cx1020 Hwen
cx1020 Hwen
CX1020-0xxx
CX1020-Nxxx
CX1030-0xxx
CX1030-Nxxx
version: 2.2
date: 2012-11-07
                                            Table of contents
Table of contents
    1. Foreword
         Notes on the documentation               4
         Safety instructions                      5
         Documentation issue status               7
    2. Product overview                          8
         Appropriate use                          8
         System overview                          9
         Basic modules                          12
              Technical data CX1020             12
              Technical data CX1030             13
              Configurations CX1020             15
              Configurations CX1030             16
              Connections                       17
              Battery compartment               20
              Compact Flash slot                21
              Compact Flash card                22
              Fan cartridge                     23
              Memory overview                   25
              PC 104 Bus                        26
         System interfaces                      28
              Technical data                    28
              Connections CX1020-N010           31
              Connections CX1020-N020           33
              Connections CX1020-N030/40        39
              Connections CX1020-N031/41        40
              Connections CX1020-N060           43
         Power supply units                     45
              Overview power supply units       45
              Technical data CX1100-0001        46
              Technical data CX1100-0002        47
              Technical data CX1100-0012        48
              Technical data CX1100-0003        49
              Technical data CX1100-0013        50
              Technical data CX1100-0004        51
              Technical data CX1100-0014        52
              Connections CX1100-0001           53
              Connections CX1100-00x2           54
              Connections CX1100-00x3           55
              Connections CX1100-00x4           56
              LCD display                       57
Embedded PC                                                1
Table of contents
      3. Transport                                                58
            Unpacking, installation and transport                 58
      4. Assembly and connecting                                  59
            Mechanical assembly                                   59
                    Dimensions                                    59
                    Mechanical assembly of basic module           67
                    Mechanical assembly of fieldbus connectors    72
                    Ground connection                             74
            Start-up procedure                                    75
                    Switching on / off                            75
            BIOS Setup                                            76
                    Standard CMOS Features                        78
                         IDE Primary Master                        80
                         IDE Primary Slave                         82
                    Advanced BIOS Features                        84
                         CPU Feature                               87
                    Advanced Chipset Features                     88
                    Integrated Peripherals                        90
                         OnChip IDE Device                         91
                         Onboard Device                            92
                         SuperIO Device                            93
                    Power Management Setup                        94
                    PnP / PCI Configuration                       96
                         IRQ Resources                             97
                         Memory Resources                          98
                    PC Health Status                              99
                    Frequency / Voltage Control                  101
2                                                                Embedded PC
                               Table of contents
         Certifications           120
         Approvals                120
         Support and service      121
Embedded PC                                   3
Foreword
1. Foreword
Liability Conditions
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for
safety, including all the relevant laws, regulations, guidelines and standards.
The documentation has been prepared with care. The products described are, however, constantly under
development. For that reason the documentation is not in every case checked for consistency with performance data,
standards or other characteristics. None of the statements of this manual represents a guarantee (Garantie) in the
meaning of § 443 BGB of the German Civil Code or a statement about the contractually expected fitness for a
particular purpose in the meaning of § 434 par. 1 sentence 1 BGB. In the event that it contains technical or editorial
errors, we retain the right to make alterations at any time and without warning. No claims for the modification of
products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this
documentation.
© This documentation is copyrighted. Any reproduction or third party use of this publication, whether in whole or in
part, without the written permission of Beckhoff Automation GmbH, is forbidden.
4                                                                                                        Embedded PC
                                                                                                            Foreword
Safety Instructions
Safety Rules
The responsible staff must ensure that the application or use of the products described satisfy all the requirements for
safety, including all the relevant laws, regulations, guidelines and standards.
State at Delivery
All the components are supplied in particular hardware and software configurations appropriate for the application.
Modifications to hardware or software configurations other than those described in the documentation are not
permitted, and nullify the liability of Beckhoff Automation GmbH.
Personnel Qualification
This description is only intended for the use of trained specialists in control and automation engineering who are
familiar with the applicable national standards.
Danger
             This symbol is intended to highlight risks for the life or health of personnel.
Warning
             This symbol is intended to highlight risks for equipment, materials or the environment.
Note
             This symbol indicates information that contributes to better understanding.
Embedded PC                                                                                                            5
Foreword
controllers of such machines will apply, and must be observed by the operator. These regulations cover, amongst
other things, the intervals between inspections of the controller. The operator must initiate such inspections in good
time.
Operator requirements
Read the operating instructions
All users of the product must have read the operating instructions for the system they work with.
System know-how
All users must be familiar with all accessible functions of the product.
6                                                                                                      Embedded PC
                                                                                     Foreword
Version   Changes
2.2       changes in PC104 description
2.1       annotations to battery recycling added
2.0       installation position for active and passive cooling inserted
1.9.1     installation positions are inserted as stand alone chapter
1.9       system interfaces CX1200-xxxx removed
1.8       names changed for CX10x0-N070 and CX10x0-N80
1.7       note for CX1030, CX10x0-N070 and CX10x0-N80 added
1.6       cable length for DVI cable corrected, notes on temperature sensors added
1.5       cable length for ethernet cable in use of CX1020-N060 added
1.4       changes in new BIOS added
1.3       consumption value for CX1020-A001 added
1.2       notes for ground connection added
1.1       LED blink codes for power supply CX1100-0004 (EtherCAT) extended
1.0.0     notes for use of fieldbus connector added
0.1.0     installation guide for system interface CX1020-N60 and licenses added
0.0.6     LED - diagnostics for CX1020-N060 added
0.0.5     memorymapping (Busmaster, DPRAM I/O)
0.0.4     system interface CX1020-N060 and notes to network interfaces added
0.0.3     basic version
0.0.2     revised Version
0.0.1     preliminarily version
Embedded PC                                                                                 7
Product overview
2. Product overview
Appropriate Use
The CX1020 device series is a modular control system designed for top-hat rail installation. The system is scalable,
so that the required modules can be assembled and installed in the control cabinet or terminal box as required.
Danger
                    Do not exchange any parts when under power!
When components are being fitted or removed, the supply voltage must be switched off.
Software knowledge
Warning
                             Mandatory software knowledge!
Every user must be familiar with any of the functions of the software installed on the PC that he can reach.
8                                                                                                        Embedded PC
                                                                                                  Product overview
System overview
The system
With the CX series of Embedded PCs Beckhoff has combined PC technology and modular I/O level to form a top-hat
rail unit in the control cabinet. The CX1020 extends the CX product family by a version with higher CPU performance.
The CX1020 enables direct connection of Bus Terminals and EtherCAT terminals.
While the CX1000 features an 266 MHz AMD Geode processor, the CX1020 is equipped with a 1 GHz Intel(r) CPU.
It is an energy-saving device that operates with ultra-low core voltage and features low thermal power dissipation of
only 7 W TDP (thermal design power). As a result, no fan is required despite the compact design of the CX1020
Embedded PC. Since Compact Flash is used as boot and memory medium, no rotating media are required in the
controller. This is an important aspect for increasing the MTBF (Mean Time Between Failures) of the overall system.
The case and assembly concept of the CX1020 is similar to that of its smaller brother, the CX1000:
It also consists of several components that can be assembled by the user. The simplest configuration consists of a
CPU module and a multi-functional power supply unit. The PC104 bus is used for the connection between these and
all other CX components, although in the CX1020 this was extended with EtherCAT signals. The basic CPU module
is equipped with two RJ-45 sockets and an integrated 3-port switch as standard. In practice, this often means that no
separate switch is required, since a line topology can be configured conveniently:
For example in building installations, where several room controls can be distributed across each floor, which
otherwise would have to be networked via a star topology.
