Brazed plate heat exchangers
A product catalogue for comfort heating
2
     Inside view
 4   The Alfa Laval Brazed Plate Heat Exchanger
 6   Benefits
 7   Applications
 8   BHE data  tables
10   Accessories
11   Instructions
12   Using webcALcTM
14   Radiator heating  tables
15   Tap water heating  tables
                                                  3
The Alfa Laval brazed heat exchanger
The Alfa Laval BHE is the original brazed plate heat exchanger. The BHE concept
is a variation of the traditional plate and frame heat exchanger, but without gaskets
and frame parts. The BHE simply consists of channel plates, two cover plates and
connections. All including parts are made of stainless steel material.
 Compact and tough
 Easy to install
 Cost efficient
                                                                                    brazing material seals as well as holds
                                                                                    the plates together at the contact points.
                                                                                    Alfa Lavals brazed heat exchangers are
                                                                                    always brazed at all contact points,
                                                                                    which ensures optimal heat transfer
                                                                                    efficiency and pressure resistance. The
                                                                                    plates are designed to achieve longest
                                                                                    possible lifetime.
                                                                                    Since virtually all material is used for heat
                                                                                    transfer the BHE is very compact in size
                                                                                    and has a low weight and a low hold-up
                                                                                    volume. Alfa Laval offers a flexible design
                                                                                    that can be customised to meet the
                                                                                    customers specific requirements. The
                                                                                    brazed plate heat exchangers from Alfa
                                                                                    Laval ensure the customer the most
                                                                                    cost-efficient solution to his heat transfer
                                                                                    duties.
Material                                together using either copper or nickel
The brazed plate heat exchanger (BHE)   as the brazing material. In HVAC
consists of thin corrugated stainless   applications copper brazed units are
steel plates which are vacuum brazed    most frequently used, while nickel-
                                        brazed units are preferred in for
                                        example food applications and in
                                        applications involving aggressive fluids.
                                        Design
                                        Brazing the stainless steel plates
                                        together eliminates the need for sealing
                                        gaskets and thick frame plates. The
4
 First class manufacturing facilities
 High and consistent quality
 Leak and pressure testing of all units before delivery
Flow principle
The basic flow principle in a brazed
heat exchanger for HVAC applications
is parallel and counter current flow to
achieve the most efficient heat transfer
process. In a single pass design all
connections are located on one side of
the heat exchanger, making installation
very easy.
                                            tions are available, and there is also     Production
                                            the option of choosing the location        Alfa Laval leads the development
                                            of the connection. Alfa Laval offers a     towards optimal quality. We do it with
Multipass                                  wide range of standard heat exchanger       advanced production technology in high
The design options of the brazed           models and sizes tailor-made for HVAC       volumes. We do it with new technology
heat exchanger are extensive. The heat     applications which are available from       through constant research and develop-
exchanger can be designed as a mul-        stock, but customer specific designs        ment. We do it in deliveries and service.
tipass unit, different types of connec-    can of course also be offered when          As a leading global manufacturer we do
                                           requested.                                  it in offering a complete product range
                                                                                       of heat exchangers. Our knowledge
                                           Mix proof design                            gives you the best solutions, products
                                           In applications where legal regulations     with higher technical performance and
                                           or other reasons call for extra security,   a focus on energy savings. Quality must
                                           Alfa Lavals patented double wall design    prevail through the whole chain from
                                           for brazed units could be used. When        development to after sales. The brazed
                                           using double walls the two media are        heat exchangers are individually leak
                                           separated by two stainless steel plates.    and pressure tested to ensure first class
                                           In the unlikely event of an internal        quality, and Alfa Laval has approvals
                                           leakage it will be visible on the outside   from all major approval bodies.
                                           of the heat exchanger and no mixing of
                                           the two fluids will occur.
                                                                                                                              5
Benefits
            P
           Pressure and temperature resistant low weight heat exchanger
            E
           Easy installation
            R
           Rapid response to changes in temperature thanks to small
           hold up volume
            F
           Fouling minimised by the well engineered plate patterns creat-
           ing turbulent flow, which results in a self cleaning effect
            O
           Optimised design for every duty ensured by tailor made heat
           exchangers
            R
           Requires less space/kW than other types of heat exchangers,
           making the BHE very compact
            M
           Material utilisation almost 100%, virtually all material is used
           for heat transfer
            A
           A close temperature approach can be achieved thanks to well
           engineered plate patterns
            N
           No gaskets mean less need for maitainance
            C
           Cost efficient in several apects
            E
           Every single BHE is pressure tested before delivery ensuring
           top quality products
6
                                                                                                     Applications
Applications
Brazed plate heat exchangers are com-
monly used in all types of heating
applications with demands on comfort,
reliability and safety. Heating, in most
cases, is a matter of providing a com-
fortable indoor environment, whether at
home, at work or in a public facility.
