if the            from a temporary fault, the element should monitor for
PCC is remote from the electrical impedance center, the                    all phases going low.
voltage drop seen at the PCC might be difficult to sense.             3. The 27T-3/3 should be time delayed only a matter of
                                                                           cycles. If the PCC is at the electrical impedance center
                                                                           where k=0.5, VPCC will transiently approach OV and
                                                                           will be below 0.5pu for only about 1/3 of the slip cycle.
                                                                           Assuming the slip is 1 pole slip per second, this gives a
                                                                           low voltage for around 20 cycles. If the PCC is not at
                                                                           the electrical center, the minimum low voltage will be
                                                                           higher than 0V and the low voltage condition will last a
                                                                           shorter time. If the slip was faster, there would be even
                                                                           less time for the relay to respond. Time delay may need
                                                                           to be as low as 5 cycles, if the voltage dip can be sensed
           Fig. 14. VPCC for Varying k as Generator Slips Pole             at all.
There is some difficulty in stating the apparent impedance of a       4.   The 27-3/3 could be fooled by external events that
generator during a pole slip event. This paper takes the                   deliberately remove power at the PCC, so an input to
generally accepted view (which is in agreement with generator              the relay to block operation for such conditions may be
simulation tests performed at the Basler factory) that the                 necessary.
transient reactance, XD, is a reasonable representation of the       5. If the breaker is opened at the moment of lowest PCC
generator impedance during a pole slip event, falling in the               voltage, then the breaker will try to interrupt current
0.3pu range. During a slow pole slip, when a slip cycle                    with the generator and system 1800 out of phase and
exceeds twice the XD time constant (typically about 0.3                   with twice the system voltage across the breaker at the
second time frame), it would be anticipated that the apparent              moment after current is interrupted. It may be advisable
generator impedance will start to increase somewhat.                       to delay tripping until the 27-3/3 element drops out.
Let us look at our sample system in Fig. 13. The generator was          Current during Loss of Synchronism
rated at half the system load, so its effective impedance at the
base of 1.0 PU will be XD = 0.6pu. A power system that is              The current that will flow in the circuit in Fig. 6 during an out
capable of delivering 1pu current with good voltage regulation          of step condition can be approximated by the equation:
likely has a fault duty on the order of 10 times the load current
level, so we might assume XSys of around 0.1pu, which is
                                                                    9
                     VSys  VGen                                                the relay to respond. A delay of 5-10 cycles may be
          IPCC    =                                                            appropriate.
                    Z +Z                                                   5.    If the breaker is opened at the moment of highest
                     Sys     Gen                            (16)                current, the breaker will try to interrupt current with the
                         2                                                        generator and system 1800 out of phase and with twice
     IPCC, Peak   
                    ZSys + ZGen                                                   the system voltage across the breaker at the moment
                                                                                  after current is interrupted. It may be advisable to delay
This current does not reflect the load flow that will be                          tripping until the 50T-3/3 element drops out.
superimposed on top of these currents. Again, see [2] for a
more detailed analysis, and see earlier discussion on the use of           The 67POS during Loss of Synchronism
XD. From the previous discussion, let us assume ZSys = 0.1pu
                                                                           The above equations for current and voltage at the PCC can be
and ZGen = XD = 0.6pu after converting to our common base.
                                                                           combined to create equations for the apparent impedance
This gives a peak current of around 2.9pu. If a generator had
                                                                           during the loss of synchronism.
