ANNUAL TOWER INSPECTION REPORT
Wisconsin Department of Transportation
                                                          SP4599 9/2007
Tower Site Name                                                                            Date Inspected
                                                                                                BULB REPLACEMENT shall be performed for every incandescent beacon and obstruction lamp for each tower.
Replacement shall be performed in conjunction with the tower and lighting inspection. Strobes and LED lighting shall only
be replaced as needed. Contractor shall use only new, high-grade bulbs with Pyrex glass, long life, 130 volt rating. No
reimbursement will be made to Contractor for bulbs installed during the bulb change.
Indicate quantity and type of lamp (incandescent, LED or strobe) used on each tower.
Beacon – Quantity and Type                                            Obstruction – Quantity and Type
                                                                           
TEST TOWER LIGHTING CONTROLLER AND ALARM SYSTEMS
 Satisfactory Unsatisfactory
                             Darken photocell to verify night-mode lighting activation
                             Proper flashing or strobe of beacons and steady illumination of all obstruction lights
                             Daytime lighting is functioning properly, where applicable
                             Alarm system detects failure of tower lighting, as applicable at each tower site
Lighting Controller Model Number                                                           Controller Serial Number
                                                                                                ELECTRICAL AND LIGHTING INSPECTIONS
 Satisfactory Unsatisfactory
                             Proper functioning of photocell
                             Proper functioning of flasher
                             Proper functioning of ALL bulbs after replacement
                             Inspect for damaged red obstruction lens
                             Inspect for damaged ruby liner and clear glass lens in beacon
                             Functioning of strobe light, if applicable
                             All strobe lights are working
                             Tower lighting electrical system
                             Junction box wiring and bulb sockets at all points above the photocell, specifically:
                             Tightness of electrical screw terminals – Tighten loose connections
                             Deterioration of insulation of electrical wiring
                             Evidence of overheating of electrical wiring
                             Bulb sockets condition – Number of sockets replaced:      
Inspect and record incandescent lamp voltage at all sockets under load.
                     Socket 1        Socket 2         Socket 3
Level 1                                                  
Level 2                                                  
Level 3                                                  
Level 4                                                  
TOWER INSPECTION
 Satisfactory Unsatisfactory
                                  Attachment and physical condition of antennas and transmission lines
                                  Site deterioration or vandalism
                                  Proper conduit attachment - Repair or replace defective conduit attachments
                                  Paint fading to be checked with the In-service Aviation Orange Color Tolerance Chart
                                      Paint Good                    Paint OK                       Needs Painting
                                  Guy anchor condition and integrity including turnbuckles, wire rope clamps and nuts
                                  and safety cable through all turnbuckles; Inspect for sagging, rust and grounding
                                  Guy attachments to tower
       Tighten loose bolts and replace missing hardware on tower and attachments.
       Tighten loose bolts and replace missing hardware on guys and anchors.
       Replace missing or damaged safety cable through turnbuckles.
GUY WIRE TENSION - Inspect and provide guy tension measurement data for each applicable site. Direct Method of
measuring guy wire tension should be used.
Tension Meter Serial Number                   Air Temperature                      Cable Size
                                                                                            GUY LEVEL                                 Proper Tension                               Measured Tension
    Bottom to top                Leg 1            Leg 2            Leg 3      Leg 1             Leg 2            Leg 3
1                                                                                                                  
2                                                                                                                  
3                                                                                                                  
4                                                                                                                  
5                                                                                                                  
Note: If the tower is plumb and readings are normal on one leg, no further measurements are necessary.
EXPLANATION OF UNSATISFACTORY CONDITIONS
    Specification Section               Description of Condition and Action Taken                               
                                           
                                           
                                           
                                           
                                           
Continue on next page as needed