CHAPTER 16
Synchronous Generators
16.0 Introduction
nree-phase synchronous generators. are the
primary source of all the electrical energy we
‘consume. These machines are the largest energy con
verters in the world. They c
into electrical energy, in powers ranging up to 1500
MW. In this chapter we will study the construction
and characteristics ofthese large, modern generators
‘They are based upon the elementary principles cov
cred in Section 8.6, and the reader may wish (0 re=
view this material before proceeding further:
nvert mechanical energy
16.1 Commercial synchronous
generators
Commercial synchronous generators are built with
either a stationary or a rotating de magnetic field.
A stationaay-field synchtonous generator has the
same outward appearance as a de generator. The
salient poles create the de field, which is cut by a re-
volving armature, The armature possesses a
3-phuse winding whose terminals are connected t
three slip-rings mounted on the shall, A set of
brushes, sliding on the slip-rings, enables the arma
lure t@ be connected to an external 3-phase loa
The armature is driven by a gasoline engine, or
‘some other source of motive power, As it rotates, &
Z-phase voltage is induced, whose value depends
‘upon the speed of rotation and upon the de exciting
ceurrent inthe stationary poles. The frequency of the
voltage depends upon the speed and the number of
Poles on the field. s Id generators are
used when the power output is less than 5 kVA
However, for greater outputs. it is cheaper. safer
and more practical to employ a revolving de field.
A revolving-field synchronous generator bas 3
Mationary armature called a stator. The 3-phase sta
tor winding is directly connected to the load, with-
cout going through large, unreliable slip-rings and
brushes. A stationary stator also makes it easier 10
insulate the windings because they are not sub-
jected to centrifugal forces. Fig. 16.1 isa schematic
diagram of such led an
erator, sometimes
alternator. The field is excited by a de wenerator,
usually mounted on the same shaft. Note that the
brushes on the commutator have to be connected 10
another set of brushes riding on slip-rings to feed
the de current / into the revolving field,
16.2 Number of poles
The numberof poles on a synchronous generator de
pends upon the speed of rotation and the frequencyNe ELC TCAL MACHES AD TanroReRS
ee
it G90 oe .
x = ph rotor
pilot erie AAS eee
Si be
an "Ee ,
St QB
vain, 2/7
Pure 164
‘Schematic diagram and cross-section view of atypical 500 MW synchronous generator and its 2400 KW de excitor.
The dc exciting current J, (6000 A) flows through the commutator and two siiprings. The de contrl current J rom
the pilot exciter permits variable field contra ofthe main excite, which, in turn, controls
we wish to produce, Consider, for example, a stator
‘conductor that is successively swept by the N und S.
poles of the rotor. Ifa positive voltage is induced
when am N pole sweeps across the conductor, a si
Har aegarive voltage 1S induced When the 3 pole
speeds by. Thus. every time a complete pair of poles.
crosses the conductor, the induced voltage
through a complete excle. The same is true for e
other conductor on the stator: we ean therefore de.
luce that the alternator frequency is given by
_m
120
(16.1)
where
J/= frequency of the induced voltage [Hz]
umber of poles on the rotor
speed of the rotor [r/mia}
p
Example 16-1
A laydaulie “a0 200 afin is 0
rected (0 a synchronous generator, If the induced
age hay frequency of 60 H7, how many poles
volt
does the rotor have?
Solusion
From By. 16.1, we have
p= 1209
= 120 x 60200
= 36 poles. oF 18 pairs of Nand S poles
16.3 Main features of the stator
From an electrical standpoint. the stator of a syn
Cchronous generator is identical to that of a 3-phase.
induction motor (Section 13.17). I is composed of
cylindrical laminated core containing a set of slots
that carry «1 3-phase lap winding (Figs. 16.2, 16.3),
‘The winding is always connected in wye and the
neutral is com wund. A wye conne:
preferred to a delta connection because
1. The voltage per phase is only WA13 oF S8% of
the voltage between the lines, This means that
the highest voltage between a stator conductor
and the grounded stator eore is only 58% ofthe
line voltage. We can therefore reduce the
amount of insulation in the slots whieh, in cura,
‘enables us to inerease the cross section of the
conductors. A larger conductor permits us t0 in
crease the current and, hence. the power output
of the machineAW
Figure 16.28
»
SYNCHRONOUS GENERATORS 387
Stator of a 3-phase, 500 MVA, 0.95 power factor, 15 KV, 60 Hz, 200 rimin generator. Inernal diameter: 9250 mm:
c’tfective axial langth of iron stacking: 2850 mm: 378 slots.
(Courtesy of Marine Industrc)
2, When a synchronous generator is under lead. the
voltage induced in ea
and the wavetorm is
distortion is mainly due to an undesired sid
harmonic voltage whose trequeney is three times
that of the fundamental frequency: With a wye
‘connection, the distorting line-to-neutral harmon
jes do not appear between the lines because they
each other. Consequently. the
fine voltages remain sinusoidal under all lod
becomes distorted
Sinusoidal, The:
‘conditions, Unfortunately. when a delta connec
monie voltages do not cancel
aM
tion is used th
but ad up. B
they proce ath
ren which incre
se the delta is closed 0
hharmonie circulating cur
wsthe PR losses.
The nominal line voltage ofa synchronou
erator depends upon its KVA rat eneral, the
greater the power rating, the higher the volta
However. the nominal line-to-line vol
seldom
5 KY because the increased slot insulation
takes up valuable space atthe expense of the copper
conductors‘The copper bars connecting successive stalor poles are designed to carry a current of 3200 A. The total output is
19250 A per phase
rtesy of Marine Industrie)
Figure 16.2¢
The stators bul up from toothed segments of high-quality
silcon-iron steel laminations (0.5 mm thick), covered with
fan insulating varnish. The siots are 22.3 mm wide and 169
rmvm deep. The salient poles of the rotar are composed of
Inch Uomo (2 rn) on laraniatons. Thee larialiors
are nat insulated because the de flux they cary does not
vary The width of the poles from tip to tip is 600 mm and
the air gap fongth is 33 mm. The 8 round holes in the face
ofthe salient pole carry the bars of a squirrel-cage windingSl
Figure 16.3
Slalor ofa 3-phase, 722 MVA, 3600 r/min, 19 kV, 60 Hz steam-turbine generator during the construction phase,
“The windings are water-cooled. The stator wil eventually be completely enclosed in a metal housing (see back
{ground}. The housing contains hydrogen under pressure to further improve the cooling
(Courtesy of ABB)M0 ELECTRICAL MACHINES AND TRANSFORMERS
16.4 Main features of the rotor
Synchronous generators are built with two types of
rotors: salient-pole rotors cylindrical
rotors. Salient-pole rotors are usually driven by
low-speed hydraulic turbines, and eylindrieal rotors
are driven by high-speed steam turbines.
1. Salient-pole rotors
have to turn at Tow speods (hetween 50 and 300
rfmin) in order co extraet the maximum power from
aa waterfall, Because the rotor is direetly coupled 10
the waterwhe
(or 60 HY is required, a large number of poles are re
{quired on the rotor. Low-speed rotors always poss
sess large diameter 1 provid essary space
Tor the poles. The salient poles are mounted on
circular Steel frame which is fixed to a revolu~
16.4), To ensure good cool:
Most hydraulic turbines
and because a frequency of 50 Hz
Figure 16.4
This 36-pole rotor is being lowered into the stator shown in Fig, 16.2. The 2400 A de exciting current is supplied by
390, electronic rectifier, Other details are: mass: 600; moment of inertia: 4140 tm; air gap: 33 mm.
(Courtesy of Marine Industrie)
ing. the field coils are made of bare copper bars.
with the turns insulated from each other by strips of
mica (Fig, 16.5), The coils are connected in series.
with adjacent poles having opposite polarities
In addition to the de field winding
a squirrel-cage winding, embedded in the po!
(Fig, 16.6). Under normal conditions, this winding
does not carry any current because the rotor turns:
synchronous speed, However, when the load on the
generator changes suddenly, the rotor speed begins
to Muctuate, proxlucin ations
‘above and below synchronous speed. This induces a
nthe squirtel-
we often add
voltag ‘winding, causing a large
current to flow therein, The current reacts with the
‘magnetic field ofthe stator, producing forces which
dampen the oscillation of the rotor. For this reason,
the squirrel-cage winding is sometimes called a
damper winding.Figure 16.5 Figure 16.6
This rotor winding for a 250 MVA salient-pole genera- Salient pole of a 250 MVA generator showing 12 slots
tors made of 18 turns of bare copper bars having a to carry the squirel-cage winding,
width of 89 mm and a thickness of 9 mm 7
Figure 16.72
FRotor of a 3-phase steam-turbine ganerator rated 1530 MVA, 1500 r/min, 27 KY. 50 Hz. The 40 longitudinal siots
are being milled out ofthe sold steel mass. They will cary the de winding, Etlective axial magnetic length 7490
rm; diameter: 1800 mm,
(Courtesy of Alis-Chalmers Power Systems inc., West lis, Wisconsin)Figure 16.7
ELECTRICAL MACHINES AND TRANSFORMERS
Rotor wit its 4-pole de winding. Total mass: 204 t; moment of inertia: 85 tm; ar gap: 120 mm. The de exciting cur
rent of 11.2 KA is supplied by a 600 V de brushless excites bolted to the end of the main shatt
(Courtesy of Alis-Chalmers Power Systems inc., West Allis, Wisconsin)
The damper windin
anced 3-phase voltags
Js to maintain bal-
between the lines, even
when the Tine currents are unequal due to uabal-
anced load conditions,
2. Cylindrical rotors. I is well known that high
speed steam turbines are smaller and more efficient
irbines, The sume is true of high:
speed synchronous
ate the required frequency we eannot use less than
2 poles. and this Tixes the highest possible speed
(On 2 60 Hz system itis 3600 e/min, The next lower
speed is. 1800 r/min, corresponding to a 4-pole ma
chine. Consequently, these stewm-rurbine genera
tors possess either
The rotor of a turbine-generator is @ long. solid
than low-speed
eneraiors, However, to
for 4 poles,
steel eylinder which contains a Series of ly
slots millee out of the cylindrical mass (Fi
Concentric
eld coils, firmly wedged into the slots
ined by high-strength end-rin
create the N and $ poles.
The high speed of rotation produces strong cen.
Uifugal forces, which impose an upper limit on the
diameter of the rotor. In the case of a rotor tuenin
at 3600 r/min, the elastic limit of the steel requires
the manufacturer to limit the diameter to a maxi
mum of 1.2 m, On the other hand. 1 build the pow
erful 1000 MVA to 1500 MVA generators the vol
ume of the rotors has to be large. It follows that
high-power, high-speed rotors have to be very long.
16.5 Field excitation and exciters
The de field excitation of a large synchronous
generator isan important part ofits overall design,SYNCHRONOUS GENERATORS 343
stonaey bls
stator A | alternator
Penson = ee
T Fee bridge } oe
Cr — , =F
= 2 phase rotor
‘oe
£4z2
Figure 168
Typical brushless exoter system,
The reason is thatthe field must ensure not only a voltage may have to Five Yo Lge its momma val in
Stable ac terminal voltage, but must also respond
to sudden load changes in order to maintain sys-
tom stability. Quickness of response is one of the
important features of the field excitation, In order
to attain it, two de generators are used: a main es
citer and a pilor exciter Static exciters that involve
no rotating paris at all are also employed.
The main exciter feeds the exciting Current to the
ld of the synchronous generator by way of brushes
tnd slip-rings, Under normal conditions the exciter
voltage lies between 125 Vand 600 V. I is regulated
‘manually or automatically by control signals that vary
the current J, produced by the pilot exciter (Fig. 16.1),
The power rating of the main exeiter depends
‘upon the capacity of the synchronous generator.
