Structural Plywood Bracing Guide
Structural Plywood Bracing Guide
ACKNOWLEDGEMENT                                                                        JAS-ANZ
This literature was developed with funding assistance from
 the Forest and Wood Products Reseach and Development
                        Corporation.
Design Example 18
                    Appendix                                                                                 19
                                                               Permissible Stress Design Capacities
2
WHY PLYWOOD BRACING
The Australian Standard ‘Residential Timber-Framed                     The structural plywood bracing systems described in this
Construction’ states “Permanent bracing shall be provided to           manual provide a safe and reliable means of permanent
enable the roof, wall and floor framework to resist horizontal         bracing that is easy to install and very cost effective.
forces (racking forces) applied to the building. Appropriate
connection shall also be provided to transfer these forces             Diagram 1 provides an illustration of how wind forces act on
through the framework and sub-floor structure to the                   a building.
building’s foundation.”
The horizontal wind (racking) forces resulting from the wind flow      If one applies this logic to double storey construction it can be
on the top half of the external cladding are transferred into the      demonstrated the wind forces applied to lower storeys can
ceiling (roof or top floor) diaphragm. These forces can be safely      approach 3 times those on the top storey. This fact, coupled with
and reliably resisted by vertical structural plywood shear walls.      the trend of having large rooms (with less walls) with wider
The racking forces from the lower half of the external cladding        openings and the use of non-structural linings makes the
and those from the plywood bracing are both transferred by the         structural design of these modern buildings more critical.
floor (diaphragm) and its supports down into the foundations.
DESIGN METHODOLOGY
Design Approach
1. Establish the wind forces on the walls of the building,             2. Select the appropriate structural plywood bracing system or
perpendicular to the wind flow in the two primary building             combination of systems.
dimensions, viz. normal to the building length and width. These        3. Through multiplying the selected bracing resistances by the
forces can be assessed using AS1170.2 ‘Wind Loading Code’,             length of each bracing system parallel to the wind direction,
AS4055 ‘Wind Loads for Housing’ or AS1684 ‘Residential                 ensure the total bracing resistance in these walls equals or
Timber-Framed Construction’. For convenience, Table 4                  exceeds the design wind forces in this direction. Do likewise for
provides the wind pressure tables for Wind Classification N2           the other primary direction.
from AS1684.
Design Parameters
1. Buildings whose plan shape is essentially rectangular or a          4. Up to 2.7m wall height. Over 2.7m linearly reduce
combination of rectangular elements.                                   the bracing resistance in the ratio of 2.7m divided by the
2. Maximum building width of 15m.                                      actual height.
3. Maximum roof pitch is 350.
Design Criteria
The following design criteria were applied to the full scale           loads were taken prior to the onset of any buckling.
prototype tests done in approved Australian laboratories to the        The strength limit state (irrespective of its cause) was
requirements of AS1720.1-1997 ‘Timber Structures Code’ to              determined by working backwards from the test panel ultimate
establish limit states for structural plywood sheathed panels.         load to establish an Equivalent Test Load (ETL). From this the
1. The allowable deflection i.e., racking out of square, was limited   design action effect for the bracing walls were determined.
to panel height/300 or 8mm at the serviceability limit state.          3. The serviceability limit state loads incorporate a minimum
2. Where plywood buckling generated an alternative                     factor of safety of 2.0 on the ultimate failure load of the prototype
serviceability limit state the design load was taken within the        test panels.
Limit of Proportionality of the load/deflection plot i.e., design
                                                                                                                                           3
MATERIALS SPECIFICATION
Permanent structural bracing enables wall systems to resist           system and subfloor to the ground. Thus for safety and
horizontal forces i.e. racking forces, applied to the building by     reliability of structural bracing the following material
wind and/or earthquake. Appropriate connections are                   specifications are critical.
required to transfer these forces through a structurally sound
Plywood
To comply with the requirements of this manual the plywood
must be branded with the PAA/JAS-ANZ ‘tested structural’
Product Certification stamp. This stamp ensures the plywood
has been manufactured to the requirements of AS/NZS2269
‘Plywood-Structural’ under the PAA/JAS-ANZ accredited
third party audited, process based, quality assurance
program, and that the plywood will be predictable and reliable
making it fit for purpose in this engineered application.
