From Bus To Bus CB
Rating(kVA)
380V / 220 Existing AC SYSTEM
Existing AC panel Protection panels 4.40 25
Existing AC panel Remot control panels 6 16
Existing AC panel LCC 6 16
Existing AC panel Battery charger -1 33 63
Existing AC panel Battery charger -2 33 63
125V DC AUXILIARY SYSTEM-1-From existing DC panel
Existing DC panel F01 Trip Coil -1 2.0 20
Existing DC panel F02 Trip Coil -1 2.0 20
Existing DC panel F03 Trip Coil -1 2.0 20
Existing DC panel F04 Trip Coil -1 2.0 20
Existing DC panel F05 Trip Coil -1 2.0 20
Existing DC panel F06 Trip Coil -1 2.0 20
66KV protection
Existing DC panel 2.0 20
panels(F01,F04) supply-1
66KV protection
Existing DC panel panels(F02,F03,F05,F06) 2.0 20
supply-1
66KV protection BB
Existing DC panel 2.0 20
panelssupply-1
125 V DC AUXILIARY SYSTEM-2-For NEW DC panel
125 VDC
F01 Trip Coil -2 2.0 20
SwitchBoard-B
125 VDC
F02 Trip Coil -2 2.0 20
SwitchBoard-B
125 VDC
F03 Trip Coil -2 2.0 20
SwitchBoard-B
125 VDC
F04 Trip Coil -2 2.0 20
SwitchBoard-B
125 VDC
F05 Trip Coil -2 2.0 20
SwitchBoard-B
125 VDC
F06 Trip Coil -2 2.0 20
SwitchBoard-B
125 VDC 66KV remote control
2.0 20
SwitchBoard-B panels(F01,F04)
125 VDC 66KV remote control
2.0 20
SwitchBoard-B panels(F02,F03,F05,F06)
125 VDC 66KV protection
2.0 20
SwitchBoard-B panels(F01,F04) supply-2
66KV protection
125 VDC
panels(F02,F03,F05,F06) 2.0 20
SwitchBoard-B
supply-2
Load
From Bus To Bus CB
Rating(kVA)
125 VDC 66KV protection BB panels
2.0 20
SwitchBoard-B supply-2
125 VDC
battery charger-1 12.50 125
SwitchBoard-B
battery charger-1 battery charger-2 12.50 125
battery-1 battery charger-1 12.50 125