It can also involve heating tap water,
swimming pools, greenhouses etc.
Heating and District Heating
General heating applications are often
divided into heating and district heating,
based on several major differences.
Heating systems normally have the heat
                                             The compactness of the BHE makes them easy
source inside the building and supply
                                             to install in district heating modules, both in large
heat to a single building. The heat is       and small capacity systems.
normally provided from a boiler, but
it can also come from heat pumps
and solar panels. In contrast, district
heating systems distribute hot water
or steam to multiple buildings. The
heat can be provided from a variety
of sources, including geothermal sourc-
es, co-generation plants, waste heat
from industry, and purpose-built heating
plants. Whether it is heating or district
heating, the BHE has its natural place
in the system.
Tap water heating
The advantages of using a brazed plate
heat exchanger to produce hot tap
water compared to traditional coil
in tank systems are numerous. The
BHE instantly heats the tap water to
the required temperature when it pass-
es through the heat exchanger. This
means that hot water is available imme-       The small hold up volume means that the tap
                                              water heater is easy to regulate and provides
diately and at any time. Another benefit
                                              instant hot water.
with using plate heat exchangers for
hot tap water production is that the
system requires much less spaces than
a traditional tank and coil system. If
solar energy is used to produce hot
tap water a BHE makes it possible to
separate the treated water in the solar
panels from the tap water circuit. Also,
scaling problems and corrosion risks in
the solar panels are reduced when sep-
arating the circuits with a BHE.
                                                                                                                7
                                                               BHE Data & Dimensions                          BP10           CB14           CB20
                                                                Max./min. working temp. (C)                  120/3          225/-160       150/-50
                                          b
                                                                Max. working pressure S3-S4/S1-S2 (bar)*      10/3           30/30          16/16
         A                                d
                                                                Volume/channel (litres)                       0,022          0,028          0,032
                                                                Max. flowrate (m3/h)**                        2,8/2,0        3,6            8,1
                                                                Height, a, (mm)                               190            208            324
                                     S4       S1                Width, b, (mm)                                83             78             94
                                                                Vertical connection distance, c, (mm)         154            172            270
                                                                Horizontal connection distance, d, (mm)       40             42             46
                                                                Plate pack length, A, (mm)                    (n*2,3)+7      (n*2,35)+8     (n*1,3)+9
                                                      c   a
                                                                Weight, empty, (kg)                           (n*0,04)+0,2   (n*0,06)+0,7   (n*0,08)+0,9
                                                                Standard connection, external thread (inch)   3/4 / 1/2    3/4           1
                                                                Plate material                                AISI 316       AISI 316       AISI 316
                                                                Connection material                           AISI 316/cs    AISI 316       AISI 316
                                     S3       S2
                                                                Brazing material                              Copper         Copper         Copper
                                                              * Acc to Swedish pressure vessel code
                                                              ** Water at 5 m/s (connection velocity)
                                                                 n=number of plates
                                                                BHE Insulation                                BP10           CB14           CB20
                       B
                                                                Type A: Polyurethane/blue ABS cover
                                                                Height, A, (mm)                                                             384
                  S4       S1                                   Width, B, (mm)                                                              157
                                                                Thickness (mm)                                                                30
                                                                Max. temperature (C)                                                       140
                                     A
                                                                Type B: Black polypropylene/no cover
                                                                Height, A, (mm)                                              245            384
                  S3       S2
                                                                Width, B, (mm)                                               120            140
                                                                Thickness (mm)                                                 20             20
                                                                Max. temperature (C)                                        110            110
                                              L                                                               BP10           CB14           CB20
                                                               Couplings for welding or soldering
                                                                Size (inch)                                                  3/4           3/4 and 1
                                                                Pipe length carbon steel, L, (mm)                            23             50
                                                                OD/ID (mm) carbon steel pipe                                 21,3/17        26,9/22
                   OD           ID
                                                                Pipe length brass, L, (mm)                                   16             20
                                                                OD/ID (mm) brass pipe                                        18/15          25/22
                                                                Seal washer                                                  Klingersil     Klingersil
                                                               Feet                                           BP10           CB14           CB20
                                                                Height, X, (mm)
    T2       T3
                                                                Width, Y, (mm)
                                                                Length, Z, (mm)
                                                                Wall mounted
                            X                                   Material
                                                               Mounting brackets                              BP10           CB14           CB20