Framing
The framing must be designed to carry the horizontal forces to        timber of a minimum joint strength of J4 or JD4. Additional
and from the plywood. In the case of timber the framing must be       testing has verified if the framing is of the lower joint strength
in accordance with the requirements of AS1684, or framing             JD5 then the design racking resistances must be reduced by
manual produced in accordance with the design parameters of           121/2%, requiring a proportional increase in the required bracing
AS1684. The testing of bracing on structural timber was on            wall length.
Fasteners
Connection of the structural plywood to the framing is critical       driven fasteners for timber framing. The spacings for staples
in bracing. In general, the failure in testing was in the             are two thirds (i.e. fastener spacing multiplied by 0.66) those
connections. Table 1 specifies the minimum hand or power              shown for nails or screws.
                       2.80mm dia. x 30mm flathead Senco TN22-38 APB (2.33mm       Senco N17 BAB
                       structural clouts or connector dia. x 38mm flathead)
                       nails
                                                     Bostitch CR3D (3.06dia. x 32   Bostitch BCS4-1232
                                                     flathead)
                                                     Bostitch C45D-250 or AC45P-
                                                     250-GW (2.5dia. x 45 flathead)
                                                     Jambro B20998 (RBC 2.80mm Jambro A10617
                                                     dia. x 32mm zinc plate barb) (G5562-38mm)
                                                     Duo-Fast C27/32GD
                       Notes: 1. Fasteners with equivalent dimension i.e. head size and shape, shank
                              diameter and length to those in Table 1 are deemed acceptable.
                                 2. All fasteners are to be galvanised or suitably coated.
                                 3. Minimum edge clearance for fasteners is 7mm.
                                 4. If smaller diameter hand driven nails are used, the spacings of nails can
                                 be reduced in the ratio of the basic lateral loads per nail for J4 or JD4 joint
                                 group given in Table 4.1 of AS1720.1 ‘Timber Structures Code’ for the lower
                                 nail diameter relative to the tabulated load for a 2.8mm diameter nail.
                                 5. Fasteners are not to be overdriven.
                                 6. Fasteners for structural plywood linings as detailed in Tables 13 and 14
                                 can be a minimum of 2.5mm dia. x 40mm bullet head nails.
When coach screws or bolts are used to fix plywood panels,            Circular washers of equivalent thickness and nett bearing
bottom plates or as tie rods, steel washers must be used.             area are an acceptable alternative.
Table 2 provides detail of the minimum allowable washer size.
4
ESTABLISH DESIGN RACKING FORCES
The limit state design racking forces can be calculated using                 prerequisite for use of this simpler method described below is the
AS1170.2 ‘Wind Loading Code’, or more simply, by using the                    ‘design gust wind speed’ and/or ‘wind classification’, and the ‘area
AS1684 ‘Residential Timber-Framed Construction’ method. The                   of elevation’.
Wind Classification
The AS1684 wind classification system is a rationalised means of              design gust wind speed. Also included in the table is a multiplier to
categorising the wind speeds into bands for the non-cyclonic                  be applied to the pressures given in Table 4 for other than N2 wind
Regions A and B, and the cyclonic Regions C and D. Table 3                    classification.
shows the various wind classifications in terms of the maximum
N1 - 28 26 34 0.72
N2 - 33 26 40 1.00
N3 C1 41 32 50 1.56
N4 C2 50 39 61 2.33
- C3 60 47 74 3.42
         Note:    The regions are given in detail in AS1170.2 and AS4055. Regions B, C and D occur within 100km of the Australian coast
                  north of the 300 latitude line (i.e. just north of Coffs Harbour). The balance of Australia being designated as Region A.
Preservative treated structual plywood serving the dual purposes of cladding and of bracing
                                                                                                                                                   5
Area of Elevation
The area of elevation, to which the pressures from Table 4 are               The wind direction used shall be that resulting in the greatest load.
applied to calculate the design racking force, is proportional to the        As wind can blow from any direction, e.g. a single storey dwelling
wind force applied to the frame of the relevant storey of the building.      having a gable at one end and hip the other, will result in a higher
The area referred to is the area of the full building elevation above        load at right angles to the width of the house when the gable end is
half way up the wall frame for the particular storey of the building         facing the wind. For complex building shapes a combination of
being assessed. This is illustrated in Diagram 2.                            shapes may be considered individually and individual loads added
                                                                             together later.
