MALAYSIAN MS 2103:2007
STANDARD
ELECTRIC CABLE AND WIRE:
600/1 000 (Um = 1 200) V MULTI CORE PVC
INSULATED CABLE – ARMOURED
ICS: 29.060, 33.120
Descriptors: electric cable, wire, multi-core, PVC insulated, PVC sheathed, armoured cable
© Copyright 2007
DEPARTMENT OF STANDARDS MALAYSIA
© STANDARDS MALAYSIA 2007 - All rights reserved
DEVELOPMENT OF MALAYSIAN STANDARDS
The Department of Standards Malaysia (STANDARDS MALAYSIA) is the national
standardisation and accreditation body.
The main function of the Department is to foster and promote standards,
standardisation and accreditation as a means of advancing the national economy,
promoting industrial efficiency and development, benefiting the health and safety of
the public, protecting the consumers, facilitating domestic and international trade and
furthering international cooperation in relation to standards and standardisation.
Malaysian Standards are developed through consensus by committees which
comprise of balanced representation of producers, users, consumers and others with
relevant interests, as may be appropriate to the subject in hand. To the greatest
extent possible, Malaysian Standards are aligned to or are adoption of international
standards. Approval of a standard as a Malaysian Standard is governed by the
Standards of Malaysia Act 1996 (Act 549). Malaysian Standards are reviewed
periodically. The use of Malaysian Standards is voluntary except in so far as they are
made mandatory by regulatory authorities by means of regulations, local by-laws or
any other similar ways.
The Department of Standards appoints SIRIM Berhad as the agent to develop
Malaysian Standards. The Department also appoints SIRIM Berhad as the agent for
distribution and sale of Malaysian Standards.
For further information on Malaysian Standards, please contact:
Department of Standards Malaysia OR SIRIM Berhad
Level 1 & 2, Block C4, Parcel C (Company No. 367474 - V)
Federal Government Administrative Centre 1, Persiaran Dato’ Menteri
62502 Putrajaya P.O. Box 7035, Section 2
MALAYSIA 40911 Shah Alam
Selangor D.E.
Tel: 60 3 88858000 Tel: 60 3 5544 6000
Fax: 60 3 88885060 Fax: 60 3 5510 8095
http://www.standardsmalaysia.gov.my http://www.sirim.my
E-mail: central@standardsmalaysia.gov.my
© STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
CONTENTS
Page
Committee representation .............................................................................. ii
Foreword ...................................................................................................... iii
1 Scope ........................................................................................................... 1
2 Normative references ..................................................................................... 1
3 Definitions ..................................................................................................... 2
4 Construction .................................................................................................. 2
4.1 Conductors.................................................................................................... 2
4.2 Insulation ...................................................................................................... 2
4.3 Core identification.......................................................................................... 2
4.4 Laying up ...................................................................................................... 2
4.5 Bedding ........................................................................................................ 3
4.6 Armour.......................................................................................................... 3
4.7 Oversheath ................................................................................................... 3
4.8 Oversheath marking....................................................................................... 3
5 Drumming and packaging............................................................................... 4
6 Tests ............................................................................................................ 4
Tables
1 Two core cables 600/1 000 (1 200) V .............................................................. 5
2 Three core cables 600/1 000 (1 200) V............................................................ 6
3 Four core cables 600/1 000 (1 200) V ............................................................. 7
4 Five core cables 600/1 000 (1 200) V .............................................................. 8
5 Auxiliary cables 600/1 000 (1 200) V ............................................................... 9