         Y                                        Z
                                                                Height, X, (mm)
                                                                Width, Y, (mm)
                                                                Wall mounted
                                                                Material
8
CB26           CB27           CB51           CB51-DW      CB52           CB76                CB77               CB200            CB300
225/-160       225/-160       225/-160       225/3        225/-160       225/-160            225/-160           225/-160         225/-160
30/30          30/30          30/30          16/16        30/30          30/30               25/16              25/25            25/16
0,059          0,059          0,1            0,1          0,1            0,19(1/0,26         0,26               0,51             0,7/0,58(3
8,1            12,7/7,5       8,1            8,1          12,7/7,5       39                  63/34              102              140 / 60
310            310            526            526          526            617                 617                734              990
112            112            112            112          112            192                 192                319              365
250            250            466            466          466            519                 519                622              816 / 861
50             50             50             50           50             92                  92                 205              213,5
(n*2,4)+9      (n*2,4)+9      (n*2,4)+10     (n*2,4)+10   (n*2,4)+10     (n*2,85)+10(2       (n*2,85)+10        (n*2,65)+12,5    (n*2,62)+15
(n*0,13)+1,2   (n*0,13)+1,2   (n*0,23)+1,9   (n*0,23)+2   (n*0,23)+1,9   (n*0,44)+7          (n*0,44)+7         (n*0,6)+29       (n*1,26)+57
1             1 1/4 / 1    1             1           1 1/4 / 1    2                  3 weld/ 2        3               4 / 2 1/2
AISI 316       AISI 316       AISI 316       AISI 316     AISI 316       AISI 316            AISI 316           AISI 316         AISI 316
AISI 316       AISI 316       AISI 316       AISI 316     AISI 316       AISI 316            AISI 316           AISI 316         AISI 316
Copper         Copper         Copper         Copper       Copper         Copper              Copper             Copper           Copper
                                                                                                                                 (3
                                                                         (1
                                                                            E channels                                                S3/S4
                                                                         (2
                                                                            A channels (n*2,5)+10
                                                                            E channels (n*2,2)+1
                                                                                                                          (1
CB26           CB27           CB51           CB51-DW      CB52           CB76                CB77               CB200            CB300
360            360            588                 588     588                 670            670                  811            1094
182            182            182                 182     182                 240            240                  370                 470
  30            30              30                 30      30                  30              30                    27                50
140            140            140                 140     140                 140            140                  140                 140
                                                                                                           (1
                                                                                                                Type C: Mineral wool/blue ABS cover
350            350            565                 565     565
153            153            153                 153     153
  20            20              20                 20      20
110            110            110                 110     110
CB26/27        CB27           CB51/52        CB51-DW      CB52           CB76/77              CB76/77           CB200           CB300
1             1 1/4         1             1           1 1/4         2/ cs flange         2
50             50             50             50           50             90                    50
26,9/22        33,7/28        26,9/22        26,9/22      33,7/28        48,3/44               60,3/54,3
20             50             20             20           50             50                    50
25/22          32/28          25/22          25/22        32/28          51/44                 51/44
Klingersil     TM9014         Klingersil     Klingersil   TM9014         Klingersil/TM9014     TM9014
CB26           CB27           CB51           CB51-DW       CB52          CB76                CB77               CB200           CB300
                                                                         199                 199                178             217 (S2)/194,5 (S3)
                                                                         260                 260                400             466
                                                                         A+180               A+180              A+160           A+260
                                                                         no                  no                 no              no
                                                                         galvanized          galvanized         galvanized      galvanized
CB26           CB27           CB51           CB51-DW      CB52            CB76               CB77               CB200           CB300
155            155            155            155          155            199                 199
100            100            100            100          100            182                 182
yes            yes            yes            yes          yes            no                  no
galvanized     galvanized     galvanized     galvanized   galvanized     galvanized          galvanized
                                                                                                                                                      9
Accessories
Cleaning-In-Place (CIP)
All types of heat exchangers need to
be cleaned regularly to remove deposits
such as scale, sludge and microorgan-
isms. Alfa-CIP is a convenient solution
that carefully removes the deposit on
all heat transfer surfaces in the heat
exchanger. Alfa-CIP 75, 200 and 400
are constructed in stainless steel using
high quality components (pumps, valves
etc.) according to ISO 9001 and with
the CE-mark. The smaller units Alfa-CIP
20 and 40 are made of industrial grade
plastic. Alfa-CIP is mobile due to its
compact design. The units have revers-
ible flow, and Alfa-CIP 75, 200 and 400
also have a built in heater. All cleaning
detergents used by Alfa Laval are envi-
ronmentally friendly and do not damage
the equipment.
                                                        Couplings for welding or soldering
                                                        The couplings fits on the threaded con-
                                                        nections of the units. Future service is
                                                        then easy made by dismantling the heat
                                                        exchanger from the pipes via the cou-
                                                        plings. This connection is approved in
                                                        most countries when weld or flange
                                                        connection is required. A flat washer is
                                                        used as sealing between the coupling
                                                        and connections.