Typically, 2 25 kW exciter is needed 10 excite a
1000 kVA alternator (2.5% of its rating) whereas a
2500 kW exciter suffices for an alternator of
500 MW (only 0.5% of its rating).
‘Under normal conditions the excitation is varied
automatically. [responds to the load chang
‘maintain a constant ae Tine voltage or to control the re
active power delivered tothe electric utility system. A.
serious disturbance on the system may produce a stu
den voltage drop aevoss the terminals of the alterna
tor, The exciter must then react very quickly to hep
the se voltage from falling. For example, the exciter
as Tittle as 308) 19-400 milliseconds. This represents
very quick response, considering that the power the
fer may be several thousand kilowatts
16.6 Brushless excitation
Due to brush wear and carbon dust, we constantly
have to clean, repair. and replace brushes. sips
nal de excitation sys-
and commutators on conve
tems. Toeliminate the problem, brushless exeitation
systems have been developed. Such a system con-
sists oF a 3-phase stationary-field generator whose
ac output is rectified hy a group of rectifiers, The de
‘output from the rectifiers is fed dirvetly into the Feld
of the synchronous generator (Fig, 16.8.
The urmature of the ae exciter ancl the rectifiers
are mounted on the min shaft and turn together
with the synchronous generutor, In comparing the
excitation system of Fig, 16.8 with that of Fig. 16.1
we can see the} except that the
Sphase rectifier replaces the commutator. slip-
rings, and brushes, In other words, the commutator
(owhich is really a mechanical wetitier) is replaced
by an electronic rectifier, The result is that the
brushes und slip-rings are no fon
The de control current J, from the pilot e
regulates the main exciter output /. sin the ease oF
are Went:Mi ELECTRICAL, MACHINES AND TRANSFORMERS
4 conventional de exciter. The frequeney of the
main exciter is zenerully We to thice times the syn=
cchronous generator frequency (60 Hz). The in
{erease in frequency is obtained by using more poles.
fon the exeiter than on the synchronous generator
16.9 shows the rotating portion of a typical
brushless exciter, Static exciters that involve n0 10.
tating parts at al are also employed
16.7 Factors affecting the size
of synchronous generators
The prodigious amount of energy generated by el
trical utility: compan
scious about the efficiency of their
‘example, ifthe efficiency oF 1000 MW generating
ation improves by only 1. itreprevents extra rev
cenues of several thousand dollars per day, In this ne
rd. the size of the
tant because its efficiency automatically improves
as the power ineteases, For example, if small
has made them very con
enerators, For
encrator is particularly impor
kilowatt synchronous zenerator has an efficiency of
‘50% a larger bul similar model having a capacity of
10 MW inevitably has an elficieney of about 90%
‘This improvement in efficieney with size is the «
ators of 1000 MW and
Lup possess efficiencies of the onder of 99%
Another auvantage of large machines is that th
power ouput per kilogram increases as the power
increases. For example, ita AW
20 kg yielding 1000 W,
nerator weighs
aloMw
Figure 16.9
This brushless exciter provides the de current for
the rolor shown in Fig. 16.7. The exciter consists
cof a 7000 KVA generator and two sets of diodes.
Each set, cortesponding respectively tothe post
live and negative terminals, is housed in the ei
cular rings mounted on the shatt, as seen in the
center ofthe photograph. The ac exciter is seen
to the night The two round conductors protruding
from the center of the shatt(loreground) lead the
‘exciting current to the 1530 MVA generator
(Courtesy of Alls-Chalmers Power Systems ine.
West ats, Wisconsin)
Figure 16.10
Partial view of @ S-phase, salent-pole generator rated
£87 MVA, 428 vimin, 50 Hz. Bath the rotor and stator
are water-cooled, The high resistivity of pure water
land the use of insulating plasic tubing enables the
‘water to be brought inta direct contact with the live
parts of the machine.
(Courtesy of ABB)generator of similar construction will weigh only
20.000 kg, thus yielding 00 Wikg. From a power
Standpoint, large machines weigh relatively less than
small machines: consequently, they are cheaper.
Section 16.24 at the end of this chapter explains
why the efficiency and output per kilogram increase
with size
Everything. therefore, favors the large machines.
ase in size, we run inte seri-
1g problems. In effect. large machines in-
horently produce high power losses per unit surface
area (Wim?); consequently, they tend to overheat
To prevent an unacceptable temperature rise, we
‘must design efficient cooling systems that become
‘ever more elaborate as the power increases. For ex-
ample, a circulating cold-air system is adequate 10
coal synchronous generators whose rating is below
50 MW. but beiween 50 MW and 300 MW, we have
tw resort fo hydrogen cooling. Very bi
in the 1000 MW range have to be equipped with
hollow. water-cooled conductors, Ultimately. a
is reached where the increased cost of eooliny
and this fixes
exceeds the savings macle elsewher
the upper Limit to size.
To sum up. the evolution of big alternators has,
‘mainly been determined by the evolution of sophis-
SYNCHRONOUS GENERATORS MS
ticated cooling techniques (Figs, 16,10 and 16,11),
Other technological breakthroughs. such as better
materials, and novel windings have also played 3
‘major part in modifying the design of early mt
chines (Fig, 16.12).
AAs regards speed, low-speed generators ane al
ways bigger than high-speed machines. of equal
power. Slow-speed bigness simplifies the cooling
problem: a good air-cooling system, completed with
‘aheat exchanger, usually suffices. For example, the
large, slow-speed 500 MVA, 200 r/min synchronous
generators installed ina typical hydropower plant
Ja smaller high-speed!
ane air-cooled whereas the mu
SO MVA. [800 r/min units instalfed in steam pint
hhave to be hydrogen-cooled.
16.8 No-load saturation curve
Fig, 16.130 shows a 2-pole synchronous generator
operating at no-load. It is driven at constant speed
by a turbine (not shown), The leads trom the
have, wye-connected stator are brought out t0
terminals A. B,C. N. and a variable exciting current
J, produces the fu in the air gap.
Let us gradually increase the exciting
while observing the ac voltage £, between terminal
current
Figure 16.11
The electrical energy needed on board the Concord aircraft is supplied by four S-phase generators rated 60 kVA,
200/118 V, 12.000 rimin, 400 H2. Each generator is driven by a hydraulic motor, which absoros a small portion of
the enormous power developed by the turhoreactor engines, The hydraulic fluid streaming from the hydraulic motor
is used to cool the generator and is than recycled. The generator isell weighs only 54.5 ka,
(Courtesy of Air France)346 ELECTRICAL MACHINES AND TRANSFORMERS:
Figure 16.12
‘This rotating told generator was first installed in North America in 1888. I was used in a 1000-1amp street lighting
system. The alternator was driven by an 1100 rin steam engine and had a rated output of 2000 V, $0 A at a tro-
‘quency of 110 Hz. It weighed 2320 kg, which represents 26 Wikg, A modern generator of equal speed and power
‘produces about 140 Wikg and occupies only one:tnird the floor space.
A. say, and the neutral N. For small values of fy. the
tage increases in direct proportion to the excit.
ing current, However, asthe iron beginsto saturate,
the voltage rises much less for the same inerease in
J, Me we plot the curve of &,, versus f,, We obtain
the no-load saturation curve of the synchronous
generator. It is similar to that of a de generator
(Seetion 4.13).
Fig, 16.13h shows the actual no-load saturation
curve of «36 MW, 3-phase generator having a
nominal vohage of 12 kV (line to neutral). Up to
bout 9 KY, the voltage inereases in proportion to
the current, but then the iron begins (© saturate,
Thus. an exciting curvent of 100.A produces an out
put of 12 kV, but if the current is doubled, the volt-
age rises only 10 15 kV.
Fig. 16.13¢ isa schematic diagram of the gener
ator showing the revolving rotor and the three
phases on the stator.
16.9 Synchronous reactance—
equivalent circuit of an ac
generator
Consider a 3-phase synchronous generator having
terminals A, B, C feeding a balanced 3-phase load
(Fig, 16.14), The xeneratoris driven by a turbine (not
shown), and is excited by a de curtent f,. The ma
chine and! its load are both connected in wye, yield
ing the circuit of Fig. 16.15. Although neutrals Ny
sand Np are not connected. they are at the samme po:
tential because the load is balanced, ConsequentlyFigure 16.13
{. Generator operating at no-load,
'. Norload saturation curve of a 36 MVA, 21 KV,
S-phase generator.
wwe cand connect them together (as indicated by the
short dish ine) without affecting the behavior ofthe
‘oltages or curents in the circuit.
The field caries an exciting current which pro-
duces flux b. As the field revolves. the flux in-
laces in the stator thre equal voltages, that are
120° out of phase Fig. 16.16)
Each phase of the stator winding possesses a te-
sistance R and a certain inductance L. Because this
SYNCHRONOUS GENERATORS 347
i Gaertn \
Figure 16.13¢
Eloctric circuit representing the generator of
Fig, 16 13a,
is an alternating-current machine, the inductance
‘manifests itself as a reactance X.. given by
X= Qafl
where
synchronous reactance, per phase [0]
J-= generator frequency [Hz]
L = apparent inductance of the stator wind:
ing, per phase [HJ
The synchronous reactance oa generator isan in-
{eral impedance. just like its internal resistance R.
The impedance is there, but it can neither he seen
nor touched. The value of X, is typically 10 10 100
times greater than R: consequently, we can always.
neglect the resistance. unless we are interested in
efficiency oF heating effects.
‘We can simplily the schematic diagram of Fi
16.16 by showing only one phase of the stator In ef
Jeet, the two other phases are identical, except that
their respective voltages (and currents) are out of
phase by 120°, Furthermore. if we neglect the tesis-
tance of the windings. we obtain the very simple cir-
cuit of Fig, 16.17. A synchronous generaior can there-
fore be represented by an equivalent circuit composed
‘ofan induced voltage E, in series witha reactance X,
Inthis circuit the exciting current J, produces the
Fux cb which induces the imernal voltage E,, For aM8 ELECTRICAL MACHINES AND TRANSFORMERS
Figure 16.14
Generator connected to a load
Figure 16.15
Electic circuit representing the installation of Fig. 16.14
Figure 16.16
Voltages and impedances in a 3-phase generator and
its connected load
lows
+
Figure 16.17
Equivalent circuit of a 3-phase generator, showing
oni one phase.
given synchronous reactance, the volta
terminals of the generator depends upon E,, and the
load Z Note that £, and F are line-to-neutral volt
‘ages and Fis the line current
16.10 Determining the value of X,
We can determine the unsaturated value of X. by the
following open-circuit and short-circuit test
During the open-circuit test the generators driven
at rated speed ancl the exciting current is raised until
the rated line-to-line voltage is attained. The corr.
sponding exciting current J, and line-to-neutral volt
age E,, are recorded.
‘The exeitation is then reduced to zero and the
three stator terminals are short-circuited together,
With the generator again running at rated speed. the
exciting current is gradually raised to its original
value fy
The resulting short-circuit current 1. in the sti-
tor windings is measured and X,is calculated by us-
ing the expression
ths (162)
where
X, = synchronous reaetanee, per phase [12)*
E, = rated open-cireuit line-to-neuteal voltage
vl
This ave wf X, cones othe dean yess
eaetance, Is widely used to deseo synconoas methine
behavior1, = short-circuit current. per phase, using
the same exeiting current Jy that was
required 0 produce E, [A]
‘The synchronous reactance is not constant, but
varies with the degree of saturation. When the iron
is heavily saturated, the value of X, may be only hall
its unsaturated value. Despite this broad range we
usually take the unsaturated value for X, because it
yields sufficient accuraey in most cases of interest
rample 16-2
A 3ephase synchronous generator produces. an
‘open-circuit Fine voltage of 6928 V when the dee
citing current is $0. The ae terminals are then
short-circuited, smd the three fine currents are found
to be 800 A,
44, Calculate the synchronous reactance per phase.
b. Caleulate the terminal voltage if three 12.0
resistors are connected in wye aeross the ter-
mminals,
Solution
a. The line-to-neutral induced voltag
Ey = ENS BAY
69283
= 4000
xyo82
2088
e han
he
som 308.8
o 7 oo } BAT soos
-o4 —— 2008,
Te voltage = 63580
aaaarer
Figure 16.18
a. See Example 16-2.
. Actual ina voltages and currents.
SYNCHRONOUS GENERATORS 349
When the terminals are short-circuited, the only
impedance limiting the current flow is tht due
to the synebronous reactance. Consequently.
X= BM
=50
000/800
The yynchronous reactance per pase is there-
fore $0.
b. The equivalent circuit per phase is shown
Fig. 16.184,
‘The impedunce of the cireuit is
Z-\R 4x 21
avin bs
130
‘The current is
EZ = AOS = 308.