Like the CX1000, the CX1020 can be expanded with optional system interfaces. A DVI-I (=DVI-D + VGA) output, two
USB-2.0 interfaces, up to four RS232 interfaces and audio are available. The four RS232 interfaces feature opto-
decoupling and can optionally be implemented as RS422/RS.
The same reusability also applies to the multi-functional power supplied units (CX1100-000x) of the CX1020: one
without I/O terminal connection, one with K-Bus connection, one with K-Bus and IP-Link connection for IP-67-
protected Fieldbus Box modules, and a power supply unit with direct connection facility for Beckhoff EtherCAT
Terminals.
Embedded PC                                                                                                             9
Product overview
characteristics - e.g. both support PROFIBUS DP-V2. In practice, this means that the PROFIBUS master can be
positioned exactly where it is required within a machine. It no longer has to be implemented as a plug-in card in the
IPC or a master controller in the control cabinet.
System interfaces
Further system interfaces for serial communication (2x RS 232 or RS422, RS485), 2 x USB 2.0 interfaces, video
output (DVI +) , CF card reader/writer or audio signals can be ordered separately.
Fieldbus interfaces
All CX1500 fieldbus modules and all CX1100 power supply units from the CX1000 series can be used in combination
with the CX1020.
The fieldbus interfaces are currently available as master and slave versions for the following fieldbuses:
Beckhoff Lightbus, Profibus DP, CANopen, DeviceNet or SERCOS interface (only master)
The master fieldbus connections enable a CX1020 system to use Beckhoff fieldbus components (such as Bus
Coupler, Bus Terminal Controller or Drive Technology) as local control components for complex systems.
Slave fieldbus connections enable the CX1020 system to be used as a subordinate distributed control system for
complex or modular systems.
Note:
Documentation describing the fieldbus connections is available separately.
10                                                                                                     Embedded PC
                                                                                                 Product overview
The software
In combination with the TwinCAT automation software, the CX1020 Industrial PC becomes a powerful IEC 61131-3
PLC with up to four user tasks. Additionally, Motion Control tasks can also be executed. Depending on the required
cycle time, several servo axes can be controlled. Even special functions such as flying saw, electronic gearbox and
cam plate can be realized.
The CX1020 system is programmed in the same way as other bus controllers:
Visualization
The Beckhoff OPC server is available for interfacing with SCADA packets, if the two operating system variants
“Windows CE.NET” or “Windows XP Embedded” are used. In other words, the CX1020 also offers straightforward
visualization and simultaneous control in real-time on a single system.
Embedded PC                                                                                                       11
Product overview
Basic modules
The basic configuration of the CX1020 includes a 64 MB Compact Flash card. Two Ethernet RJ 45 interfaces are
also part of the basic configuration. These interfaces are connected to an internal switch and offer a simple option for
creating a line topology without the need for additional Ethernet switches. All other CX family components can be
connected via the PC104 interface that is available on both sides.
The passive cooling module is included in the scope of supply. For power supply one of the system power supply
modules (CX1100-000x) is needed)
12                                                                                                      Embedded PC
                                                                                                    Product overview
The basic configuration of the CX1030 includes a 64 MB Compact Flash card. Two Ethernet RJ 45 interfaces are
also part of the basic configuration. These interfaces are connected to an internal switch and offer a simple option for
creating a line topology without the need for additional Ethernet switches. All other CX family components can be
connected via the PC104 interface that is available on both sides.
The active cooling module is included in the scope of supply. For power supply one of the system power supply
modules (CX1100-001x) is needed)
Embedded PC                                                                                                           13
Product overview
Note
            For operating this unit need a power supply of type CX1100-001x.
14                                                                             Embedded PC
                                                                                              Product overview
Configurations
The Basic CPU-Module can be ordered with different hardware and software variations. As operating systems there
are "Windows CE.NET" and "Windows XP Embedded" available. The TwinCAT automation software transforms a
CX1020 system into powerful PLC and Motion Control system that can be operated with or without visualisation.
The order identifier of the basic CPU module is derived as follows:
Note:
For detailed information about the software images see the CX10x0 Software Documentation.
Embedded PC                                                                                                   15
Product overview
Configurations
The Basic CPU-Module can be ordered with different hardware and software variations. As operating systems there
are "Windows CE.NET" and "Windows XP Embedded" available. The TwinCAT automation software transforms a
CX1030 system into powerful PLC and Motion Control system that can be operated with or without visualisation.
The order identifier of the basic CPU module is derived as follows:
Note:
For detailed information about the software images see the CX10x0 Software Documentation.
16                                                                                               Embedded PC
                                                                                                Product overview
Connections
The basic CPU module is available with different hardware and software options. It is supplied from the power supply
unit, so that only the connections are described here.
Embedded PC                                                                                                       17
Product overview
The CX1020 features two MAC blocks. The first one (MAC1) operates the network interfaces for the Ethernet ports.
The two outputs are connected via a switch. In this way a line structure can be configured as described below. From
an operating system perspective this represents a single connection. The second block (MAC2) operates the
extended PC104 bus. The second physical network connection can be utilised via additional system interfaces. This
requires either a CX1100-0004 power supply unit or a CX1020-N060 system interface. A connection to the E-bus for
EtherCAT terminals is realised via the power supply unit. The CX1020-N060 interface establishes the Ethernet
connection, thereby making a further network interface available.
Note
These interfaces are connected to an internal 3-port switch and offer a simple option for creating a line topology
without the need for additional Ethernet switches.
18                                                                                                     Embedded PC
                                                                                                 Product overview
PC 104 Bus
The PC 104 bus is a standardised bus with 104 ISA signals for compact embedded systems.
Embedded PC                                                                                                        19
Product overview
Battery compartment
The battery compartment is located on the left-hand side of the CPU module, between the two Ethernet ports.
It can be opened with the aid of a screwdriver (proceed carefully in order to avoid damage).
Danger
                  Replace Battery Part. No. CR2032 manufactured by Sanyo or Panasonic Only. Use of Another
                  Battery May Present A Risk Of Fire Or Explosion.
Note
                  The battery must be changed every 5 years.
Battery-recycling:
                  Used batteries must must be disposed of in accordance with national electronics scrap
                  regulations.
                  Used batteries may contain harmful substances or heavy metal that can harm the environment
                  and health. Batteries will be recycled. They contain important commodities as iron, zinc, nickel or
                  manganese.
                  The environment and Beckhoff thank for your understanding
20                                                                                                      Embedded PC
                                                                                                Product overview
Warning
             The Compact Flash slot is a memory interface, not an I/O type CF slot.
Embedded PC                                                                                                      21
Product overview
Compact-Flash card
The Compact Flash card (CF card) is a non-volatile memory medium.
Data to be retained in the event of a power failure should be saved on the CF card. The CF card operates similar to a
hard disk.
Warning
          It is recommended only use CF cards supplied by Beckhoff Automation GmbH.
          The CF cards are made for industrial use. They possess a higher number of read / write cycles and
          an enhance temperature range (up to + 85°C).
          A proper operation of the CX-System can only be guaranteed with the use of CF cards from
          Beckhoff Automation GmbH!
22                                                                                                   Embedded PC
                                                                                                     Product overview
Fan cartridge
On the lower side of the heat sink resides the fan cartridge. The fan is necessary to operate the unit in industrial
environment. Due to the continuous operation the fan needs replacement every 5 years.