6 Schedule of tests ........................................................................................... 10
© STANDARDS MALAYSIA 2007 - All rights reserved i
MS 2103:2007
Committee representation
The Electrotechnical-1 Industry Standards Committee (ISC E-1) under whose authority this Malaysian Standard was
developed, comprises representatives from the following organisations:
Association of Consulting Engineers Malaysia
Department of Standards Malaysia
Federation of Malaysian Manufacturers
Independent Power Producer
Jabatan Kerja Raya Malaysia
Malaysian Cable Manufacturers Association
Malaysian Electrical Appliances and Distributors Association
Ministry of Domestic Trade and Consumer Affairs
Ministry of International Trade and Industry
Persatuan Pengguna-Pengguna Standard Malaysia
Pusat Tenaga Malaysia
SIRIM QAS International Sdn Bhd (Electrotechnical Testing Section)
SIRIM QAS International Sdn Bhd (Product Certification and Inspection Section)
Suruhanjaya Komunikasi dan Multimedia Malaysia
Suruhanjaya Tenaga
Tenaga Nasional Berhad
The Electrical and Electronics Association of Malaysia
The Institution of Engineers, Malaysia
Universiti Teknologi Malaysia
The Technical Committee on Cables and Cable Accessories which developed this Malaysian Standard was managed
by the Malaysian Cable Manufacturers Association (MCMA) in its capacity as the Standards -Writing Organisation
which consists of representatives from the following organisations:
Association of Consulting Engineers Malaysia
Jabatan Bomba dan Penyelamat Malaysia
Jabatan Kerja Raya Malaysia
Malaysian Cable Manufacturers Association (Secretariat)
Malaysian Electrical Appliances and Distributors Association
Persatuan Pengguna-Pengguna Standard Malaysia
PETRONAS
SIRIM Berhad
SIRIM QAS International Sdn Bhd (Electrotechnical Testing Section)
SIRIM QAS International Sdn Bhd (Product Certification and Inspection Section)
Suruhanjaya Tenaga
Telekom Malaysia Berhad
Tenaga Nasional Berhad
Universiti Malaya
ii © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
Committee representation (continued)
The Working Group on Cables and Cable Accessories which developed this Malaysian Standard consists of
representatives from the following organisations:
Fajar Cables Sdn Bhd
FEC Cables (M) Sdn Bhd
Fujikura Federal Cables Sdn Bhd
Leader Cable Industry Berhad
Mega Kabel Sdn Bhd
Olympic Cable Company Sdn Bhd
Pan International Wire & Cable Sdn Bhd
Power Cables Malaysia Sdn Bhd
Sama Kabel Sdn Bhd
Sindutch Cable Manufacturer Sdn Bhd
Southern Cable Sdn Bhd
Tai Sin Electric Cables (M) Sdn Bhd
Tenaga Cable Industries Sdn Bhd
Universal Cable (M) Bhd
Utama Cables Sdn Bhd
Wonderf ul Wire & Cable Berhad
Co-opted members:
Federal Power Sdn Bhd
SDKM Fibers, Wires & Cables Berhad
Supercomal Technologies Sdn Bhd
Universiti Teknologi Malaysia
© STANDARDS MALAYSIA 2007 - All rights reserved iii
MS 2103:2007
FOREWORD
This Malaysian Standard was developed by the Technical Committee on Cables and Cable
Accessories under the authority of the Electrotechnical Industry Standards Committee (ISC E-
1). Development of this standard was carried out by the Malaysian Cable Manufacturers
Association which is the Standards-Writing Organisation appointed by SIRIM Berhad to
develop standards for cables and cable accessories.
In the preparation of this standard, consideration was given to IEC 60502-1:2004 Second
edition, Power cables with extruded insulation and their accessories for rated voltage from 1
kV (U m = 1.2 kV) up to 30 kV (Um = 36 kV) – Part 1: Cables for rated voltage of 1 kV (Um = 1.2
kV) and 3 kV (Um = 3.6 kV), published by the International Electrotechnical Commission.
The Technical Committee has determined that minor differences in construction and test
requirement to the IEC 60502-1 are necessary and this has been incorporated to comply with
the prevailing practices of cable manufacturers and users in Malaysia. These are as follows:
a)spark testing of insulation has been included;
b)requirement for oversheath markings has been included;
c) standard requirements for drumming and packaging of completed cables have been
included; and
d)tests at low temperature for insulation and oversheath which are not suited to conditions in
Malaysia have been excluded.
Compliance with a Malaysian Standard does not of itself confer immunity from legal
obligations.
iv © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
ELECTRIC CABLE AND WIRE: 600/1 000 (U m = 1 200) V MULTI CORE
PVC INSULATED CABLES – ARMOURED
1. Scope
This Malaysian Standard specifies the construction, dimension and test requirements of PVC
insulated, PVC sheathed multi-core cables, armoured for operation at rated voltage 600/1 000
(1 200) V.