“The voltage across the lou resistor is
696 V
E=IR= 38 x 12
The Hine voltage under foal is
B= 3k
V3 x 3096
= 6402
‘The schematic diagram of Fig. 16,186 helps us vi-
swalize what is happening in the actual circuit,
16.11 Base impedance, per-unit X,
We recall that when using the per-unit system we
first select a base voltage and a base power. In the
cease of a synchronous generator. we use the rated
ws the buse voltage Ey and
line-to-neutral voltage
the rated power per phase asthe base power.* It fol-
lows thatthe base impedance Z, is given by
Be 4
(163)
tn many por sts the bas parr is select 0 Fe ga
errand ths ise vole
ame vale Ze the
tothe rated power of the
Ath Hn-tine ols, Ths il
tose pte350 ELECTRICAL MACHINES AND TRANSFORMERS
where
Zp, = base impednee (line-to-neutral) of
erator [2]
Ey, = base voltage (line-to-neutral) [V]
Sip = base power per phase [VA]
‘The base impedance is used a
for other impedances that the generator possesses.
“Thus. the synchronous reactance may be expressed is
a per-unit value of Z,. n general, X(pu) lies between
(O.8and 2, depending upon the design of the machine
usis of comparison
Example 16-3 plieesi eee
A30 MVA, 15 KV. 60 H7 ae generator has a synchro-
nous reactance of 1.2 pu and at resistance oF 0,02 pu,
Cateulate
a. The base voltage. buse power and base imped
lance of the generator
>. The aetual value of the synchronous reactance
ce. The actual winding resistance, per phase
d. The total full-load copper losses
Solution
a. The base voltage is
y= ENS = 18 0003
= 8660 V
The base power is
Sy = 30 MVA3 = 10 MVA,
0” VA
(16.3)
= 8607/10"
=150
b. The synchronous reactance is
X= Napuy x Zp
1.2Zq = 12x75
=90
. The resistance per phase is
R= Ripuy X Zy
= 002 Zy
= 0150
0.02 x 75
Note that all impedance values are from Tine 1
neutral
1d, The per-unit copper losses at full-load are
Pepa) Ripa)
=F x 002 = 002
Pipu)
Note thy
equal to 1
The copper losses for all 3 phases are
P= 0.02 Sy = 0.02 x 30 = 0.6MW
= 600 kW
16.12 Short-circuit ratio
Instead of expressing the synchronous reactance as
a per-unit value of Zy. the short-circuit rusia is
‘Sometimes used, It isthe ratio of the field current fy
needed to generate rated open-circuit armature vol
age Ey to the Jha needed to produce
rated current Jy, on a Sustained short-circuit. The
short-circuit ratio (f/f) is exactly equal 10 the
reciprocal of the per-unit value of X, as defined in
Eq. 16.2. Thus. ifthe per-unit value of X is 1.2. the
short-circuit ratio is 1.2 or 0.833,
1 Fullload the per-unit value of Js
16.13 Synchronous generator
under load
The behavior of a synchronous generator depends
upon the type of load it has to supply. There are
many types of loads. but they ean all be reduced to
two basic eategor
Figure 16.19
Equivalent circuit of a generator under load,1. Isolated loads. supplied by a sing!
2. The infinite bus
We begin our study with isolated loads, leaving
the discussion of the infinite bus to Section 16.16.
Consider a 3-phase generator that supplies power
toa load having a lagging power factor. Fig, 16,19
represents the equivalent circuit forone phase. In or-
der to construct the phasor diagram for this ei
swe list the following
1. Current fags bebind terminal voltage £ by an
le 0
2. Cosine #
generator
power factor ofthe load.
3. Voltage E, across the synchronous reactance
leads current / by 90°. ILis given by the expres
sion E, = jIX.
4. Voltage £,, generated by the flux is equal to
the phasor sum of E plus Ey
and £, are voltages that exist inside
Jhronous generator windings and cannot
be mensured directly
6, Flux «bis that produced by the de exciting eur-
rent
Figure 16.20
Phasor diagram for a lagging power factor load,
Figure 16.21
Phasor diagram for a leading power factor load.
SYNCHRONOUS GENERATORS 351
‘The resulting phasor
1620. Note that £, leads E by 8 degrees
Furthermore, the interally-generated voltage By is
greater than the terminal voltage, as we would expect.
In some cases the lod is somewhat eapacitive, so
that current / leads the terminal voltage by an angle 8.
‘What effect does this have on the phasor diagram?
The answer is found in Fig. 16.21, The voltage E,
across the synchronous reactance is still 0° ahead of
the current, Furthermore isan equal to the phi
sorsum of Eund £,. However. the terminal voltage is
row greater than the induced voltage £,. which is
very surprising result, In effect, the inductive reac-
tance X, enters into partial resonance with the
itive reactance of the load. Although it may appear we
are getting something For nothing. the higher terminal
voltage does not yield any more power
If the load is entirely capacitive. a very high ter-
minal voltage ean be produced with a sinall exeit-
ing current. However, in later chapters. we wil see
that such under-excitation is undesirable.
fiagram is given in Fi
Example 16-$
A386 MVA, 20.8 KV. 3-phuse alternator has a Syn
cchronous reactance of 9 Q and a nominal current of
KA. The no-load saturation curve giving the refa-
tionship between £,, and f, is given in Fig, 16.13b,
Ifthe excitation is adjusted so that the terminal volt-
age remains fixed at 21 KY, calculate the exeiting
current required and draw the phasor diagram for
the following conditions:
1a, No-load
b. Resistive load of 36 MW
cc. Capacitive load of 12 Mvar
Soluion
‘We shall immediately simplify the circuit to show
only one phase. The line
for all cases is fixed at
E= 2083 = 12kV
c is no voltage drop
ince: consequently.
the syn
IkV352 ELECTRICAL MACHINES AND TRANSFORMERS,
Fb
Gaara
Figure 16.228
PPhasor diagram at no-load.
‘The exciting current is
1, = 100 (see Fig. 16.130)
The phasor diagram is given in Fig. 16.2
With a resistive load of 36 MW:
bs. The power per phase is
P= 363 = 12MW
The full-oad line eurrent is,
= 12 x 10712. 000 = 1000.
The current isin phase with the
‘The voltage across X, is
= JIX, = j1000 x 9 = 9 RV 290°
1 PIE
al voltage
is. 90° ahead of J.
F,, generated by [is equal to the
phasor stim af Find #, Rofhering te the pha.
‘Sor diagram, its value is given by
‘The required exciting current is
1, = 200A (see Fig. 16.136)
‘The phasor diagram is given in Fig. 16.22b.
With a capacitive load of 12 Mya
ce. The reactive power per phase is
be fo
sxy| wy to,
1
i
1
T =
1a kv
Figure 16.220
PPhasor diagram with unity power factor load.
Q= 128 = 4 Mvar
‘The line current is
1 = QIE = 4x 10°12 000
=33A
The voltage across Xi
By = IK, = 333 <9 = 34V290°
As before E, leads / by 90° (Fig. 16.22e)
aa
z tak
anv ow
Figure 16.226
Phasor diagram with a capacitive load
‘The voltage £, generated by J is equal to the
phasor sum of E and E
E,= E+ B= 12+ (“9
= 9kV
‘The corresponding exciting current is
1
= TOA (see Fig. 16.135)
Note that £ jn less than the terminal volt
age E.
‘The phasor diagram for this capacitive load is
given in Fig. 16.22¢,
16.14 Regulation curves
‘When a single synchronous generator feeds variable
Toxsd, we are interested in knowing how the terminal
voltage £ changes as a function of the load current
‘The relationship between E and fis called the regu
son curve, Regulation curves are plotted with the field
excitation fixed and for a given load power fucto.
ig. 16.23 shows the regulation curves for the 36
MVA, 21 KV, 3phase generator discussed in
Example 16-4. They are given for loads having
unity power factor, 0.9 power factor lagging. and
0.9 power factor leading, respectively. These curves
‘were derived using the method of Example 1-1,0 leading
ao soo 780—*1000«— es
Load curent | ——+
Figure 16.23
Regulation curves of @ synchronous generator at
three different load power factors.
except that £,, was kept fixed instead of E. In each
‘of the three cases, the value oF E, was set so that the
tuting point for all the curves was the rated line-
neutral terminal voltage (12 KV at rated line cur
sent (1000 A).
‘The change in voltage between no-load and full-
load is expressed as a percent of the rated terminal
voltage. The percent regulation is given by the
equation
Eu Fi
% regulation = "100
Ey
Eq, = no-s
Ey
voltage [V]
ated voltage [VI
Example 16-5 —
Calculate the percent regulation corresponding. to
the unity power factor curve in Fig. 16.23,
Solution
‘The rated line-to-neutral volta
Ey = 12AV
at full-load is
‘The no-load terminal voltage is
Egy = ISKV.
SYNCHRONOUS GENERATORS. 358
‘The perweat regulation is
We note that the percent regulation of a synchro:
nous generators much greater than that of ade
‘erat, The reason isthe Ligh inpedsice of the yt
Cchronous reactance.
16.15 Synchronization
of a generator
We olten has
parallel fo supply a common load, For example, as
the power requirements of « large utility: system
build up during the day. generators are successively
connected to the system to provide the extra power
Later, when the power demand falls, selected g
cerators are temporarily disconnected from the sys
‘tem until power again builds up the Following day
Synchronous generators are therefore regularly b
ing connected and disconnected fron large power
_grid in response to customer demand. Sueh 3 grid is,
said to be an infinite bus because it contains so
‘many generators essentially connected in parallel
‘that neither the voltage nor the frequency of the grid
ccan be altered.
Before connecting a generator to an infinite bus.
(or in parallel with another generator), it must be
synchronized. A generator is said to be synchro
nized when it meets all the following conditions:
1. The generator frequency is equal to the system,
frequency,
‘The
voltage
10 connect Wo oF more generators in
snerator voltage is equal to the system
3. The generator voltage isin phase with the sys-
tem voltage
4. The phase sequence of the generator isthe
same as that OF the system,
‘Tosynehronize an alt
tor. we proceed as Follows:S84 ELECTRICAL MACHINES AND TRANSFORMERS
| Adjust the speed regukitor ofthe turbine so that 3, Observe the phase angle between E, and E by
the acy is close to the system means of a syeloscope (Fig, 16.24). This iaseu
Trequeney, ment has a pointer that continually indicates the
phase angle between the two voltages. covering
the entire range from zer0 to 360 d
Although the degrees are not shown, the dial has.
zero marker to indicate when the voltages are in
phase. In practice, when we synchronize an alter
ator. the pointer rotates slowly as it tracks the
phase
voltages. If the generator frequency is lightly
ystem frequency. the pointer ro
2. Adjust the excitation so that the generator volt
‘between the alternator and syste
tates clockwise
tendeny to lea he system fequeny.
Fe Conversely. i the generator frequency is lig
A rncunaseont Tow the pve tte countrlockwise The We
7 bine speed regulators ine-uned acondingys0
thatthe poimter barely erp aronthe dil A
hal check is made See hat the allem v
isl equal the system voltage. Then atthe
Figure 16.24
Synchroscope 4. The line circuit breaker is closed, connecting
(Courtesy of Lab-Voln the generator to the syst
Figure 16.25
This loatng oil derrick provides its own energy needs. Four diesel-drivan generators rated 1200 KYA, 440 V, 900
‘min, 60 Hz supply all the electrical energy. Athough ac power is generated and distributed, all the motors on
board are thyistor-cantralled de motors,
(Courtesy of Siemens)In modern generating stations, synchronization
is usually done automatically
16.16 Synchronous generator
on an infinite bus
We seldom have to connect only two generators in
parallel except in isolated locations (Fig. 16.25).
‘As mentioned previously, itis much more common
to connect a generator to a large power system
(infinite bus) that already hay many alternators
connected to it
An infinite bus is a system so powerful that it
imposes its own voltage and frequency upon any
apparatus. connected 10 its terminals. Once con
nected 10 a large system (infinite bus). 2 synch:
‘nous generator becomes part of a network compris
ing hundreds of other generators that deliver power
to thousands of loads. It is impossible, therefore. 10
specily the nature of the load (large or small, resis-
tive oF capacitive) connected to the terminals of this
particular generator. What, the
power the machine delivers? To answer this qt
tion, we must remember that both the value and the
frequency of the terminal voltage across the gener-
ator are fixed. Consequently, we can vary only two
‘machine parameters:
determines the
1, The exciting e
2. The mechanical torque exerted by the turbine
rent I,
Let us see how a change in these parameters a
fects the performance of the machine.