3. Take the cartridge towards the front. The cartridge is now removed.
Embedded PC                                                                                                            23
Product overview
4. Open the packaging of the new fan cartridge and take out the new cartridge. Hold the cartridge in front of
the mounting notches.Take care that the notches fit the holes in the back of the housing.
Note
              The fan must be changed every 5 years.
24                                                                                             Embedded PC
                                                                                               Product overview
Note
          Two connection modules (master or slave) can be used simultaneously.
          If more than two connections are needed call Beckhoff Automation GmbH for further information.
Embedded PC                                                                                                  25
Product overview
PC 104 Bus
The PC 104 bus is a standardized bus with 104ISA signals for compact embedded systems.
For the functionality of the CX1020 modules eight further signals have been added (here marked with color).
Pin assignment of 16 Bit PC 104 Bus:
Pin
Number          Row A               Row B                           Row C4          Row D4
1               IOCHCHK*            GND                             GND             GND
2               SD7                 RESETDRV                        SBHE*           MEMCS16*
3               SD6                 +5V                             LA23            IOCS16*
4               SD5                 IRQ9                            LA22            IRQ10
5               SD4                 n.c. (+12V internal)            LA21            IRQ11
6               SD3                 DRQ2                            LA20            IRQ12
7               SD2                 n.c. (+5V internal)             LA19            IRQ13
8               SD1                 ENDXFR*                         LA18            IRQ14
9               SD0                 +12V                            LA17            DACK0*
10              IOCHRDY             (KEY)²                          MEMR*           DRQ0
11              AEN                 SMEMW*                          MEMW*           DACK5*
12              SA19                SMEMR*                          SD8             DRQ5
13              SA18                IOW*                            SD9             DACK6*
14              SA17                IOR*                            SD10            DRQ6
15              SA16                DACK3*                          SD11            DACK7*
16              SA15                DRQ3                            SD12            DRQ7
17              SA14                DACK1*                          SD13            +5V
18              SA13                DRQ1                            SD14            MASTER*
19              SA12                REFRESH*                        SD15            GND
20              SA11                SYSCLK                          (KEY)²          GND
21              SA10                IRQ7                            --              --
22              SA9                 IRQ6                            --              --
23              SA8                 IRQ5                            --              --
24              SA7                 IRQ4                            --              --
25              SA6                 IRQ3                            --              --
26              SA5                 DACK2*                          --              --
27              SA4                 TC                              --              --
28              SA3                 BALE                            --              --
29              SA2                 +5V                             --              --
30              SA1                 OSC                             --              --
31              SA0                 GND                             --              --
32              GND                 GND                             --              --
26                                                                                            Embedded PC
                                                                                                Product overview
Remarks:
1. B10 and C19 are key locations.
2. Signal timing and function are as specified in ISA specification.
3. Signal source/sink current differs from ISA values.
4. Negative voltages are not supported.
5. in the specification the pins are counted from 0 to 19
Note:
Further information to PC104 Bus can be found in the datasheet or under http://www.pc104.org.
Embedded PC                                                                                                  27
Product overview
System interfaces
Technical Data
Dimensions:
Like for the CX1000, a number of optional interface modules are available for the basic CX1020 CPU module that
can be installed ex works. The following interfaces are available:
28                                                                                                Embedded PC
                                                                                             Product overview
 CX1020-N060 Ethernet-interface
The CX1020-N010 option can be connected to Beckhoff Control Panels or standard monitors with DVI or VGA input
via the DVI or USB interfaces.Devices such as printer, scanner, mouse, keyboard, mass storage, CR-RW etc. can be
connected via the USB 2.0 interfaces. Multimedia capability is realized via the CX1020-N020 audio interface. The
modules CX1020-N030 and CX1020-N040 offer a total of four serial RS232 interfaces with a maximum transfer
speed of 115 kbaud. These four interfaces can be implemented in pairs as RS422/RS485, in which casethey are
identified as CX1020-N031 and CX1020-N041 respectively.The system interfaces cannot be retrofitted or expanded
in the field. They are supplied ex factory in the specified configuration and cannot be separated from the CPU
module. The system interfaces run through the internal PC104 bus, so that further CX components can
be connected. The power supply of the system interface modules is ensured via the internal PC104 bus.
Embedded PC                                                                                                  29
Product overview
                                                                    CX10x0-N030           CX10x0-N031
Technical data               CX10x0-N010         CX10x0-N020        CX10x0-N040           CX10x0-N041
Interfaces                   1 x DVI +           Line IN,           1 x COM1+2,           1 x COM1+2,
                             2 x USB 2.0         MIC IN,            RS232                 RS422/RS485
                             max. 100 mA         Line OUT           1 x COM3+4,           1 x COM3+4,RS422/RS485
                             per port                               RS232
Connection type              DVI-I 29-pin        3,5 mm socket      2 x D-Sub plug        2 x D-Sub plug 9-pin
                             socket + 2 USB      for jack plug      9-pin
                             Ports type A
Properties                   DVI-I interface     built-in PC-       max. baud rate        max. baud rate 115 kbaud,
                             also carries out    Beeper             115 kbaud,            can not be used
                             VGA signals         Line OUT output,   can not be used       simultaneously with
                             (DVI-A)             max. 200 mW,       simultaneously with   N030/N040
                                                 suitable for       N031/N041
                                                 earphones
Power supply                 via system bus (Through CX1100-000x power supply module)
Dimensions                   19 mm x 100 mm x 51 mm
Operating temperature        0 °C ... +55 °C
Storage temperature          -25 °C ... +85 °C
Relative humidity            95% no condensations
Vibration/Shock resistance   conforms to EN 60068-2-6 / EN 60068-2-27/29
EMC resistance burst / ESD   conforms to EN 61000-6-2/EN 61000-6-4
Protection class             IP 20
weight                       app. 80 g
30                                                                                               Embedded PC
                                                                                                   Product overview
CX1020-N001 connections
In addition to the two Ethernet interfaces, this module features a DVI-I and two USB interfaces.
DVI-I interface
The DVI-I interface transfers analog and digital data and is suitable for connection to analog graphics cards with 15
pin D-Sub connector and digital graphics cards with DVI-D output. The resolution at the screen or the Beckhoff
Control Panel depends on the distance (maximum 5 m).
The DVI interface uses VGA signals, so that the connection of CRT VGA monitors to the CX1000 system using a DVI
to VGA adapter is also possible.
This adapter is available as an accessory.
DVI-I socket:
Embedded PC                                                                                                         31
Product overview
Pin                    Assignment
C1                     Analog Red Video Out
C2                     Analog Green Video Out
C3                     Analog Blue Video Out
C4                     Analog Horizontal Sync
USB interface:
The USB socket is a type A socket. The USB interface complies to USB 2.0 specification
32                                                                                       Embedded PC
                                                                                                        Product overview
CX1020-N020 connections
This system interface provides the audio interface for the CX1020 system. Two inputs, "LINE IN" and "MIC IN", are
available. The "LINE OUT" connection is used as output for audio signals. It can also be used for connecting
headphones with a maximum output of 200 mW. It also features a PC beeper. The audio interfaces are accessed via
the operating system. "Windows XPe" offers an option for switching the audio module to surround mode.
The 3.5 mm sockets are designed for jack plugs.
The left channel is transferred via the tip of the jack plug, the right channel via the first ring. The remainder of the
sleeve is used for earthing.
