MEC 351 REFRIGERATION &
AIR CONDITIONG
                   CHAPTER 5: Air Distribution Systems
                     Prepared by: Ahmad Najmie Rusli
CHAPTER 5                        Faculty of Mechanical Engineering,
                                 UiTM Kampus Pasir Gudang.
                     Email: ahmad7586@johor.uitm.edu.my
5.0   TABLE OF CONTENTS
      5.1 Air Conditioning System
      5.2 Air Distribution System
          5.2.1    Air Distribution System  Components
          5.2.2    Air Distribution System  Ducting System
      5.3 Ducting System
          5.3.1    Ducting System  Fittings
          5.3.2    Ducting System  Diffusers & Grilles
      5.4 Diffusers Selection & Consideration
      5.5 Duct Sizes Consideration
      5.6 Procedures for Design Centralised Air Conditioning System
      5.7 Required Air Quantity in a Room (CFM)
      5.8 Losses in Ducts System
5.1          Air Conditioning System
       Air conditioning system depend on air ventilation and
        refrigeration cycles.
       The objective of air conditioning design system is:
           1. Achieving desirable temperature
          2. Achieving desirable humidity
          3. Achieving right amount of conditioned air
          4. Provides air movement
          5. Distribute conditioned air within the space
5.2
       Air Distribution System
       The good of an air distribution in air condition system must:
          1. No excessive draft (air motion) to users:
          a. Avoid excessive throw near walls to prevent
              bouncing.
          b. Diffusers with adjusting features (for balancing of
              flow)
         2. No excessive room air temperature
5.2
      Air Distribution System
      3. No excessive fluctuation room temperature and air motion.
      a. Row of diffusers may be located closer to the outside wall to
          compensate extra heat load
      4. No excessive room air noise
      a. Adequate return grilles (suction noise)
      b. Low level of CFM supply per diffuser (400  700 CFM)
      5. Avoid short circuiting
      a. Return grille not located where by-passing of supply air
5.2.1   Air Distribution System - Components
               Figure: Schematic Diagram Air Ventilation
5.2.2   Air Distribution System  Ducting System
                                                           AHU
                           SA
                                                            RA
            Figure: Example of Air Ventilation Ducting Connection
5.2.1   Air Distribution System  Ducting System
           Figure: Examples of Air Ventilation Ducting Connection
5.3.1   Ducting System - Fittings
          Figure: Fitting for air ventilation ducting (PanelDuct Product)
5.3
5.3.2
        Ducting System  Diffusers & Grilles
        Diffuser: The supply outlet of SA. Symbol
        1. Square (2x2, rooms / halls)
        2. Round (nice looking, difficult to install)
        3. Slot/linear (hotel ball rooms)
        Grille: The return air inlet RA (rectangular, square).
         Normally situated in the stagment zones (room corner or end)
        Air distribution by square diffuser    Air distribution by round diffuser
5.3
5.3.2   Ducting System  Diffusers & Grilles
            Square Diffuser
5.3.2
5.3     Ducting System  Diffusers & Grilles
        Round Diffuser    Slot/Wall Mounted Diffuser
        Swiral Diffuser     Grille Return Air Diffuser
5.4
      Diffusers Selection & Consideration
       The selection of diffuser depend on:
      1. Architectural requirement
      2. Structural requirement
      3. Diffusion temperature difference
      4. Size of diffuser / grilles
5.5         Duct Sizes Consideration
      1. Round or rectangular ducting size depend on the space
         available as example ceiling height.
      2. Return air ducts can be sized in the same manner as the supply
         air units.
5.5         Duct Sizes Consideration
      3. Round ducts has minimal friction compared to rectangular
         ducts.
      4. If youre choosing rectangular duct, try to be as square as
         possible size.
      5. The branches from main duct could be flexible round duct for
         easy positioning.
                                    Flexible round duct
5.6   Procedures for Design Centralised A/C System
        1. Estimate the cooling load (Btu/hr)
        2. Determine the supply condition.
        3. Choose the type of system.
        4. Plan the equipment and duct location.
        5. Determine the duct size.
        * See an examples provided in class room for the design and calculation stages
5.7   Required Air Quantity in a Room (CFM)
      There are two methods to determine the required CFM for
      each room.
      1. Considering the diffusion temperature:
                                (/)                  (/)
                =                                  =
                          1.09    () 1.2    ()
      2. Considering the rule of thumb:                22F
                                             (/)
                                  =
                                                12  103
5.7   Required Air Quantity in a Room (CFM)
                                         Diffusion
                                       Temperature
                                           22C
             Figure: Diffusion temperature in a room
5.8     Losses in Ducts System
       Friction loss from air flow in ducts divided to major and minor loss:
         1. Major: Friction loss due to air flow along the ducting.
         2. Minor: Friction loss due to air flow through the ducts fitting.
       Friction loss of air through the duct could be determined by
        using standard chart air flow in galvanized steel round ducts.
       However, the chart only limited to:
        1. Clean galvanized steel.
        2. Air at standard conditions.
        3. General HVAC temperatures.
        4. Altitude up to 2000 ft.
5.8
                 Duct
               diameter
Air velocity
               L or W
                          Convert round to rectangular duct
5.8   Example
      Question 1:
      A 12 inch diameter galvanised duct 250 ft. has 1000 CFM of air flowing
      through.
      What is the pressure loss due to friction and velocity in the duct?
                                                 [hf = 0.55 in w.g, Velocity = 1300 FPM]
      Question 2:
      A 30 x 19 inch rectangular duct deliver 7000 CFM of air. What is the friction / 100
      ft.?
                                                                    [hf /100 ft = 0.17 in w.g]
5.8     Example
        Question 3:
        Figure below shows a symmetry ducting system from AHU to the diffusers
        with equal friction hf = 0.4 in w.g per 100 ft.
        What is the pressure loss due to friction and velocity in the duct section AB
        and BC by neglecting the fitting loss?
                                         14                                           9
      Answers:
      Section    CFM    Duct L   FPM      hf /100   hf (in wg)
        AB       2000   10 ft    1950       0.4       0.04
        BC       1000    3 ft    1480       0.4       0.012
END