16.17 Infinite bus—effect of varying
the exciting current
Immediately after we synchronize a generator and
connect it 10 an infinite bus, the induced voltage F,,
is equal , and in phase with, the terminal voltag
E ofthe system (Fig, 16.26). There is no difference
‘of potential aeross the synchronous reactance and,
ly, the load current / is zero. Although
is connected to the system, it delivery
no power: its said to float on the line
SYNCHRONOUS GENERATORS 355
If we now inereave the exciting current, the volt-
age E, will inerease and the synchronous reactance 3
\ill experience a difference of potential E, given by
E.=B-E
A current will therefore circulate in the circuit
given by
Because the synchronous seis inductive
the current lags 90° behind E, (Fig. 16.26). The
‘current is therefore 90° behind £, which means that
the generator sees the system as iit were an induc
e. Consequ
‘ayynchronous generator, it supplies 1
to the infinite bus. The reactive power increases as
we raise the de exciting current. Contrary 19 what
\we might expect. iis impossible 10 make a genera-
tor deliver active power by raising its excitation,
Let us now decrease the exciting current so that
E, becomes smaller than E. Asa resull, phasor E, =
E,,~ E becomes negative and therefore points to the
left (Fig. 16.26e). As always, curnent = EI, lags
90° behind £,. However. this puts 190° ahead of E,
which means thatthe alternator sees the system as if
it were a capacitor, Consequ
‘excite an alternator. it draws reactive power trom the
system. This reactive power produces part of the
‘magnetic field required by the machine: the remain
der is supplied by exciting current I,
tive react ly. when we over-encite
ive power
16.18 Infinite bus—effect of varying
the mechanical torque
Let us return to the situation with the synchronous
generator floating on the line. £, and F being equal
‘and in phase. If we open the steam valve of the 1ur-
bine driving the generator, the immediate result is
an increase in mechanical torque (Fig. 16.274). The
rotor will accelerate and, consequently. E,, will t=
tain its maximum value 3 fttle sooner than before.
Phasor £;, will slip ahead of phasor F, leading it by
4 phase angle 8 Although both voltages have the
same value, the phase angle produces a differenceinfrite bus
Figure 16.26a
‘Generator floating on an infinite bus.
Figure 16.260
‘Overexcited generator on an infinite bus.
Figure 16.26¢
Under-excted generator on an infinite bus.
urbine +
L-G
save [+
infioite bus
bara
by £ f
avi
ow
00
av ah Tv
I
Figure 16.27
a Turbine driving the generator.
. Phasor diagram showing the torque angle 8
®
356of potential £, = E, ~ Eacross the synchronous re
actance (Fig. 16.27)
A current F will flow (again lagging 90° behind
,), but this time itis almost in phase with E. I fol:
lows that the generator feeds active power into the
system. Under the driving force ofthe turbine, the t0-
tor wi the angle 8 will con-
tinue to diverge, and the electrical power delivered to
the system will gradually build up. However, as soon
ay the electrical power delivered to the system is
{equal to the mechanical power supplied by the tur
bine. the rotor will cease to accelerate. The generator
Will again run at synchronous speed, and the torque
angle 8 between E,, and E will remain constant.
nis important to understand that a difference of
potential is created when two equal voltages are out
‘of phase, Thus, in Fig. 16.27, a potential difference
of 4 KV exisis between £, and £, although beth
voltages have a value of 12 kV.
continue to accelerate,
16.19 Physical interpretation
of alternator behavior
‘The phasor diagram of Fig, 16.27b shows that when,
the phase angle between E, and £ increases, the
value of E, inereases and, hence, the value of Fin-
creases. But a larger current means that the
tive
SYNCHRONOUS GENERATORS 357
power delivered by the generator also increases. To
‘understand the physical meaning of the diagram. let
us examine the currents, fluxes,
poles inside the machine.
‘Whenever 3-phase currents flow in the stator of
erator, they produce a rotating magnetic field
identical to that in an induction motor. Ina synchro.
hous generator this field rotates at the same speed
and in the same direction as the rotor. Furthermor
i has the same number of poles. The respective
fields produced by the rotor and stator are, therefore,
stationary with respect to cach other. Depending on
the relative position of the stator poles on the on
hand and the rotor poles on the other hand, powerful
Forces of attraction and repulsion may be set up be
tween them, When the generator oats on the line
the stator current J is zero and so no forees are de
veloped. ‘The only flux is that ereated by the rotor,
and it induces the voltage
Ifa mechanical torque is applied to the gener-
ator (by admitting more steam to the turbine). the
rotor aecelerates and gradually advances by a
angle «., compared to its original po-
sition (Fig. 16.28b). Stator currents immediately
begin to flow, owing to the electrical phase angle
8 between induced voltage £,, and terminal volt-
age E, The stator currents create a revolving
ind position of the
‘mechanica
Figure 16.28a
‘The N poles of the rotor are lined up withthe S poles
ofthe stator,
Figure 16.28
‘The N poles of the rotor are ahead af the S poles of
the stator.ASN ELECTRICAL. MACHINES AND TRANSFORMERS.
xl a corresponding set of N and § poles, Forces
of attraction and repulsion are developed be:
‘oyeen the stator poles and rotor poles, and these
magnetic forces produce a torque that opposes
the mechanical torque exerted by the turbine,
‘When the electromagnetic torque is equal 10 the
mechanical torque. the mechanical angle will no.
longer increase but will remain at a constant
value @,
‘There is a direct relationship between the 1
chanical angle ec and the torque angle 8. given by
(16.4)
= pa
where
' = torque angle between the terminal
voltage E and the excitation voltage
al degrees|
number of poles on the generator
7
«c= mechanival angle between the centers
Cf the stator and rotor poles [mechar
ical degrees}
Example 16-6 —
‘The rotor poles of an S-pole synchronous generator
shift by 10 mechanical degrees from no-load 10 full
Fou
a, Calculate the torque angle between E,, and the
terminal voltage & at full-load
E oor Eq. is leading?
Solution
a, The torque angle is:
= pad =8X WOR
= 40°
tor delivers active power, B, ol-
ways leads &
16.20 Active power delivered
by the generator
We can prove (see Section 16.23) thatthe active
power delivered by a synchronous generator is
sivem by the equation
6s)
active power, per phase [W|]
E,, = induced voltage, per phase [V]
E = terminal voltage, per phase [V]
X\ = synehronous reactance per phase [12]
8 = torque angle between E,, and E[°|
This equation ean be used under all load eandi-
tions, ineluding the ease when the generator is eon
nected to an infinite bus
To understand its meaning, suppose a generator
is connected to an infinite bus having a voltage E.
Furthermore. suppose thatthe de excitation of the
generator is kept constant so that &,, is constant
The term E,EIX, is then fixed, and the active
power which the alternator delivers to the bus will
vary directly with sin 8, the sine of the torque a
ele. Thus. as we admit more steam, 8 will increase
and so, 100, wil the active power outpat. The rel
tionship between the two is shown eraphieally in
Fig. 16.29. Note that between zero and 30° the
powcr increases aha Heatly wit the wrque
angle. Rated power is typically attained ut an an
ale of 30°
"
rete
om aD
— angles
grees
Figure 16.29,
Graph showing the relationship between the active
ower delivered by a synchronous generator and the
tarque angle.However, there is an upper limit to the active
power the generator can deliver. This limit is
reached when 6 is 90°, The peak power output is
then Pry ~ E,EIX, HE we try 10 exceed this limit
(such as by admitting more Steam to the turbine),
the rotor will accelerate andl lose synchronism with
the infinite bus. The rotor will wen faster than the
rotating field ofthe stator, and large, pulsating eur-
rents will low in the stator, In practice. this condi
tion is never reached because the cireuit breakers
{rip as soon as synchronism is lost, We then have 10
resynchronize the generator before it can again de-
liver power to the grid.
Example 16-7, —___
A236 MVA, 21 KV, 1800 r/min, 3-phase generator
connected 10 a power grid has 2 synchronous reac~
tance of 9.0 per phase. Ifthe exciting voltage is
12 KV (line-to-neutral), and the system voltage is
17.3 KV (line-to-line), calculate the Follow
a, The active power which the machine delivers
when the torque angle 8 is 30° (electrical)
'b, The peak power that the generator ean delive
belore it falls our of step (loses synchronism)
Solution
a. We have
E, = 12k
E> ITRVIN3 = 1OKV
b= 30"
‘The active power delivered to the power grid is
P= (BEIX) sin
(12 1099) x 05
6.67 MW
The total power delivered by all three phases is
(3 x 667) = 20MW
b. The maximum power, per phase. is attained
when 8 = 90"
P= (E,EIX) Sin 90
= (12 x 1019) x1
SYNCHRONOUS GENERATORS 389
= 1aMW
‘The peak power output of the alternator is,
therefore
x 13.3) = 40MW
16.21 Control of active power
When a synchronous generator is connected (0 3
system, its speed is kept constant by an extremely
sensitive governor. This device can detect speed
changes as small as 0.01%. An automatic control
system sensitive to such snmill speed changes in
mediately modifies the valve (or gate) opening of
the turbine so as to maintain a constant speed and
‘constant power output
On a big uility network, the power delivered by
‘each generator depends upon a program established
in advance between the various generating stations.
The station operators communicate with each other
to modify the power delivered by each station so that
the generation and transinission of energy is one as
clficiently as possible, In-more elaborate systems.
the entire network is under the contra of a computer,
In addition, individual overspeed detectors are
always ready 10 respond to a karge speed cha
particularly ifa generator for one reason or another.
should suddenly become disconnected from the
system, Because the steam valves are still wide:
‘open. the generator will rapidly accelerate and may
attain a speed 50 percent above normal in t0 5 se
‘nds. The centrifugal forces at synchronous speed
are already close to the Limit the materials can with
stand. so any excess speed can quickly
dangerous Situation. Consequently, steam valves
‘must immediately be closed off during such eme
gencies. Atthe same time, the pressure build-up in
the steam boilers must be relieved and the fuel
bbumers must be shut att:
ea very
16.22 Transient reactance
A synchronous nected (0 3 system is
subject fo unpredictable load changes that some-
times occur very quickly. In such eases the simple
wenerior e36). RLECTRICAL MACHINES AND TRANSFORMERS
yoru
fe iat ate
Figure 16.30
Variation of generator reactance following a short-
cut.
equivalent circuit shown in Fig. 16.17 does not re-
Tlect the behavior of the machine, This circuit is
‘only valid under steady-state conditions or when
the load changes gradually,
For sudden load current changes, the synchro
ouy reactance X, must be replied by another reac-
tance X” whose walue varies as a function of time,
ig, 16.30 shows how X’ varies when a generator is
euited. Prior to the short-circuit,
y cance is simply X, However, at
the instant of short-circuit, the reactance immedi=
ately falls toa much lower value X’,, Tt then in-
creases gradually until itis again equal to X, after a
time interval T. The duration of the interval depends,
upon the size of the generator, For machines below
100 KYA it only lasts a traction of a second, but for
‘machines in the 1000 MVA range it may fast as long
as 10 seconds
‘The reactance Xy isealled the trutsient reactance
‘of the alternator. H may be as low as 15 percent ofthe
synchronous reactance. Consequently. the initial
shori-circuit current is much higher than that corre
the synchronous reactance X, This hasa
direct bearing on the eapacity of the eireut breakers
atthe generator output, In effect, because they must
interrupt short-circuit in three 10 six
cscs, it follows that they have to inkerrupt a very
current,
On the other hand,
simplifies the voltage regulation problem when the
load on the generator increases rapidly. Firs the in
ternal voltage drop due to X’y is smaller than it
would be if the synchronous rouctanes N. wore set
ing. Second, ” stays at a value far below X. fora
sufficiently long time t quickly raise the exciting
current f,. Raising the excitation increases Ey.
which helps to stabilize the terminal vole.
Example 16-8
A250 MVA, -phase steam-turbine gener-
aor has a synchronous reactance of 1.6 pu and &
Uwansient reaetance X', of 0.23 pu. It delivers ity
rated output at a power Factor of 100%. A short-
circuit suddenly occurs on the line, close to the
generating station.