(i) Plan
Notes: 1         h = half the height of the wall (half of the floor to ceiling height).
           2     For lower storey of two storey section h = half of the height of the lower storey (i.e. lower storey floor to lower storey ceiling).
           3     The area of elevation of eaves up to 1000mm wide may be ignored in the determination of area of elevation.
6
Design Racking Force
The design racking force for each storey or level of the building for        The Lateral Wind Pressures for Wind Classification N2 are given
each wind direction is the product of the Area of Elevation and the          in Table 4. For other Wind Classifications, the pressures from
relevant wind pressure for the particular Wind Classification, i.e.          Table 4 are to be factored down or up using the multiplier given
                                                                             in Table 3 e.g. for N1 wind classification the pressures from Table
Total Racking Force (kN) = Projected Area of Elevation (m2)                  4 are to be multiplied by 0.72.
                            x Lateral Wind Pressure (kPa).
Pressure = 0.92kPa
                                                                                                                                               7
Table 4 (cont.)
                  (b) Single storey or upper of two storey - long length of building - hip or gable ends
(c) Lower storey or sub-floor - long length of building - hip or gable ends
8
Table 4 (cont.)
                  (d)     Single storey or upper of two storey - short end of building - hip ends
                                                                                                                   9
 STRUCTURAL PLYWOOD BRACING SYSTEMS
 After establishing the design racking forces for each storey or      bottom and top plates must be a minimum of 70 x 70mm F5
 level and in both primary directions, a building frame can be        or 90 x 45mm F5 or equivalent.
 braced by installing sufficient length of an appropriate
 system or a combination of the structural plywood bracing            The bracing resistances given in Tables 5-14 are applicable
 systems shown in Tables 5 to 14.                                     to frames sheathed one side only. The resistances are
                                                                      additive for frames sheathed on two sides, however, the hold
 It is good practice to use bracing in all corners in external        down requirements of the bottom plate must also be
 walls for each direction and level. Additionally, it is necessary    increased accordingly. Bottom plate sizes should be checked
 to use an even distribution of bracing rather than to                under these circumstances to ensure safe moment capacity.
 concentrate a large proportion of the bracing resistance in a
 comparatively short length of a high capacity bracing                If approved staples are used the spacings are to be a
 resistance system. The distribution and maximum spacings             maximum of two thirds those for nails or screws shown in
 are detailed in the section Additional Installation                  Tables 5 to 14.
 Requirements.
                                                                      The allowable design resistances are appropriate to all
 The bracing resistances shown in Tables 5-14 apply to wall           species, joint strength groups to J4 or JD4 and stress grades
 frames up to a height of 2.7m. For wall heights over 2.7m the        of wall framing timber. This covers most Australian hardwood
 bracing is reduced in the ratio of 2.7m divided by the higher        and exotic pines. If species of JD5 joint strengths are used
 wall height, e.g. with a 3m high frame, this reduction factor        then additional testing has shown that the design values
 would be 0.9 .                                                       should be reduced 12.5%. Imported unidentified softwood
 For bracing system resistances greater than 6.4kN/m the              may fall into this category.
        TABLE 5: Minimum Structural Plywood Thicknesses for 3kN/m Bracing Capacity Systems (mm)
     Plywood           Stud                                                                            Horizontal Butt Joints Permitted
                                                                                                       Provided fixed to Nogging at
      Stress         Spacing                                                                           100mm Centres
                                                                               100mm
      Grade          600mm
                                                                                                               100mm
                      (max)
        F8               7
       F11              4.5                                   100mm
                                                                                                    Fastener Centres:
       F14               4                                                                          100mm Top and Bottom Plate
                                                                                                    100mm Vertical Edges
       F27               3                                                                          100mm Intermediate Studs
                                                              100mm
 NOTE: These systems are only applicable to
 sheathed sections a minimum of 900mm wide.