been used that could have supported the entire facility, XGen =
0.3, then the peak current would be around 5pu. Let us call an
overcurrent element that we want to sense the out of step                                                        VSys  VGen    
                                                                                                   VSys  ZSys                  
condition a 50T-3/3 (T indicates the 50 is a definite time delay
                                                                                          VPCC                   Z +Z
element, and 3/3 indicates all 3 phases must be high for a trip).                ZPCC   =       =                Sys      Gen    
Some issues that need consideration when setting the 50T-3/3                              IPCC            VSys  VGen 
are:                                                                                                                                 (17)
  1. The peak current for an out of step condition needs to be                                             ZSys + ZGen 
       determined, and the peak load and/or transformer inrush                            VSys ZGen + VGen ZSys
       as seen at the relay location needs to be determined. The                        =
       pickup setting for 50T-3/3 element needs to be about                                    VSys  VGen
       75% or less of the peak out of step current (= 2.1pu for
       our small generator case and 3.75pu for our large                   The apparent ZPCC will be lowest when VGen is 1800 out of
       generator case). We also need the pickup to be at least             phase with VGen. The impedance takes a path shown in Fig. 15,
       125% or more of the worst case load/transformer inrush              seen in many resources. Fig. 15 includes the forward and
       at the facility (maybe 2pu in this example). For the                reverse zones for the 67POS element. At the point where the
       small generator case, we have a marginal condition. On              67POS sees reverse current, the generator voltage will be just
       a case-by-case basis, these pickup setting requirements             past 1800 out of phase, so current will still be high. If this is a
       may very well conflict with one another. If the conflict            facility that should not be sending large amounts of current to
       arises, either i) external logic must be used to block the          the utility, then we have a signature for out of step that we can
       relay element for load inrush conditions, or ii) the relay          monitor with what we will call a 67/50T-3/3. Some issues that
       should be put at the generator terminals and should be              need consideration when setting the 67/50T-3/3 are:
       set based upon peak load inrush as seen at the generator,             1. The peak current for an out of step condition needs to be
       rather than at the PCC.                                                    determined, and the peak current that the facility will
  2. Pole slip currents can be seen better at the generator                       ever send out to the utility needs to be determined.
       terminals rather than at the PCC. In facilities with                       Similar to the 50T-3/3, the 67/50T-3/3 pickup setting
       smaller generators, the load current flow at the PCC                       for 50T-3/3 element needs to be about 75% or less of
       may mask the pole slip condition. Further, generators                      the peak out of step current but, in this case, it only
       are not typically exposed to load currents above 1.5pu,                    needs to be about 125% or more of the worst case
       which makes for easier discrimination between load                         outrush from the facility to the utility. Because the
       current and loss of synchronism current.                                   67/50T-3/3 element is not turned on by the 67POS until
  3. The high current for a pole slip will be seen on all 3                       the pole slip is just past its peak, a more sensitive pickup
       phases, so to help differentiate a pole slip from a fault,                 of 50% of peak current might be good, if possible.
       the element should monitor for all phases going high. A               2. Pole slip currents can be seen better at the generator
       positive sequence overcurrent current element, 50-I1,                      terminals rather than at the PCC. In facilities with
       would not be appropriate since phase to phase and phase                    smaller generators, the load current flow at the PCC
       to ground faults can cause high I1.                                        may mask the pole slip condition.
  4. The 50T-3/3 should operate in a matter of cycles. Just as               3. The high current for a pole slip will be seen on all 3
       in the voltage dip discussions, the current level will                     phases, so to help differentiate a pole slip from a fault,
       oscillate from 0 to IPCC,Peak and back to 0 in one slip                    the element should monitor for all phases going high. A
       cycle and will be above about 2/3 of IPCC,Peak for only                    positive sequence overcurrent current element, 50-I1,
       about 1/3 of the slip cycle. For a 1 second slip rate, a                   would not be appropriate since phase to phase and phase
       pickup of 2pu current, and a peak current of 2.9pu, the                    to ground faults can cause high I1.
       relay will be picked up for less than 20 cycles. If the slip          4. The 67/50T-3/3 should operate in a matter of cycles.
       was faster, there would be proportionately less time for                   Because the element is not turned on by the 67POS until
                                                                                  the pole slip is just past its peak, high speed operation is
                                                                      10
      more important. At the turn-on point of the 67/50T-3/3,
      and given a 1 second slip cycle, the current may decay
      to below pickup in less than 10 cycles, and there would
      be even less time if the slip rate were higher. A 3-5
      cycle delay would be appropriate. Of course, the faster
      one makes the relay, the more chance of a transient load
      swing or CT error causing a misoperation of the
      element.