Cateutate
a, The induced voltaze B,, prior to the short-cireuit
bb, The initial value of the short-circuit current
cc. The final value of the short-circuit current if
the circuit breakers should fal 10 0p.
Solution
‘The base impedance of the gene
2y> ES
= 25 0007/250 10")
250
‘The synchronous reactance is
(pw) Zp
6x8
40
The rated line-to4
EH
cutral voltage per phase is
MakV
The rated load current per phase isFigure 16.31
See Example 16-8
I= SNE
= 250 x 10°1.73 x 25 000)
= SIT4A
‘The internal voltage drop E, is
= IX= 9774 x4
3.1 kV
“The current is in phase with & because the
power factor ofthe load is unity. Thus. reer:
ring to the phasor diagram (Fig, 16.31), £, is
E,=V
= Vid + 23
= 27.2kV
b. The transient reaetance is
Xy = X pw Zy
= 0.23 x25
= 05750
‘The initial short-cireuit current is
Lo EX
27.200575
4TSKA
which is 8.2 times rated current
. I the short-circuit is sustained and the excita
tion is unchanged, the current will eventually
level off at a steady-state value:
SYNCHRONOUS GENERATORS 36t
: rua
* |5.78 Kal BBkA
Figure 16.32
CChange in current when a short-circuit occurs across
the terminals of a generator. See Example 16-8.
I= BUX = 274
= 68 kA
which is only 1.2 times rated current
Fig. 16.32 shows the generator curn
sand during the short-circuit, We ass
terval T of 5 seconds, Note that in practice the eit
cuit breakers would vertainly trip within 0.1 afer
the short-circuit occurs. Consequently. they have 10
current of about 47 KA.
K prior 0.
yea time ine
interrupt
16.23 Power transfer between
two sources
‘The cireuit of Fig. 16.33a is particutarly important
because itis encountered in the study of generators,
synchronous motors, and transmission lines. In
such circuits we are often interested in the active
power transmitted from a source A to a source B or
Vive versa, The magnitude of voltages Ey and Es, as
well as the phase angle between them. are quite ar
bitrary. Applying Kirehhoti"s voltage law to this
circuit, we obtain the equation
Ey = By 4 jx
If we assume that / lass behind Es by an arbitia
angle # and Ey leads Ey by an angle 8, we obra the
phasor diagram shown (Fig. 16.335). Phasor 1X
Teads / by 90°, The active power absorbed by Bis
P> Esl cos (16.6)302 ELECTRICAL MACHINES AND TRANSFORMERS
or .
8
@
x
©
*
Figure 16.33
Power flow between two vollage sources,
From the sine law for triangles, we have
Whin B= Khio
Ey/sin (90 + 8)
= E\leos 8
Consequently, feos 8 = E sin BI (16.7)
Substituting (16.7) in Bq. 16.6, we find
EE
pa PE in (16.8)
x
where
sansmitted [W]
voltage of source 1 |V]
voltage of source 2 [VI
phase angle hetw
‘The active power P received by B is equal to that
delivered by A, because the reactance consumes 0
active power. The magnitude of P is determined by
the phase angle between £ and Ey: the angle # be-
tween E, and / does not have to be specified,
Theactive power always flows from the leading 10
the lagging voltage. In Fig. 16.33. itis obvious that E,
leaus Ey: hence power flows from left to right
Example 16-9
Referring to Fig, 16.338, source A generates a volt.
age Ey = 20 KV 2 5° and source B generates a volt
age Es = 15 RV Z 42°, The transmission fine co
them has an inductive reactance of 14 0,
Calculate the active power that flows over the fine
sand specify which source is actually a load.
Solution
The phave angle between the two sources is 42° —
5° = 37°. The voltage of source B leads that of
Source A because its phase angle is more positive.
Consequer
Iy. power Hows from B 0.4 and so. is
tactually & load. The active power is given by:
BE
n= FE ns sa)
oAV kV
200 150 aga = 19 1
- 20 sn
Note that. strange as it may seem, power flows,
from the source having the lower voltage (15 KV) t0
the one having the higher voltage (20 kV).
16.24 Efficiency, power, and size of
electrical machines
The physical size of an electrical machine hasa pro-
found effet upon its efficiency. power output, rela-
tive cost, and temperature rise. The following
analysis reveals why these characteristics are inti-
mately related,
[Let us consider a simall ae geuerawor having the
following characteristics:
power output raw
rated voltage 120-V.3 phase
raed current ABA
rated speed 1800 r/minefficiency 3%
input torque 727m
mosnent of inertia 0.0075 kgm
external diameter 0.180.m
external length Os m
mass 20ke
power ourpatimass 50 Wikg
Using this information, we can calculate the losses
oF the machine
P.
x 100
awe
eg. 3.6
B 100
input power P, = 1.37 kW
logses = 1.37 KW — LOKW = 0.37 kW
‘The losses comprise the 17R losses in the windings,
the hysteresis and eddy-current losses in the iron
and the windage and friction losses.
Let us increase the size of the mal
a way that ils Finear dimensions are raised in ex-
actly the same proportion. while keeping the same
materials throughout, Thus, ifa particular type of
iron lamination was used in the stator, the same
type is used in the larger machine. The same type
oF insulation is also used, thereby duplicating and
‘magnifying everything, including the bearings,
‘nuts and bolts
In this larger generator we will keep the sume
current densities (A/a) ay inthe original machine
We will also maintain the same Mux densities (1es-
las) in the various parts of the magnetic circuit
(core, air gap, stator teeth, ee.)
Asa result, the FR losses per em" and the iron
losses perenr’ will be everywhere the
original machine, It follows that the copper losses
and iron losses will inerease in proportion wits vole
lume, Let's assume that the windage and friction
losses also increase the sume way.
We further assume that the number of slots, eon.
‘ductors and interconnections remain the same as.
befowe und that the speed of rotation (1800 min) is
left unchanged,
ne in such
nes inthe
SYNCHRONOUS GENERATORS 363
Under these conditions, we ean predict the prop:
erties of the generator as its size is increased.
For example, suppose that all the linear dimen-
sions ate sripled, The volume will therefore in-
crease by a factor of 3° = 27. Consequently, the
‘mass will increase by a factor of 27 and so. 00, will
the losses, The mass of the bigger machine will
therefore be 27 X 20 kg = 540 kg. The losses will
rise to 27 % 0.37 kW = JOKW
‘The slots are 3 times wider and 3 times deeper.
As a result, the cross section of the conductors is 9
times greater which means they can carry 9 times
‘more current. The larger machine can therefore de-
liver a current of 9 X48 A= 43.2.4,
AAs regards the generated voltage per conductor, it
is determined by equation (2.25) = Bl: We recall
that B isthe flux density. is the length ofthe condue-
torand vis the speed at which the flux cuts across it
‘The flux density in the larger machine is the same
as before, However, the length has tripled
Furthermore. the peripheral speed ¥ has increased 3
limes because the diameter ofthe rotor has tripled. As
a result the voltage generated per conductor also in-
creases by a factor of 9, Because the langer generator
has the same number of conductors ts before and be
‘cause they are connected the same way. the genera-
{or will produce a voltage of 9 % 120 V = 1080 V.
‘Thus, by tripling the linear dimensions. the volt-
‘age and current both increase by a factor of 9. This
‘means that the power output inereases 9 9 = 81
times, The power output of the new generator is
therefore 81 1 AW = 81 KW.
‘The power input needed! to drive the ae genera
tor is P, = 81 KW + losses = 81 kW + 10 KW =
ST KW. The new efficiency is therefore:
SEW 100
ork *
= 089
89%
‘The efficiency has increased from 73% to 89%
Which is a dramatic improvement, The reason is that
the power output has inereased 81 times, whil30s ELECTRICAL MACHINES AND TRANSFORMERS
losses increased only 27 times. Consequently. the ef
ciency ofthe machine was bound to increase with size.
inal machine produced an output of 50
Wikg. The larger machine has a mass of S40 kg and
produces 81 kW. Consequently. it produces 81
KW/S4O ky = 150 Wokg which is 3 times greater
than before.
‘The larger generator is therefore relatively
Tighter ane cheaper than the snraller machine, AS
proof. if eighty-one I kW generators were used to
prosluce 81 kW, their combined mass would be 81
X 20 ke ~ 1620 kg, This generating center would
obviously be more costly and take up more floor
space than the single 81 kW generator
As another matter of interest, we recall that the
‘moment of inertia J of a rotor is proportional to its
sand the square of its radius (see Table 3A)
Hence. when linear dimensions are tripled. J will
we by a faetor of J = mir? = 77 x ¥ = 3 =
243. The moment of inertia of the larger machine is
therelove 243 0.0075 ky-m? = L8 ky:
‘The characteristics of the larger generator are
summarized below. They are in striking contrast to
the original | kW machine,
power output Br kw
rated voltage 1080 V, 3 phase
rated current BIA
rated speed 1800 r/min
elticieney 89%
input torgu 483 Nom
moment ofinentia 1.8 kgm?
external diameter O.s4.m
external length 0.45 m
mss 540 kg
power outpuiimass 150 Wa
The one big problem is temperature rise. When
linear dimensions are tripled, the heat-dissipating
surface area of the machine inereases 9 times but
the loyses inerwase 27 times. Hence, the power dis-
Sipated per square meter inereases by a factor of 3.
Consequently, unless better cooling means are
used, the langer machine is howd to be hotter: To
prevent damage to the insulating materials. the tem-
perature rise has t0 be limited t a maximum of
ns
about 200°C. Consequently, the evoling of large
machines isa very important matter.
In conclusion, ihe general principles covered here
reganling physical size, power output, efficiency,
temperature rise and so forth, apply’ to all machines,
including ae and de motors and transformer.
Questions and Problems
Practical level
VoL What are the advan
of using a stutionury
large synchronous generators?
Why is the stato always connected in wye?
16-2 State the main differences between st
turbine generators and salient-pole gener
ators. For a given power output. whieh of
these machines is the larger?
16-3. In analyzing a hydropower site it is Found
that the turbines should turn at close &9
350 r/min, Ifthe directly-coupled gener
tors must generate a frequency of 60 Hz,
calculate the following:
The number of poles on the ror
>. The exact turbine speed
16-4 An isolated 3-phave generator proces 3
‘no-load line voltage oF 13.2 kV. Ifa load
hhaving a lagging power factor of 0.8 is
cconnevted to the machine, must the exei-
tation be increased or decreased in order
{© maintain the same line voltage?
16-5 What conditions must be met before a gener
‘ator ca be connected 0 a 3-phase system?
16-6 Caleulate the number of poles on the gener
torin Fig. 16.12 using the information given.
Calculate the number of poles on th
ceralt generator shown in Fig, 16.1
16-7
16-8 A 3-phave generator turning at 1200 r/min
generates @ no-load voltage of 9 KY. 60)
Hy. How will he terminal voltage be al
fected ifthe following loads are connected
to its terminals?
a Resistive oad
Bb. Inductive lod
© Capwitive load169
In Problem 16-8, ifthe field current is
kept constant, calculate the no-load volt~
age and frequency if the speed is
1000 e/min
b. Simin,
Intermediate level
16-10
tot
told
lols
lol
16-15
16-16
‘What is meant by the synchronous reac
tance of a 3:phase generator? Draw the
equivalent circuit of a generator and ex
plain the meaning of all the parameters.
State the advantages of brushless excita
tion systems over conventional systems
Using a schematic circuit diagram, show
how the rotor in Fig. 16.7 is excited.
Referring to Fig. 16.13, calculate the ex-
ng current needed to generate a no:
load fine voltage of
a. 42kV
BRT
A 3ephaye generator possesses a yynehro-
nous reactance of 6 $1 and the excitation
voltage E, is 3 kV per phase (ref. Fig.
16.19). Calculate the fine-to-neutral volt
tage E for a resistive load of § Q and draw
the phasor diagram,
28, In Problem 16-13. draw the curve of E ver-
sus / forthe following resistive loads: in
ity. 24, 12.6, 3.0 ohms,
i. Caleulate the ative power P per phase in
cach ase,
«e. Draw the curve of £ versus P For what
value of load resistance isthe power output
Referring to Fig. 16.2, calculate the length
‘of one pole-pitch measured along the in-
ternal circumference of the stator
‘The 3-phase generator shown in Fig.
