ZP3 Operator Manual
Introduction
-
System in Alarm 01
Ev ent Action Panel Notes
LCD = Zone No, text and time
of ev ent
Status Display = Red Activ e
sounders, remote alarm &
Initiate f ire saf ety control O/P
Fire
strategy
Objectiv e’s = Ensure saf ety ,
f ind the source & silence/ reset
the sy stem
LCD = Point address, ty pe,
text, time of ev ent, zone No &
text
Status Display = No change
Fire - Find
Source Objectiv e = Locate dev ice &
identif y cause. MORE buttons
denote more f ires waiting to be
shown see page 4. Also
network sy stems will hav e
panel number detailed.
LCD = Enter control key code
****
Fire –
Silence Status Display = No change
Alarms
Objectiv e = Enter lev el 2
access code ty pically 2000
KEY PAD
LCD = **** changes to
2000 f ollowed by ; XXXX as user inputs the
access code.
Enter
Access
code Once access is granted the
sy stem operates a 2 min timer
f rom last button press bef ore it
logs the user out.
LCD = Zone No & text
Status Display = Activ e
Sounder extinguished and
Mute y ellow sounders silenced
Buzzer
Objectiv e = ensure the source
will not cause the sy stem to re-
trigger. This can be achiev ed
by disabling the point address
LCD = Sy stem return to
normal
Status Display = returns to
Reset normal
Objectiv e = record incident in
the log book
Disable a Point 02
Ev ent Action Panel Notes
LCD = Point address, ty pe,
text, time of ev ent, zone No &
text
Status Display = Red Activ e
False Alarm sounders, remote alarm &
control O/P
Objectiv e = Record the point
address e.g. 1001
Key Pad
LCD = Top menu page
View Menu Status Display = N/A
Selection
Objectiv e = Disable the point
address bef ore reset
Key Pad
LCD = Maintenance Menu
Enter On the key pad press
the number: Status Display = No change
Maintenance
Menu
Objectiv e = Disable the point
address bef ore reset
2
Key Pad
On the key pad press LCD = Maintenance Menu
the number:
Enter edit
disable Status Display = No change
menu
1 Objectiv e = Disable the point
address bef ore reset
Key Pad
On the key pad enter
the point address e.g.:
LCD = Maintenance Menu
Specif y
point to be
1001 Status Display = No change
disabled (then)
Objectiv e = Disable the point
address bef ore reset
Key Pad LCD = Sy stem return to
normal
On the key pad press
the number Status Display = returns to
normal
Specif y the
point to be
1 (then) Objectiv e = Sav e data by
pressing the f ollowing on the
disabled key pad & record in log book:
Silencing the Fault Buzzer 03
Ev ent Action Panel Notes
LCD = Zone No, text and time
of ev ent
Inv estigate the nature Status Display = Y ellow
Sy stem
of the f ault Faulty Zone & point
Fault
Objectiv e’s = Record Fault in
log book & action repair
LCD = Point address, ty pe,
text, time of ev ent, zone No &
text
Find source Status Display = No change
Objectiv e = Locate dev ice &
identif y any obv ious cause e.g.
dev ice remov ed or water leak
LCD = N/A
Status Display = No change
Silence
buzzer Objectiv e = Ensure the f ault is
attended to & leav e the f ault on
screen i.e. do not reset or
disable f ault
Setting the Clock 04
Ev ent Action Panel Notes
Key Pad
LCD = Top menu page
View Menu Status Display = N/A
Selection
Objectiv e = Set the time, day
and date
Key Pad
LCD = Operator Menu
Enter On the key pad press
Operator the number:
Status Display = No change
Menu
Objectiv e = No Change
1
Key Pad
On the key pad press Set the date by entering
Enter date the number: dd/mm/y yyy and then adjust
menu the day by using the arrow
up/down
Key Pad
Set the time by entering
Enter time hh:mm f ollowed by enter
Key Pad
Return to
Note new time, date & day
home page
Other Panel Controls 05
Ev ent Action Panel Notes
Illuminate when more
inf ormation is waiting to be
shown. Press either button to
More v iew the next ev ent. The
button ev ents will scroll around with
each push of the
corresponding more button.
Used to enable prev iously
disabled sounders quickly to
f acilitate an ev acuation during
routine maintenance. If
pressed with access code
Restore when the sy stem is in f ire the
disabled alarms will activ ate.
alarm
Other outputs such as
lif ts/Gas/HVAC and Fire
Brigade will not hav e
activ ated
Ev ents are prioritised with
Viewing any f ire ev ent hav ing the
dif f erent highest priority . Howev er, to
ev ent ty pes v iew any ty pe of ev ent press
i.e. Fire, the corresponding button to
Fault, v iew zonal inf ormation
Disabled f ollowed by v iew points f or
f urther inf ormation.
When this is in the “of f ”
Controls position the controls detailed
On/Of f Turn to the of f position will be isolated to prev ent un-
switch
authorised operation.