LOAD ROUTING CONNECTOR
"CONDUIT OR
APPLICATION LENGTH
CABLE No." KW VOLTS FROM VIA TO DETAILS "CATALOG No." REMARKS
(m)
PF-100-FA1,2,3,4,5,6 CONTROL BOARD #1 910 480 VAC GENERATOR # 1 TRAY,TRENCH SYNC PANEL #1 6C 350 kCM XLPE 1000V,SUPERFLEX 18 -
PF-100-FB1,2,3,4,5,6 CONTROL BOARD #1 910 480 VAC GENERATOR # 1 TRAY,TRENCH SYNC PANEL #1 6C 350 kCM XLPE 1000V,SUPERFLEX 18 -
PF-100-FC1,2,3,4,5,6 CONTROL BOARD #1 910 480 VAC GENERATOR # 1 TRAY,TRENCH SYNC PANEL #1 6C 350 kCM XLPE 1000V,SUPERFLEX 18 -
PF-200-FA1,2,3,4,5,6 CONTROL BOARD #2 910 480 VAC GENERATOR # 2 TRAY,TRENCH SYNC PANEL #2 6C 350 kCM XLPE 1000V,SUPERFLEX 21 -
PF-200-FB1,2,3,4,5,6 CONTROL BOARD #2 910 480 VAC GENERATOR # 2 TRAY,TRENCH SYNC PANEL #2 6C 350 kCM XLPE 1000V,SUPERFLEX 21 -
PF-200-FC1,2,3,4,5,6 CONTROL BOARD #2 910 480 VAC GENERATOR # 2 TRAY,TRENCH SYNC PANEL #2 6C 350 kCM XLPE 1000V,SUPERFLEX 21 -
PF-300-FA1,2,3 CONTROL BOARD #3 350 480 VAC GENERATOR # 3 TRAY,TRENCH SYNC PANEL #3 3C 350 kCM XLPE 1000V,SUPERFLEX 26 -
PF-300-FB1,2,3 CONTROL BOARD #3 350 480 VAC GENERATOR # 3 TRAY,TRENCH SYNC PANEL #3 3C 350 kCM XLPE 1000V,SUPERFLEX 26 -
PF-300-FC1,2,3 CONTROL BOARD #3 350 480 VAC GENERATOR # 3 TRAY,TRENCH SYNC PANEL #3 3C 350 kCM XLPE 1000V,SUPERFLEX 26 -