16.16 has the following characteristics:
E, = 2440
X= 440
R=179.
load impedance Z = 175.0 (resistive)
SYNCHRONOUS GENERATORS WS
Catewtate
1. The total resistance of the
phase
«6 The total reactance of the circuit, per
phase
4. The line curent
€. The line-to-neutral voltage eros the load
1. The line voltage aerons the load
18 The power of the turine driving the alter
hh The phase angle between E, and the vol
age across the load
A 3.phase generator rated 3000 KA,
20 KV, 900 r/min, 60 Hz delivers power 10
22400 KVA, 16 kV load having a lagging
power factor of 0.8. If the synchronous re-
actance is 1002, calculate the value of
E,, per phase.
16-17
16-18 ‘The generator in Fig. 16.2 has a synchro
nous reactance of 0.4 £2, per phase. It is
connected to an infinite bus having a line
voltage of 14 KY, and the excitation volt-
ic adjusted 10 1 14 pu
Catealate
erator de
1 The torque angle 8 when the g
livers 420 MW
bb. The mechanical displacement angle o
«6. The linear pole shift (measured along the
inside stator cireuference) corresponding
to this displacement angle {i}
16-19 test taken on the S00 MVA alternator of
Fig, 16.2 yields the following results:
1. Open-circut ine voge is 15 kV for a de
‘exciting current of 1400 A.
2. Using the same de current, withthe arma-
ture short-cireited the resulting ae line eur
rent is 21 000 A.
Catewlare
‘8, The base impedance of the generator, per
phase
‘The valve ofthe synehionous reactance
The perunit value of X,
I The short-circuit ratio
aoe366
Advane
16.20
16-23
16-24
PLECTRICAL MACHINES AND TRANSFORMERS
ved level
The synchronous generator in Fig. 16.2
hasan efficiency of 98.4% when it deliv-
cers an output of S00 MW. Knowing that
the de exciting current is 2400 A at a de
‘voltage of 300 V, calculate the Following:
a, The total losses in the machine
D. The copper losses in the rotor
The torque developed by the turbine
4. The average difference in temperature be
tween the coo! incoming airand warm out
oing ai, ithe airflow is 280
Referring to Fig, 16.4, each coil on the ro-
torhas 21.5 tums, and carries a de current
‘of 500 A. Knowing that the air gap length
is 1.3 inches, calculate the Mux density in
the air gap at no-load. Neglect the mmf re-
{quired forthe iron portion of the magnetic
citeuit. (See Section 2.17),
g. 16.17. the following in-
ven about a generator:
I2kV
B= 14kV
20
, leads E by 30°
CCaleuate the total aetive power output of
i
Dy, Draw the phusor diagram for one phase
«6. Cleat the power factor of the load
‘The steam-turbine generator shown in Fig
16.3 has. a synchronous reactance of 1.3 pu
The excitation voltage E, is adjusted 10 1.2
pat and the machine is connected tan infi-
nite bus of 19 KV. IFthe torque angle & is
20° eaeulate the following:
a, The active power output
bi. The line easrent
(6 Dray the phasor ukagram, cor ome pase
In Problem 16-23, ealeulate the active
power output of the generator ifthe steam
valves are closed. Does the alternator re-
ceive or deliver reactive power and how
‘much?
16.25 ‘The generator in Problem 16-20 is driven
by a hydraulic turbine whose moment of
inertia is 54 x 10? Ih, The rotor has a J
of 4.14 x 10° kg’
a Ite line circuit beakers sakleny tip. ca
culate the sped ofthe generating unit (tur
bine an alternator) secon! ater. as
ing that the wicket zates remain wie open
b, By how many mechanival deszees do the
poles advance (vith espe
positon aunt
hhow many electrical degrees?
A 400 Hz alternator has a 2-hour rating of
TSKVA, 1200 rimin, 3-phase, 450 V. 80
percent power luctor (Fig, 16.34a). The
stator possesses 180 slots and has an inter-
nal diameter of 22 inches and an axial
length of 9.5 in, The rotor is designated
for a Field current of 31 A.at 115 V.
16-26
Cateutate
‘a, The number of poles on the rotor
bi. The number of coils on the stator
6 The number of coil por phase group on
the stator
4, The lensth of one pole pateh, measured
slong the cireumference ofthe stator
fe. The resistance of the de winding on the ro
tor and the power needed to excite i
Industrial application
16-27 A338 RVA. 480 V. 3-phase, 60 Hz diesel
driven emergency alternator is designed 10
‘operate ata power factor of 80 percent, The
following additional information is given:
Efficiency: 83.4%
Weight: 730 Ib
WA" (moment of inertia) : 15.7 1b.
Insulation: class B
Caleutate
8. The minimum horsepower rating of the
icsel engine to dive the generator
b. The maximum allowable temperature of the
‘windings, using the resistance methoA220 MVA, 500 r/min, 13.8 kV, 50 Hy,
0.9 power factor, water-turbine synchro-
nous generator, manufactured by Siemens,
has the following properties:
Insulation class: F
Moment of inertia: 525 tm”
Tonal mass of stator: 158 1
mmettie ton)
Total mass of rotor: 270 t
SYNCHRONOUS GENERATORS 367
Efficiency at full-load. unity power Factor
98.95%
insaturated synchronous reactance: 1.27 pu
Transient
uectance: 0.37 pu
Runaway speed in generator mode:
890 r/min
Static excitation is used and the excitation
current is 2980 A under an excitation volt-
age of 258 V.
Figure 16.34a
Rotor and stator of a 75 kVA, 1200 «min, 3-phase, 450\V, 400 He alternator for shipboard use. The alternator is.
riven by @ 100 hp, 1209 rimin synchronous motor.
Figure 16.34b
Stator and rotor ofthe 100 hp, 1200 r/min, 60 Hz synchronous motor. The stator is mounted on a bedplate that also
serves as a base forthe alternator. The rotor is equipped with a squirel cage winding to permt starting as an in-
duction motor. (Courtesy of Electro-Mécanik)Sok
ELECTRICAL MACHINES AND TRANSFORMERS
‘The generator is also designed to oper- 16-29
ae as a motor, driving the turbine as a
pump. Under these conditions, the motor
develops an output of 145 MW,
Both the stator and rotor are water-
‘cooled by passing the water through the
hollow current-carrying conductors, The
el So tha ivity is
less than 5 S/em, The pure water ows
through the stator at a rate of 8.9 liters per
second and through the rotor at 5.9 Titers
per second, Given the above information,
make the following calculations:
a. The
unity power factor and at 0.9 lagging power
factor
bb The rated reactive power output, in Mvar
. The short circuit ratio
4. The value ofthe line-0-ne
nous reactance, per phase
the total losses of the generator at Fall load
and unity power factor
its con
active power oatpat, in MW at 1630
ul synch:
In industry application Problem 16-28,
calculate the following:
4a. The horsepower rating of the generstor
when it rans asa pump moto
1, The kinetic energy of the rotor when it uns
at rte spec.
6. The kinetic energy of the rotor when it
sehes its maimum allowable runaway
speed
44. The time wo each the ranawsay speed inthe
‘erator is delivering its rate! load and asi
ing thatthe water continues to flow unchecked.
though the turbine (gates wide open)
In Problem 16-28 calculate the power di
sipated in the rotor windings and the
ower loss per pole. Knowing the rate of
water flow and that the inlet eemperature
is 26°C, calculate the temperature of the
‘water flowing out of the rotor windings.
‘What is the minimum resistivity (Qn) of
the circulating water?CHAPT
ER 17
Synchronous Motors
17.0 Introduction
he synchronous generators described in the pre
vious chapter can operate either as generators
‘oF ay motors, When operating as motors (by con
necting them to a 3:phase source), they are called
svaichronous morors, As the name implies, synchro-
nous motors run in synchronism with the revolving
field, The speed of rotation is therefore tied 0 the
Frequency of the source. Because the frequency is
fixed, the motor speed stays constant. irrespective
of the load oF voltage of the 3-phase line. However.
synchronous motors are used not so much because
they rum at constant speed but because they possess
fother unique electrical properties. We will study
wpe.
these features in this
Most synchronous motors are rated. between
150 KW (200 hp) and 15 MW (20 000 hp) and turn at
speeds ranging from 1500 1800 /min, Consequently
these machines are mainly used in heavy industry
igure 17.1
Three-phase, unity power factor synchro:
nous motor rated 3000 hyp (2200 KW), 327
rimin, 4000 V, 60 He driving a compressor
Used in a pumping station on the Trans-
Canada pipeline. Brushless excitation is
provided by a 21 kW, 250 V altematorract
tier, which Is mounted on the shaft bonwaen
the bearing pedestal and the main rotor
(Courtesy of General Electric)310 ELECTRICAL. MACHINES AND TRANSFORMERS
1. 17-1). Atthe other end of the power spectrum,
‘we find tiny single-phase synchronous motors used
in control devices und electric clocks. They are dis
cussed in Chapter 18,
17.1 Construction
‘Synchronous motors are identical in construction 10
salient-pole ac generators. The stator is composed
of a slotted magnetic core. which carries a 3-phase
Tap winding. Consequently, the winding is also
identical to that of a 3-phase induction motor
‘The roror has aset of salient poles that are excited
by a de current (Fig, 17.2), The exciting coils are
‘connected in series to two slip-rings. and the de cur
=
Figure 17.3
rent is fed into the winding from an external exciter
Slots arc also punched out along the circumference
of the salient poles. They carry
ing similar to that ina 3-phase induction motor. This
damper winding serves to start the motor.
Modern synchronous motors often employ brush:
less excitation, similar to that used in synchronous
wonerators. Refers tively small
hase generator, called exciter and a 3-phase recti-
The
a squirrel-cage wind:
o Fig. 17.3. are
Fier are mennted at one end of the motor sh
ide current f, from the rectifier is fed directly into the
salient-pole windings, without going through
brushes and slip-rings, The current ean be varied by
controlling the small exciting current f, that flows in
the stationary field winding of the excites, Fig. 17.4
Figure 17.2
Rotor ofa 50 He to 16 23 Hz frequency
corwerter used to power an electric railway.
‘The 4-pole rotor atthe leitis associated
with a single-phase alternator rated 7000
KVA, 16 2/3 He, PF 85%, The rotor on the
ght tora GYUU KVA, SU Mz, YO%e PE
‘synehronaus motor which dives the sin-
le-phase alternator. Both rotors are
‘equipped with squitrel-cage windings.
(Courtesy of ABB)
Sphawe input to tator
Diagram showing the main components of a brushless excite fora synchronous motor. tis similar to that of a syn-
Cchronous generator.shows how the exci
‘mounted in 3000 kW synchronous motor:
The rotor and stator always have the same mum:
ber of poles, As in the case of an induetion motor:
teeter, and salient poles are
the number of poles determines the synchronous
speed of the motor:
a _
n= 1204 any
where
= motor speed {r/min}
J = frequency of the source [Hz]
p= number of poles.
SYNCHRONOUS MOTORS
Example 17-1
Calculate the number oF salient poles on the rotor of
the synchronous motor showa in Fig. 17.4
Solution
The motor operates at 60 Hz and runs at 200 s/mins
consequently
n= 120 fp
200 = (120 x 60y4p
p= 36 poles
The rotor possesses 18 north poles and 18 south poles
Figure 17.4
‘Synchronous motor rated 4000 hp (3000
KW), 200 rimin, 6.9 KV. 60 He, 80%
power factor designed to drive an ore
crusher. The brushless exciter(allerna-
torirectfer) is mounted on the overhung
‘shatt and ig rated 50 KW, 250 V.
(Courtesy of General Electric)
Figure 17.4b
Close-up ofthe 50 kW exciter. showing
the armature winging and 5 of the 6
diodes used to recy the ac current
(Courtesy of General Eiectric)372 ELECTRICAL MACHINES AND TRANSFORMERS
17.2 Starting a synchronous motor
A synchronous motor cannot start by itself; cons
quently, the rotor is usually equipped with a yquirrel-
ceage winding so that it ean start up as an induction
‘motor, When the stator is connected to the 3-phase
fine, the motor accelerates until it reaches a speed
slightly below synchronous speed, The de excitation
iy suppressed during this starting period.