Embedded PC                                                                                                                33
Product overview
The only existing channel is transferred via the tip, the remainder of the sleeve is used for earthing.
Pin assignment:
Signal                               Description
L                                    left channel, back
R                                    right channel, back
Ground                               Ground
Signal                               Description
C                                    centre channel
S                                    subwoofer channel
Ground                               Ground
Signal                               Description
L                                    left channel, front
R                                    right channel, front
Ground                               Ground
34                                                                                                        Embedded PC
                                                                                                 Product overview
The number of speakers is selected in the "Speaker Configuration" tab. The connection details are displayed on
the right-hand side of the window.
Embedded PC                                                                                                       35
Product overview
The colours of the connections shown match those on the CX1020-N020 module. Once a configuration has been set
it can be tested via the "Speaker Test" tab.
Clicking on a speaker causes a signal to be sent to the selected speaker. The user can thus check the positioning or
allocation of the individual speakers to the audio channels. Once all speakers have been set correctly, the surround
sound can be tested via "HRTF Demo".
36                                                                                                   Embedded PC
                                                                                                     Product overview
Sound:
        Buzzing Bee
Path:
 Horizontal
 Vertical
 Bathroom (filter)
 Arena (filter)
Embedded PC                                                                                                               37
Product overview
Parameters for controlling certain frequency bands can be set under "Equalizer". Standard settings for certain types
of music (e.g. rock, pop, bass, ...) are also available.
Noise suppression for the microphone input can be selected in the "Microphone" tab.
Although the "S/PDIF In" and "S/PIF Out" tabs are available in the driver, they are currently not supported.
38                                                                                                   Embedded PC
                                                                                                 Product overview
CX1020-N030/40 connections
The CX1020-N030 system interface features two RS232 interfaces, COM1 and COM2 (9 pin Sub-D plug connector).
If there is need for more than two serial interfaces two further RS232 interfaces, COM3 and COM4 (9 pin Sub-D plug
connector) can be added to the system via the system interface CX1020-N40. The maximum baud rate on all
channels is 115 kBit. The pin assignment for all interfaces is equal and described below. The interface parameter can
be set in the operating system or in the PLC program.
Note
          The system interface CX1020-N30 can only be used instead and not simultaneously with system
          interface CX1020-N031.
          The system interface CX1020-N40 can only be used instead and not simultaneously with system
          interface CX1020-N041.
Embedded PC                                                                                                       39
Product overview
CX1020-N031/41 connections
The CX1020-N031 system interface features two RS422 / RS 485 interfaces, COM1 and COM2 (9 pin Sub-D plug
connector). If there is need for more than two serial interfaces two further RS422 / RS485 interfaces, COM3 and
COM4 (9 pin Sub-D plug connector) can be added to the system via the system interface CX1020-N41. The
maximum baud rate on all channels is 115 kBit. The pin assignment for all interfaces is equal and described below.
The interface parameter can be set in the operating system or in the PLC program.
For RS 485 Pin 2 and 3 ( Data +) as well as Pin7 and 8 (Data -) have to be connected..
40                                                                                                    Embedded PC
                                                                                                 Product overview
The upper switch sets the parameters for the upper interface, the lower switch sets the parameter for the lower
interface. The system must be powered down, if the settings of the switches are changed! The settings for default
use should be mentioned by ordering the interface module.
Embedded PC                                                                                                         41
Product overview
Note
         The system interface CX1020-N31 can only be used instead and not at the same time with
         system interface CX1020-N030.
         The system interface CX1020-N41 can only be used instead and not at the same time with
         system interface CX1020-N040.
42                                                                                           Embedded PC
                                                                                                    Product overview
CX1020-N060 connections
The CX1020-N060 system interface provides a further network interface. It can only be used if the CX1100-0004
power supply unit is not connected, since in this case the only internal interface available is used for connecting the
Ethernet port. (Details see Basic module description.)
RJ 45 interface (socket):
Warning
            The CX1020-N060 system interface may only be mounted on the right, directly at the CPU
            module. The setup is shown in the following figures.
Embedded PC                                                                                                           43
Product overview
Warning
The connected network cable must not have a length of more than 15 meters!
Note
          The CX1020-N060 system interface can only be used in place of the CX1100-0004 power supply
          unit, not at the same time.
44                                                                                                    Embedded PC
                                                                                                  Product overview
A choice of four power supply modules is available for use with a CX10x0 system. The power supply of all other
system components is ensured via the internal PC104 bus; no separate supply lines are required. However, the
CX1100 components offer further important characteristics that go beyond a pure power supply: an integrated
NOVRAM enables the fail-safe storage of process data, an LCD display with two lines of 16 characters each is used
for displaying system and user messages. A 4 + 1 keypad enables user input without additional keyboard or input
panel. Local I/O signals are connected via the CX1100-0002 power supply variant, to which all Beckhoff Bus
Terminals can be connected, or via CX1100-0003, which in addition to the Bus Terminals enables the connection of
Extension Box IExxxx type Beckhoff Fieldbus Box modules. The option to connect Bus Terminals or a fieldbus Box
creates a control system with a very variable, expandable I/O level with large signal variety. The I/O data are stored
in a DPRAM, which is accessible by the CPU via the system bus. The power supply units of the CX system can be
changed in the field: If, for example, local I/O via Bus Terminals is required, CX1100-0001 can be replaced with
CX1100-0002 in the field. EtherCAT terminals can be connected via the CX1100-0004 power supply unit. The I/O
data are stored directly in the main memory of the CX1100-0004 CPU; a DPRAM is no longer required. The CX1100-
0004 power supply unit for EtherCAT terminals can not be connected in conjunction with the basic CX1000 CPU
module.
The technical data are provided with the individual power supply unit specifications:
 CX1100-0002 (K-Bus)
 CX1100-0012 (K-Bus for CX1030 and CX10x0 for alternative installation positions)
 CX1100-0013 (K-Bus, IP-Link for CX1030 and CX10x0 for alternative installation positions)
 CX1100-0004 (E-Bus)
        CX1100-0014 (E-Bus for CX1030 and CX10x0 for alternative installation positions)
An overview of the power supply architecture and a detailed description of the general system components such as
GCB, ACB, NOVRAM, display and keypad can be found in the documentation for the power supply units.
Embedded PC                                                                                                        45
Product overview
Dimensions:
One of power supply modules can be selected for a CX10x0 system. The power supply of all other system
components is ensured via the internal PC104 bus; no separate supply lines are required. However, the CX1100
components offer further important characteristics that go beyond a pure power supply: an integrated NOVRAM
enables the fail-safe storage of process data, an LCD display with two lines of 16 characters each is used for
displaying system and user messages.The power supply CX1100-N001 has no I/O interfaces.
46                                                                                                 Embedded PC
                                                                                         Product overview
Dimensions:
Embedded PC                                                                                             47
Product overview
Dimensions:
48                                                                                            Embedded PC
                                                                                         Product overview
Dimensions:
Embedded PC                                                                                             49
Product overview
Dimensions:
50                                                                                            Embedded PC
                                                                                             Product overview
Dimensions:
With the CX1100-0004 power supply EtherCAT Terminals can be connected to the CX10x0-System. With CX1100-
0004 the I/O data are stored directly in the main memory of the CPU; a DPRAM is no longer required. The CX1100-
0004 power supply unit for EtherCAT Terminals can not be connected in conjunction with the basic CX1000 CPU
module.