The cable as prescribe are generally use for low voltage, underground fixed installation
system for the distribution network. It is not intended for use in prolonged water logged
conditions and for specialised applications (e.g. welding, crane lifting, mines, aerial), which
are covered by other Malaysian Standards, where applicable.
2. Normative references
The following normative references are indispensable for the application of this standard. For
dated references, only the edition cited applies. For undated references, the latest edition of
the normative references (including any amendments) applies.
BS 5099, Specification for spark testing of electric cable
MS IEC 60228, Conductors of insulated cables
MS IEC 60811-1-1, Common test methods for insulating and sheathing materials of electric
cables – Part 1: Methods for general application – Section 1: Measurement of thickness and
overall dimensions – Tests for determining the mechanical properties
MS IEC 60811-1-2, Common test methods for insulating and sheathing materials of electric
cables - Part 1: Methods for general application - Section 2: Thermal ageing methods
MS IEC 60811-1-3, Common test methods for insulating and sheathing materials of electric
cables - Part 1: Methods for general application - Section 3: Methods for determining the
density - Water absorption tests - shrinkage test
MS IEC 60811-3-1, Common test methods for insulating and sheathing materials of electric
cables - Part 3: Methods specific to PVC compounds - Section 1: Pressure test at high
temperature - Test for resistance to cracking
MS IEC 60811-3-2, Common test methods for insulating and sheathing materials of electric
cables - Part 3: Methods specific to PVC compounds - Section 2: Loss of mass test - Thermal
stability test
IEC 60502-1, Power cables with extruded insulation and their accessories for rated voltages
from 1 kV (U m = 1.2 kV) up to 30 kV (U m = 36 kV) - Part 1: Cables for rated voltages of 1 kV
(U m = 1.2 kV) and 3 kV (Um = 3.6 kV)
© STANDARDS MALAYSIA 2007 - All rights reserved 1
MS 2103:2007
3. Definitions
For the purposes of this standard, the definitions given in IEC 60502-1 apply.
4. Construction
4.1 Conductors
4.1.1 The conductor shall be Class 1 or Class 2 plain aluminium or annealed copper
complying with the requirements of MS IEC 60228.
4.1.2 The nominal areas of the conductors are given in Tables 1, 2, 3, 4 and 5.
4.2 Insulation
4.2.1 The insulation shall be PVC/A in accordance with IEC 60502-1.
4.2.2 The nominal and minimum thickness of insulation shall be as specified in Tables 1, 2,
3, 4 and 5. For each piece of core, the smallest value measured shall not fall below 90 % of
the nominal value by more than 0.1 mm.
4.3 Core identification
The cores shall be identified by colours for cables up to 5 cores and by numbers for cables of
6 cores and above.
4.3.1 Colour coding shall be in accordance with the following sequence:
Number of cores Identification
Two-core Red, Black
Three-core Red, Yellow, Blue
Four-core Red, Yellow, Blue, Black
Five -core Red, Yellow, Blue, Black, Green/Yellow
The colour shall remain identifiable throughout the length of the cable.
4.3.2 Numbers of each core shall be printed in a colour contrasting with that of the
insulation. Numbers shall be marked sequentially starting with number 1. The intervals
between adjacent numbers shall not exceed 70 mm. The height of individual number shall not
be less than 1.5 mm.
4.4 Laying up
The outermost layer of the laid-up cores shall be of right hand direction of lay. Where
necessary, non-hygroscopic fillers may be applied integrally with the bedding to form a
compact and circular cable. There shall be no adhesion between the bedding and the
insulation. Where the bedding is applied integrally with the fillers, it shall be possible to strip it
from the cable without damaging the insulation of the cores.
2 © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
4.5 Bedding
The bedding shall be an extruded layer of PVC ST1 in accordance with IEC 60502-1. Unless
otherwise specified, the colour of the bedding shall be black.
The nominal and minimum thickness of extruded bedding shall be as specified in Tables 1, 2,
3, 4 and 5.
4.6 Armour
4.6.1 Wire armour, which consist of a single layer of galvanized steel wires of the size
indicated in Tables 1, 2, 3, 4 and 5, complying with the requirements of IEC 60502-1, shall be
applied over the bedding.
4.6.2 When joint in armour wire are necessary they shall be brazed or welded and any
surface irregularity shall be removed. A joint in any wire shall be not less than 1 m from the
nearest joint in the complete cable.