While the rotor accelerates, the rotating flux ere
tated by the stator sweeps across the slower movin
salient poles. Because the coils on the rotor possess
a relatively large number of turns, x high voltage is
duced in the rotor winding when it turns at low
speeds. This voltage appears between the slip-rings
nd it decreases as the rotor accelerates, eventually
becoming negligible when the rotor approaches
synchronous speed. To limit the voltage, and to im-
prove the starting torque, we either short-circuit the
slip-rings or connect them to an auxiliary resistor
during the starting period.
If the power capacity of the supply Tine is Tim-
ited, we sometimes have to apply reduced voltage
{o the stator. Asin the ease of induction motors, we
Use either autotransformers oF series reactors to
limit the starting current (see Chapter 20). Very
large synchronous motors (20 MW and more) are
sometimes brought up to speed by an auxiliary mo~
tor, called a pony motor Finally. in some big instal-
lations the motor may be brought up to speed by a
variable-frequency electronie sour.
17.3 Pull-in torque
As soon as the motor is running at close t0 53
cchronous speed. the rotor is excited with de current
‘This produces alternate N and S poles around the
circumference of the rotor (Fig. 17.5). Ifthe poles.
at this moment happen to be facing poles of eppo-
site polarity on the stator. a strong magnetic attrac
on is set up between them, The mutual attction
Jocks the rotor and stator poles together, and the ro-
tor is literally yanked into step with the revolving
field, The torque developed at this moment is ap-
propriately called the pul-in torque.
miateee—ob gain
Figure 17.5.
‘The poles ofthe rotor are attracted tothe opposite
poles on the stator. Al no-load the axes of the poles
coincide.
‘The pull-in torque of @ synchronous motor is,
powerful, but the de current must be applied at the
right momeat, For example. if it should happen that
the emerging N.S poles ofthe rotor are opposite the
N, S poles of the stator, the resulting magnetic re-
pulsion produces a violent mechanical shock, The
‘motor will immediately slow down and the circuit
breakers will wip. In practice, starters for synchro
‘nous motors are designed to detect the precise mo:
‘ment when excitation should be applied. The motor
then pulls automatically and smoothly into step
with the revolving field
Once the motor tums at synchronous speed, no,
voltage is induced in the squirrel-cage winding and so
it carries no current, Consequently, the behavior of 2
synchronous motor is entirely different from that of
aan induction motor. Basically, a synchronous motor
rolatesbecause of the magnetic attraction between the
poles ofthe rotor and the opposite poles ofthe stator.
To reverse the direction of rotation, we simply
interchange any two lines connected to the stator.
17.4 Motor under load—
general description
‘When a synchronous motor runs at no-load, the ro:
tor poles are directly opposite the stator poles and
their axes coincide (Fig. 17.5). However, if we ap-
ply a mechanical load, the rotor poles fall slightlyauisofN poe
Figure 17.6
“The rotor poles are displaced with respect to the axes
‘of the stator poles when the motor delivers mechani-
cal power,
behind the stator poles, but the rotor continues to
tum at synchronous speed. The mechanical angle
«between the poles increases progressively as we
increase the load (Fig. 17.6). Nevertheless, the
magnetic attraction keeps the rotor locked to the
revolving field, and the motor develops an ever
‘more powerful torque as the angle increases
But there is a Fimit, If the mechanical load ex-
‘ceeds the pull-out torque of the motor, the rotor
poles suddenly pull away from the stator poles and
the motor comes 10 a halt, A motor that pulls out of
sep creates a major disturbance on the line, and the
citeuit breakers immediately trip, This protects the
motor because both the squirrel-cage and stator
windings overheat rapidly when the machine ceases
to run at synchronous speed.
The pull-out torque depends upon the magneto-
motive force developed by the rotor and the stator
poles, The mmf ofthe rotor poles depends upon the
de excitation J,, while that of the stator depends
upon the ac current Mowing in the windings. The
pull-out torque is usually 1.5 t0 2.5 times the nom
inal full-load torque.
The mechanical angle « between the rotor and
stator poles has a direct bearing on the stator current
AAs the angle increases, the current increases, This is
tobe expected because a larger angle corresponds to
SYNCHRONOUS MOTORS 373
aa bigger mechanical load, and the increased power
ccan only come from the 3-phase ae source
17.5 Motor under load—
simple calculations
We can get a better understanding of the operation
of a synchronous motor by referring tw the equiva:
lent circuit shown in Fig. 17.7a, It represents one
phase of a wye-connected motor. It is identical 10
the equivalent or, because
both machines are built the sam
ux eb created by the rotor induces a vol
the stator. This flux depends on the de exci
rent 4. Consequently, £, varies with th
As already mentioned, the rotor and stator poles
are lined up at no-load, Under these conditions, in-
duced voltage &, isin phase with the line-to-neutral
voltage E (Fig. 17.7b). If in addition, we adjust the
excitation so that E,, = £, the motor “floats” on the
line and the line current J is practically zero. la ef-
fect, the only current needed is to supply the small
swindage and friction losses in the motor, and so itis
negligible
‘What happens if we apply a mechanical load 10
the shaft? The motor will begin to slow down,
causing the rotor poles to Fall behind the stator
poles by an angle a, Due to this mec shift,
Ey litte tater than
before. Thus, referring to Fig. 17.7e, Eis now 8
electrical degrees behind £, The mechanical dis
placement a produces an electrical phase shift 5
between E, and E.
‘The phase shift produces a difference of poten.
tial E, across the synehronous reactance X, given by
iches its maximum value
Consequently, a current / must Mow in the circuit,
‘given by
JK,
from which
= jE IK,
HE ~ BUX,AM ELECTRICAL MACHINES AND TRANSFORMERS
Figure 17.74
Equivalent crcut of a synchronous motor, showing
fone phase,
EE,
Figure 17.7b
‘Motor at no-load, with, adjusted to equal E
5= pala
Figure 17.76
‘Motor under load has the same value a in Fig,
17-70, butitlags behind E.
The current lags 90° behind E, because X, is in-
ductive, The phasor diagram under load is shoven in
17-Je, Because /is nearly in phase with E, the
motor absorbs active power, This power is entirely
transformed into mechanical power, except for the
relatively small copper and iron losses inthe stator.
In practice, the excitation voltage B, is adjusted,
to be greater or less than the supply voltage &. Tts
value depends upon the power output of the motor
and the desired power factor.
Example 17-2¢
'AS(\) hp. 720 ehnin synchronous motor connected to
4 3980 V, 3-phase line generates an excitation volt-
age E,,of 1790 V (line-to-neutral) when the de excit-
ing current is 25 A. The synchronous reactance is 22
{and the torque angle between E,, and E is 30°,
Calewlare
a, The value of Ey
b. The ac line current
ce. The power factor of the motor
4. The approximate horsepower developed by the
motor
. The approximate torque developed at the shat
Solution
‘This problem can best be solved by using vector no-
tation,
a The vole £ ineto-netr applied to the
motor has value
B= IVI = 39809
OV
Let us select Eas the reference phasor. whose
angle with respeot to the horizontal axis is as
sumed to be zero, Thus,
E
3002.0"
I follows that E, is given by the phasor
7902 —30°
‘The equivalent circuit per phase is given in Fig.
178,
Moving clockwise around the circuit and ap-
Kirchhoft's voltage law we can write
30°
2300 (cos 0° + j sin 0°)
1790 (cos =30° + j sin 30°
2300 ~ 1550 + 895
= 750 + j 895
= 11682.50°Figure 17.88
Equivalent circuit ofa synchronous motor connected
toa source E.
‘Thus, phasor £, has a value of 1168 V and it
leads phasor £ by 50°
. The line current Fis given by
pars Ey
1168 2 50°
ward
532-40"
‘Thus, phasor J has a value of 53 A and it lags
40° behind phasor E.
cc. The power factor of the motor is given by the
cosine of the angle between the line-to-neutral
voltage E across the motor terminals and the
current J, Hence,
power Factor = cos = cos 40°
= 0.766, 01 76.6%
‘The power factor is lagging because the current
lags behind the voltage.
‘The complete phasor diagram is shown in Fig.
17.8b,
4d, ‘Total active power input to the stator:
P,= 3X Fixh cos
3.6 2300 ¥. $3 ¥ eon 10
= 280 142 W = 280.1kW
Neglecting the FR losses and iron losses in the
stator, the electrical power transmitted across
the airgap to the rotor is 280.1 KW.
Approximate horsepower developed:
P= 280.1 x 109746 = 375 hp
SYNCHRONOUS MOTORS 375
e
2300
fo sh
1
53a
D
vay
Figure 17.80
‘See Example 17-2.
fe. Approximate torque
955 XP _ 9.55 x 280.1 x 10°
n 70
15Nem
Example 17-2b
‘The motor in Example 17-2a has a stator resistance
of 0.64 Q per phase and possesses the following
osses:
PR losses in the rotor:
Stator core loss:
‘Windage and friction loss
Catewlate
a, The actual horsepower developed.
b. The actual torque developed at the shaft
cc. The efficiency of the motor
Solution
a4, Power imput to the Stators 280.1 kW
Stator PR losses = 3X 53? X 0.64.2 = S4kW
Total stator losses = 5.4 + 3.3 = 8.7 kW
Power transmitted fo the rotor = 280.1 ~ 87
= 14 kW
“The power at the shaft is the power to the rotor
‘minus the windage and friction losses. The rotor376 ELECTRICAL MACHINES AND TRANSFORMERS
FR losses are supplied by an external de source
and so they do not affect the mechanical power,
Power available at the shat
P= ITA 1S = 269.9kW
= 200910" ae gy
ieee te
‘This power is very close to the approximate
‘value calculated in Example 17-24,
'. The corresponding torque is
pa DSS XP _ 955 X 260.9 10°
Sn 0.
= 3580 Nem
c. Tonal lowes = $4433 +324 15 = BARW
‘Total power input = 280.1 + 3.2 = 283.3 KW
“Total power output ~ 269.9 KW
Eificiency = 269,9/283,3 = 0.9527
95.3 %
Note that the stator resistance of 0.64 is very
small compared to the reactance of 22. Q.
Consequently. the true phasor diagram is very
close tthe phasor diagram of Fig, 17.86,
17.6 Power and torque
‘When « synchronous motor operates under load, it
draws active power from the Tine. ‘The power is
iziven by the same equation we previously used for
the synchronous generator in Chapter 16:
P= (EEIX) sin (16.5)
Asin the ease of a
absorbed by the motor depends upon the supply
voltage E, the excitation voltage E,, and the phase
angle 6 between them. If we neglect the relatively
small 7° and ion losses in the stator, all the
power is transmitted across the air gap 10 the rotor.
This is analogous to the power P, transmitted
across the air gap of an induction motor (S
13.13), However, in a synchronous motor, the 10>
tor FR losses are entizely supplied by the de
source, Consequently. all the power transmitted
nerator, the active power
tio
stcross the air gap is available in the form of me
nical power, The mechanical power developed
by a synchronous motor is therefore expressed by
the equation
sind 7.2)
where
P = mechanival power of the motor, per
phase [WI
., = line-to-neutral voltage induced by 1, [V1
re of the source [V]
= fine-to-neutral volt
synchronous reactance per phase [0]
torque angle between E, and E
[electrical deg:
This equation shows that the mechanical
power ineteases with the torque angle. and ity
maximum value is reached when 8 is 90°. The
poles of the rotor are then midway between the N
and S poles of the stator, The peak power P,
(per-phase) is given by
7
(150/600) = 600 V
‘The frequency is also proportional to the speed,
and so
f> 60 (15/60)
S Hz
‘The synchronous reactance is proportional 10
insane comeateny
Figur 1.208
160
2e00v
Motor turning at 600 vimin (Example 17-6)
600 ein600
150 ri
Figur 1.208
Motor turning at 180 rin (Example 17-6),
= 16 x (15/00) = 4.0
Referring to Fig. 17.22b the new impedance per
phase at 150 r/min is
Z-\OP +P =40
“The current phase is
T= EZ = 6004 = 150
Thuis the short
chan;
rmin to 150 r/min, The power dissipated in the
3 phases is therefore the same as before:
reuit current remains un-
ed as the motor decelerates from 600
P= 13.5kW
The kinetic energy at 600 e/min is
By = 548 x 10 Te G8)
= 548 x 10-* x 275 x 600°
= 542.5 kl
4. The kinetic
Eqs = 548 x 10-8 x 275 x 150"
=339k
ray at 150 r/min is
‘e. The loss in kinetic energy in decelerating from
(600 r/min to 10 r/min is
W=6-&
= 5425 — 33.9
= 508.6 KI
This energy is lost as heat in the armature re
tance, The time for the speed 10 drop from 600
min 10 150 eimin is given by
SYNCHRONOUS MOTORS 385
P= Wh Gay
13.5 = 508.6i7
whence 1 = 37.7.