 5.   If the breaker is opened at the moment of highest
      current, the breaker will try to interrupt current with the
      generator and system 1800 out of phase and with twice
      the system voltage across the breaker at the moment
      after current is interrupted. It may be advisable to delay
      tripping until the 67/50T-3/3 element drops out.
 6.   The function can be augmented with voltage
      supervision, enabling the 67/50-3/3 only under 3 phase                            Fig. 16. Ground Fault Sensing Schematic
      low voltage. This might be viewed as a form of a 51VR
      or 51VC relay. An element that uses a 51 may be too
      slow to sense a pole slip, so a very high speed 51 or a              XI. APPLICATION NOTE 5: DIRECTION TO FAULT ON HIGH
      50T is appropriate.                                                             IMPEDANCE GROUNDED SYSTEMS
                                                                         Some DG systems are run in an ungrounded or high
                                                                         impedance grounded mode behind a transformer that isolates
                                                                         the plant from the utility ground grid. In a system with a high
                                                                         impedance ground, the existence of a ground somewhere in
                                                                         the system is indicated by a high V0 voltage and sensed by
                                                                         appropriate relaying, typically called a 59N relay. Once the
                                                                         fault is detected, the faulted phase will be indicated by a low
                                                                         VLG on the faulted phase. However, when multiple feeders or
                                                                         generators are connected to the bus, the specific faulted feeder
                                                                         or generator is unknown.
                                                                    11
the relay can determine if there is a ground fault forward and            concerned utility engineer that it is still possible and should be
hence on the feeder, or reverse and hence on another feeder.              protected against.
Another issue is that if the phase to ground capacitance of the           The negative sequence directional element (67/51Q) at the
system is small (XC large), there may not be enough current               PCC in this case may see high current unbalance. The load
for the relay to work with. There are two issues: a) there needs          current will appear as a reverse phase to ground fault. The
to be sufficient current for the overcurrent element to operate,          current and voltage unbalance may be enough for the 67NEG or
and b) there must be sufficient current for the 67ZERO to                 67ZERO to enable sensitive reverse looking overcurrent
determine direction to the fault. These issues are in part                elements. Another element that will see the situation is a
addressed by CT selection, Also, for the current level to be              reverse looking 32 element. A 32 element set to monitor on a
detectable, it will likely be necessary that the relay monitor a          three phase basis will not see the situation, but a 32 element
window CT that wraps all phases, that the CT ratio be low,                that is set to monitor power flow one phase at a time will sense
and the ground input (Ig) of the relay be configured as a 1A              the problem. The 32 element is usually settable to be highly
input, rather than the more typical 5A input (U.S. market).               sensitive, so it may be more able to sense the condition than a
Further, in some relays a sensitive earth fault (SEF) feature is          67/51Q.
available that makes the IG input highly sensitive to current in
the 10s of milliamps. One should study the relay
manufacturers instruction manuals for the minimum currents               XIII. APPLICATION NOTE 7: UNBALANCED LOAD CONDITIONS
and voltages that are required for the 51/67G and 67ZERO                           CAUSE PICKUP OF DIRECTIONAL ELEMENT
elements to operate.                                                      In an industrial facility, there is a possibility of unbalanced
                                                                          loading that could result in sufficient negative or zero
One more issue that some may be concerned about is ground                 sequence current flow and voltage for the 67NEG or 67ZERO
fault detection when the fault impedance itself is very high;             directional element bit to set. If forward is into the facility as
possibly on the order of thousands of ohms of resistance. The             in Fig. 6, the 67NEG or 67ZERO will be set as forward and this
fault resistance will make the V0 neutral shift small and make            will turn on the forward version of the appropriate 67/51
the ground fault hard to sense, especially if there is any                elements. It would be anticipated that the 67/51P-Forward and
standing V0 in the system due to unbalanced ZLG in the                    67/51G-Forward element pickup will be set above highest
system. The fault resistance also will turn capacitive current            expected forward current conditions, so only turning on the
flow into a capacitive/resistive flow, so that instead of I0              forward direction bit set should not be a problem. Further, in
leading V0 by 900, it will lead by, for instance, 300, and also           such current conditions the 67POS element is already set to
reduce a small current into an even smaller current. If one is            forward due to high facility load current, and hence the 67/51P
concerned about fault impedance, then the zero sequence                   forward looking element is already enabled, so setting the
MTA can be adjusted from 900 leading to some value closer to              negative sequence directional has not affected the matter.