        TABLE 6: Minimum Structural Plywood Thicknesses for 3.4kN/m Bracing Capacity Systems (mm)
     Plywood                                                                      150mm
      Stress          Stud Spacing                                                                                 Horizontal Butt Joints
      Grade                                                                                                        Permitted Provided fixed to
                                                                                                                   Nogging at150mm Centres
                    450mm      600mm
        F8             7          9                                                                                150mm
       F14             4          6
       F27             3         4.5
                                                                                                         Fastener Centres:
                                                                                                         150mm Top and Bottom Plate
                                                                                                         150mm Vertical Edges
                                                                                                         300mm Intermediate Studs
10
TABLE 7: Minimum Structural Plywood Thicknesses for Alternate 3.4kN/m Systems Utilising Nogging (mm)
   Plywood          Stud Spacing
    Stress             600mm                                                           150mm                              Horizontal Butt Joints Permitted
    Grade               (max)                                                                                             Provided fixed to Nogging at
                                                                                                                          150mm Centres
       F8                  7
      F11                 4.5
      F14                  4                                   150mm                                                                  1 row of Nogging
      F27                  3                                                                                                          Staggered or Single Line
                                                                                                                                      at Half Wall Height
150mm
                                                                                                                           Fastener Centres:
                                                                                                                           150mm Top and Bottom Plate
NOTE: For sheathed systems less than 900mm in                                                                              150mm Vertical Edges
                                                                                                                           150mm Nogging
width the appropriate reduction factor from Table 9                                                                        300mm Intermediate Studs
must be applied to the 3.4kN/m bracing capacity.
300mm
      TABLE 8: Minimum Structural Plywood Thicknesses for 6.4kN/m Bracing Capacity Systems (mm)
   Plywood
                                Stud Spacing                   M12 Rod Top to Bottom plate
    Stress                                                     Each End of Sheathed Section*
                                                                                                  150mm
    Grade               450mm                 600mm
       F8                  7                     9                                                                              Horizontal Butt Joints Permitted
                                                                                                                                Provided fixed to Nogging at
      F11                  6                     7                                                                              150mm Centres
      F14                  4                     6
      F27                  4                    4.5            150mm
                                                                                                                             Fastener Centres:
                                                                                                                             150mm Top and Bottom Plate
                                                                                                                             150mm Vertical Edges
                                                                                                                             300mm Intermediate Studs
NOTE: For sheathed systems less than 900mm in                                                                                Sheathed Panels are to be
                                                                                                                             Connected to Sub-Floor by
width reduction factors from Table 9 must be applied.                                                                        a minimum of 13kN tie
For 600mm or wider sections the fitting of M10                                                                               down every 1200mm
                                                                                                                             between rods. *An exception
Coachscrews are not required to achieve the reduction                                                                        to the requirement for tie rods
                                                               300mm                                                         for each end is when 6.4N/m
factor of 1 as the two M12 tie rods make them                                                                                systems are used either side
                                                                                                                             of an opening up to 2.4m - in
superfluous.                                                                                                                 such a case tie rods at the
                                                                                                                             opening are not mandatory.
              0.6                      0.5
             0.45                      0.25
              0.3                       0.2
  0.6 (with M10 coach                  1.0
  screws at the panel
  corners)
                                                                                                                                                             11
         TABLE 10: Minimum Structural Plywood Thicknesses 6kN/m Bracing Capacity Systems (mm)
     Plywood
                            Stud Spacing                                                                         Horizontal Butt Joints
      Stress                                                       50mm Staggered                                Permitted Provided fixed to
                                                                                                                 Nogging at 50mm Centres
      Grade         450mm              600mm
        F8             7                  9                                                                      50mm
       F11             6                  7      150mm
       F14             4                  6
       F27             4                 4.5
                                                                                                     Fastener Centres:
                                                                                                     50mm Top and Bottom Plate
                                                                                                     150mm Vertical Edges
                                                                                                     300mm Intermediate Studs
       TABLE 11: Minimum Structural Plywood Thicknesses for 7.5kN/m Bracing Capacity Systems (mm)
     Plywood
                            Stud Spacing         M12 Rod Top to Bottom plate
      Stress                                     Each End of Sheathed Section
      Grade                                                                     50mm
                    450mm              600mm
       F11            4.5                4.5                                                                  Horizontal Butt Joints Permitted
                                                                                                              Provided fixed to Nogging at
                                                                                                              50mm Centres
                                                 100mm
                                                                                                          Fastener Centres:
                                                                                                          50mm Top and Bottom Plate
                                                                                                          100mm Vertical Edges
                                                                                                          100mm Intermediate Studs
      TABLE 12: Minimum Structural Plywood Thicknesses for 8.7kN/m Bracing Capacity Systems (mm)
     Plywood
                            Stud Spacing         M12 Rod Top to Bottom plate
      Stress                                     Each End of Sheathed Section
      Grade                                                                     50mm
                    450mm              600mm
       F11            7.0                7.0                                                                  Horizontal Butt Joints Permitted
                                                                                                              Provided fixed to Nogging at
                                                                                                              50mm Centres
                                                 100mm
                                                                                                          Fastener Centres:
                                                                                                          50mm Top and Bottom Plate
                                                                                                          100mm Vertical Edges
                                                                                                          100mm Intermediate Studs
12
Internal Lining - Bullet Head Fasteners
Decorative structural plywood wall lining fixed with       be punched just below the plywood surface and the
2.5mm dia x 40mm bullet head nails can provide             holes filled with a suitable putty. In grooved plywood
bracing resistance against wind loads. The nails may       lining the nails may be in the grooves.