Insulation
The heat exchanger insulation is easily     Feet and mounting brackets
assembled and dismantled. The Alfa          CB26 and larger units can be delivered
Laval insulation provides protection        with feet or mounting brackets. These
from the heat pack and the climate in       make the installation work easier and
the operating room will be dry and not      minimise stresses in the connected
too hot. The insulation material used for   pipes. The unit can also be bolted
most models is polyurethane, which has      to the floor. CB26, CB27, CB51 and
a thermal conductivity of 0,031 W/mK.       CB52 can be wall mounted using the
Depending on the temperature require-       standard feet frame. CB200 and CB300
ments two types of insulation are avail-    are always supplied with feet and a lift-
able for most models, max 110C and         ing hook to ensure safe and functional
max 140C.                                  installation.
10
                                                                                                          Instructions
     Start up procedure                     Shut down procedure             Installation instructions
                                                                            In HVAC applications it is from a per-
1.   Before starting any pump,         1.   First establish whether         formance point of view recommended
     check whether instructions             instructions exist as to        to install the heat exchanger so that
     exist stating which pump               which side should be            a counter current flow is obtained. It
     should be started first.               stopped first.                  does not matter if the heat exchanger
                                                                            is mounted vertically or horizontally, as
2.   Check that the valve              2.   Slowly close the valve con-     long as no change of phase takes place
     between the pump and the               trolling the flow rate of the   (evaporation/condensation). If drainage
     heat exchanger is closed.              pump you are about to           of the heat exchanger is needed for
                                            stop.                           some reason, please take this into con-
3.   Check that the valve at the                                            sideration when positioning the heat
     exit, if there is one, is fully   3.   When the valve is closed,       exchanger. The heat exchanger can be
     open.                                  stop the pump.                  mounted with brackets or standing on
                                                                            feet supplied by Alfa Laval. It is impor-
4.   Open the ventilation.             4.   Repeat the procedure for        tant to minimise vibrations or pulsations
                                            the other side.                 from being transferred from the pipes
5.   Start the pump.                                                        to the heat exchanger. The usage of
                                       5.   If the heat exchanger for       flexible hoses is one way of reducing
6.   Open the valve slowly.                 any reason is shut down for     stresses caused by vibrations, and
                                            a longer period, more than      stresses from the piping system.
7.   When all the air is out, close         a few days, it should be
     the ventilation.                       drained.                        Operation
                                                                            Adjustments in flow rates to maintain
8.   Repeat the procedure for the                                           correct temperatures or pressure drops
     other side.                                                            should be made slowly in order to pre-
                                                                            vent pressure shocks to the system.
                                                                            Therefore fast closing valves should
                                                                            not be used unless the pipes in the sys-
                                                                            tem are very short. Any problems with
                                                                            keeping the performance of the heat
                                                                            exchanger may be caused by changing
                                                                            temperature conditions, changing flow
                                                                            rates or by fouling.
                                                                            Maintenance instructions
                                                                            The heat transfer through the plates can
                                                                            be seriously reduced by the formation
                                                                            of deposits of various kinds on the plate
                                                                            surfaces. Even if the highly turbulent
                                                                            flow gives a strong resistance to the for-
                                                                            mation of deposits the turbulence can
                                                                            not completely eliminate fouling. Thanks
                                                                            to CIP (Cleaning In Place) it is possible
                                                                            to remove calcium deposits and other
                                                                            forms of scaling from the plate surfaces
                                                                            in an easy and effective way. Different
                                                                            cleaning solutions can be used depend-
                                                                            ing on the type of deposits. Alfa Laval
                                                                            has a world-wide service organisation.
                                                                            Service is available in 130 countries at
                                                                            15 major service centres and a network
                                                                            of service stations around the globe.
                                                                                                                   11
Using webcALcTM
Using webcALcTM
webcALcTM is an easy to use selection tool available on-line that can be used
for sizing heat exchangers for applications like tap water heating, district heating,
cooling, and district heating.
 Available on www.alfalaval.com
 Easy to use
 Detailed results
How to calculate and select a heat           simplified version of the software used        ferent input fields in webcALcTM. Move
exchanger with webcALcTM                     by Alfa Laval, and therefore the result        between the different input fields by
For duties that are not covered in the       may differ slightly when comparing with        using either the mouse or the tabulator.
selection tables, and if you want to         the selection tables and/or quotations
get a more tailor made design, you           made by Alfa Laval representatives.            How to use webcALcTMs control
can design your heat exchanger on-line       webcALcTM is quite easy to use, but            panel
on the internet site www.alfalaval.com       if you need instructions just follow the       Design pressure: Select the required
using a selection tool called webcALcTM.     step by step instructions below. You           pressure resistance for the heat
It should be noted that webcALcTM is a       enter the data for your fluids into the dif-   exchanger. (Default 10 bar)
                                                                                            Display: webcALcTM selects from the
                                                                                            complete range of gasketed and brazed
 Step by step guide                                                                         heat exchangers included in the soft-
                                                                                            ware (default). You can specify if you
                                                                                            only want a choice of either PHEs or
 1.   Start by selecting the hotter           4.   Enter the inlet temperature of
                                                                                            BHEs or standard sizes of BHEs.