4.6.3 The direction of lay of the armour in cable shall be left hand.
4.6.4 Layer(s) of binding tape may be applied over the armour.
4.7 Oversheath
The oversheath shall be PVC ST1 in accordance with IEC 60502-1, shall be applied over the
armour. Unless otherwise specified, the colour of the oversheath shall be black.
The nominal and minimum thickness of the oversheath shall be as specified in Tables 1,2,
3, 4 and 5.
4.8 Oversheath marking
The oversheath shall be marked with a complete set of elements in the order specified below.
The distance between the end and start of each element shall not exceed 50 mm while the
distance between the end and start of each complete set of element shall not exceed 250
mm. The markings shall consist of upright block characters of approximately the same height
of between 1.5 mm to 10 mm.
Element Example of marking
Electric cable ELECTRIC CABLE
Voltage designation 600/1000 V
Standard no. MS WWWW
Manufacturer’s identification
Number of cores, nominal area and type of conductor, e.g. for 4 core cables
a) Copper conductor cables 4 x 300 SQMM CU
© STANDARDS MALAYSIA 2007 - All rights reserved 3
MS 2103:2007
b) Aluminium conductor cables 4 x 300 SQMM AL
Year of manufacture
5. Drumming and packaging
Both ends of the cable shall be effectively sealed against ingress of moisture, dirt and insects.
Cable drums shall be lagged in order to protect the cable from damage, and the end of the
cable projecting from the drum shall also be protected from damage.
Each drum shall bear a distinguished number on the outside of the flange and particulars as
follows:
a) Cable type PVC/PVC/SWA/PVC
b) Voltage rating 600/1000 V
c) Length (m)
d) Conductor size (mm²)
e) Net weight (kg)
f) Gross weight (kg)
g) Manufacturer’s identification
h) Contract number (if applicable)
i) Drum number
For cables supplied in coils, the manufacturer shall similarly provide the above particulars in a
manner as deemed appropriate
6. Tests
Cables shall comply with the test specified in this clause. The category of test, criteria and
reference for the tests method for cables manufactured to this standard are given in Table 6.
The tests shall be performed at room temperature, unless otherwise specified.
4 © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
Table 1. Two core cables 600/1 000 (1 200) V
Shape of Nominal Thickness of insulation Thickness of bedding Nominal Thickness of
conductor area of armour oversheath
conductor Nominal Minimum Nominal Minimum wire Nominal Minimum
at any at any diameter at any
point point point
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
Circular solid 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
conductor
2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
Circular or 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
circular
compacted 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
stranded
4 1.0 0.80 1.0 0.60 0.9 1.8 1.24
conductor
6 1.0 0.80 1.0 0.60 1.25 1.8 1.24
10 1.0 0.80 1.0 0.60 1.25 1.8 1.24
16 1.0 0.80 1.0 0.60 1.25 1.8 1.24
25 1.2 0.98 1.0 0.60 1.6 1.8 1.24
35 1.2 0.98 1.0 0.60 1.6 1.8 1.24
Shape 16 1.0 0.80 1.0 0.60 1.25 1.8 1.24
stranded
conductor 25 1.2 0.98 1.0 0.60 1.6 1.8 1.24