     Table 13: Minimum Structural Plywood Lining Thicknesses for 2.1kN/m Bracing Resistance (mm)
   Plywood
                            Stud Spacing
    Stress                                                                                  Horizontal Butt Joints Permitted
                                                                                            Provided fixed to Nogging at
    Grade           450mm              600mm                                                100mm Centres
                                                                      100mm
     F11               6                  6
                                                                                                   100mm
                                                   100mm
                                                                                        Fastener Centres:
                                                                                        100mm Top and Bottom Plate
                                                                                        100mm Vertical Edges
                                                                                        200mm Intermediate Studs
200mm
           TABLE 14: Minimum Structural Plywood Glue/Nailed Lining for 5.3kN/m Bracing Resistance
   Plywood
                            Stud Spacing
    Stress                                                               200mm
    Grade           450mm              600mm                                                           Horizontal Butt Joints
     F11               6                  6                                                            Permitted Provided fixed
                                                                                                       to Nogging at 200mm
                                                                                                       Centres
                                                                                                      200mm
                                                   200mm
                                                                                                                                13
 ADDITIONAL INSTALLATION REQUIREMENTS
                                                                  General
 To ensure the maximum effectiveness of structural                All fasteners shall be a minimum of 7mm from the plywood
 plywood bracing the additional installation requirements         edges. All plywood panel butt joints, either at vertical or
 detailed in this section are critical. The even distribution     horizontal edges, must be via connection of each panel to
 and maximum spacing of the bracing panels is vitally             a common nogging or stud. Unattached panel edges or ‘fly
 important to the structural performance of the structure.        joints’ are not permitted.
 The tie down of the bottom plate against sideways forces,
 and the panels against overturning forces within the             Each plywood bracing panel must be effectively fastened
 building framework, are crucial to the performance of the        to the top and bottom plates and studs. In cases where
 bracing. In addition, there must be sufficient structural        secondary (ribbon) top plates are employed and the
 connection between the ceiling/roof diaphragms and the           plywood bracing has been fixed to the lower top plate, the
 top of the bracing walls to transfer the forces through the      two plates must be connected together with fasteners of
 structure to the shear wall then down to the ground.             equivalent lateral shear capacity to the plywood to lower
                                                                  top plate fixings.
     Notes: 1. Internal wall bracing can be cupboard backs or in rooms with shorter walls.
            2. Where possible some bracing should be placed at all external corners of the building.
14
   Distribution and Spacing of Bracing Walls (cont.)
                                                                                                                                                                               15
 Fixing of Bottom of Bracing Walls
 The horizontal forces due to wind and earthquakes being              The second action is due to rotation or overturning and is
 resisted by bracing walls results in two separate types of           best resisted by tie rods from the top plate to the sub-floor
 action on the bracing panels. The first action is a sideways         and located at each end of the bracing wall. For the lower
 sliding force pushing on the bottom plate. Sufficient fixings        capacity bracing walls connection of the bottom plate to
 of the bottom plate to the sub-floor can be designed to              the sub-floor can overcome these overturning moments.
 resist this sideways ‘shear’ force.
 The tie down capacity of some bolts through a range of               appropriately embedded. For lower capacity bolt joints
 timber joint strengths are presented in Table 17. If the             the resistance can be accomplished by reducing the
 bolts are used in concrete slabs they must be                        spacing of the bolts.