      fluid, fluid 1, by clicking on               fluid 1 in the input field temper-
      the arrow in the pull down                   ature in, and if applicable the
                                                                                            Max no. of exchangers: webcALcTM will
      menu. Available fluids are: water            required outlet temperature in the
                                                                                            select one or more identical units (maxi-
      (default value), seawater (contain-          input field temperature out.
                                                                                            mum 9 units) depending on the require-
      ing approximately 3% NaCl), eth-        5.   Enter the data for the colder fluid,
                                                                                            ment of the thermal duty (default). If you
      ylene glycol and propylene gly-              fluid 2, in the same way as for
                                                                                            want webcALcTM to suggest only solu-
      col. When selecting glycol fill in           fluid 1 (point 1 to 4).
                                                                                            tions with a certain number of identical
      the concentration, %, in the input      6.   At the bottom of the page you
                                                                                            units, then select from one unit to nine
      field.                                       select which material that should
                                                                                            units.
 2.   Enter the maximum allowed                    be used for the heat transfer
      pressure drop over the heat                  plates. You can choose between
                                                                                            After you have entered the data
      exchanger in the next input field.           stainless steel AISI 316 (default),
                                                                                            When you have entered your data,
      (Default 100 kPa)                            stainless steel AISI 304 and tita-
                                                                                            press the heat balance button and
 3.   Enter the available flow rate of             nium.
                                                                                            webcALcTM will present the tempera-
      fluid 1. Omit this value if the heat    7.   Heat load is an optional field to
                                                                                            tures graphically. Via the heat balance
      load is specified either at the bot-         be used if the in- and outlet tem-
                                                                                            webcALcTM will calculate the missing
      tom of the page or if the heat               peratures as well as flow rate
                                                                                            parameters (heat load, flows or tem-
      load is specified through the full           have not been specified on either
                                                                                            peratures). Heat balance will also indi-
      input on the Cold Side. There                the cold or the hot side.
                                                                                            cate if any input parameters for a suc-
      must always be heat balance in          8.   The field units makes it possible
                                                                                            cessful thermal calculation are missing.
      the heat exchanger, which means              to change between SI, American
                                                                                            Please note that if both heat load and
      that the heat load on the hot side           or metric units.l
      is always equal to the heat load                                                      flows have been specified, webcALcTM
      on the cold side.                                                                     will give higher priority to the heat load.
12
 Lower cost
 Plug-and-play installation
 Full Technical support
Press calculate to perform the thermal
calculation. webcALcTM will present up
to nine alternative heat exchanger solu-
tions. It is possible to use the calculate
button without previous usage of heat        webcALcTM selects from the
balance. Press reset to empty your           complete range of gas-
input before entering new data for a         keted and brazed heat
                                             exchangers included in the
new thermal calculation. The input fields
                                             software (default).
will be reset to webcALcTMs default val-
ues.
How to use and interpret
webcALcTMs results
The heat exchanger solutions can
be sorted by four different criteria:
price (default sorting is based on an
approximate price comparison between
the different solutions), height, weight,    Press calculate to perform
and extension capacity. Brazed heat          the thermal calculation.
exchangers do not offer any extension        webcALcTM will present up
                                             to nine alternative heat
possibility. Please note that the speci-
                                             exchanger solutions.
fied weights may be slightly lower due
to different pressure vessel codes and
local standards. Select your solution by
clicking on the unit type in the table.
The output of webcALcTM
Each solution is presented with a stand-
ardised drawing and the specific tech-
nical parameters. Each solution also
has a corresponding AutoCAD drawing,         Each solution is presented
which can be downloaded to your com-         with a standardised draw-
puter. To print the technical parameters     ing and the specific techni-
use the printer friendly page offered at     cal parameters.
the bottom of the result page. It is also
possible to download specification texts
for different types of heat exchangers.