300 leading, but outside of this option, one will need to look            Therefore, the effect of the unbalanced load on the directional
for specialized ground fault sensing relays or equipment.                 elements can be ignored in this case. One should think through
                                                                          this issue for ones facility.
 XII. APPLICATION NOTE 6: DETECTING HIDDEN PHASE LOSS
Examine Fig. 18. In this case one phase feeding the DG has                  XIV. APPLICATION NOTE 8: USING SETTING GROUPS TO
been lost, but due to generation on site, the matter is not easily         CONFIGURE THE 67/51 FOR CHANGING SYSTEM CONDITIONS
detected simply from a voltage standpoint. It is likely that a            In DGs with many possible modes of operation (e.g. Fig. 19),
fault occurred that caused this situation to arise, but somehow           there are various conditions where it may be worthwhile to
the fault has cleared and the DG is left back feeding an                  consider different setting groups to change the performance of
unfaulted phase. One might make the argument that this                    a relay at the PCC.
situation would not likely occur, but that will not dissuade the
                                                                     12
   A facility with multiple generators may operate the PCC
    with more or less generators on line. With increased
    generation on line, the current that the facility may feed
    into a utility fault will increase. Higher sensitivity may
    be required when only one generator is on line, and less
    sensitivity when three generators are on line and
    connected in parallel.
   With increased generation and the PCC being run closer
    to the float (0 power flow) point, the risk of transient
    reverse power flow increases. If there is risk of a
    sensitive reverse current relay from operation, some
    allowance may be needed for desensitizing the current
    relay when a large amount of generation is on line.
   If there are one or two breakers or transformers that
    connect the DG to the utility and the system might be run
    with either one or two transformers, or generation tied to
    either source, the 67/51 and relay logic may need to be
    modified appropriately for system conditions. For
    example, which breakers should be tripped for a reverse
    fault? Which generators?
                          IX. CONCLUSIONS
The paper discussed some of the variations in directional
control that can be found in the relays on the market. When
testing the relay, determining relay settings, or analyzing event
reports, some concept of how the relay determines direction to
a fault will be needed.
                            REFERENCES
[1]   John Horak, A Derivation of Symmetrical Component Theory and
      Symmetrical Component Networks, Georgia Tech Protective Relaying
      Conference, April 2005. Available at www.basler.com.
[2]   PoleSlip_R0.xls spreadsheet to model voltages, currents, and power
      flow during a pole slip event. File is available at www.basler.com.
                      AUTHOR BIOGRAPHY
John Horak (M,1987) received his BSEE in 1987 from the University of
Houston and an MSEE in the field of power system analysis in 1995 from the
University of Colorado. He has worked for Houston Lighting and Power,
Chevron, and Stone and Webster Engineering, where he spent several years
on assignment in the System Protection Engineering offices of Public Service
Company of Colorado. In 1997 he began his present position as an
Application Engineer for Basler Electric.
                                                                               13
                                         Route 143, Box 269, Highland, Illinois U.S.A. 62249
  If you have any questions or need        Tel +1 618.654.2341 Fax +1 618.654.2351
                                                                                                         No. 1300 North Zhongshan Road
                                                                                                      Wujiang Economic Development Zone
additional information, please contact               e-mail: info@basler.com                       Suzhou, Jiangsu Province - P.R. China 215200
                                                                                               Tel +86(0)512 6346 1730 Fax +86(0)512 6346 1760
      Basler Electric Company.                                                                            e-mail: beichina@basler.com
      Our web site is located at:        P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE
                                           Tel +33 3.88.87.1010 Fax +33 3.88.87.0808
        http://www.basler.com                    e-mail: beifrance@basler.com
       e-mail: info@basler.com