Embedded PC                                                                                                   51
Product overview
Dimensions:
52                                                                                               Embedded PC
                                                                                               Product overview
CX1100-0001 connections
This power supply unit does not have an I/O interface. The power supply is therefore connected through the 5-pin
open pluggable connector. The power supply unit supplies all further system components with a voltage of 24 V DC (-
15 %/+20%) via the PC104 bus. The dielectric strength of the power supply unit is 500 Vrms.
The integrated NOVRAM permits storage of process data that is safe against power failure.
LED:
With proper connection of the power supply unit and with power supply turned on, the power LED (PWR) lights up
green. In the case of a short-circuit, it lights up red.
Embedded PC                                                                                                      53
Product overview
CX1100-00x2 connections
This power supply unit is equipped with an I/O interface, which permits connection of the Beckhoff Bus Terminals.
The power is supplied via the upper spring-loaded terminals labelled “24V” and “0V”.
The supply voltage feeds the CX system and supplies a voltage of 24 V DC (-15 %/+20%) to the Bus Terminals via
the K-Bus. The dielectric strength of the power supply unit is 500 Vrms. Since the K-Bus does no more than pass data
on, a further power supply is necessary for the Bus Terminals. This is provided by means of the power contacts,
which are not connected to the power supply.
The integrated NOVRAM permits storage of process data that is safe against power failure.
LED:
With proper connection of the power supply unit and with power supply turned on, the power LED (PWR) lights up
green. In the case of a short-circuit, it lights up red.
The I/O LEDs display the operation status of the Bus Terminals. Error-free start-up of the configuration is signalled by
the red "I/O ERR" LED being extinguished. If the ”I/O ERR" LED blinks, an error in the area of the terminals is
indicated. The error code can be determined from the frequency and number of blinks.
PE power contacts
The ”PE" power contact must not be used for other potentials.
54                                                                                                     Embedded PC
                                                                                                    Product overview
CX1100-00x3 connections
This power supply unit permits not only the connection of the Beckhoff Bus Terminals, but also the serial connection
of the Beckhoff fieldbus box modules of the type extension box IExxxx. The power is supplied via the upper spring-
loaded terminals labeled “24V” and “0V”.
The supply voltage feeds the CX system and, over the K-Bus, the Bus Terminals. Since the K-Bus does no more
than pass data on, a further power supply is necessary for the Bus Terminals. This is provided by means of the
power contacts, which are not connected to the power supply.
Fieldbus connection:
Plug the IP link connector into the respective connections, i.e. one fibre-optic cable each into IN (x03) and OUT (x04).
You then connect the other end with the corresponding IP link interface of the extension box. The connection must be
made so that the output of the fieldbus connection is connected to the input of the extension box and vice versa.
LED:
With proper connection of the power supply unit and with power supply turned on, the power LED (PWR) lights up
green. In the case of a short-circuit, it lights up red. The I/O LEDs display the operation status of the Bus Terminals.
Error-free start-up of the configuration is signaled by the red "I/O ERR" LED being extinguished. If the ”I/O ERR" LED
blinks, an error in the area of the terminals is indicated. The error code can be determined from the frequency and
number of blinks.
PE power contacts
The ”PE" power contact must not be used for other potentials.
Embedded PC                                                                                                          55
Product overview
CX1100-00x4 connections
This power supply unit is equipped with an I/O interface, which permits connection of the Beckhoff Bus Terminals.
The power is supplied via the upper spring-loaded terminals labeled “24V” and “0V”.
The supply voltage feeds the CX system and supplies a voltage of 24 V DC (-15 %/+20%) to the Bus Terminals via
the E-Bus. The dielectric strength of the power supply unit is 500 Vrms. Since the E-Bus does no more than pass data
on, a further power supply is necessary for the Bus Terminals. This is provided by means of the power contacts,
which are not connected to the power supply.
The integrated NOVRAM permits storage of process data that is safe against power failure.
LED:
With proper connection of the power supply unit and with power supply turned on, the power LED (PWR) lights up
green. In the case of a short-circuit, it lights up red.
PE power contacts
The ”PE" power contact must not be used for other potentials.
Note
          This power supply is designed for use with CX1020 systems only. Operation with CX1000 systems
          is not possible because the EtherCAT protocol is not implemented / designed in the hardware of
          the CX1000 systems.
Note
          The power supply CX1100-0004 can only be used instead and not simultaneously with system
          interface CX1020-N060
Warning
            It is important to keep attention to the hardware revision of the power supply. Power supplies with
           a hardware revision > 2.0 only work with CX1020 systems with a hardware revision > 2.1 !
56                                                                                                    Embedded PC
                                                                                                  Product overview
LC Display
The LC Display of the power supply units has two rows of 16 characters each and is used for displaying system and
user messages.
Embedded PC                                                                                                     57
Transport
3. Transport
Unpacking, installation and transport
The specified storage conditions must be adhered to (see "Technical data").
Unpacking
Proceed as follows to unpack the unit:
1. Remove packaging.
2. Do not discard the original packaging. Keep it for future relocation.
3. Check the delivery for completeness by comparing it with your order.
4. Please keep the associated paperwork. It contains important information for handling the unit.
5. Check the contents for visible shipping damage.
6. If you notice any shipping damage or inconsistencies between the contents and your order, you should notify
Beckhoff Service.
              Avoid condensation on and inside the unit, If the unit is transported in cold conditions or if the unit is
              subjected to extreme fluctuation of temperature.
              Prior to operation, the unit must be allowed to slowly adjust to room temperature. Should condensation
              occur, a delay time of approximately 12 hours must be waited before the unit is set operational.
Installation
The devices are designed for installation in control cabinets. You will find installation instructions in the chapter
mechanical mounting.
58                                                                                                        Embedded PC
                                                                                         Assembly and connecting
Dimensions
The CX1000 product range is characterized by small overall installed size and high modularity. For project planning
purposes, a CPU module, a power supply unit and the associated system interfaces and fieldbus interfaces have to
be provided. The overall width of the application is made up of the individual modules. With a height of 100 mm, the
module dimensions exactly match those of the Beckhoff Bus Terminals. Together with the lowered connector
surfaces, this means that it can be used in a standard terminal box with a height of 120 mm.
Warning
          To ensure cooling to the device in operation it is important keep the safety distances. Details see
          installation position below.
Embedded PC                                                                                                        59
Assembly and connecting
60                                             Embedded PC
                                                     Assembly and connecting
CX1100-0002
power supply with I/O-interface (K-Bus-connection)
Embedded PC                                                              61
Assembly and connecting
CX1100-0003
power supply with I/O-interfaces (K-Bus-connection and IP-Link)
62                                                                Embedded PC
                           Assembly and connecting
CX1100-0910
Embedded PC                                    63
Assembly and connecting
CX1100-0920
64                        Embedded PC
                                                                                    Assembly and connecting
CX1500-Bxxx
Embedded PC                                                                                                  65
Assembly and connecting
CX1500-Mxxx
66                        Embedded PC
                                                                                        Assembly and connecting
Embedded PC                                                                                                       67
Assembly and connecting
Then fix the CX1020 block on the top hat-rail using the latching straps. You should hear a soft click.
Note:
A locking mechanism prevents the individual housings from being pulled off again. Detailed information relating to
disassembly of the CX1020 configuration from the top-hat rail can be found on page "Removal and disposal".
Installation position:
Warning
            The maximum ambient temperature for CPU modules mounted on a top-hat rail is 55°C. The
            orientation in which the device is fitted must be selected in such a way that cooling air can flow
            vertically through the ventilation holes. The images show the correct (Fig. 8) and two incorrect
            installation positions (Figs. 9 & 10).