                                                                            13
Radiator Heating
Prim.in->out/out<-Sec.in     160->80/90<-70   136->70/70<-55   135->80/95<-70   135->80/95<-70   135->80/90<-70   135->80/90<-70   130->80/95<-70
Max pressure drop prim/sec   Max 50/20 kPa    Max 20/20 kPa    Max 10/20 kPa    Max 20/30 kPa    Max 10/20 kPa    Max 20/30 kPa    Max 10/20 kPa
 Capacity, kW                    Model           Model             Model           Model            Model            Model            Model           kW
       20                     CB14-12H         CB14-14H         CB14-20H         CB14-20H        CB14-14H         CB14-14H          CB14-20H          20
       50                     CB14-20H         CB14-30H         CB26-18H         CB26-18H        CB14-30H         CB14-30H          CB26-18H          50
      100                     CB27-24M         CB27-34M         CB26-34H         CB26-34H        CB27-34M         CB27-34M          CB26-34H         100
      150                     CB27-34M         CB27-50M         CB52-40L         CB26-50H        CB27-50M         CB27-50M          CB27-50H         150
      200                     CB27-50M         CB76L-30L        CB76L-30M        CB26-70H        CB76L-30M        CB76L-20M         CB27-70H         200
      300                     CB76L-40M        CB76L-40L        CB76L-30M        CB76L-30M       CB76L-40M        CB76L-30M         CB76L-30M        300
      400                     CB76L-50M        CB76L-50L        CB76L-40M        CB76L-40M       CB76L-50M        CB76L-40M         CB76L-40M        400
      500                     CB77-60M         CB77-60L         CB76L-50M        CB76L-50M       CB77-60M         CB76L-50M         CB76L-50M        500
      750                     CB77-90M         CB77-90L         CB77-70M         CB76L-70M       CB77-90M         CB77-70M          CB76L-70M        750
     1,000                    CB77-130M        CB200-76L        CB200-51M        CB200-45M       CB200-55M        CB200-49M         CB200-51M       1,000
Prim.in->out/out<-Sec.in     130->80/95<-70   130->80/90<-70   130->80/90<-70   130->75/95<-70   130->75/90<-70   130->70/85<-65   130->60/78<-58
Max pressure drop prim/sec   Max 20/30 kPa    Max 10/20 kPa    Max 20/30 kPa    Max 50/20 kPa    Max 50/20 kPa    Max 50/20 kPa    Max 20/20 kPa
 Capacity, kW                    Model           Model             Model           Model            Model            Model            Model           kW
       20                     CB14-20H         CB14-14H         CB14-14H         CB26-18H        CB14-30H         CB14-30H          CB26-18H          20
       50                     CB26-18H         CB14-30H         CB14-30H         CB26-34H        CB26-34H         CB26-24H          CB26-50H          50
      100                     CB26-34H         CB26-50H         CB27-34H         CB26-70H        CB26-50H         CB26-50H          CB26-70H         100
      150                     CB26-50H         CB27-50M         CB26-70H         CB27-100H       CB27-70H         CB27-70H          CB27-100H        150
      200                     CB26-70H         CB76L-30M        CB76L-20M        CB27-120H       CB27-100H        CB27-100H         CB52-60L         200
      300                     CB27-100H        CB76L-40M        CB76L-30M        CB76-50H        CB76L-50M        CB76L-40M         CB76-60H         300
      400                     CB76L-40M        CB76L-50M        CB76L-40M        CB76-70H        CB76L-60M        CB76L-60M         CB76-80H         400
      500                     CB76L-50M        CB76L-60M        CB76L-50M        CB76-90H        CB76L-70M        CB76L-70M         CB76-110H        500
      750                     CB76L-70M        CB77-90M         CB77-70M         CB77-120H       CB77-110M        CB77-100M         CB77-150H        750
     1,000                    CB200-45M        CB200-57M        CB200-49M        CB200-61M       CB200-71M        CB200-71M         CB200-80M       1,000
Prim.in->out/out<-Sec.in     120->50/90<-45   110->70/85<-65   110->70/80<-65   110->60/80<-55   110->60/70<-50   105->70/85<-65   95->45/75<-40
Max pressure drop prim/sec   Max 20/20 kPa    Max 20/20 kPa    Max 30/30 kPa    Max 30/30 kPa    Max 30/30 kPa    Max 50/20 kPa    Max 20/20 kPa
 Capacity, kW                    Model           Model             Model           Model            Model            Model            Model           kW
       20                     CB51-10H         CB26-18H         CB14-30H         CB26-18H        CB14-20H         CB26-24H          CB51-10H          20
       50                     CB51-20H         CB52-20L         CB26-24H         CB52-20L        CB26-18H         CB26-50H          CB51-20H          50
      100                     CB51-30H         CB52-30L         CB26-50H         CB52-30L        CB26-34H         CB52-30L          CB51-40H         100
      150                     CB51-40H         CB52-50L         CB27-70H         CB52-40L        CB27-50H         CB52-50L          CB51-60H         150
      200                     CB51-50H         CB76-40H         CB27-120H        CB52-50L        CB27-70H         CB52-80L          CB52-80H         200