Note that the motor would stop much sooner if
external resistors were connected
tor termi
oss the Ste
17.14 The synchronous motor
versus the induction motor
We have already seen that induction motors have
excellent properties for speeds above 600 r/min,
But at lower speeds they become heavy. costly. and
have relatively low power factors and efficiencies,
Synchronous motors are particukarly autrctive
for low-speed drives because the power factor ean
altways be adjusted to I, and the efficiency is high,
Although moze complex to build, their weight and
cost are ofien less than those of induction motors of
cequall power and speed. This is particularly true for
speeds below 3000 r/min,
A synchronous motor ean improve the power fae:
tor of a plant while cumying its nated load.
Furthermore, its starting torque eam be made consid
cably greater than that of an induetion motor. The
reason is that the resistance ofthe squirtel-cage wind-
ing can be high without alTecting the speed or eff
ciency at synchronous speed. Figure 17.23 compares
the properties of a squirrel-eage induction motor and
asynchronous motor having the sume nominal r
The biggest difference is in the starting torque,
High-power electronic converters. generating
Jhronous
very low frequencies enable us to fun
motors at ullraclow speeds, ‘Thus. h
the 10 MW range drive crushers, rotary kilns, and
variable-speed ball mills,
17.15 Synchronous capacitor
Asynchronous capacitor is essentially asynchronous,
motor running at no-load. Its only purpose isto ab.
sorb or deliver maetive power on a 3-phase system
in order to stabilize the voltage (see Chapter 25), The
‘machine aets as an enormous 3-phase capacitor (or386 ELECTRICAL MACHINES AND TRANSFORMERS
x
PS eee peels eee ee
» &
;
» 2
9939 409080 Too %
eet eaad
Figure 17.23
Comparison between the ficiency (a) and starting
torque (b) ofa squitel-cage induction motor and a
ssynehzonous motor, both rated at 4000 hp, 1800,
rimin, 6.9 KV, 60 He.
Inductor) whose reactive power ean be varied by
changing the de exci
Most synchronous capacitors have ratings that
range from 20 Myar to 200 Mar and many are
hydrogen-cooled (Fig. 17.24). They are started up
like synchronous motors. However, if the system
cannot furnish the requited starting power, a pony
motor is used to bring them up to synchronous
speed. For example, in one installation, a 160 Mvar
Figure 17.24a
“Three-phase, 16 kV, 900 rimin synchronous capacitor
rated ~200 Mvar (supplying reactive power) to +300
‘Mvar (absorbing reactive power). Ils used to regulate
the voltage of @ 735 kV transmission line, Other char-
acteristics: mass of rotor: 143 t; rotor diameter: 2670
rim; axal length of stator iron: 3200 mm; air gap
length: 39.7 mm
Figure 17.24b
‘Synchronous capacitor enclosed ints stee! housing
containing hydrogen under pressure (300 kPa, or
about 44 loin’)
(Courtesy of Hydro-Québec)synchronous capacitor is started and brought up 10
speed by means of a 1270 kW wound-rotor motor,
Example 17-7 7
A synchronous capacitor is rated at 160 Mvar,
16 kV. 1200 rimin, 60 Hz. It has a synchronous re-
actance of 0.8 pu and is connected to a 16 kV Tine.
Calculate the value of E, so that the machine
1a. Absorbs 160 Mvar
b. Delivers 120 Myar
Solution
a. The nominal impedance of the machine is
‘The synchronous reactance per phase is
X, = Xe(pu) Z, = 08 1.6
128.0
‘The line current for a reactive load of 160 Mvar
SUV3 Bg
160 x 10°21.73 16000)
STS
‘The drop across the synchronous reactance is
E.= IX. = S780 % 1.28
7400 V
The line-to-neutral voltage is
BING = 16 000/173
9250V
Selecting Fas the reference phasor. we have
E= 9250
‘The current Flags 90° behind E because the
machine is absorbing reactive power conse-
quently
1= 57802 -90"
SYNCHRONOUS MOTORS 387
4295.8
5850 9250 14800
Figure 17.25b
Over-excited synchronous capacitor delivers reactive
power (Example 17-7).
From Fig, 17.25a we ean write
HE + jIX, + E,=0
hence:
Ey = B= jIX,
= 925020" ~ S780 x 1.282(90° — 90°)
= 185020
Note that the excitation voltage (1850 V) is
sch less han the fine voltage (9250 V),
b. The load current when the machine is dativer-
ing 120 Moar is
.= OUT)
= 120 10°.73 * 16.000)
= 454
This time / leads £ by 90° and so
14335290"
From Fig. 17.25b we ean write
E,= B= JIX,
= 925020" — 4335 1.287180"
(9250 + $550)20
= 14 80020388 ELECTRICAL MACHINES AND TRANSFORMERS
5780.8
Figure 17.254
Under-excitad synchronous capacitor absorbs reac-
tive power (Example 17-7),
‘The excitation voltage (14 800 V) is now con
siderably greater than the fine voltage (925
Questions and Problems
Prcctictl level
17-1 Compare the construction of a synehro-
‘nous generator, a synchronous motor, and
fa squirrel-cage induetion motor.
Explain how a synchronous motor starts up.
‘When should the de excitation be applied?
Why does the speed of a synchronous motor
remain constant even under variable load?
Name some of the advantages of a syn-
cchronous motor compared to a squirrel
cage induction motor.
m5
What is meant by a synefyonous capacitor
and what is it used for?
1, What is meant by an under-esvited sy
chronons motor?
b, Ir we overexcitea synchronous motor,
does its mechanical power output increase?
Agynchronous motor draws 2000 kVA at
a power factor of 90% leading. Calculate
the approximate power developed by the
176
m7
motor [hp] knowing it has an efficiency
of 95%.
17-8 Asynchronous motor driving a pump
‘operates at a power Factor of 100%
‘What happens if the de excitation is in-
creased?
17-9 A 3-phase, 225 r/min synchronous motor
connected t0 a4 KV, 60 Hz line draws a
current of 320 A and absorbs 2000 kW.
Cateulate
4. The apparent power supplied the mator
b. The power factor
The reactive power absorbed
44. The number of poles on the rotor
A synchronous motor draws 150 A from a
3-phuse line, IF the exciting current is
raised, the current deops to 140.4. Was the
motor over- or under-excited before the
excitation was changed?
17-10
Intermediate level
IT-I1 a, Calculate the approximate full-load current
‘of the 3000 hp mevor ia Fig. 17.1, i thas
an efficiency of 97%,
17-12 Referring to Fig. 17.2, at what speed must
the rotor turn to generate the indicated fre~
quencies?
17-13 A 3:phase synchronous motor rated 800
hp, 2.4 KV, 60 Hz operates at unity power
factor, The line voltage suddenly drops 10
1.8 kV, but the exciting current remains
unchanged. Explain how the Following
quantities are affected:
2, Motor speed and mechanical power output
D. Torque angle 8
€. Position ofthe rotor poles
4. Power factor
©. Stator current
A.synchronous motor has the followin,
parameters, per phase (Fig. 17,74):
E = 24KV:E, = 3kV
20
900.4,
Wt
x,Draw the phasor diagram and determine:
‘a. Torgue angle 8
by Active power, per phase
«Power factor ofthe motor
4. Reactive power absorbed (or delivered),
per phase
17-15 a, In Problem 17-14 calculate the Hine current
and the new torque sigh 8 i the mechani
cal load is suddenly eemoved.
De. Calculate the new reactive power absorbed
(or delivered) by the motor, per phase
4.500 hp synchronous motor drives a
compressor and its excitation is adjusted
so that the power factor is unity. IV the ex-
citation is increased without making any
‘other change, what isthe effect upon the
following:
a. The active power absorbed by the motor
bb. The line cure
«6. The reactive power absorbed (or delivered)
bythe motor
4. The torque angle
1716
Advanced level
17-17 The 4000 hp, 6.9 KY motor shown in Fig
174 possesses a synchronous reactance of
10.2, per phase. The stator is connected
in wye, and the motor operates at full-load
(4000 hp) with a leading power factor of
(0.89. Ifthe efficiency is 97%, calculate
the following:
a, The apparent power
bb The line current
«. The value of E,. per phase
4. The mechanical displaceme
From theie no-load position
, The worl reactive power supplied to the
clecricl system
6 The approximate maximum power the
motor ein develop. ssithout palling oat of
step (hp
In Problem 17-17 we wish to adjust the
power factor to unity
‘oF the poles
i718
Cateutare
a. The exciting volge E, required. per phase
i. The new torque angle
119
SYNCHRONOUS MOTORS 389
A3-phase, unity power factor synchro-
hous motor rated 400 hp, 2300 V, 450
min, 80 A, 60 Hz, drives a compressor.
‘The stator has a synchronous reactance of
0.88 pu, and the excitation , is adjusted
10 1.2 pu.
Catewlate
17.20
‘a, The value of X.and of E,
bb. The pull out torgue [ft 1bt)
«6 The line current when the motor is about to
pull out of synchronism
‘The synchronous capacitor in Fig, 17.28
possesses a synchronous reactance of
0.6 © per phase. The resistance per
phase is 0.007 Q. If the machine coasts
toa stop, it will run for about 3 h. In or-
der to shorten the stopping time, the sta-
tor is connected to three large 0.6 0
braking resistors connected in wye. The
de excitation is fixed at 250 A so that the
initial line voltage across the resistors is
‘one-tenth of its rated value, oF 1600 V, at
900 min,
per phase
Cateulate
‘a, The total braking power and braking torque
900 g/min
be. The braking power and braking torque at
450 min
The average braking torque between 900
rien and 480 einin
‘4. The time for the speed ofall rary 900 chm
1 450 ein, knowing that the moment of
ria of the rotor is 7 % HOP
Industrial application
1721
‘A 500 hp, 3-phase, 2200 V, unity power
factor synchronous motor has a rated cur-
rent of 103.A. It can deliver its rated out-
pput so long as the air inlet temperature
40°C ov less. The manufacturer states that
‘the output of the motor must be decreased
by I percent for each degree Celsius
above 40°C. If the air inlet temperature is
46°C. calculate the maximum allowable
‘motor current.ELECTRICAL MACHINES AND TRANSFORMERS
An 8800 KW. 6.0 kV, 1500 r/min, 3-phase,
50 Hz, 0.9 power factor synchronous mo-
tor manufactured by Siemens has the fol-
lowing properties:
1. Rated curren:
2. Rated tog
3 Pall-cut torque:
4. Locked-rotor eucrent:
Excitation voltage: 160.V
Excitation currents 387A
Fui-ioad ettciency. excluding exenation
system losses: 97.8%
8. Moment of inertia of rotor
9. Temperature rise of cooking water:
Ie
Flow of cooling water:
Maximum permis
inertia: 1370 kgm?
Mass of ro1or 6.10 111 = metric ton)
Mass ofstator: 7.501
Mass ofenclosure: 3.971
962
S60kNm
15 pu
4.9 pu
5
6.
S20ke
2c
465 Limin
2
13
MW
Usi
lowing:
he above information, calculate the fol-
8, The total ass of the motor inching its
enclosure. in metric tons
“The flow of cooling water in gallons (U.S.)
per eninute
“The maximum total moment of inertia (in
Ibs), which the motor ean pull nto sya
hronismt
4d. The total losses oF the motor at Ful-ead
fe The sal etic oF te nn all
load
6. The resetive power delivered by the motor
a fll-load
If the iron losses are equal to the stator cop:
per losses, caleulate the approximate resis
tance between two terminals ofthe Stator
1h, Caleulate the resistance of the Field circuit
b.