68                                                                                                       Embedded PC
                                                                                         Assembly and connecting
Embedded PC                                                                                                             69
Assembly and connecting
70                                                                                                      Embedded PC
                                                                                       Assembly and connecting
The installation position "backside down" is only allowed with the right power supply. The power supply should have a
cooling plate (CX1100-001x).
Embedded PC                                                                                                       71
Assembly and connecting
72                                                                                                    Embedded PC
                                                                                         Assembly and connecting
3. Install cover
If the connection area does not have a closing cover on the left-hand side, the cover that was previously removed
should be pressed over the connections until it audibly engages.
Note:
If the CX1000/CX1020 configuration is not positioned on the top-hat rail, it is possible to connect the assembly with
the CX1000/CX1020 configuration first and then latch the whole module onto the top-hat rail. The installation is
described in section Installation and wiring.
Note:
A locking mechanism prevents the individual housings from being pulled off again.
Embedded PC                                                                                                             73
Assembly and connecting
The ground connection is realized via a lug of size M4. The following picture shows the order of the grommets and
the lug.
The lug is placed between the middle grommets. First the screw is fixed by turns with the hand. Then a wrench of
size S7 can be used to fix the screw. To avoid damage to the unit, its a good idea to make use of a torque wrench.
Warning
            The torque of the screw must not exceed 2,4 Nm! Otherwise the unit might get damaged.
74                                                                                                  Embedded PC
                                                                                           Assembly and connecting
Start-up procedure
Switching off
The Embedded PC switches off when the power supply unit is switched off. The control software typically running on
Embedded PCs should be shut down or stopped correctly. A user who may not close software may also not switch
the Embedded PC off, since data can be lost from the hard disk by switching off while software is running.
Once the software has been stopped, the operating system can be shut down. Only then should the power supply be
interrupted.
Embedded PC                                                                                                     75
Assembly and connecting
Warning
            Beckhoff Automation GmbH supplies the CX1020 systems pre-configured, which means they are
            READY FOR USE!
            The BIOS settings should only be modified by appropriately trained staff.
            Under Windows CE the BIOS should not be changed at all, since the operating system is
            adapted to the hardware configuration. Any change in the addresses or interrupts would lead to
            unstable system behaviour or even crashing.
Within the individual setup pages, F6 can be used for loading fail-safe defaults, and F7 for optimised default values
for the individual setup entries. These default values are applied irrespective of whether the board was previously
booted successfully with a particular setup setting. The situation is different if the defaults are called from the TOP
menu. Once a setup setting that subsequently led to successful booting was saved, both menu items will load these
values as defaults for the setup pages. See also "Load Fail-Safe Defaults" and "Load Optimized Defaults".
Top menu
► PC Health Status
ESC: Quit                                                                                                    ↑ ↓
→ ← Select Item
F10: Save & Exit Setup
A „►“ sign in front of the menu item indicates that a submenu is available. A „x“ sign in front of a menu item indicates
that a setting option is available that first has to be activated via a higher-level setting.
Set Passwort
Here you can enter a setup password for preventing unauthorised invoking of the BIOS.
76                                                                                                         Embedded PC
                                                                                        Assembly and connecting
Embedded PC                                                                                                      77
Assembly and connecting
Video                                    [EGA/VGA]
Halt On                                  [All, But Keyboard]
Date (mm:dd:yy)
Options:
 mm … month
 dd … day
 yy … year
Time (hh:mm:ss)
Options:
 hh … hours
 mm … minutes
 ss … seconds
VIDEO
Parameter for setting the graphics mode for the graphics card / the graphics output. EGA / VGA is standard today.
Options:
 EGA/VGA
 CGA 40
 CGA 80
 Mono
78                                                                                                    Embedded PC
                                                                                        Assembly and connecting
Halt On
This parameter can be used for stopping the boot process in the event of errors. Errors may be ignored. This menu
item is used to configure the settings.
Options:
Base Memory
This option is used for displaying the conventional memory (0 KB to 640 KB) in order to indicate whether it was
detected by the POST.
Extended Memory
Available memory from the first MB to the maximum memory capacity.
Total Memory
This is the total of base memory, extended memory and other memory.
Embedded PC                                                                                                         79
Assembly and connecting
Capacity 0 MB
Cylinder
Head                                            0
Precomp                                         0
Landing Zone                                    0
Sector                                          0
Access Mode:
This option can be used to select the operating system for the hard disk. Setting options: CHS, LBA, LARGE, or Auto.
Auto is the recommended setting. Normal (standard) mode supports hard disks with a capacity of up to 528 MB. This
mode uses positions for data access that are specified via cylinders (CYLS), heads, and sectors. The older LBA
(Logical Block Addressing) mode can support hard disks with a capacity of up to 8.4 GB. This mode uses a different
method for calculating the position disk data to be accessed. It translates cylinders, heads and sectors into a logical
address for the data location. Large hard disks support this mode. The BIOS supports the INT 13h extension function
that enables the LBA mode to manage hard disk drives with a capacity of more than 8.4 GB. If the number of
cylinders (CYLs) on the hard disk exceeds 1024 and DOS cannot support it, or if your operating system does not
support LBA mode, LARGE mode should be selected. The following options are available for setting the hard disk
access mode:
 CHS
 LBA
 LARGE
80                                                                                                     Embedded PC
                                                                                          Assembly and connecting
        Auto
The following parameters are automatically determined and displayed.
Capacity
Storage capacity of the hard disk. This value is calculated from the individual hard disk parameters.
Cylinder
Define or set the number of cylinders. Depending on the BIOS version and the manufacturer it varies between 1,024
and 16,384 cylinders.
Head
Define or set the number of heads. The number is between 1 and 16 heads.
Precomp
Write pre-compensation, required for older hard disks. This parameter specifies the cylinder from which a difference
in the information density is to be expected.
Landing Zone
This parameter defines the so-called landing zone or park cylinder. This is the resting position for the hard disk head
when the hard disk motor is switched off.
Sector
Define or set the number of sectors per track. Up to 63 sectors are supported, for Phoenix up to 64.
Embedded PC                                                                                                          81
Assembly and connecting
Capacity 0 MB
Cylinder
Head                                            0
Precomp                                         0
Landing Zone                                    0
Sector                                          0
Access Mode:
This option can be used to select the operating system for the hard disk. Setting options: CHS, LBA, LARGE, or Auto.
Auto is the recommended setting. Normal (standard) mode supports hard disks with a capacity of up to 528 MB. This
mode uses positions for data access that are specified via cylinders (CYLS), heads, and sectors. The older LBA
(Logical Block Addressing) mode can support hard disks with a capacity of up to 8.4 GB. This mode uses a different
method for calculating the position disk data to be accessed. It translates cylinders, heads and sectors into a logical
address for the data location. Large hard disks support this mode. The BIOS supports the INT 13h extension function
that enables the LBA mode to manage hard disk drives with a capacity of more than 8.4 GB. If the number of
cylinders (CYLs) on the hard disk exceeds 1024 and DOS cannot support it, or if your operating system does not
support LBA mode, LARGE mode should be selected. The following options are available for setting the hard disk
access mode:
 CHS
 LBA
 LARGE
82                                                                                                     Embedded PC
                                                                                          Assembly and connecting
        Auto
The following parameters are automatically determined and displayed.
Capacity
Storage capacity of the hard disk. This value is calculated from the individual hard disk parameters.