      300                     CB52-80H         CB76-60H         CB76L-50M        CB76-40H        CB76L-30M        CB76-60H          CB76-71A         300
      400                     CB52-100H        CB76-80H         CB76L-60M        CB76-60H        CB76L-40M        CB76-80H          CB76-101A        400
      500                     CB76-91A         CB76-110H        CB76L-80M        CB76-70H        CB76L-50M        CB76-110H         CB76-116A        500
      750                     CB76-131A        CB200-57M        CB200-57M        CB77-110H       CB77-70M         CB200-59M         CB200-67M        750
     1,000                    CB200-69M        CB200-77M        CB300-42M        CB77-140H       CB77-90M         CB200-80M         CB200-87M       1,000
Prim.in->out/out<-Sec.in     90->70/80<-60    90->70/70<-50    75->40/70<-35    65->40/60<-35    60->50/45<-35
Max pressure drop prim/sec   Max 20/20 kPa    Max 20/20 kPa    Max 10/20 kPa    Max 10/20 kPa    Max 20/20 kPa
 Capacity, kW                    Model           Model             Model           Model            Model            kW
       20                     CB26-18H         CB14-12H         CB51-60H         CB51-30H        CB14-20H            20
       50                     CB26-50H         CB14-30H         CB76-71A         CB52-80M        CB27-24M            50
      100                     CB52-40L         CB27-24M         CB76-131A        CB76-91A        CB76L-20L          100
      150                     CB52-50L         CB27-50M         CB300-44H        CB76-131A       CB76L-30L          150
      200                     CB76-40H         CB76L-30M        CB300-56H        CB200-56H       CB76L-30L          200
      300                     CB76-60H         CB76L-40M        CB300-80H        CB300-48H       CB76L-50L          300
      400                     CB76-90H         CB76L-50M        CB300-104H       CB300-62H       CB200-43L          400
      500                     CB76-110H        CB76L-70M        CB300-126H       CB300-78H       CB200-55L          500
      750                     CB200-63M        CB200-45L        CB300-186H       CB300-116H      CB200-92L          750
     1,000                    CB200-85M        CB200-61L        CB300-246H       CB300-154H                       1,000
14
                                                                                                                                         Tap Water Heating
Prim.in->out/out<-Sec.in     90->70/60<-10   90->70/55<-10   90->70/55<-10   90->70/50<-10   90->60/55<-30   80->60/55<-10     80->50/60<-10
Max pressure drop prim/sec   Max 20/20 kPa   Max 20/30 kPa   Max 30/30 kPa   Max 30/30 kPa   Max 30/30 kPa   Max 30/30 kPa     Max 20/20 kPa
Capacity, kW                     Model          Model            Model          Model          Model            Model             Model              kW
       20                     CB14-10H        CB14-10H        CB14-10H        CB14-10H       CB14-10H        CB14-10H           CB14-14H             20
       50                     CB14-30H        CB14-30H        CB14-20H        CB14-20H       CB14-14H        CB14-20H           CB14-30H             50
      100                     CB27-24H        CB27-24M        CB14-40H        CB27-18M       CB14-30H        CB27-18M           CB26-24H           100
      150                     CB27-34H        CB27-34M        CB27-34M        CB27-24M       CB27-24M        CB27-34M           CB26-34H           150
      200                     CB27-50H        CB27-50M        CB27-34M        CB27-34M       CB27-34M        CB27-50M           CB26-50H           200
      300                     CB76L-20L       CB76L-20L       CB76L-20L       CB76L-20L      CB76L-20L       CB76L-30L          CB27-70H           300
      400                     CB76L-30L       CB76L-30L       CB76L-30L       CB76L-30L      CB76L-30M       CB76L-40M          CB76L-30M          400
      500                     CB77-40L        CB76L-40L       CB76L-30L       CB76L-30L      CB76L-40M       CB76L-50L          CB76L-40M          500
      750                     CB77-60L        CB77-60L        CB77-50L        CB76L-50L      CB77-60L        CB77-70L           CB76L-60M          750
    1,000                     CB200-52L       CB200-52L       CB77-60L        CB77-60L       CB77-70M        CB200-42L          CB76L-70M        1,000
Prim.in->out/out<-Sec.in     70->50/60<-10   70->50/55<-10   70->40/55<-5    70->35/55<-10   70->35/55<-10   70->35/55<-5      70->35/55<-5
Max pressure drop prim/sec   Max 20/20 kPa   Max 20/30 kPa   Max 30/30 kPa   Max 20/20 kPa   Max 30/30 kPa   Max 20/20 kPa     Max 30/30 kPa
Capacity, kW                     Model          Model            Model          Model          Model            Model             Model              kW
       20                     CB14-20H        CB14-14H        CB14-20H        CB26-18H       CB26-18H        CB14-30H           CB14-30H             20
       50                     CB14-24H        CB14-30H        CB26-18H        CB26-34H       CB26-34H        CB26-24H           CB26-24H             50
      100                     CB26-50H        CB26-50H        CB26-34H        CB26-50H       CB26-50H        CB52-20L           CB52-20L           100
