White Paper:
Understanding the Harmonic Analysis Report
Contributed by Ben Bowman August 2013                                                                                   Figure 1. Right click on
                                                                                                                        the graph to generate a
ABSTRACT                                                                                                                report.
Harmonics are distortions in the 60Hz voltage or current
caused by non-linear loads on the system. Harmonics
are of interest to utilities as they can cause damage
to equipment, such as creating extra vibrations in
motors or causing excess heat in transformers. Power
Monitors, Inc. (PMI) ProVision software features
advanced harmonic analysis features. One such
feature is the ability to generate harmonic analysis
reports. This paper will examine how to create a
harmonic report in ProVision, describe the various
pieces of the report, and also discuss when to use this
report vs. other ProVision harmonic tools.
Opening a Harmonic Report
The Harmonic Report is the tabular version of
the Harmonic Graph in ProVision. This harmonic
information is calculated by ProVision from raw
waveform data captured by the recorder. While the
harmonic bar chart in the graph is useful for spotting
patterns and getting a quick overview, the harmonic
report is better for a more detailed analysis.
                                                              Report Header
To see the Harmonic Report, it is necessary first to          The report starts with the basic header information at
select the harmonic analysis via the graph. Once you          the top of every ProVision report, such as the recorder
have loaded a recording file, go to the main toolbar          used to make the recording, and the firmware and
and click on “Graph”. In the drop down that appears           software currently installed on it. Next is additional
click on “Harmonic Analysis” and “Magnitudes”. The            information about the recorder, and the recording
harmonic analysis is computed by ProVision for the            interval used.
cycle shown in the grey rectangle at the top of the
graph. Click and drag the rectangle to cover the cycle        Next is the specific data source selected in the grey Figure 2. Detail from
to analyze; ProVision will recalculate the harmonics as       box on the graph screen (Figure 2). In this example, Waveform #5
it moves. For harmonics, a “normal” cycle should be
selected, so representative steady-state harmonics
are computed, not the harmonics of a disturbance
(unless that’s really what’s needed). Once positioned,
right click on the graph that appears on the section
that you wish to generate a report from, in this example
we will right click on the Volts bar graph and select
“Launch Report” (Figure 1).
A detailed report of harmonics present in the recording
will appear. This report is a textual representation of the
previous graph. The report can be exported to several
formats, including CSV, by right clicking on the body
of the report. There are several sections to the report,
which we will discuss in turn. The sections are a report
header, a section on Total Harmonic Distortion (THD)
and other distortion measures, Harmonic Magnitude,
and lastly a section on Harmonic Phase Angle.
         Tools you need. People you trust.      081313 WP131         Power Monitors, Inc. • Call Us: 800.296.4120 • www.powermonitors.com
White Paper:
Understanding the Harmonic Analysis Report
                           waveform capture #5 is used, and the cycle under the most useful measurement especially when there
                           analysis starts at point 234, 15.17 ms into the waveform. is high harmonic content. The THD-R measurement
                                                                                     can be prone to misinterpretation, which can easily
                           The next section (Figure 3) is a block of statistics lead to measurement errors when measuring larger
                           computed from the harmonic data, including several distortions.
                           THD measurements, TIF, and K-Factor values in this
                           table are percents, with two main categories, THD THD Fundamental
                           Fundamental and THD RMS. These terms are defined Total Harmonic Distortion in reference to (F)
                           here:                                                     Fundamental, represents the ratio, in percent, of
                                                                                     the voltage/current harmonic components relative
                           THD-F and THD-R                                           to the voltage/current of the fundamental. When the
                           There are two typical definitions used when dealing reference is not indicated (i.e. simply THD), then it is
                           with Total Harmonic Distortion. The two types of Total usually assumed the reference is fundamental. For
                           Harmonic Distortion are THD-F and THD-R. They both power systems, THD-F is by far the best measurement
                           are figures of merit used to quantify harmonic levels to use.
                           in voltage and current waveforms; however, each one
        Figure 3. Block of uses a different reference. THD-F is a comparison to THD-R
statistics computed from the fundamental and THD-R is a comparison to the Total Harmonic Distortion in reference to (R) RMS, is
            harmonic data signal’s RMS value. For power systems, the THD-F is the ratio, in percent, of the voltage/current harmonic
                                                                                     components relative to the absolute voltage/current
                                                                                     RMS. Because this is related to an RMS base, all
                                                                                     harmonic values must be calculated in RMS. Since
                                                                                     no harmonic, or the fundamental, can be larger than
                                                                                     the entire RMS value, the THD-R value can never be
                                                                                     greater than 100%. In cases of large distortion, the
                                                                                     value approaches 100%, and it is more difficult to
                                                                                     distinguish similar readings, compared to the THD-F
                                                                                     value (which can exceed 100%).
                                                                                  THD is further classified on the report as odd, even,
                                                                                  and triplen harmonics. Even harmonics are simply
                                                                                  the even number harmonics; harmonics 2, 4, 6, etc.