35 1.2 0.98 1.0 0.60 1.6 1.8 1.24
50 1.4 1.16 1.0 0.60 1.6 1.9 1.32
70 1.4 1.16 1.0 0.60 2.0 2.0 1.40
95 1.6 1.34 1.2 0.76 2.0 2.2 1.56
120 1.6 1.34 1.2 0.76 2.0 2.3 1.64
150 1.8 1.52 1.2 0.76 2.5 2.4 1.72
185 2.0 1.70 1.4 0.92 2.5 2.6 1.88
240 2.2 1.88 1.4 0.92 2.5 2.8 2.04
300 2.4 2.06 1.6 1.08 2.5 2.9 2.12
400 2.6 2.24 1.6 1.08 2.5 3.2 2.36
500 2.8 2.42 1.8 1.24 3.15 3.4 2.52
© STANDARDS MALAYSIA 2007 - All rights reserved 5
MS 2103:2007
Table 2. Three core cables 600/1 000 (1 200) V
Shape of Nominal Thickness of Thickness of bedding Nominal Thickness of
conductor area of insulation armour oversheath
conductor Nominal Minimum Nominal Minimum wire Nominal Minimum
at any at any diameter at any
point point point
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
Circular 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
solid
conductor 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
Circular or 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
circular
compacted 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
stranded
4 1.0 0.80 1.0 0.60 1.25 1.8 1.24
conductor
6 1.0 0.80 1.0 0.60 1.25 1.8 1.24
10 1.0 0.80 1.0 0.60 1.25 1.8 1.24
16 1.0 0.80 1.0 0.60 1.25 1.8 1.24
25 1.2 0.98 1.0 0.60 1.6 1.8 1.24
35 1.2 0.98 1.0 0.60 1.6 1.8 1.24
Shape 16 1.0 0.80 1.0 0.60 1.25 1.8 1.24
stranded
conductor 25 1.2 0.98 1.0 0.60 1.6 1.8 1.24
35 1.2 0.98 1.0 0.60 1.6 1.8 1.24
50 1.4 1.16 1.0 0.60 1.6 2.0 1.40
70 1.4 1.16 1.2 0.76 2.0 2.1 1.48
95 1.6 1.34 1.2 0.76 2.0 2.2 1.56
120 1.6 1.34 1.2 0.76 2.0 2.3 1.64
150 1.8 1.52 1.4 0.92 2.5 2.5 1.80
185 2.0 1.70 1.4 0.92 2.5 2.7 1.96
240 2.2 1.88 1.6 1.08 2.5 2.9 2.12
300 2.4 2.06 1.6 1.08 2.5 3.1 2.28
400 2.6 2.24 1.6 1.08 3.15 3.4 2.52
500 2.8 2.42 1.8 1.24 3.15 3.6 2.68
6 © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
Table 3. Four core cables 600/1 000 (1 200) V
Shape of Nominal Thickness of Thickness of bedding Nominal Thickness of
conductor area of insulation armour oversheath
conductor Nominal Minimum Nominal Minimum wire Nominal Minimum
at any at any diameter at any
point point point
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
Circular 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
solid
conductor 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
Circular or 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
circular
compacted 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
stranded
4 1.0 0.80 1.0 0.60 1.25 1.8 1.24
conductor
6 1.0 0.80 1.0 0.60 1.25 1.8 1.24
10 1.0 0.80 1.0 0.60 1.25 1.8 1.24
16 1.0 0.80 1.0 0.60 1.6 1.8 1.24
25 1.2 0.98 1.0 0.60 1.6 1.8 1.24
35 1.2 0.98 1.0 0.60 1.6 1.9 1.32
Shape 16 1.0 0.80 1.0 0.60 1.6 1.8 1.24
stranded
conductor 25 1.2 0.98 1.0 0.60 1.6 1.8 1.24
35 1.2 0.98 1.0 0.60 1.6 1.9 1.32
50 1.4 1.16 1.2 0.76 2.0 2.1 1.48
70 1.4 1.16 1.2 0.76 2.0 2.2 1.56
95 1.6 1.34 1.2 0.76 2.5 2.4 1.72
120 1.6 1.34 1.4 0.92 2.5 2.5 1.80
150 1.8 1.52 1.4 0.92 2.5 2.7 1.96
185 2.0 1.70 1.6 1.08 2.5 2.9 2.12
240 2.2 1.88 1.6 1.08 2.5 3.1 2.28
300 2.4 2.06 1.6 1.08 2.5 3.3 2.44
400 2.6 2.24 1.8 1.24 3.15 3.6 2.68
500 2.8 2.42 1.8 1.24 3.15 3.9 2.92
© STANDARDS MALAYSIA 2007 - All rights reserved 7
MS 2103:2007
Table 4. Five core cables 600/1 000 (1 200) V
