0% found this document useful (0 votes)
227 views5 pages

Stack Height Cal

This document contains calculations to determine the appropriate stack height for a plastic manufacturing facility. It calculates pollution indexes, discharge velocities, momentum factors, and building dimensions to determine that a final stack height of 16.5 meters is required for a clean gas exhaust from a thermal oxidizer unit based on a desired discharge velocity of 15 m/s. Revision A provides the initial calculations and design.

Uploaded by

Anonymous msVFza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views5 pages

Stack Height Cal

This document contains calculations to determine the appropriate stack height for a plastic manufacturing facility. It calculates pollution indexes, discharge velocities, momentum factors, and building dimensions to determine that a final stack height of 16.5 meters is required for a clean gas exhaust from a thermal oxidizer unit based on a desired discharge velocity of 15 m/s. Revision A provides the initial calculations and design.

Uploaded by

Anonymous msVFza
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Design / Calculation Sheet

Customer: Plastic-Omnium Proposal / Project No. ES03-2101892


Site: Warrington Created By: JIS Date:25.02.15
Project: Bumper Paintshop Checked By: Date:

Title: Stack Height Calculation

Revision History
Issue Description Name Date

A Initial Issue JIS 25.02.15


PlasticOmnium-Gliwice STACK DATA
Desired Stack Velocity Resulting C.S.A of Stack Diameter of Stack Diameter of
ES03-2101892 (m/s) (m2) (m) Stack (mm)
Item Description Flowrate Operating Flowrate Flowrate 20m/s 15m/s 20m/s 15m/s 20m/s 15/m/s
(Nm3/hr) Temperature (Am3/hr) (Am3/s)
(°C)
1 RTO 3050 - Clean Gas 15 000 100 20 495 5.7 20 15 0.28 0.38 0.60 0.70 700
PlasticOmnium-Gliwice STACK DATA
EVG Fan Size Diameter of Stack
ES03-2101892 (mm)
Item Description Motor Operating Flowrate Pressure from DSOC Efflux Stack height
(KW) Temperature (Am3/hr) (Pa) Velocity above local
(°C) (m/s) building truss
(m)

1 RTO 3050 - Clean Gas 37.0 100 20 495 6 000 700 14.8 3.00
D1 Ref. RTO 3050 - Clean Gas
1.1 Basic data
Discharge volume 20 495 Nm3/hr
Efflux velocity 14.79 m/s
Stack diameter 0.7 m
Efflux temperature 100 degC
Assumed ambient temp 10 degC

1.2 Calculating the Pollution Index STEL Notes


Solvent Content of Paint (subject to confirmation by paint supplyer) % weight mg/m3 STEL data otained from EH40/2005 Workplace exposure limits
Xylene 20% 441
Toluene 20% 384
Heptan-2-One 10% 475
Butyl Acetate 10% 966
MEK 20% 899
Ethanol 20% 1920
100%
Solids Bc Assumption:
Paint Solids 22% Highly developed large
urban area

Total VOC Discharge Rate - g/s 0.110

STEL Gd Bc D Pi
Solvents mg/m3 mg/m3 mg/m3 g/s m3/s
Xylene 966 24.15 0 0.022 0.91
Toluene 384 9.60 0 0.022 2.29
Heptan-2-One 475 11.88 0 0.011 0.93
Butyl Acetate 966 24.15 0 0.011 0.46
MEK 899 22.48 0 0.022 0.98
Ethanol 1920 48.00 0 0.022 0.46
Total 0.110 6.02
Particulates
Particulates not considered for thermal oxidiser exhaust 0 0 0 0.000 0.00

Total 0 0 0 0.000 0.00


Selected Value 6.02
1.3 Calculating the Discharge Height

1.3.1 Calculating U b
V Volume rate of discharge (per stack) m3/s 5.69
Td Temperature of discharge gases K 374
Q Heat Release MW 0.478

a Equation Factor -1.049


b Equation Factor 0.488
Ub Uncorrected Discharge Height m 0.215
Ub Minimum Uncorrected Discharge Height m 1.695
Value for Calculations m 1.695
5.3 Calculating U m
ρd Air Density at discharge conditions kg/m3 0.944
ρa Air Density at ambient conditions kg/m3 1.248
V Volume rate of discharge (per stack) m3/s 5.69
w Stack discharge velocity m/s 14.79
M Discharge Momentum m4/s2 64
logM (logM)2 (logM)3
1.804 3.255494 5.873884
x Equation Factor -1.999
y Equation Factor 4.774
z Equation Factor -8.887
logUm Cannot be Calculated
Um Uncorrected Discharge Height Cannot be Calculated
Um Minimum Uncorrected Discharge Height m 3.10
Value for Calculations m 3.10
5.4 Calculating C - Final Stack Height
U Uncorrected Discharge Height m 1.69
A Stack Height Ratio 1.83
Main Building
H Building Height m 13.5
B Building Width m 150
K Lesser of Building Height or Width m 13.5
T Height of Disturbed Flow m 33.75
U/H 0.126
C Calculated Final Stack Discharge Height m 15.92
C Selected Final Stack Discharge Height m 16.50

Adjoining Buildings
5 x Um m 15.49