                                                                                  Odd harmonics are the odd numbers, not including
                                                                                  the 1st harmonic (the fundamental). Most loads create
                                                                                  more odd harmonics than even harmonics. Triplen
                                                                                  harmonics are odd multiples of the third harmonic.
                                                                                  Even Harmonics
                                                                                  While inspecting a sinusoidal wave, if both the upper
                                                                                  half and the lower half of the wave are symmetrical,
                                                                                  then no even harmonics are present. An asymmetrical
                                                                                  wave indicates the presence of even harmonics. Even
                                                                                  harmonics are an indicator of an unusual load in the
                                                                                  system. Even Total Harmonic Distortion should be
                                                                                  close to zero in a normal system. If the THD of even
                                                                                  harmonics is a significant part of the total, further
                                                                                  investigation is warranted.
                                                                                  Odd Harmonics
                                                                                  Odd harmonics make up most harmonic currents found
                                                                                  in distribution systems. Of particular interest are the
                                                                                  5th and 11th harmonics. The 5th and 11th harmonic
                                                                                  have a negative sequence, and when applied to some
  Tools you need. People you trust. 081313 WP131        Power Monitors, Inc. • Call Us: 800.296.4120 • www.powermonitors.com
White Paper:
Understanding the Harmonic Analysis Report
three-phase motors, they will try to run the motor    audible range and are based on the response of the         Figure 4. Harmonic
backwards. A major source of the 5th, 7th, and 11th   human ear. The higher the factor the more interference     magnitudes are broken
harmonics is 6-Pulse variable frequency drives (see   is being generated. Other forms of communication,          down by frequency in the
the PMI white paper: Monitoring Variable Frequency    besides telephones, are also affected.                     Magnitude section of the
Drives for more information).                                                                                    report.
                                                      K Factor
Triplen Harmonics                                     K Factor is a measurement of current harmonic
Triplens are especially detrimental to grounded-wye   distortion used in rating transformers. It’s used in
systems with current flowing through the neutral.     calculating the value necessary to de-rate a transformer
Normally balanced wye current cancels out in the      for harmonics. Harmonic current flow in a transformer
neutral, but triplen harmonics add together in the    causes increased heating (due to various losses in the
neutral instead of cancelling. This can overload      core). Some of these losses increase linearly or even
the neutral and cause excessive heating. Devices      more than linearly with the harmonic number.
sometimes malfunction because the line-to-neutral
voltage is badly misshapen by the triplen harmonic    Magnitude
voltage drop in the neutral conductor.                In the magnitude section of the report, harmonic
                                                      magnitudes present in the cycle are broken down
Telephone Interference Factor (TIF)                   by frequency as shown in Figure 4. Amounts are
TIF is a measure of the potential telephone noise     represented in real units, i.e. voltage magnitude is
caused by the harmonic distortions from a power systemrepresented in volts present in each channel, while
on nearby telephone equipment. It is a dimensionless  current is represented as amps. The frequency and
quantity that depends upon a weighting factor derived harmonic number are both shown.
from 1960 weighting curve by the Edison Electric
Institute. This weighting factor is weighted heavier In addition, the real power at each harmonic is shown,
on frequencies that tend to cause interference in the computed by taking the product of harmonic voltage
        Tools you need. People you trust.   081313 WP131     Power Monitors, Inc. • Call Us: 800.296.4120 • www.powermonitors.com
White Paper:
Understanding the Harmonic Analysis Report
and current, and the cosine of the phase angle to record as stripcharts. The waveform-based method Figure 5. Phase angles
between them.                                           has the advantage of showing all harmonics, and with for each voltage, current,
                                                        much less memory cost. It’s also useful for harmonic and power harmonic
Phase                                                   analysis of an existing recording, where no harmonics
Phase measures the offset between each phase of were explicitly enabled. For a detailed explanation of
power, in degrees. The phase angle for each voltage, the strategies for using waveform capture for harmonic
current, and power are shown after the magnitudes analysis in ProVision, see the white paper Harmonics
(Figure 5). The channel 1 voltage fundamental is used From Periodic Waveform Capture.
for the phase angle reference for all harmonics and
voltage and current channels. The power phase angle Conclusion
is the phase difference between current and voltage at The Harmonic Analysis Report is a powerful tool
that frequency.                                         featured in PMI ProVision. It features a plethora of
                                                        detailed data, presented in an easy to read format.
Harmonic Report vs. Stripchart                          In addition, the data can be exported to CSV and a
ProVision also features harmonic stripcharts, which number of other formats.
allow for long-term study of harmonics. An important
difference between a harmonic stripchart and a Ben Bowman
harmonic report is that a harmonic report only shows Web Software Developer
harmonics for a one-cycle period. A harmonic stripchart bbowman@powermonitors.com
may be more suited for a long-term trend study of www.powermonitors.com
harmonics present in a system, but requires more 800.296.4120
recorder memory, and selection of specific harmonics
   Tools you need. People you trust. 081313 WP131        Power Monitors, Inc. • Call Us: 800.296.4120 • www.powermonitors.com