Altivar 1200 Brochure
Altivar 1200 Brochure
                                                                                                                      1
    Compact design and improved
    security
                             Checking window
                             • 4 peepholes on each door of Power cell cabinet
All-in-one
cabinet
Easy maintenance
• Front access transformer
	 & control
Efficient cooling
• Separated Air Flow
• No additional fans to 		
	maintain
• Washable filters
Fully equipped
• UPS (30 mins)
• 10” HMI touch screen
• Indoor cabinet lights
• Audible alarm
• Separated access to MV
• Free I/O
• Limit switch
                             Separated access to MV
                             • Interlock system
                             • Special tool to open each door is needed
                             • Handle lock
                             • DC bus power-off signal
2
Well proven technology for
performance and reliability
                                High-performance inverter
                                Inverter efficiency                        Motor-friendly
                                • 98.5% efficiency                         •	Up to 19 levels of pulse-width modulation 	
                                                                           	 (PWM) for minimal switching surges
                                                                           •	Insignificant harmonics
                                                                           •	Up to 2km motor cable length without 		
                                                                           	 output filter
Control
Easy access
& compactness
•	Integrated high
	 speed control
• Customizable
	 interface and control
Uninterrupted Power
Supply
•	30 mins continuous 		
	 operation after Power
	 supply lose
•	Protection against supply 	
	 instability (voltage drop)
                                Integrated transformer
                                Compactness
                                •	Fewer cables and simpler commissioning
                                Clean power
                                • 18-54 pulse operation
                                • Clean sinusoidal wave
                                                                                                                 3
Compact and environmentally friendly
Clean power
                                                                    Input                                                 Output
        3-phase input
        power supply
                                               Voltage                                                      Voltage
                                               Current                                                      Current
                                                                                                                  5
User-friendly interface interface with
many control features
Easy-to-use 10-inch color LCD touch-screen with the
results available at your fingertips.
•	Multiple languages
•	Consistent menus within the Altivar ranges
•	Parameter and operation records
•	Dedicated multi-level menu to guide you with different 		
	 access levels for service and commissioning 			
	 engineers (operator, manager, administrator)
6
Make your life easier
with complete solutions
Altivar 1200 is open to most networks, and can be integrated in                                          The Altivar 1200
any medium architecture.                                                                                 solution is based on a
                                                                                                         transformer, drive and
With the Altivar 1200, Schneider Electric has created a                                                  medium-voltage electric
                                                                                                         motor assembly.
comprehensive and consistent offer for:
•	Controlling and supplying equipment                                                                    Schneider Electric
•	Improving performance                                                                                  can provide a turnkey
                                                                                                         solution complete with
                                                                                                         drive and associated
Schneider Electric, a world leader in electrical distribution and control                                equipment (electrical
systems, presents a range of products, solutions and services for:                                       distribution, control
                                                                                                         systems).
•	Transforming and routing energy
•	Automating machines and processes                                                                      For more information,
                                                                                                         please contact our
                                                                                                         project teams.
Electric substation
                  Secondary electric
                  substation
                                                                                                                                   7
Build a competitive advantage with the
help from our industry experts
By applying our industrialization skills to our services, we can help to ensure your
success.
                                                     •	Factory tests
                                                     	 - Deliver Factory Acceptance Test
                                                     	 - Test at maximum power with or without motor
                                                     •	Customized training
                                                     	 - On user site or in Schneider Electric training center
                                                     	 - Official qualification for medium-voltage drive operations
8
Altivar 1200
General Technical Specification
 Standard features
Input                                 18-54 pulse diode rectifier bridge
Output                                Multilevel PWM with 2 level low-voltage IGBT inverter cells
Input voltage                         p 2.4kV, 3.0kV, 3.3kV, 4.16kV, 5.5kV, 6.0kV, 6.3kV, 6.6kV, 6.9kV, 10kV, 11kV, 13.8 kV
p Variation: standard±10%
Allowable voltage fluctuation         The drive is subject to de-rating operation when the voltage drop of power supply is within -30%
Input frequency                       50/60 Hz ±5%	
Acceleration deceleration time        0-3200 s