Shape of Nominal Thickness of Thickn ess of bedding Nominal Thickness of
conductor area of insulation armour oversheath
conductor Nominal Minimum Nominal Minimum wire Nominal Minimum
at any at any diameter at any
point point point
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
Circular 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
solid
conductor 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
Circular or 1.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
circular
compacted 2.5 0.8 0.62 1.0 0.60 0.9 1.8 1.24
stranded
4 1.0 0.80 1.0 0.60 1.25 1.8 1.24
conductor
6 1.0 0.80 1.0 0.60 1.25 1.8 1.24
10 1.0 0.80 1.0 0.60 1.6 1.8 1.24
16 1.0 0.80 1.0 0.60 1.6 1.8 1.24
25 1.2 0.98 1.0 0.60 1.6 1.9 1.32
35 1.2 0.98 1.0 0.60 1.6 2.0 1.40
50 1.4 1.16 1.2 0.76 2.0 2.2 1.56
70 1.4 1.16 1.2 0.76 2.0 2.3 1.64
95 1.6 1.34 1.4 0.92 2.5 2.5 1.80
120 1.6 1.34 1.4 0.92 2.5 2.7 1.96
8 © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
Table 5. Auxiliary cables 600/1 000 (1 200) V
Number of Nominal Thickness of Thickness of bedding Nominal Thickness of
cores area of insulation armour oversheath
conductor Nominal Minimum Nominal Minimum diameter Nominal Minimum
at any at any at any
point point point
(mm²) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
7 1.0 0.60 0.9 1.8 1.24
12 1.0 0.60 1.25 1.8 1.24
19 1.5 0.8 0.62 1.0 0.60 1.6 1.8 1.24
27 1.0 0.60 1.6 1.8 1.24
37 1.0 0.60 1.6 1.9 1.32
48 1.0 0.60 1.6 2.0 1.40
7 1.0 0.60 1.25 1.8 1.24
12 1.0 0.60 1.25 1.8 1.24
19 2.5 0.8 0.62 1.0 0.60 1.6 1.8 1.24
27 1.0 0.60 1.6 1.9 1.32
37 1.0 0.60 1.6 2.0 1.40
48 1.2 0.76 2.0 2.1 1.48
7 1.0 0.60 1.25 1.8 1.24
12 1.0 0.60 1.6 1.8 1.24
19 4 1.0 0.80 1.0 0.60 1.6 1.9 1.32
27 1.2 0.76 2.0 2.1 1.48
37 1.2 0.76 2.0 2.2 1.56
48 1.2 0.76 2.5 2.4 1.72
© STANDARDS MALAYSIA 2007 - All rights reserved 9
MS 2103:2007
Table 6. Schedule of tests
Tests Requirement Category Reference test
of test* method
Conductors:
Conductor construction Shall comply with MS IEC 60228 S MS IEC 60228
Insulation:
Thickness Shall comply with Tables 1, 2, 3, 4, S/T MS IEC 60811-1-1
and 5
Mechanical test without Shall comply with IEC 60502-1 T MS IEC 60811-1-1
ageing
Mechanical test after ageing Shall comply with IEC 60502-1 T MS IEC 60811-1-1
in air oven MS IEC 60811-1-2
Hot pressure test Shall comply with IEC 60502-1 T MS IEC 60811-3-1
(indentation)
Heat shock test Shall comply with IEC 60502-1 T MS IEC 60811-3-1
Water absorption test Shall comply with IEC 60502-1 T MS IEC 60811-1-3
Spark test (online) Shall comply with BS 5099 R BS 5099
Bedding:
Mechanical test without Tensile strength not les s than 4 N/mm² S MS IEC 60811-1-1
ageing
Elongation at break not less than 50 % S MS IEC 60811-1-1
Armour:
Wire diameter Shall comply with IEC 60502-1 S IEC 60502-1
10 © STANDARDS MALAYSIA 2007 - All rights reserved
MS 2103:2007
Table 6. Schedule of tests (continued)
Tests Requirement Category Reference test
of test* method
Oversheath:
Thickness Shall comply with Tables 1, 2, 3, 4 and S/T MS IEC 60811-1-1
5
Mechanical test without Shall comply with IEC 60502-1 S MS IEC 60811-1-1
ageing
S MS IEC 60811-1-1
Mechanical test after ageing Shall comply with IEC 60502-1 MS IEC 60811-1-2
in air oven