      150                     CB26-70H        CB26-70H        CB52-30L        CB52-30L       CB52-30L        CB52-30L           CB52-30L           150
      200                     CB27-100H       CB27-70M        CB26-70H        CB52-40L       CB52-40L        CB52-40L           CB52-40L           200
      300                     CB76L-40M       CB76L-30M       CB52-50L        CB52-60L       CB52-50L        CB52-50L           CB52-50L           300
      400                     CB76L-50M       CB77-40M        CB76L-50M       CB76-50H       CB76-40H        CB76-50H           CB76-40H           400
      500                     CB76L-60M       CB77-50M        CB76L-60M       CB76-60H       CB76-50H        CB76-60H           CB76-50H           500
      750                     CB77-90M        CB77-80M        CB77-80M        CB77-80H       CB77-70H        CB77-80H           CB76-70H           750
    1,000                     CB200-65M       CB200-57M       CB77-110H       CB77-110H      CB77-90H        CB77-110H          CB77-90H         1,000
Prim.in->out/out<-Sec.in     70->30/60<-5    70->25/60<-10   65->20/55<-10   60->30/55<-25   60->25/55<-5    60->25/55<-5      60->20/55<-10
Max pressure drop prim/sec   Max 50/50 kPa   Max 20/20 kPa   Max 20/25 kPa   Max 30/30 kPa   Max 20/20 kPa   Max 30/30 kPa     Max 20/25 kPa
Capacity, kW                     Model          Model            Model          Model          Model            Model             Model              kW
       20                     CB26-24H        CB51-20H        CB51-20H        CB51-50H       CB51-20H        CB51-20H           CB51-40H             20
       50                     CB51-20H        CB51-30H        CB51-40H        CB76-71A       CB51-31H        CB51-31H           CB52-80H             50
      100                     CB51-20H        CB51-40H        CB52-80M        CB76-131A      CB51-50H        CB51-50H           CB76-101A          100
      150                     CB51-30H        CB51-60H        CB76-71A        CB200-66H      CB52-80H        CB52-80H           CB76-131A          150
      200                     CB51-40H        CB52-80H        CB76-91A        CB300-52H      CB52-100H       CB52-100H          CB200-64H          200
      300                     CB51-60H        CB76-91A        CB76-131A       CB300-74H      CB76-91A        CB76-91A           CB300-56H          300
      400                     CB52-80H        CB76-116A       CB200-58H       CB300-96H      CB76-131A       CB76-131A          CB300-72H          400
      500                     CB52-100H       CB76-149A       CB300-42H       CB300-118H     CB200-50H       CB200-50H          CB300-88H          500
      750                     CB76-101A       CB200-61H       CB300-60H       CB300-174H     CB200-72H       CB200-72H          CB300-128H         750
    1,000                     CB76-149A       CB200-79H       CB300-80H       CB300-230H     CB200-94H       CB200-94H          CB300-168H       1,000
  Heat exchanger selection tables
  The selection tables in this catalogue enables you to find a suitable heat exchang-                             Disclaimer
  er model and size in a quick and easy way for a number of pre-defined duties. The                               While every precaution has been taken,
  duties are based on radiator and tap water heating duties which are common in                                   Alfa Laval assumes no responsibility for
  some European countries where district heating is used. It is of course impossible                              errors or omissions, or for damages
  to cover all temperatures and capacities in tables like these, but hopefully they can                           resulting from the use of the informa-
  provide you with some guidance when selecting a heat exchanger for your duty.                                   tion contained herein. We reserve the
  For a more tailor made design you can also use the on-line selection tool called                                right to change our products and the
  webcALc, which is presented in detail in this catalogue. Of course you are also                                 specifications detailed in this brochure
  most welcome to contact any Alfa Laval representative who will be happy to assist
                                                                                                                  without prior notice
  you with a heat exchanger selection.
                                                                                                                                                             15
Alfa Laval in brief
Alfa Laval is a leading global provider
of specialized products and engineer-
ing solutions.
   Our equipment, systems and
services are dedicated to assisting
customers in optimizing the perform-
ance of their processes. Time and
time again.
   We help our customers to heat,
cool, separate and transport products
such as oil, water, chemicals, bever-
ages, foodstuff, starch and pharma-
ceuticals.
   Our worldwide organization works
closely with customers in almost
100 countries to help them stay ahead.
How to contact Alfa Laval
Contact details for all countries are
continually updated on our website.
Please visit www.alfalaval.com to
access the information.
PC68209 E 0110