Overload capability                   p Standard overload 120% 60s/10 min and 150% 3s/10 min, instand trip threshold 200%
p High overload 150% 60s/10 min, 185% 3s/10 min, instand trip threshold 250%
Total harmonics THDI                  Comply with the requirements of power quality standard of IEEE519-1992
Frequency resolution                  0.01 HZ
Trigger signal transmission           Fiber optic transmission
Input Power factor                    ≥ 0.96 from 20 % to 100 % of speed
Efficiency at rated power             The efficiency of the drive including input transformer 96% or over 96.5% depending on product
                                      Inverter efficiency without transformer is 98.5%
Type of motor                         Asynchronous motor, synchronous motor
Three-phase output voltage for        0...2400V - 0...3000V - 0...3300V - 0...4160V - 0...5500V - 0...6000V
motor connection                      0...6300V - 0...6600V - 0...6900V - 0...10000V - 0...11000V
Output frequency                      120Hz for V/f, 70Hz for Vector Control
Input transformer                     Indoor type integrated in the frequency variable device, the dry phase-shifting transformer can be supplied
                                      with 24 – 54 pulse rectifier
Control power supply                  p 220 VAC, capacity 3 kVA, with UPS 30 min autonomy, other voltage on request
 Environment
Storage temperature                   -10°C to 60°C
Working temperature                   0-40°C, up to 50°C possible with derating
Relative humidity                     90% (without condensate), Optional: maximum up to 95%
Altitude                              ≤ 1000 m without derating. With derating of 0.6% every 100m up to 2000 meters, can be
                                      customized for high altitude
Vibration                             Acceleration: 4.9 m/s2 acceptable (10-50 Hz)
Noise level                           ≤ 80 dB (A) (including the noise of the cooling fan on the cabinet top)
Identification code
   AT V 1 2 0 0           A             XXX                                 66
     Serial Name    Cooling Type       Drive (kVA) Input Voltage Output Voltage                     Style            IP          Drive Efficiency
                    A→Air Cooled                       24→ 2 .4 k V     4 2→ 4 .1 6k V   S→Sync. Motor Control     3→ I P3 1 S→ Standard Efficiency
                                                       3 3→ 3. 3 k V    60→6k V          A→ Async. Motor Control   4→ I P41 H→ High Efficiency
                                                       5 5→5. 5 k V     66→6.6k V                                  5→ I P4 2
                                                       6 3→6. 3 k V     1 1→ 1 1 k V
                                                       10→ 10 k V
For Example
AT V 1 2 0 0 - A 5 6 00                 -    6 6 60 A 3 H
The capacity of Altivar 1200 series of Medium-Voltage Drive is 5600kVA, Air Cooled, input voltage is 6.6 kV, output voltage is 6kV, Asynchronous
motor Control, IP31 and with high efficiency input transformer.
                                                                                                                                                    9
       Power specifications
      Voltage class                                                        3.3 kV
     1) ... Please contact Schneider Electric for other combinations of input and output voltage.
     2) ... For higher drive capacity please contact Schneider Electric.
     3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
            equipment used.
     4) ... Values valid only for standard efficiency.
10
  Power specifications
 Voltage class                                                       4.16 kV
1) ... Please contact Schneider Electric for other combinations of input and output voltage.
2) ... For higher drive capacity please contact Schneider Electric.
3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
       equipment used.
4) ... Values valid only for standard efficiency.
                                                                                                                                             11
       Power specifications
      Voltage class                                                        5.5 kV
     1) ... Please contact Schneider Electric for other combinations of input and output voltage.
     2) ... For higher drive capacity please contact Schneider Electric
     3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
            equipment used.
     4) ... Values valid only for standard efficiency.
12
  Power specifications
 Voltage class                                                        6.0 kV
1) ... Please contact Schneider Electric for other combinations of input and output voltage.
2) ... For higher drive capacity please contact Schneider Electric
3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
       equipment used.
4) ... Values valid only for standard efficiency.
                                                                                                                                             13
       Power specifications
      Voltage class                                                        6.3 kV
     1) ... Please contact Schneider Electric for other combinations of input and output voltage.
     2) ... For higher drive capacity please contact Schneider Electric
     3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
            equipment used.
     4) ... Values valid only for standard efficiency.
14
  Power specifications
 Voltage class                                                        6.6 kV
1) ... Please contact Schneider Electric for other combinations of input and output voltage.
2) ... For higher drive capacity please contact Schneider Electric
3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
       equipment used.
4) ... Values valid only for standard efficiency.
                                                                                                                                             15
       Power specifications
      Voltage class                                                        10 kV
     1) ... Please contact Schneider Electric for other combinations of input and output voltage.
     2) ... For higher drive capacity please contact Schneider Electric
     3) ... Values are caclulated with motor power factor of 0.88 and efficiency of 95%. The real value must be calculated on the basis of the
            equipment used.
     4) ... Values valid only for standard efficiency.
16
17
Altivar 1200: Basic guidelines on
installation and maintenance
                                                            D Amplification
                                                                 1:5
±0.00mm
18