16
Bottom Plate Fixing for 7.5 and 8.7kN/m Systems
The minimum fixing requirement as used in the actual              tie down every 600mm or equivalent. Reference to the tie
testing of 7.5 and 8.7kN/m bracing capacity systems is 13kN       down capacities shown in Table 17 provides some guidance.
Table 18 gives the allowable uplift resistance in kN per rafter   stress grades given in Tables 5 to 12. A single 900mm
for two plywood to top and bottom plate connection methods.       bracing panel can provide the specified uplift resistance for a
The fastener specification is as detailed in Table 1 and the      rafter if the rafter is fixed a minimum of 300mm from either
uplift resistances apply to all the plywood thicknesses and       end of the plywood panel as shown in Diagram 5.
                                                                                                                               17
 Fixing of top of bracing walls
 If the horizontal forces due to wind or earthquakes in       transferred into the wall bracing there must be sufficient
 the ceiling/top floor/roof diaphragm are to be               structural connection between the two.
 DESIGN EXAMPLE
 Determine the bracing requirements for a 15m x 9m            Assume the Local Authority has advised the Wind
 double storey gable roofed dwelling with 200 roof pitch      Classification for the site to be N2.
 and 2.7m ceiling heights as shown in Diagram 8.
 Firstly, the wind forces to be resisted by the building      been given, the next step is to calculate the Areas of
 frames in both primary directions and for both storeys       Elevation using the dimensions from Diagram 8 as
 need to be established. As the Wind Classification has       detailed in Table 19.
18
DESIGN EXAMPLE (cont.)
                                     TABLE 19: Areas of Elevation for Design Example
       Storey         Wind Direction                        Calculation                                     Area of Elevation
                                                                                                                  (m2)
       Upper                   A                            15m x 3.1m                                              46.5
                               B                    9m x 1.35m + 9m x 1.75m/2                                        20
       Lower                   A                            15m x 5.8m                                               87
                               B                    9m x 4.05m + 9m x 1.75m/2                                       44.3
The second step, as detailed in Table 20, is to calculate                  and storey using the Area of Elevation and the relevant
the Design Racking Forces for each primary direction                       Wind Pressure from Table 4.
Table 21 provides one option for minimum AS1684                            for wind direction A will require some of the bracing to
bracing requirements, and all that remains now is to                       be installed in internal walls, as the relevant external
evenly distribute the panels throughout the framing. To                    walls are spaced at 15m. These panels can be located
brace the frames in both storeys for wind direction B,                     in the backs of built-in cupboards, or on the walls of
installation of the plywood in the front and back 15m                      smaller rooms, e.g. toilets. Decorative structural
walls of both storeys, preferably at each corner, would                    plywood wall panelling is another alternative. It must be
meet the Code requirements as these walls are 9m                           remembered these internal bracing walls have to be
apart - the maximum allowed in Table 15 for Wind                           structurally connected to the ceiling/roof framing to be
Classifications N1 and N2. The bracing of the framing                      effective as bracing.
                                                                                                                                                19
                             ADDITIONAL PAA LITERATURE
The following technical manuals and publications are available from Plywood Association of Australia.
      • Plywood Webbed Structural Beams for                                            • Plywood Association of Australia Ltd. - Role
         Domestic Housing - 50 pages                                                      and Activities - 8 pages
      • Structual Plywood for Commercial and                                           • Plywood - the Only Engineered Wood Panel
         Industrial Flooring - Design Manual - 12                                         - 4 pages
         pages
                                                                                       • Facts About Plywood - 42 pages
      • Plywood in Concrete Formwork - 56 pages
     PLYWOOD ASSOCIATION OF AUSTRALIA LTD.,
                                                                                                                                                                     JAS-ANZ
                                           PLYWOOD ASSOCIATION OF AUSTRALIA LTD.
                                                                (A.C.N. 009 704 901)
                    ‘PLYWOOD HOUSE’, 3 DUNLOP STREET, NEWSTEAD, QUEENSLAND, AUSTRALIA
               P.O. Box 2108, Fortitude Valley, M.A.C. Qld. 4006. Phone (07) 3854 1228 ● Fax (07) 3252 4769                                ISO 9002 NATA CERTIFIED
5M/1/00
20