This document contains a panel board schedule with details of the mains, circuit breakers, wire sizes, enclosures and connected loads for different circuits. It lists 26 circuits with information like circuit number, breaker rating, wire size, room or area served and connected lighting, fan, FCU loads. It also notes requirements like MCCBs, TVSS, ELCBs etc.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
219 views4 pages

Phae Balance Edb-S2b1

This document contains a panel board schedule with details of the mains, circuit breakers, wire sizes, enclosures and connected loads for different circuits. It lists 26 circuits with information like circuit number, breaker rating, wire size, room or area served and connected lighting, fan, FCU loads. It also notes requirements like MCCBs, TVSS, ELCBs etc.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

HORIZON FOR TRADING DB / PANEL BOARD SCHEDULE

AND CONTRACTING According to IEC & Master Spec


NOTE:

PANEL NO. : EDB-S2B1 LOCATION : Notes: 1,4 1-MCCB's required 6-TVSS required 11-ELCB,100 mA required

Mains Rating Duty Enclosure Dimensions 2-Isolated Earth Bus 7-Cotactor and PB 12-ELCB,30 mA required

Fed From : Main C.B. : 40 A 380 / 220 V SURFACE W mm 3-200%neutral 8-Photocell and timer 13-Split Bus with Shunt trip
size
Cable No. : << TCL 4284 kw KA-symm. IP30 D mm 4-Indicating 9-Two-Section Panel 14-Metering
Lamps

Cable size : (4X35)mm2+1x16mmÉ2 Max.Dem.: 4284 kw KA-peak. FORM 2 H mm 5-BMS 10-…………………. 15-……………….

N SER NO. CCT C.B WIRE ECC CONNECTED LOAD - No, Of points per circuit

O 1P-C.B.'S REF SIZE SIZE NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

T OR # ROOM / AREA / SUB PANEL / LOAD DISCRIP. LIGHTING FAN FCU SPU H.D EWH 1 PH SOCKET
E TYPE LTA EXIT LTB O L1 L2 L3 L4 L5 l14 l19 S.S DU.S P.S

WAYS NO. A MM2 MM2 unit load 72 8 72 50 24 11.5 14.1 6.5 9.3 9.3 18.6 250 500 1500 1.5

3 R1 16 3 3 LIGHTING 2
5 2 Y1 16 3 3 SPARE
1 B1 16 3 3 LIGHTING 6
4 R2 16 3 3 LIGHTING 11
5 5 Y2 16 3 3 LIGHTING 3
6 B2 16 3 3 LIGHTING 4
5 7 R3 16 3 3 LIGHTING 2
5 8 Y3 16 3 3 SPARE
9 B3 16 3 3 LIGHTING 5
5 10 R4 16 3 3 LIGHTING 42
11 Y4 16 3 3 LIGHTING 12
5 12 B4 16 3 3 LIGHTING 3
13 R5 16 3 3 LIGHTING 2
14 Y5 16 3 3 LIGHTING 58 2
15 B5 16 3 3 LIGHTING 46
16 R6 16 3 3 LIGHTING 28
17 Y6 16 3 3 LIGHTING 12
5 18 B6 16 3 3 LIGHTING 38
19 R7 16 3 3 LIGHTING 72
5 20 Y7 16 3 3 SPARE 0
21 B7 16 3 3 LIGHTING 10 2
5 22 R8 16 3 3 SPARE
5 23 Y8 16 3 3 SPARE
24 B8 16 3 3 LIGHTING 7
5 25 R9 16 3 3 SPARE
5 26 SPARE

1/4
HORIZON FOR TRADING DB / PANEL BOARD SCHEDULE
AND CONTRACTING According to IEC & Master Spec
NOTE:

PANEL NO. : EDB-S2B1 LOCATION : Notes: 1,4 1-MCCB's required 6-TVSS required 11-ELCB,100 mA required

Mains Rating Duty Enclosure Dimensions 2-Isolated Earth Bus 7-Cotactor and PB 12-ELCB,30 mA required

Fed From : Main C.B. : 40 A 380 / 220 V SURFACE W mm 3-200%neutral 8-Photocell and timer 13-Split Bus with Shunt trip
size
Cable No. : << TCL 4284 kw KA-symm. IP30 D mm 4-Indicating 9-Two-Section Panel 14-Metering
Lamps

Cable size : (4X35)mm2+1x16mmÉ2 Max.Dem.: 4284 kw KA-peak. FORM 2 H mm 5-BMS 10-…………………. 15-……………….

N SER NO. CCT C.B WIRE ECC CONNECTED LOAD - No, Of points per circuit

O 1P-C.B.'S REF SIZE SIZE NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

T OR # ROOM / AREA / SUB PANEL / LOAD DISCRIP. LIGHTING FAN FCU SPU H.D EWH 1 PH SOCKET
E TYPE LTA EXIT LTB O L1 L2 L3 L4 L5 l14 l19 S.S DU.S P.S

WAYS NO. A MM2 MM2 unit load 72 8 72 50 24 11.5 14.1 6.5 9.3 9.3 18.6 250 500 1500 1.5

Dem. Factor ( DF ) Application 4104 80 0 100 0 1104 0 0 1767 93 37.2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

first 100 Kw next 200 Kw remaining SETTING CURRENT


Lighting 1 1 0.9 Ltg Power HVAV HEATING TOTAL I design= 8.15
Power 0.8 0.7 0.6 TCL ( KW ) 4284 0 0 0 4284 I thermal= 8.96
Heating 1 1 0.8 ------>> MD ( KW ) 4284 0 0 0 4284 I magnetic= 40.73
A/C 1 0.9 0.8 Result. Dem. Factor 1 1.0 I ground fault=

2/4
NEL BOARD SCHEDULE Proj.NO.1234/1

ding to IEC & Master Spec rev.0

11-ELCB,100 mA required

12-ELCB,30 mA required

13-Split Bus with Shunt trip


14-Metering

15-……………….

CONNECTED LOAD - No, Of points per circuit CONNECTED LOAD

PRE - PHASE

R S T

KVA KVA KVA

144 144
0 0
432 432
792 792
24 24
288 288
100 100
0 0
360 360
390.6 390.6
864 864
216 216
144 144
685.6 685.6
427.8 427.8
260.4 260.4
864 864
437 437
669.6 669.6
0 0
130.2 130.2
0 0
0 0
56 56
0 0
0 0

3/4
NEL BOARD SCHEDULE Proj.NO.1234/1

ding to IEC & Master Spec rev.0

11-ELCB,100 mA required

12-ELCB,30 mA required

13-Split Bus with Shunt trip


14-Metering

15-……………….

CONNECTED LOAD - No, Of points per circuit CONNECTED LOAD

PRE - PHASE

R S T

KVA KVA KVA

7285.2 2500.6 2437.6 2347

0 7285.2

#VALUE! Kilo - Watts


Total

UN BALANCE RATIO
6%

4/4