Hot pressure test Shall comply with IEC 60502-1 T MS IEC 60811-3-1
(indentation)
Heat shock test Shall comply with IEC 60502-1 T MS IEC 60811-3-1
Tests on complete cables:
Measurement of electrical Shall comply with IEC 60502-1 R MS IEC 60228
resistance
High voltage a.c. test for 5 Shall comply with IEC 60502-1 R IEC 60502-1
min
High voltage a.c. test for 4 h Shall comply with IEC 60502-1 T IEC 60502-1
Insulation resistance at 20°C Shall comply with IEC 60502-1 T IEC 60502-1
and at maximum conductor
temperature
Cable markings Shall comply with this standard R Visual
Flame spread test on single Shall comply with IEC 60502-1 T IEC 60502-1
cables
Additional ageing test of Shall comply with IEC 60502-1 T IEC 60502-1
completed cables
* The categories of tests as defined in MS XXXX are as follows:
R – Routine test
T – Type test
S – Sample test
© STANDARDS MALAYSIA 2007 - All rights reserved 11
Acknowledgements
Technical Committee on Cables and Cable Accessories members:
Mr Lokman Ahmad Dahlan (Chairman) Malaysian Cable Manufacturers Association
Ms Sara Kong (Secretary) Malaysian Cable Manufacturers Association
Ir Looi Hip Peu Association of Consulting Engineers
Malaysia
Mr Ahmad Izram Osman Jabatan Bomba dan Penyelamat Malaysia
Mr Ir. Chuang Chu Kuen/ Jabatan Kerja Raya Malaysia
Mr Muhamed Tarmizy Yaacob/
Mr Yusof Ramli
Mr V. T. Doshi Malaysian Electrical Appliances and
Distributors Association (MEADA)
Ms Anuradha Chelliah Persatuan Pengguna-Pengguna Standard
Malaysia
Mr M. Faudzi M. Yasir/ PETRONAS
Mr Nik Abdul Aziz Mohamed
Ms Nuriyati Abdul Rahman SIRIM Berhad
Mr Lim Cheng Meng SIRIM QAS International Sdn Bhd
(Electrotechnical Testing Section)
Ms Roslinah Abdullah SIRIM QAS International Sdn Bhd
(Product Certification and Inspection
Section)
Ir Ismail Anuar Suruhanjaya Tenaga
Mr Loh Siew Kwee Telekom Malaysia Berhad
Mr Muhd Azizi Abd Rahman Tenaga Nasional Berhad
Dr Mohd Rozailan Ibrahim Universiti Malaya
Working Group on Cables and Cable Accessories:
Mr Saupian Mohamad Zin Fajar Cables Sdn Bhd
Mr Albert Tan/ FEC Cables (M) Sdn Bhd
Mr Amizar Hashim/
Mr Jaafar Noor
Ms Cheng Siew Guay/ Fujikura Federal Cables Sdn Bhd
Mr Teoh Seng Long
Mr Ir. Oo Kim Seng/ Leader Cable Industry Berhad
Mr Tan Lip Keat
Mr Loo Kam Tim/ Mega Kabel Sdn Bhd
Mr Tan Kean Boon
Mr Cheng Yam Guan/ Olympic Cable Company Sdn Bhd
Mr Tan Kian Chai/
Mr Tui Kim Chuan
Mr Yong Foo Seng Power Cables Malaysia Sdn Bhd
Mr Low Yoon Onn/ Sindutch Cable Manufacturer Sdn Bhd
Mr Ong Boon Sun
Mr Ng Hien Shui Tai Sin Electric Cables (M) Sdn Bhd
Ms Nor Hanita Binti Abdul Ghani Tenaga Cable Industries Sdn Bhd
© STANDARDS MALAYSIA 2007 - All rights reserved
Acknowledgements (continued)
Mr Azman Yusoff/ Universal Cable (M) Bhd
Mr Chen Wee Tong/
Ms Tay Shin Yea
Mr Lim Oui Kiong/ Utama Cables Sdn Bhd
Mr Ng Ah Dai
Mr Foong Kam Cheng/ Wonderful Wire & Cable Berhad
Mr Kamal Azahari Khamis
Co-opted members:
Mr Mohd Nasir Hashim/ Federal Power Sdn Bhd
Mr Mohd Zainurin Ayob/
Mr Ramzi Hassan/
Mr Satoru Yoshikawa
Mr Moh Ket Wai SDKM Fibers, Wires & Cables Berhad
Mr Lim Chin Gian/ Supercomal Technologies Sdn Bhd
Mr Nik Abd. Aziz/
Mr Yap Ee Leong
Dr Hussein Ahmad Universiti Teknologi Malaysia
© STANDARDS MALAYSIA 2007 - All rights reserved