SITE TEST REPORT DATE :
AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 1 of 4
CT SUPERVISION RELAY - MVTP
1. Information:
Panel No. Designation
Make ALSTOM Type MVTP31
Serial No. Aux. Voltage 125V DC
Model No. MVTP31V1CB0751E No. of Contacts 5 NO
2. Mechanical Checks and Visual Inspection:
Item Description Remarks
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check tightness of all connections.
4 Check that serial no. of relay matching with serial no. of case.
Check condition of any connectors, contacts alignment and
5
travel. (if applicable)
6 Check Reset mechanism.
3. Electrical Test:
ITEM DESCRIPTION REMARKS
1 Check the continuity of the contacts.
2 All output contacts resistance measured. (0.2 Ω Max).
3 Check Flag Operation (if applicable).
4 Check Reset Operation.
5 Check operate and Reset Coil resistance.
6 Check the cut off facility.
Tested by Witnessed by
Name: Sherif Mamdouh
Signature:
CSD ID OSA-019
Date:
SITE TEST REPORT DATE :
AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 2 of 4
CT SUPERVISION RELAY - MVTP
3.1 Operating Time Test:
COIL R Y B
TERMINAL NO 23,24 25,26 27,28
RELAY RESISTANCE IN Ω 89.50 89.67 89.65
SET OPERATING VOLTS
OPERATING TIME
VOLTS R Y B
2
4
RELAY 6
OPERATES 8
AT
10
12
14
16
* OPERATING VOLTAGE 2 TO 16 V ** OPERATING TIME AT 3Sec +/- 5%
3.2 CT SEC. CIRCIUT SHORTING TERMINAL:
Tested by Witnessed by
Name: Sherif Mamdouh
Signature:
CSD ID OSA-019
Date:
SITE TEST REPORT DATE :
AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 3 of 4
CT SUPERVISION RELAY - MVTP
MEASURED RESISTANCE
CONTACT
CONTACT NO FOR CONTACTS (When
TERMINAL NO
Closed) in Ω
R 5,7
Y 6,8
B 9,11
3.3 ALARM CIRCUIT TERMINAL:
MEASURED RESISTANCE
CONTACT
CONTACT NO FOR CONTACTS (When
TERMINAL NO
Closed) in Ω
TO SAS 1,3
SPARE 2,4
1. FLAG INDICATION :
2. MANUAL RESET OPERATION :
3. RELAY FOUND HEALTHY : YES / NO
Tested by Witnessed by
Name: Sherif Mamdouh
Signature:
CSD ID OSA-019
Date:
SITE TEST REPORT DATE :
AL-OSAIS CO.
SEC – EOA CONTRACT NO :
KHUDARIYAH S/S 115/13.8 kV S/S 4400003554/00
SHEET NO : Page 4 of 4
CT SUPERVISION RELAY - MVTP
TEST EQUIPMENTS USED.
1) FREJA 300 S/N: Calibration Due Date:
2) MULTI METER S/N: Calibration Due Date:
Tested by Witnessed by
Name: Sherif Mamdouh
Signature:
CSD ID OSA-019
Date: