CARRIER AIDDED PROTECTION
Phase Comparison Relaying
Relay combination used with phase comparison systems are SLD or SKBU
carrier relaying and CO( Residual Ground)/ ICC (Directional ground).
Phase comparison relaying compares current phasors at local and remote
terminals. Line and Neutral potential are not required.
Faults in the protected zone would cause the currents to trip in less than 3
cycles
Fault detector turns on carrier signal during Fault
Transmitter generates blocking pulse during negative half cycle.
During external fault both transmitters produce additive blocking pulse for
the full cycle.
During internal fault out of phase pulse cancel blocking pulse, allowing the relay
to trip
SPCU relays are used for Phase comparison for Phase and Phase to
Ground faults
Microwave is used for communication of current phasors. Guard signals
are transmitted for communication health. Relay trips in 9 cycles on loss of
guard signal. Noise on communication channel will block tripping.
SRU/ UIO as auxiliary relay for annunciation purpose
Directional comparison blocking ( SLYP/ SLYN) compares current direction
at both terminals to determine in zone or out of zone faults to block
tripping
SLYP provides Zone1 element ( 80% of line: instantaneous trip with TT),
Zone2 (125% of Line) (Instantaneous for in zone fault and TT or blocking
signal for out of zone faults) and Zone3 (180% of line sends blocking signal
out of zone faults)
SLYN provides Directional overcurrent, trip for in zone faults and block for
out of zone faults
DCB Philosoph
Impedance relays trip instantaneously for z1 faults covering 80% of line
Over reaching impedance relays with z2 faults operate with time delay covering
125% of the line
Directional comparison Blocking (DCB) allows over reaching relays to trip
instantaneously by blocking out of zone faults
Thus Phase Distance Relays and ground over current relays can provide
instantaneous protection for in zone faults
Only one Communication channel is used for sending blocking signal only , used
with PLC schemes
Typical Transfer Trip Relaying
Transfer Trip schemes are another flavor of Directional comparison schemes,
where two relays communicate to trip rather than block.
The two frequencies transmitted through two communication channels are:
Guard frequency to keep guard relays closed to block tripping over
channel noise
Tripping Frequency to allow tripping relay to pickup and trip circuit
breakers
Basic Transfer trip Schemes:
Direct Transfer Trip (DTP)
Direct Overreaching Transfer Trip (DOTT) 125%
Direct Under reaching Transfer Trip (DUTT) 80%
Permissive Transfer Trip
Permissive Overreaching Transfer Trip (POTT) 125 %
Permissive Under reaching Transfer Trip (PUTT) 80%
Typical PUTT Relaying Scheme
Typical POTT Relaying Scheme
Typical POTT Relaying Scheme would have following components:
3 CEY (Impedance relay with zone 2 timer- starts at fault detection)
1 SLYG directional Ground Relays
2 GE Type 40 Transmitter and Receiver systems
2 Transfer Trip communication channels (Primary/ Secondary)
When a terminal receives the shift from Guard to trip frequency and a trip
signal is present from Local relay, the local CB will trip
Zone 2 timer is reset after the fault is cleared
If zone 2 timer times out it will trip the local CBs irrespective of Tone
signals from receiver to provide a backup protection
If the fault is out of zone, then relay at the remote terminal will not pickup
and removes the Guard frequency, preventing local relay to trip
Loss of Guard signal for six cycles continuously will disable the channel
equipment and continuous alarm will deactivate the relays