Cylinder
Define or set the number of cylinders. Depending on the BIOS version and the manufacturer it varies between 1,024
and 16,384 cylinders.
Head
Define or set the number of heads. The number is between 1 and 16 heads.
Precomp
Write pre-compensation, required for older hard disks. This parameter specifies the cylinder from which a difference
in the information density is to be expected.
Landing Zone
This parameter defines the so-called landing zone or park cylinder. This is the resting position for the hard disk head
when the hard disk motor is switched off.
Sector
Define or set the number of sectors per track. Up to 63 sectors are supported, for Phoenix up to 64.
Embedded PC                                                                                                          83
Assembly and connecting
CPU Feature
This menu item can be used for setting the CPU behaviour for thermal profiles.
Virus Warning
On start-up the boot sectors are checked for changes since the last start. Setting options: Enabled (a virus warning
may appear until it is acknowledged with Confirm or switched off (Disabled)), Confirm (a required boot sector
modification, e.g. after reinstallation of an operating system, is confirmed), Disabled (boot sectors are not verified).
 LS120 (LS-Drive)
84                                                                                                         Embedded PC
                                                                                            Assembly and connecting
 HDD-0 (Festplatte 1)
 CDROM (CD-Laufwerk)
 HDD-1 (Festplatte 2)
 ZIP100 (Zip-Drive)
 USB-FDD (USB-Floppy)
 USB-HDD (USB-Festplatte)
 LAN (Netzwerk)
 Disabled (abgeschaltet)
 LS120 (LS-Drive)
 HDD-0 (Festplatte 1)
 CDROM (CD-Laufwerk)
 HDD-1 (Festplatte 2)
 ZIP100 (Zip-Drive)
 USB-FDD (USB-Floppy)
 USB-HDD (USB-Festplatte)
 LAN (Netzwerk)
 Disabled (abgeschaltet)
 LS120 (LS-Drive)
 HDD-0 (Festplatte 1)
 CDROM (CD-Laufwerk)
 HDD-1 (Festplatte 2)
 ZIP100 (Zip-Drive)
 USB-FDD (USB-Floppy)
 USB-HDD (USB-Festplatte)
 LAN (Netzwerk)
 Disabled (abgeschaltet)
Embedded PC                                                                                                     85
Assembly and connecting
Security Option
This parameter specifies the option for which a password applies. If the SYSTEM option is selected, a password has
to be entered during PC start-up. If the SETUP option is selected, a password is only required for accessing the
BIOS.
APIC Mode
This parameter switches the APIC Controller (Advanced Programmable Interrupt Controller) on or off. According to
the PC2001 regulations, the system may run in APIC mode. APIC mode offers extended IRQ resources (depending
on the board). Settings: Enabled or Disabled
86                                                                                                      Embedded PC
                                                                                            Assembly and connecting
CPU Features
This menu is used for setting the CPU behaviour with thermal profiles.
Thermal Management
The processor used has a thermal monitor. The profile is preset and cannot be changed.
Embedded PC                                                                                                              87
Assembly and connecting
CPU Feature
This menu item can be used for setting the CPU behaviour for thermal profiles.
Virus Warning
On start-up the boot sectors are checked for changes since the last start. Setting options: Enabled (a virus warning
may appear until it is acknowledged with Confirm or switched off (Disabled)), Confirm (a required boot sector
modification, e.g. after reinstallation of an operating system, is confirmed), Disabled (boot sectors are not verified).
88                                                                                                         Embedded PC
                                                                                          Assembly and connecting
Security Option
This parameter specifies the option for which a password applies. If the SYSTEM option is selected, a password has
to be entered during PC start-up. If the SETUP option is selected, a password is only required for accessing the
BIOS.
APIC Mode
This parameter switches the APIC Controller (Advanced Programmable Interrupt Controller) on or off. According to
the PC2001 regulations, the system may run in APIC mode. APIC mode offers extended IRQ resources (depending
on the board). Settings: Enabled or Disabled
Embedded PC                                                                                                              89
Assembly and connecting
Integrated Peripherals
This menu is used for setting the system interfaces.
Onboard Device
Here you can set the settings for the USB and audio interfaces.
SuperIO Device
Here you can set the settings for the serial interfaces (port 1 and port 2).
90                                                                                                         Embedded PC
                                                                                            Assembly and connecting
Embedded PC                                                                                                             91
Assembly and connecting
Onboard Device
This menu is used for configuring the USB and audio interfaces.
USB Controller
If the option is enabled, the system BIOS specifies the system resources (IRQs and addresses) to be used. If the
option is disabled, the USB controller is switched off.
AC97 Audio
The onboard AC'97 audio controller can be switched on or off here. Setting options: Auto, Disabled .
92                                                                                                         Embedded PC
                                                                                              Assembly and connecting
SuperIO Device
This menu is used for configuring the USB and audio interfaces.
IR Transmission Delay
If this option is activated, transmission is delayed. Setting options: Enabled, Disabled.
Use IR Pins
This option is identical to the TxD, RxD Active option. The required information can be found in the documentation for
your IR device.
Embedded PC                                                                                                                93
Assembly and connecting
ACPI Function
This option can be used for switching the ACPI (Advanced Configuration and Power Interface) functions on or off (if
available). ACPI requires an operating system that recognises ACPI.
Power Management
Settings: Disabled (no energy saving function used), Min Saving (this setting is activated after 40 minutes and offers
the lowest energy saving level), Max Saving (this setting offers the highest energy saving level).
Suspend Type
This option offers two choices: Stop Grant (the CPU is idle in energy-saving mode), and PwrOn Suspend (the CPU
remains active in energy-saving mode).
94                                                                                                       Embedded PC
                                                                                             Assembly and connecting
9, 10, 11
Suspend Mode
In User Define mode a hold time can be set here. The following values are available: Disable (off) 1 Min , 2 Min , 4
Min, 8 Min , 12 Min , 20 Min , 30Min , 40 Min , 1 Hour. The setting in Min Saving mode is 1 minute. With Max Saving
the hold time is set to 1 hour.
Power On by Ring
The system starts when the phone rings, if an external modem is connected to the onboard serial port.
Primary IDE 0
If this option is enabled, the system activates the energy-saving timer if no activity is detected on the first drive of the
first IDE/EIDE port. Setting options: Enabled, Disabled
Primary IDE 1
If this option is enabled, the system activates the energy-saving timer if no activity is detected on the second drive of
the first IDE/EIDE port. Setting options: Enabled, Disabled.
Secondary IDE 0
If this option is enabled, the system activates the energy-saving timer if no activity is detected on the first drive of the
second IDE/EIDE port. Setting options: Enabled, Disabled
Secondary IDE 1
If this option is enabled, the system activates the energy-saving timer if no activity is detected on the second drive of
the second IDE/EIDE port. Setting options: Enabled, Disabled
PCI PIRQ[A-D]#
This option can be used to influence the power management timing. If the option is enabled, a countdown
commences that is interrupted as soon as the INTA~INTD signal becomes active. The system is reset to zero.
Embedded PC                                                                                                               95
Assembly and connecting
PnP/PCI Configurations
This menu is used for configuring the PCI bus and Plug and Play Management.
Resources Controlled By
Specifies whether the PnP settings should be assigned via setup or automatically. Auto should be used, if there are
no problems with IRQ or DMA assignments.
IRQ Resources
If these resources are set manually, each system interrupt should be assigned a type, depending on the type of
device using the interrupt.
Memory Resources
If memory areas are to be protected for use by the operating system, an area can be set here.
