This experiment involves determining the performance characteristics of a grid-connected induction generator through a series of tests. The open-circuit test measures the voltage-current characteristics at synchronous speed. The load test varies the speed above synchronous to operate the generator, measuring torque, power output, power factor and efficiency against slip. The blocked rotor test obtains parameters by varying input voltage with the rotor locked. The results are used to calculate predictions and self-excitation requirements.

Uploaded by

Akhilrajscribd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
96 views2 pages

Induction1 PDF

This experiment involves determining the performance characteristics of a grid-connected induction generator through a series of tests. The open-circuit test measures the voltage-current characteristics at synchronous speed. The load test varies the speed above synchronous to operate the generator, measuring torque, power output, power factor and efficiency against slip. The blocked rotor test obtains parameters by varying input voltage with the rotor locked. The results are used to calculate predictions and self-excitation requirements.

Uploaded by

Akhilrajscribd
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Experiments on Induction Generators :

Expt. 1: Determination of the equivalent circuit parameters and the performance characteristics of a
grid-connected induction generator

Procedure:

1. In the open-circuit test, connect the circuit as shown in the figure. The stator supply is given through
an autotransformer. In this experiment the measurements are to be done when the machine is rotating
exactly at the synchronous speed (which cannot be achieved simply by running at no-load). First start the
induction machine as a motor with the help of the autotransformer. Once it reaches approximately the rated
speed, open the shorting switch across the ammeter and wattmeter.
In order to bring it to exactly the synchronous speed, give field supply to the coupled dc machine. The
d.c. machine is to be connected to the d.c. supply terminals in the separately excited configuration, with
two different switches for the field and the armature (see Fig. 1). Voltage builds up at the armature
terminals. This voltage and the supply voltage appear at the two ends of the armature switch. By varying
the field resistance, bring the armature voltage to the d.c. supply voltage. After checking the polarity and
magnitudes of these two voltages, close the armature switch. Then increase the speed by reducing the field
current of the d.c. machine.
The slip of the induction machine can be measured in two different ways. If it is a wound-rotor machine,
connect a zero-centred d.c. ammeter across two of the rotor terminals, and shunt it with an SPST switch.
The other two rotor terminals are shorted. The current passing through the ammeter will be exactly at the
slip frequency. As a result the pointer will oscillate at that frequency, which can be easily measured by
counting the number of oscillations per minute. If the machine is squirrel cage, the rotor terminals are not
available. In that case the slip is to be obtained with a line-frequency stroboscope. Put a chalk-mark on the
rotor shaft. When the strobe is on, the chalk-mark will appear to rotate at the slip frequency, which can be
also be measured by counting the number of oscillations per minute.

Fig.1: Circuit diagram for the open-circuit test and load test.

To measure the 3-phase active and reactive power, two wattmeters are used, as the load can be assumed
to be balanced. One LPF wattmeter, with the line current in the current coil and the same phase voltage in
the pressure coil, measures the active power (3-phase power = 3 times wattmeter reading). Another
wattmeter, with the line current in the current coil and the voltage between the other two lines in the
pressure coil, measures the reactive power (3-phase reactive power = 3 times the wattmeter reading). If
three-phase active/reactive power meters are available, these can also be used.
As the speed is increased by reducing the dc machine field current, the oscillation of the rotor ammeter of
the induction machine slows down, indicating a decrease in slip. Finally bring it to a standstill by adjusting
the field rheostat. The induction machine is now running at synchronous speed; the rotor is truly open-
circuited.

1
Then obtain the open-circuit voltage-current characteristics by varying the stator voltage of the induction
machine in steps, while varying the d.c. field resistance to keep the machine always at synchronous speed.
Try to obtain approximately equally spaced points on the curve, till the typical bend (knee point) is visible.
Plot while you take the readings (current in the x-axis and voltage in the y-axis).

3. Use the same circuit as in the open circuit test. The only difference is that the ammeter, voltmeter, and
wattmeter ratings should correspond to the machine ratings. Use normal wattmeters instead of the LPF
wattmetsrs. After the synchronous speed is reached, increase the speed further by reducing the field current
of the d.c. machine. The induction machine then runs in the generator mode. Increase the speed in steps up
to the maximum permissible value, and take the readings. Limit the range of experiment to the stable zone
of the torque-slip characteristics. If the oscillation of the rotor ammeters become too fast to count, short the
SPST switch and use a stroboscope to measure the slip. Calculate and plot the torque, power output, power
factor and efficiency against slip.

Fig.2: Torque-slip characteristics of an induction generator

3. Then perform the short-circuit or locked-rotor test. Note that you have to choose the ammeter rating
equal to the machine rating, and the voltmeter rating about one fourth the machine rating. The wattmeter
should be a low power factor meter. After connecting the circuit, increase the input voltage in stages, so
that input current varies from half the rated current to the rated current. Keep the rotor static by physically
holding it. Tabulate the input voltage, input current and input power.

Fig.3: Circuit diagram for the blocked rotor test

Report:

1. Obtain the parameters of the approximate equivalent circuit from the locked rotor test and the
open-circuit test at rated voltage.
2. Using the equivalent circuit, calculate the power, power factor, stator current, torque and
efficiency at slips -0.02 and -0.05, when the machine is connected to the line. Compare the
experimental results of the load test with the values predicted.
3. Obtain the minimum value of capacitance required for the machine to self-excite. Note down the
capacitance of the 3-phase capacitor bank available in the lab. Calculate the minimum speed at
which the machine will self-excite if this capacitor bank is connected to the stator terminals.
Calculate the capacitance requirement for self-excitation to 400 V at rated speed and no-load.
4. Derive qualitative conclusions from the load test graphs and write in the discussion.