96                                                                                                      Embedded PC
                                                                                             Assembly and connecting
IRQ Resources
This menu is used for disabling interrupts for free allocation to PCI slots.
Embedded PC                                                                                                              97
Assembly and connecting
Memory Resources
This menu can be used to specify a memory area for peripherals. The area is precisely defined through a base
address and length.
Reserved Base
Start address of the reserved area. N/A (not available), D000, D400, D800 or DC00 can be selected as addresses.
98                                                                                                Embedded PC
                                                                                     Assembly and connecting
PC Health Status
This menu is used for displaying the settings for CPU and motherboard temperatures, power supply, and fan speed.
CX1020 Revision                               *     2
CX1021 Revision                               *     2
         ↑ ↓ → ← :Move Enter:Select +/-/PU/PD:Value F10:Save ESC:Exit F1:Help
          F5: Previous Values F6: Fail-Safe Defaults F7: Optimized Defaults
The * marked items are only shown in HW Version > 2.1 and Bios Version > 2.03.
+12 V
Supply voltage, 12 V.
+3.3 V
Supply voltage, 3.3 V.
+5 V
Supply voltage, 5 V.
Embedded PC                                                                                                       99
Assembly and connecting
Fan1 Speed
Speed of fan no. 1 (0 in this case, since no fan present)
Fan2 Speed
Speed of fan no. 2 (0 in this case, since no fan present)
VBatt
Battery voltage.
CX1020 Revision
Hardware Version of the CPU board.
CX1021 Revision
Hardware Version of the CF board.
100                                                            Embedded PC
                                                                                        Assembly and connecting
Frequency/Voltage Control
In this menu the CLK setting for the PCI bus can be specified. Power supply tolerances can also be specified.
Spread Spectrum
This setting should be left unchanged if possible. It should only be changed in the event of EMI problems. It enables
electromagnetic interference to be reduced.
Embedded PC                                                                                                       101
Error handling and diagnostics
102                                                                                          Embedded PC
                                                                             Error handling and diagnostics
Embedded PC                                                                                            103
Error handling and diagnostics
104                                                                                                Embedded PC
                                                                                   Error handling and diagnostics
Embedded PC                                                                                                      105
Error handling and diagnostics
Note:
The supply voltage of the power supply unit, which is necessary to supply power to the CX1000 system, must not be
interrupted in the middle of operation. Switching off the supply voltage to the power supply unit refers here to the
power supply on the power contacts.
106                                                                                                    Embedded PC
                                                                                   Error handling and diagnostics
Embedded PC                                                                                                      107
Error handling and diagnostics
Note:
The supply voltage of the power supply unit, which is necessary to supply power to the CX1000 system, must not be
interrupted in the middle of operation. Switching off the supply voltage to the power supply unit refers here to the
power supply on the power contacts.
108                                                                                                    Embedded PC
                                                                                     Error handling and diagnostics
Embedded PC                                                                                                       109
Error handling and diagnostics
Note:
The supply voltage of the power supply unit, which is necessary to supply power to the CX-System, must not be
interrupted in the middle of operation. Switching off the supply voltage to the power supply unit refers here to the
power supply on the power contacts.
Note
           If an error occurs on both terminal busses (K-Bus and IP-Link-Bus) the error on K-Bus is reported
           at first. The IP-Link-Bus error is reported as second. Both error codes are introduced by their typical
           blink signal.
110                                                                                                        Embedded PC
                                                                                     Error handling and diagnostics
Embedded PC                                                                                                       111
Error handling and diagnostics
Note:
The supply voltage of the power supply unit, which is necessary to supply power to the CX-System, must not be
interrupted in the middle of operation. Switching off the supply voltage to the power supply unit refers here to the
power supply on the power contacts.
Note
112                                                                                                        Embedded PC
                                                                              Error handling and diagnostics
      If an error occurs on both terminal busses (K-Bus and IP-Link-Bus) the error on K-Bus is reported
      at first. The IP-Link-Bus error is reported as second. Both error codes are introduced by their
      typical blink signal.
Embedded PC                                                                                               113
Error handling and diagnostics
114                                                                                                Embedded PC
                                                                                   Error handling and diagnostics
Embedded PC                                                                                                      115
Error handling and diagnostics
Faults
Please also refer to the Safety instructions section.
You will also find further documentation for Beckhoff components there.
116                                                                                                     Embedded PC
                                                                                                     Decomissioning
6. Decomissioning
Removal and disposal
1.1. Release and remove the first Terminal next to the power supply unit on the top-hat rail.
First remove any wiring from power supply unit and then from the first terminal on the top-hat rail next to the power
supply unit. If the wiring is to be reused for another system, it is advisable to make a note of the connections. Then
pull the orange terminal release (see arrow) to release the terminal and pull it out.
Embedded PC                                                                                                          117
Decomissioning
Only modules (CPU, fieldbus connections and UPS modules) that can be separated non-destructively feature a
release device. Modules that cannot be separated only feature a marking point (with or without red paint seal).
Applying force to these elements will destroy them.
Warning
             Forcibly opening the module housing (e.g. removing the cover) will destroy the housing.
Disposal
The device must be fully dismantled in order to dispose of it.
Electronic parts must be disposed of in accordance with national electronics scrap regulations.
118                                                                                                    Embedded PC
                                                                                                   Appendix
7. Appendix
Accessories
Labeling Tags
order number      Description
CX1900-0200       Universal plastic labels for the CX1000 system (package contains 1000 labels)
                  – snaps into the premoulded spots on the CX1000 components
                  – labeling can be done with a X-Y plotter
                  – dimension of the single label 15 x 5 mm
                  – material: white colored plastic
                  – Murrplastik type KMR 5/15, order number 86401014
Embedded PC                                                                                              119
Appendix
Certifications
All products of the Embedded PC family are CE, UL and GOST-R certified. Since the product family is continuously
developed further, we are unable to provide a full listing here. The current list of certified products can be found on
the Embedded PC certificates web page or at www.beckhoff.com under Embedded PC.
Approvals
                                  FCC: Federal Communications Commission
                                  Radio Frequency Interference Statement
FCC Approval for USA              This equipment has been tested and found to comply with the limits for a Class A
                                  digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
                                  provide reasonable protection against harmful interference when the equipment is
                                  operated in a commercial environment. This equipment generates, uses, and can
                                  radiate radio frequency energy and, if not installed and used in accordance with the
                                  instruction manual, may cause harmful interference to radio communications.
                                  Operation of this equipment in a residential area is likely to cause harmful
                                  interference in which case the user will be required to correct the interference at his
                                  own expense.
120                                                                                                      Embedded PC
                                                                                                          Appendix
Beckhoff Headquarters
Beckhoff Automation GmbH
Eiserstr. 5
33415 Verl
Germany
Phone:                            +49(0)5246/963-0
Fax:                              +49(0)5246/963-198
e-mail:                           info@beckhoff.com
Beckhoff Support
Support offers you comprehensive technical assistance, helping you no only with the application of individual
Beckhoff products, but also with other, wide-ranging services:
 support
Hotline:                         +49(0)5246/963-157
Fax:                             +49(0)5246/963-9157
e-mail:                          support@beckhoff.com
Beckhoff Service
The Beckhoff Service Center supports you in all matters of after-sales service:
 on-site service
 repair service
 hotline service
Hotline:                         +49(0)5246/963-460
Fax:                             +49(0)5246/963-479
e-mail:                          service@beckhoff.com
Embedded PC 121